Summary
PRCOM20235207
Building Permit - Commercial
Issued
RESIDENCES AT BLACKWELL LLC
NEW MULTI-FAMILY
RESIDENCES AT BLACKWELL - BUILDING #3 - 67 UNITS - NEW APARTMENT BUILDING
10/10/2023
08/12/2024
11/06/2023
Locations
Contacts
Jake Loveless, Address:21 SE 29TH TER  
Polar Aire Heating & Cooling Service, Address:400 S. Kansas Ave, Phone:(913) 782-8238  
KDM ELECTRICAL CONTRACTORS, Address:1103 NW CASEY BLVD STE C, Phone:(816) 443-5694  
BENCHMARK MECHANICAL LLC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
NSPJ ARCHITECTS, Address:3515 W 75TH ST, SUITE 201, Phone:(913) 831-1415 Ext:278  
CFS ENGINEERS, Address:1421 EAST 104TH STREET STE 100, Phone:(816) 333-4477  
RESIDENCES AT BLACKWELL LLC, Address:21 SE 29TH TER  
Streamline General Contractors, Address:5 4TH ST SW  
Scott Runyan - Griffen Riley Property Group, Phone:(816) 500-5928  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 02/06/2025 02/07/2025
Craig Hill
Alarm Plan Review Rejected 10/01/2024 10/01/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
10/01/2024

915.1.5 Private garages. Carbon monoxide detection shall be provided in dwelling units, sleeping units and classrooms in buildings with attached private garages. Action Required: Provide Carbon Monoxide detection on the floor above and below the garage levels.
Sprinkler Plan Review Released for Construction 08/21/2024 08/21/2024
Craig Hill
Sprinkler Plan Review Rejected 07/03/2024 07/03/2024
Craig Hill
Miscellaneous Correction
Corrective Action Required
07/03/2024

Fire department connection shows 2 - 2½” siamese connection. FDC needs to be a 4” storz with a 30 degree elbow.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Multi-Family $40,475.00 $40,475.00 Paid 08/12/2024
Residential Excise Tax Fee $28,429.44 $28,429.44 Paid 08/12/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Alarm Test Pending
Sprinkler - Hydrostatic Test Pending
Sprinkler - Flow Test Pending
Erosion Control Inspection Pending
Sewer Service Inspection Pending
Water Service Inspection Pending
Electrical Service Inspection Pending
Gas Piping Inspection - Commercial Pending
Gas Service Inspection - Commercial Pending
Underground Electrical Inspection - Commercial Pending
Misc
Informational
09/24/2024
-Completion of underground raceways into building service equipment location
Miscellaneous Inspection Pending
Misc
Informational
04/25/2025
4/25-Pre-allrough walkthrough with the construction crew
Above Ceiling Inspection Pending
Misc
Corrective Action Required
07/16/2025
**Area at accessible garages/IT closet/Storage not ready
CORRIDORS
Corrective Action Required
07/16/2025
Lower level, 2->4th floors-OK 1st floor not inspected
All Rough Inspection - Commercial Pending
Misc
Corrective Action Required
08/05/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
08/05/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
08/05/2025
OK: -Pre-rock behind tubs and showers -Nail balcony joist hangers -Mud&tape seam at elevator wall at unit 004
FIRST FLOOR
Corrective Action Required
08/05/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
08/05/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall -202 cantilevered beams and trusses repair **Corrections: -Nail hanger at balcony
THIRD FLOOR
Corrective Action Required
08/05/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
08/05/2025
Dwelling units-OK Corridor- OK
ELEVATOR 1
Corrective Action Required
08/05/2025
shaft-okay
STAIR TOWER 1
Corrective Action Required
08/05/2025
ceiling okay to cover
STAIR TOWER 2
Corrective Action Required
08/05/2025
ceiling okay to cover
Suspended Slab Inspection Pending 10/1/2024
Misc
Informational
08/02/2024
Podium concrete slab-OK to pour pending approval of SI inspector
Rated Assembly Inspection Pending 8/11/2025 8/11/2025
LOWER LEVEL
Corrective Action Required
08/08/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor
FIRST FLOOR
Corrective Action Required
08/08/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
08/08/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
08/08/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
08/08/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
08/08/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
08/08/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer -inner side 1st layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
08/08/2025
STAIR TOWER 1
Corrective Action Required
08/08/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer -1st layer and rc ceiling
STAIR TOWER 2
Corrective Action Required
08/08/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer -corridor side 1st layer -above ceiling space 1st layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer -1st layer and rc ceiling
Footing Inspection - Commercial Partial 3/6/2024 3/6/2024 03/06/2024
Misc
Informational
03/06/2024
Front wall type 1 footing in progress. OK to pour pending approval of onsite 3rd party engineer
Footing Inspection - Commercial Partial 4/1/2024 4/1/2024 04/01/2024
Misc
Informational
03/06/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2
Footing Inspection - Commercial Partial 4/4/2024 4/4/2024 04/04/2024
Misc
Informational
04/01/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2 -Interior footing from M/5 to N/3
Footing Inspection - Commercial Partial 4/8/2024 4/8/2024 04/08/2024
Misc
Informational
04/04/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter
Foundation Inspection - Commercial Partial 4/10/2024 04/10/2024
Misc
Informational
04/10/2024
Foundation wall OK: -A/4 to L.5/4.2
Footing Inspection - Commercial Partial 4/10/2024 (8:00) 4/10/2024 04/10/2024
Misc
Informational
04/08/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. See deficiency for column
Misc
Corrective Action Required
04/10/2024
Rebars for 4 shelter columns not per plan
Foundation Inspection - Commercial Partial 5/3/2024 5/3/2024 05/03/2024
Misc
Informational
04/10/2024
Foundation wall OK: -A/4 to L.5/4.2; storm shelter F. wall and 4 col
Footing Inspection - Commercial Partial 5/14/2024 (1:00) 5/14/2024 05/14/2024
Misc
Informational
04/10/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. See deficiency for column - Footing for elevator 3 ok to pour, has been approved by third party inspector
Misc
Corrective Action Required
04/10/2024
Rebars for 4 shelter columns not per plan
Foundation Inspection - Commercial Partial 5/15/2024 05/15/2024
Misc
Informational
05/03/2024
Foundation wall OK: -A/4 to L.5/4.2; storm shelter F. wall and 4 col -Elev. pit wall
Underslab Plumbing Inspection - Commercial Partial 5/23/2024 5/23/2024 05/23/2024
Misc
Corrective Action Required
05/23/2024
Underslab plumbing OK below: -Area from line A to E; storm shelter
Underslab Plumbing Inspection - Commercial Passed 6/5/2024 6/5/2024 06/05/2024
Misc
Resolved
06/05/2024
Underslab plumbing OK below: -Area from line A to E; storm shelter
Footing Inspection - Commercial Partial 6/14/2024 6/14/2024 06/14/2024
Misc
Informational
05/14/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Interior footing
Suspended Slab Inspection Failed 8/1/2024 08/01/2024
Misc
Corrective Action Required
08/01/2024
Provide podium concrete slab reinforcement per plan
Suspended Slab Inspection Partial 8/2/2024 08/02/2024
Misc
Informational
08/02/2024
Podium concrete slab-OK to pour pending approval of SI inspector
Footing Inspection - Commercial Partial 9/12/2024 9/12/2024 09/12/2024
Misc
Informational
06/14/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing at front
Underground Electrical Inspection - Commercial Partial 9/17/2024 9/17/2024 09/17/2024
Misc
Informational
09/17/2024
-9 underground raceways near entrance to building to connections to previously installed raceways to car ports and garage
Underslab Plumbing Inspection - Commercial Passed 9/18/2024 09/18/2024
Informational
09/18/2024
Completion of underslab plumbing
Footing Inspection - Commercial Partial 9/24/2024 9/24/2024 09/24/2024
Misc
Informational
09/12/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing at front
Misc
Corrective Action Required
09/24/2024
Move the storm drains away from interior footing pads
Underground Electrical Inspection - Commercial Partial 9/24/2024 9/24/2024 09/24/2024
Misc
Informational
09/17/2024
-Completion of underground raceways into building service equipment location
Foundation Inspection - Commercial Partial 9/25/2024 09/25/2024
Misc
Informational
05/15/2024
Foundation wall OK: -A/4 to L.5/4.2; storm shelter F. wall and 4 col -Elev. pit wall -Stem wall at north side of bdlg
Footing Inspection - Commercial Partial 9/25/2024 09/25/2024
Misc
Informational
09/24/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing at front
Misc
Corrective Action Required
09/25/2024
Remove the storm drain away from under the 5 ft column pad at north end garage
Footing Inspection - Commercial Partial 9/26/2024 9/26/2024 09/26/2024
Misc
Informational
09/25/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing and int. footing. Except see correction below
Misc
Corrective Action Required
09/25/2024
Remove the storm drain away from under the 5 ft column pad at north end garage
Foundation Inspection - Commercial Partial 9/26/2024 09/26/2024
Misc
Informational
09/25/2024
Foundation wall OK: -A/4 to L.5/4.2; storm shelter F. wall and 4 col -Elev. pit wall -Stem wall at garages
Footing Inspection - Commercial Partial 10/1/2024 10/01/2024
Misc
Informational
09/26/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing and int. footing. -Ext and int garage stem walls
Misc
Resolved
10/01/2024
Footing Inspection - Commercial Partial 10/3/2024 10/3/2024 10/03/2024
Misc
Informational
10/01/2024
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing and int. footing. -Ext and int garage stem walls Misc: -Garage slabs
Above Ceiling Inspection Partial 12/19/2024 12/19/2024
FIRST FLOOR
Informational
12/19/2024
OK to rock: -Corridor ceiling (top of 1-hr fire barrier)
SECOND FLOOR
Informational
12/19/2024
THIRD FLOOR
Informational
12/19/2024
Misc
Informational
12/19/2024
BOTTOM/BASEMENT FLOOR:
Above Ceiling Inspection Partial 1/22/2025 1/22/2025 01/22/2025
Misc
Corrective Action Required
01/22/2025
BASEMENT FLOOR: -Corridor ceiling (top of 1-hr fire barrier)
FIRST FLOOR
Corrective Action Required
01/22/2025
OK to rock: -Corridor ceiling (top of 1-hr fire barrier)
All Rough Inspection - Commercial Failed 1/23/2025 1/23/2025 01/23/2025
Misc
Corrective Action Required
01/23/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Rated Assembly Inspection Partial 1/28/2025 1/28/2025 01/28/2025
LOWER LEVEL
Corrective Action Required
01/28/2025
Both stair A enclosures: -Door side-1st layer
Rated Assembly Inspection Partial 1/29/2025 1/29/2025 01/29/2025
Misc
Corrective Action Required
01/29/2025
BOTTOM LEVEL: -Both stair A enclosues: stair side 2nd layer
All Rough Inspection - Commercial Failed 1/23/2025 2/3/2025 02/03/2025
Misc
Informational
02/03/2025
-Nailing of exterior wall sheathing-OK to cover front, north, and south walls
Misc
Corrective Action Required
02/03/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Resolved
02/11/2025
INSPECTED BUILDING 3 - NORTH STAIR TOWER MAIN FLOOR FIRST LAYER ONLY - SOUTH STAIR TOWER MAIN FLOOR FIRST LAYER ONLY THREE SHEAR WALLS NORTH, MID-NORTH, AND SOUTH BACK OF BUILDING 3
Above Ceiling Inspection Partial 2/3/2025 2/3/2025 02/03/2025
LOWER LEVEL
Corrective Action Required
01/22/2025
Ok to rock: -Corridor ceiling (top of 1-hr fire barrier), fire sprinler drops
FIRST FLOOR
Corrective Action Required
01/22/2025
OK to rock: -Corridor ceiling (top of 1-hr fire barrier), fire sprinler drops
Rated Assembly Inspection Partial 2/3/2025 2/3/2025 02/03/2025
LOWER LEVEL
Corrective Action Required
01/29/2025
-Both stair A enclosues: stair side 2nd layer
All Rough Inspection - Commercial Failed 2/11/2025 02/11/2025
Misc
Informational
02/03/2025
-Nailing of exterior wall sheathing-OK to cover front, north, and south walls
Misc
Corrective Action Required
02/03/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
MISC
Corrective Action Required
02/11/2025
INSPECTED BUILDING 3 - NORTH STAIR TOWER MAIN FLOOR FIRST LAYER ONLY - SOUTH STAIR TOWER MAIN FLOOR FIRST LAYER ONLY THREE SHEAR WALLS NORTH, MID-NORTH, AND SOUTH BACK OF BUILDING 3
Rated Assembly Inspection Partial 2/13/2025 2/13/2025 02/13/2025
LOWER LEVEL
Informational
02/13/2025
-Both stair A enclosues: stair side 2nd layer
FIRST FLOOR
Informational
02/13/2025
-Both stair A enclosues: stair side 1st layer
Rated Assembly Inspection Partial 2/18/2025 2/18/2025 02/18/2025
LOWER LEVEL
Informational
02/13/2025
-Both stair A enclosues: stair side 2nd layer
FIRST FLOOR
Informational
02/13/2025
-Both stair A enclosues: stair side 1st layer ok
Misc
Corrective Action Required
02/18/2025
1st floor north&south stair A: 2nd layer installed; however, provide lapping at edge
Rated Assembly Inspection Partial 2/26/2025 2/26/2025 02/26/2025
LOWER LEVEL
Informational
02/18/2025
-Both stair A enclosues: stair side 2nd layer
FIRST FLOOR
Informational
02/18/2025
-Both stair A enclosues: stair side 2nd layer ok
Misc
Corrective Action Required
02/18/2025
Rated Assembly Inspection Partial 3/5/2025 3/6/2025 03/06/2025
LOWER LEVEL
Corrective Action Required
03/06/2025
FIRST FLOOR
Corrective Action Required
03/06/2025
SECOND FLOOR
Corrective Action Required
03/06/2025
THIRD FLOOR
Corrective Action Required
03/06/2025
STAIR TOWER 1
Corrective Action Required
03/06/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 1st layer
STAIR TOWER 2
Corrective Action Required
03/06/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/06/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/06/2025
Rated Assembly Inspection Partial 3/11/2025 3/11/2025 03/11/2025
LOWER LEVEL
Corrective Action Required
03/06/2025
FIRST FLOOR
Corrective Action Required
03/06/2025
SECOND FLOOR
Corrective Action Required
03/06/2025
THIRD FLOOR
Corrective Action Required
03/06/2025
STAIR TOWER 1
Corrective Action Required
03/06/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer **extend 2-hr wall to roof deck
STAIR TOWER 2
Corrective Action Required
03/06/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 1st layer **extend 2-hr wall to roof deck
STAIR TOWER 3
Corrective Action Required
03/06/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/06/2025
Rated Assembly Inspection Partial 3/12/2025 3/12/2025 03/12/2025
LOWER LEVEL
Corrective Action Required
03/11/2025
Pre-rock behind tub/shower-Firecaulk penetrations
FIRST FLOOR
Corrective Action Required
03/11/2025
Pre-rock behind tub/shower-Firecaulk penetrations
SECOND FLOOR
Corrective Action Required
03/11/2025
THIRD FLOOR
Corrective Action Required
03/11/2025
STAIR TOWER 1
Corrective Action Required
03/11/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer **extend 2-hr wall to roof deck
STAIR TOWER 2
Corrective Action Required
03/11/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 1st layer **extend 2-hr wall to roof deck
STAIR TOWER 3
Corrective Action Required
03/11/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/11/2025
Rated Assembly Inspection Partial 3/14/2025 03/14/2025
LOWER LEVEL
Corrective Action Required
03/12/2025
Pre-rock behind tub/shower-Firecaulk penetrations
FIRST FLOOR
Corrective Action Required
03/12/2025
Pre-rock behind tub/shower-Firecaulk penetrations
SECOND FLOOR
Corrective Action Required
03/12/2025
THIRD FLOOR
Corrective Action Required
03/12/2025
STAIR TOWER 1
Corrective Action Required
03/12/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer
STAIR TOWER 2
Corrective Action Required
03/12/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/12/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/12/2025
Rated Assembly Inspection Partial 3/18/2025 3/18/2025 03/18/2025
LOWER LEVEL
Corrective Action Required
03/14/2025
Pre-rock behind tub/shower-Firecaulk penetrations
FIRST FLOOR
Corrective Action Required
03/14/2025
Pre-rock behind tub/shower-Firecaulk penetrations
SECOND FLOOR
Corrective Action Required
03/14/2025
THIRD FLOOR
Corrective Action Required
03/14/2025
STAIR TOWER 1
Corrective Action Required
03/14/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 1st layer
STAIR TOWER 2
Corrective Action Required
03/14/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/14/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/14/2025
All Rough Inspection - Commercial Partial 3/20/2025 03/20/2025
Misc
Informational
02/11/2025
-Nailing of exterior wall sheathing-OK to cover front, north, and south walls
Misc
Corrective Action Required
02/11/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
02/11/2025
THREE SHEAR WALLS NORTH, MID-NORTH, AND SOUTH BACK OF BUILDING 3
LOWER LEVEL
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
03/20/2025
FOURTH FLOOR
Corrective Action Required
03/20/2025
Rated Assembly Inspection Partial 3/20/2025 03/20/2025
LOWER LEVEL
Corrective Action Required
03/18/2025
Pre-rock behind tub/shower-Firecaulk penetrations
FIRST FLOOR
Corrective Action Required
03/18/2025
Pre-rock behind tub/shower-Firecaulk penetrations
SECOND FLOOR
Corrective Action Required
03/18/2025
THIRD FLOOR
Corrective Action Required
03/18/2025
STAIR TOWER 1
Corrective Action Required
03/18/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 1st layer
STAIR TOWER 2
Corrective Action Required
03/18/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/18/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/18/2025
Lower floor: -Dwelling side 1st layer First floor: -Dwelling side 1st layer
Rated Assembly Inspection Partial 3/24/2025 3/24/2025 03/24/2025
LOWER LEVEL
Corrective Action Required
03/20/2025
FIRST FLOOR
Corrective Action Required
03/20/2025
SECOND FLOOR
Corrective Action Required
03/20/2025
THIRD FLOOR
Corrective Action Required
03/20/2025
STAIR TOWER 1
Corrective Action Required
03/20/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 2
Corrective Action Required
03/20/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 1st layer
STAIR TOWER 3
Corrective Action Required
03/20/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/20/2025
Lower floor: -Dwelling side 1st layer First floor: -Dwelling side 1st layer
Rated Assembly Inspection Partial 3/26/2025 3/26/2025 03/26/2025
LOWER LEVEL
Corrective Action Required
03/24/2025
-Tub&shower walls
FIRST FLOOR
Corrective Action Required
03/24/2025
-Tub&shower walls
SECOND FLOOR
Corrective Action Required
03/24/2025
-Tub&shower walls
THIRD FLOOR
Corrective Action Required
03/24/2025
-Tub&shower walls
STAIR TOWER 1
Corrective Action Required
03/24/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 2
Corrective Action Required
03/24/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/24/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/24/2025
Lower floor: -004 dwelling side 1st layer 1st floor: -107 dwelling side 1st layer 2nd floor: -207/209 dwelling side 1st layer 3rd floor: -307/309 dwelling side 1st layer 4th floor: -405/407 dwelling side 1st layer
FOURTH FLOOR
Corrective Action Required
03/26/2025
-Tub&shower walls
Rated Assembly Inspection Partial 4/1/2025 4/1/2025 04/01/2025
LOWER LEVEL
Corrective Action Required
03/26/2025
-Tub&shower walls
FIRST FLOOR
Corrective Action Required
03/26/2025
-Tub&shower walls
SECOND FLOOR
Corrective Action Required
03/26/2025
-Tub&shower walls
THIRD FLOOR
Corrective Action Required
03/26/2025
-Tub&shower walls -mud&taped
FOURTH FLOOR
Corrective Action Required
03/26/2025
-Tub&shower walls -mud&taped
STAIR TOWER 1
Corrective Action Required
03/26/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 2
Corrective Action Required
03/26/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
03/26/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
03/26/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer
Rated Assembly Inspection Partial 4/3/2025 04/03/2025
LOWER LEVEL
Corrective Action Required
04/01/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
04/01/2025
-Tub&shower walls -mud&taped
SECOND FLOOR
Corrective Action Required
04/01/2025
-Tub&shower walls -mud&taped
THIRD FLOOR
Corrective Action Required
04/01/2025
-Tub&shower walls -mud&taped
FOURTH FLOOR
Corrective Action Required
04/01/2025
-Tub&shower walls -mud&taped
STAIR TOWER 2
Corrective Action Required
04/01/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
04/01/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
04/01/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer
STAIR TOWER 1
Corrective Action Required
04/01/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
Rated Assembly Inspection Partial 4/8/2025 4/8/2025 04/08/2025
LOWER LEVEL
Corrective Action Required
04/03/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
04/03/2025
-Tub&shower walls -mud&taped
SECOND FLOOR
Corrective Action Required
04/03/2025
-Tub&shower walls -mud&taped
THIRD FLOOR
Corrective Action Required
04/03/2025
-Tub&shower walls -mud&taped
FOURTH FLOOR
Corrective Action Required
04/03/2025
-Tub&shower walls -mud&taped
STAIR TOWER 2
Corrective Action Required
04/03/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
04/03/2025
**THIS IS REAR STAIR B**
ELEVATOR 1
Corrective Action Required
04/03/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer
STAIR TOWER 1
Corrective Action Required
04/03/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
Misc
Corrective Action Required
04/08/2025
Corridor fire barrier: -1st, 2nd floor ceiling nailing
All Rough Inspection - Commercial Partial 4/8/2025 04/08/2025
Misc
Corrective Action Required
03/20/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
03/20/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
03/20/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
03/20/2025
FOURTH FLOOR
Corrective Action Required
03/20/2025
Above Ceiling Inspection Partial 4/17/2025 4/17/2025 04/17/2025
LOWER LEVEL
Corrective Action Required
02/03/2025
Ok to rock: -Corridor ceiling (top of 1-hr fire barrier), fire sprinler drops
FIRST FLOOR
Corrective Action Required
02/03/2025
OK to rock: -Corridor ceiling (top of 1-hr fire barrier), fire sprinler drops **Area at accessible garages/IT closet/Storage not ready
Rated Assembly Inspection Partial 4/17/2025 4/17/2025 04/17/2025
LOWER LEVEL
Corrective Action Required
04/08/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
04/08/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
04/08/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
04/08/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok
FOURTH FLOOR
Corrective Action Required
04/08/2025
-Tub&shower walls -mud&taped
STAIR TOWER 1
Corrective Action Required
04/08/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 2
Corrective Action Required
04/08/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer
STAIR TOWER 3
Corrective Action Required
04/08/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
04/08/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer
Misc
Corrective Action Required
04/08/2025
Footing Inspection - Commercial Passed 04/25/2025
Misc
Resolved
04/25/2025
Footing- OK to pour pending approval of onsite 3rd party engineer: -Ext. wall footing from A/1 to N/2; the rest of ext. GB -Interior footing from M/5 to N/3 -4 column pads in storm shelter. -Footing for elevator 3 ok to pour, has been approved by third party inspector -Lower level interior footing -1st fl ext. footing and int. footing. -Ext and int garage stem walls Misc: -Garage slabs
Foundation Inspection - Commercial Passed 10/3/2024 04/25/2025
Misc
Resolved
04/25/2025
Foundation wall OK: -A/4 to L.5/4.2; storm shelter F. wall and 4 col -Elev. pit wall -Stem wall at garages
Miscellaneous Inspection Partial 4/25/2025 04/25/2025
Misc
Informational
04/25/2025
4/25-Pre-allrough walkthrough with the construction crew
All Rough Inspection - Commercial Failed 5/5/2025 5/5/2025 05/05/2025
Misc
Corrective Action Required
04/08/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
04/08/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
04/08/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
04/08/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
04/08/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
04/08/2025
FOURTH FLOOR
Corrective Action Required
04/08/2025
**May/5-Inspection cancelled. Provide address for each building
All Rough Inspection - Commercial Failed 5/12/2025 5/12/2025 05/12/2025
Misc
Corrective Action Required
05/05/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/05/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/05/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/05/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/05/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/05/2025
FOURTH FLOOR
Corrective Action Required
05/05/2025
** = check all units **Draft stop roof space per plan **Fire caulk all wall plate penetrations **Fb all wall space from roof/ceiling space **Tie down window/door cripple studs to plates and beam and strap header to support studs per 1/S0.22. Screw studs to bottom plate per 2A/S0.05 **Install stud shoes at non-bearing wall studs bored more than 60% **Label dryer duct length and equivalent 90-deg elbows 401: -Fc penetration below media box -Complete electrical at bathroom/corridor wall; Fc wall plate penetration -Tie down beam to wall at rear 402: -Broken plumbing at bathroom -Sprinkler to bathroom -Tie down rafters above bathroom -Complete electrical to balcony; protect wiring 403: -Install fire collar at roof drain floor penetration 404: -Tie down beam to wall at rear -Provide drywall at tub/dwelling separation wall -Protect plumbing at laundry/tub wall plates; fire caulk plate penetrations at both tub and laundry walls 405: 406: -Tie down trusses to beam at rear; beam to support wall 407: -Install tie down girder truss above shower 408: -Tie down lvl beam to wall 409: -Secure dryer electrical outlet box to stud 410: -Fc laundry waste stack wall plate penetrations 411: -Fire block exterior wall space from roof&ceiling space -Protect laundry plumbing -Provide fire collar at 4” roof drain floor penetration behind tub -Fc dryer duct at top plate penetration 412: -Provide fire collar at roof drain floor penetration -Fc laundry wall bottom plate penetrations 413: -Complete electrical to balcony. A receptacle is required at balcony
All Rough Inspection - Commercial Failed 5/15/2025 5/15/2025 05/15/2025
Misc
Corrective Action Required
05/12/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/12/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/12/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/12/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/12/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/12/2025
FOURTH FLOOR
Corrective Action Required
05/12/2025
** = check all units **Draft-stop roof space per A1.07. Fire block all holes, gaps, and penetrations of draft-stop 402: -Tie down rafters above bathroom 403, 404, 411, 412-Install firestop at roof drain floor&ceiling penetrations per Hilti Instructions
All Rough Inspection - Commercial Partial 5/19/2025 05/19/2025
Misc
Corrective Action Required
05/15/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/15/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/15/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/15/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/15/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/15/2025
FOURTH FLOOR
Corrective Action Required
05/15/2025
Dwelling units only: -Draft-stop holes and gap between draftstops 7&8 -Install firestop at roof drain floor&ceiling penetrations per Hilti Instructions (403, 404, 411, 412) **Area outsie dwelling units not yet inspected
All Rough Inspection - Commercial Failed 5/22/2025 5/22/2025 05/22/2025
Misc
Corrective Action Required
05/19/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/19/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/19/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/19/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/19/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/19/2025
**Check all units -Secure wiring within 12” of ceiling boxes -Protect all back-back boxes -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Remove insulation from corridor walls -Nail together stud pack per plan -3 stud support for balcony beam -Screw studs adjacent to floor-floor screws per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work 318: -Fc gap at dead space by tub; wall plate penetration -Secure wiring within 12” of panel; light above master closet -Floor-floor screws at exterior wall 317: -Close gap at top of double stud wall 315: -Fc gap at dead space by tub; wall plate penetration 313: -Stud support under balcony beam -Fc plumbing penetration of wall and floor at tub and above laundry; media wall top plates 316: -Close/fc gap at all double stud wall spaces Protect electrical boxes 314: -Install collar for 6” roof drain 311: -Fc holes at top of laundry wall; Fc at bottom plate at tub 312: -Secure kitchen range and ceiling light cables within 12” of box 309: -Fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall -Close gap at top of double stud wall -Protect wiring below panel 310: -Provide a receptacle at panel wall space -Complete fur out at 6” roof drain 307: -Patch hole behind dryer -Fc penetration of elevator firewall 308: 305: -Provide a receptacle at panel wall space 306: 304: 303: -Gypsum at top lid of space adjacent to tub 302: -Fc top lid of space adjacent to shower -Install media box -Tie down trusses to balcony beam; tie down beam -Provide fire GB at stair tower 301: -Fc top lid of space adjacent to shower -Install media box -Tie down trusses to balcony beam; tie down beam
FOURTH FLOOR
Corrective Action Required
05/19/2025
Dwelling units only: -Draft-stop holes and gap between draftstops 7&8 -Install firestop at roof drain floor&ceiling penetrations per Hilti Instructions (403, 404, 411, 412) **Area outsie dwelling units not yet inspected
All Rough Inspection - Commercial Failed 5/29/2025 05/29/2025
Misc
Corrective Action Required
05/22/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/22/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/22/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/22/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/22/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/22/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Nail together balcony support 3-stud pack per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 -Check at demising walls adjacent to tubs, fc penetration of GB membrane -Check around elevator wall and fc all membrane penetration 318: 317: 315: 313: 316: 314: 311: 312: 309: -Close hole and fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall 310: -Complete fur out at 6” roof drain 307: 308: 305: 306: 304: 303: 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam **OK TO INSULATE
FOURTH FLOOR
Corrective Action Required
05/22/2025
Dwelling units only: -Install firestop at roof drain floor&ceiling penetrations per Hilti Instructions (403, 404, 411, 412) -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 **Area outsie dwelling units not yet inspected
All Rough Inspection - Commercial Failed 5/30/2025 5/30/2025 05/30/2025
Misc
Corrective Action Required
05/29/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/29/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/29/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/29/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/29/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/29/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Nail together balcony support 3-stud pack per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 -Check at demising walls adjacent to tubs, fc penetration of GB membrane -Check around elevator wall and fc all membrane penetration 318: 317: 315: 313: 316: 314: 311: 312: 309: -Close hole and fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall 310: -Complete fur out at 6” roof drain 307: 308: 305: 306: 304: 303: 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam **OK TO INSULATE
FOURTH FLOOR
Corrective Action Required
05/29/2025
Dwelling units only: -Install firestop at roof drain floor&ceiling penetrations per Hilti Instructions (403, 404, 411, 412) **Area outsie dwelling units not yet inspected
Rated Assembly Inspection Partial 6/2/2025 6/2/2025 06/02/2025
LOWER LEVEL
Corrective Action Required
04/17/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
04/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
04/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
04/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok
FOURTH FLOOR
Corrective Action Required
04/17/2025
-Tub&shower walls -mud&taped
STAIR TOWER 1
Corrective Action Required
04/17/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
STAIR TOWER 2
Corrective Action Required
04/17/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
STAIR TOWER 3
Corrective Action Required
04/17/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
04/17/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-1st layer&channel
Misc
Corrective Action Required
04/17/2025
Rated Assembly Inspection Partial 6/3/2025 6/3/2025 06/03/2025
LOWER LEVEL
Corrective Action Required
06/02/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/02/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/02/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/02/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok
FOURTH FLOOR
Corrective Action Required
06/02/2025
-Tub&shower walls -mud&taped
STAIR TOWER 3
Corrective Action Required
06/02/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/02/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-1st layer&channel; 2nd layer
Misc
Corrective Action Required
06/02/2025
STAIR TOWER 1
Corrective Action Required
06/02/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
STAIR TOWER 2
Corrective Action Required
06/02/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
All Rough Inspection - Commercial Failed 6/3/2025 06/03/2025
Misc
Corrective Action Required
05/30/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
05/30/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
05/30/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
05/30/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
05/30/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
05/30/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Nail together balcony support 3-stud pack per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 -Check at demising walls adjacent to tubs, fc penetration of GB membrane -Check around elevator wall and fc all membrane penetration 318: 317: 315: 313: 316: 314: 311: 312: 309: -Close hole and fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall 310: -Complete fur out at 6” roof drain 307: 308: 305: 306: 304: 303: 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam **OK TO INSULATE
FOURTH FLOOR
Corrective Action Required
05/30/2025
Dwelling units-OK to rock Corridor: -Install Simpson SDWC screw at each stud adjacent to the hold-down screw
All Rough Inspection - Commercial Partial 6/4/2025 6/4/2025 06/04/2025
Misc
Corrective Action Required
06/03/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/03/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/03/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
06/03/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
06/03/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
06/03/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Nail together balcony support 3-stud pack per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 -Check at demising walls adjacent to tubs, fc penetration of GB membrane -Check around elevator wall and fc all membrane penetration 318: 317: 315: 313: 316: 314: 311: 312: 309: -Close hole and fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall 310: -Complete fur out at 6” roof drain 307: 308: 305: 306: 304: 303: 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam **OK TO INSULATE
FOURTH FLOOR
Corrective Action Required
06/03/2025
Dwelling units-OK to rock Corridor- OK
Rated Assembly Inspection Partial 6/4/2025 6/4/2025 06/04/2025
LOWER LEVEL
Corrective Action Required
06/03/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/03/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/03/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/03/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok
FOURTH FLOOR
Corrective Action Required
06/03/2025
-Tub&shower walls -mud&taped
STAIR TOWER 3
Corrective Action Required
06/03/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/03/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-1st layer&channel; 2nd layer
Misc
Corrective Action Required
06/03/2025
STAIR TOWER 1
Corrective Action Required
06/03/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
STAIR TOWER 2
Corrective Action Required
06/03/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 1st layer
All Rough Inspection - Commercial Partial 6/5/2025 6/5/2025 06/05/2025
Misc
Corrective Action Required
06/04/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/04/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/04/2025
-Pre-rock behind tubs ad showers
FIRST FLOOR
Corrective Action Required
06/04/2025
-Pre-rock behind tubs ad showers
SECOND FLOOR
Corrective Action Required
06/04/2025
-Pre-rock behind tubs ad showers
THIRD FLOOR
Corrective Action Required
06/04/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Fire caulk all penetrations of corridor rim; all wall plate penetrations -Nail together balcony support 3-stud pack per plan -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Framing holdown and screws per 3B&4/S0.20 and C/S0.22 -Check at demising walls adjacent to tubs, fc penetration of GB membrane -Check around elevator wall and fc all membrane penetration 309: -Close hole and fc penetrations of corridor rim -Support dryer duct above rear master bedroom wall 310: -Complete fur out at 6” roof drain 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals; secure within 12" of EM light boxes
FOURTH FLOOR
Corrective Action Required
06/04/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/9/2025 06/09/2025
LOWER LEVEL
Corrective Action Required
06/04/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/04/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/04/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/04/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok
FOURTH FLOOR
Corrective Action Required
06/04/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/04/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/04/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/04/2025
STAIR TOWER 1
Corrective Action Required
06/04/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/04/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 6/9/2025 6/9/2025 06/09/2025
Misc
Corrective Action Required
06/05/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/05/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/05/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/05/2025
OK: -Pre-rock behind tubs ad showers Demising/shearwall in-wall corrections: -FB gap at top plates (101) -Anchor sill plates (110)
SECOND FLOOR
Corrective Action Required
06/05/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall
THIRD FLOOR
Corrective Action Required
06/05/2025
**Check all units -Fire stop all plumbing penetrations of floor per Hilti -Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair tower wall needs more work -Check around elevator wall and fc all membrane penetration 310: -Complete fur out at 6” roof drain 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/05/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/10/2025 6/10/2025 06/10/2025
LOWER LEVEL
Corrective Action Required
06/09/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/09/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/09/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/09/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations
FOURTH FLOOR
Corrective Action Required
06/09/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/09/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/09/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/09/2025
STAIR TOWER 1
Corrective Action Required
06/09/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/09/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 6/10/2025 06/10/2025
Misc
Corrective Action Required
06/09/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/09/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/09/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/09/2025
OK: -Pre-rock behind tubs ad showers Demising/shearwall in-wall corrections: -FB gap at top plates (101) -Anchor sill plates (110)
SECOND FLOOR
Corrective Action Required
06/09/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall
THIRD FLOOR
Corrective Action Required
06/09/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/09/2025
Dwelling units-OK Corridor- OK
All Rough Inspection - Commercial Partial 6/11/2025 6/11/2025 06/11/2025
Misc
Corrective Action Required
06/10/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/10/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/10/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/10/2025
OK: -Pre-rock behind tubs ad showers Demising/shearwall in-wall corrections: -FB gap at top plates (101) -Anchor sill plates (110)
SECOND FLOOR
Corrective Action Required
06/10/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Fc penetrations at shower&tub wall; Fc along edge -Nail stud packs per plan -Fc water line penetrations of corridor fire barrier wall -Check nail all hangers above balconies; support of balcony deck beam 218: -Protect wiring at bedroom top plate -Protect roof drain -Squash block above windows -Truss repair above master bathroom 217: -Rock&mud at top of double stud wall -Install long screw 215: -Nail 3x hanger at balcony -Protect wiring at bedroom top plate 213: 216: -Secure wiring within 12” of ceiling boxes 214: -Support (2)2x10 above balcony 211: -Engineer to address support of (2)2x10 above balcony 212: 209: -Engineer to address support of (2)2x10 above balcony -Fb gap at top of demising wall 210: -Top plate over-notched at balcony beam support -Squash block above bedroom window -Protect plumbing at master closet -Firestop roof drain at tub 207: -Fc along edge of elevator wall and at penetrations 208: 205: 206: -Squash block above windows -Protect dryer wiring at top plate **Stop at 206**
THIRD FLOOR
Corrective Action Required
06/10/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/10/2025
Dwelling units-OK Corridor- OK
All Rough Inspection - Commercial Partial 6/13/2025 06/13/2025
Misc
Corrective Action Required
06/11/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/11/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/11/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/11/2025
OK: -Pre-rock behind tubs ad showers Demising/shearwall in-wall corrections: -FB gap at top plates (101) -Anchor sill plates (110)
SECOND FLOOR
Corrective Action Required
06/11/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Fc penetrations at shower&tub wall; Fc along edge; Fc water line penetrations of corridor fire barrier wall -Check all squash block above bedroom window -Nail stud packs per plan -Check all support blocking under balcony beams -Nail hanger at balcony 218: -Truss repair above master bathroom 217: -Fb gap at double stud wall -Install long screws adjacent to door 215: -Add filler and nail hanger at balcony 213: 216: 214: 211: -Squashed blocks above windows not having min 1.5” of bearing 212: -Fb gap at top of demising wall 209: -Fb gap at top of demising wall -Provide 3-studs corner 210: -Strap across top plates at balcony beam support 207: -Fc along edge of elevator wall 208: 205: 206: 204: -Squash block above balcony door 203: 201: 202:
THIRD FLOOR
Corrective Action Required
06/11/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/11/2025
Dwelling units-OK Corridor- OK
All Rough Inspection - Commercial Partial 6/16/2025 6/16/2025 06/16/2025
Misc
Corrective Action Required
06/13/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/13/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/13/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/13/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall
SECOND FLOOR
Corrective Action Required
06/13/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 218: -Truss repair above master bathroom 211: -Squashed blocks above windows not having min 1.5” of bearing 212: -Fb gap at top of demising wall 209: -Fb gap at top of demising wall 206: -Install longer straps across cut plates at rear. Min 8 nails on each side of breaks
THIRD FLOOR
Corrective Action Required
06/13/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/13/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/17/2025 6/17/2025 06/17/2025
LOWER LEVEL
Corrective Action Required
06/10/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/10/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/10/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/10/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling, except unit 301
FOURTH FLOOR
Corrective Action Required
06/10/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/10/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/10/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/10/2025
STAIR TOWER 1
Corrective Action Required
06/10/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer *outer side 1st layer within ceiling space needs more screwing 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/10/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer *outer side 1st layer within ceiling space needs more screwing 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Failed 6/18/2025 6/18/2025 06/18/2025
Misc
Corrective Action Required
06/16/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/16/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/16/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/16/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall
SECOND FLOOR
Corrective Action Required
06/16/2025
K: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 218: -Truss repair above master bathroom 211: -Squashed blocks above windows not having min 1.5” of bearing 206: -Install longer straps across cut plates at rear. Min 8 nails on each side of breaks
THIRD FLOOR
Corrective Action Required
06/16/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/16/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/20/2025 6/20/2025 06/20/2025
LOWER LEVEL
Corrective Action Required
06/17/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/17/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/17/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/17/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/17/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/17/2025
STAIR TOWER 1
Corrective Action Required
06/17/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer -dwelling sides 1st layer *Fc penetrations of firewall at truss hangers 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/17/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer 3rd floor: -stair side 2nd layer -dwelling sides 1st layer *Fc penetrations of firewall at truss hangers 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 6/20/2025 6/20/2025 06/20/2025
Misc
Corrective Action Required
06/18/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/18/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/18/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/18/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Fc penetrations of demising wall at tub -Fc penetrations of corridor wall rim -Nail together stud packs -Nail balcony hanger 101: -Seal gap at top of kitchen wall -Fc wall plates at ATS rod; Fc gap at dead space adjacent to shower; Fc wall penetration -Protect sprinkler pipe at bedroom -Missing stud at closet wall -Damaged truss near entry door 102: -Nail balcony hanger -Check squash block above bathroom doorway 103: -Strap cut top plate at balcony beam -Fc gap at laundry wall; Fc penetrations of corridor wall 104: -Screw kitchen/corridor GB to bottom plate -Nail cantilevered joists hangers at LVL beam connections -Fc along edge of elevator firewall Elevator wall/stair 3 wall-ok for 1st layer. Remove stud for GB 105: -Nail cantilevered joists hangers at LVL beam connections -Secure NM near EM light box 106: -Secure NM near EM light box 107: 108: -Screw GB to bottom plate -Seal gap at top of kitchen wall 109: -Fc gap at top of tub wall 110: -Nail corner studs -Not ready
SECOND FLOOR
Corrective Action Required
06/18/2025
K: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 218: -Truss repair above master bathroom 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
06/18/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/18/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/23/2025 6/23/2025 06/23/2025
LOWER LEVEL
Corrective Action Required
06/20/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/20/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/20/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/20/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/20/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/20/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/20/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 1st layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 1st layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/20/2025
STAIR TOWER 1
Corrective Action Required
06/20/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer *Mud and tape all seams *Fc penetrations of firewall at truss hangers 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/20/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer **Mud and tape all seams 4th floor: -outer side 2nd layer
Rated Assembly Inspection Partial 6/24/2025 06/24/2025
LOWER LEVEL
Corrective Action Required
06/23/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/23/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/23/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/23/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/23/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/23/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/23/2025
Lower floor: -004 dwelling side 2nd layer 1st floor: -104 dwelling side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 1st layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 1st layer 4th floor: -405/407 dwelling side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/23/2025
STAIR TOWER 1
Corrective Action Required
06/23/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer *Fc penetrations of firewall (302). Protect fw above unit 304 closet 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/23/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer **Fc firewall penetrations (318) 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 6/24/2025 6/24/2025 06/24/2025
Misc
Corrective Action Required
06/20/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/20/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl-one side sheathed -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/20/2025
OK: -Pre-rock behind tubs and showers Demising/shearwall in-wall correction: -Vent cloth washer trap (006)
FIRST FLOOR
Corrective Action Required
06/20/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 102: 103: 104: -Fc along edge of elevator firewall 105: 106: 107: 108: 109: 110: -Not ready
SECOND FLOOR
Corrective Action Required
06/20/2025
K: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 218: -Truss repair above master bathroom 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
06/20/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/20/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 6/26/2025 6/26/2025 06/26/2025
LOWER LEVEL
Corrective Action Required
06/24/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/24/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/24/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
THIRD FLOOR
Corrective Action Required
06/24/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/24/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/24/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/24/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 1st layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 1st layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/24/2025
STAIR TOWER 1
Corrective Action Required
06/24/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer *Fc penetrations of firewall (302). Protect fw above unit 304 closet 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/24/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 1st layer 3rd floor: -stair side 2nd layer -outer side 2nd layer **Fc firewall penetrations (318) 4th floor: -outer side 2nd layer
Rated Assembly Inspection Partial 6/30/2025 06/30/2025
LOWER LEVEL
Corrective Action Required
06/26/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/26/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/26/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing -Dwelling demising walls and ceiling
THIRD FLOOR
Corrective Action Required
06/26/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/26/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/26/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/26/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/26/2025
STAIR TOWER 1
Corrective Action Required
06/26/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer 3rd floor: -stair side 2nd layer -outer side 2nd layer 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/26/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer 3rd floor: -stair side 2nd layer -outer side 2nd layer 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 6/30/2025 06/30/2025
Misc
Corrective Action Required
06/24/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/24/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/24/2025
OK: -Pre-rock behind tubs and showers **Check all -Fb corridors wall per code -Nail balcony joist hangers -Repair trusses per engineer letter -Extend dryer and bath fans duct to ceiling level 001: -Fb gap at top of wall; vertical fb at max 10 ft -Anchor sill plate near door -Protect plumbing 002: -Squash block above doorway 003: -Patch wall behind tub -3x squash block above window 004: -Fc edges and penetrations of elevator wall -Fc penetration of corridor wall behind tub 005: -Add another anchor at short sill plate near door 006: -Squash block above doorway -Fc penetration of corridor wall behind tub -Add another anchor at short sill plate near door -Laundry venting 007: -Protect water lines -Squash block above window 008: -Fb gap at top of wall; vertical fb at max 10 ft
FIRST FLOOR
Corrective Action Required
06/24/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 102: 103: 104: 105: 106: 107: 108: 109: 110: -Not ready
SECOND FLOOR
Corrective Action Required
06/24/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
06/24/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/24/2025
Dwelling units-OK Corridor- OK
Above Ceiling Inspection Partial 7/1/2025 7/1/2025 07/01/2025
Misc
Corrective Action Required
04/17/2025
**Area at accessible garages/IT closet/Storage not ready
CORRIDORS
Corrective Action Required
07/01/2025
Lower level and 1st floor not inspected 2-4th floors correction-Mud and Fc holes and penetrations
Rated Assembly Inspection Partial 7/1/2025 7/1/2025 07/01/2025
LOWER LEVEL
Corrective Action Required
06/30/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
06/30/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
06/30/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing -Dwelling demising walls and ceiling
THIRD FLOOR
Corrective Action Required
06/30/2025
-Tub&shower walls -mud&taped -Corridor ceiling pre-rock ok -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling
FOURTH FLOOR
Corrective Action Required
06/30/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
06/30/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
06/30/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
06/30/2025
STAIR TOWER 1
Corrective Action Required
06/30/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
06/30/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
Above Ceiling Inspection Partial 7/3/2025 7/3/2025 07/03/2025
Misc
Corrective Action Required
07/01/2025
**Area at accessible garages/IT closet/Storage not ready
CORRIDORS
Corrective Action Required
07/01/2025
Lower level and 1st floor not inspected 2->4th floors-OK
Rated Assembly Inspection Partial 7/3/2025 07/03/2025
LOWER LEVEL
Corrective Action Required
07/01/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
07/01/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing
SECOND FLOOR
Corrective Action Required
07/01/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/01/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/01/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/01/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
07/01/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/01/2025
STAIR TOWER 1
Corrective Action Required
07/01/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/01/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
Rated Assembly Inspection Partial 7/10/2025 7/9/2025 07/09/2025
LOWER LEVEL
Corrective Action Required
07/03/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
07/03/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
07/03/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/03/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/03/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/03/2025
**THIS IS REAR STAIR B** OK to rock the shear wall
ELEVATOR 1
Corrective Action Required
07/03/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/03/2025
STAIR TOWER 1
Corrective Action Required
07/03/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/03/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 7/14/2025 7/14/2025 07/14/2025
Misc
Corrective Action Required
06/30/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
06/30/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
06/30/2025
OK: -Pre-rock behind tubs and showers **Check all -Fb corridors wall per code -Nail balcony joist hangers -Repair trusses per engineer letter -Extend dryer and bath fans duct to patio ceiling level -Fb opening at top plates between the two 2x4 (space adjacent to tub) 001: -Fasten bedroom/bathroom wall to floor and protect plumbing 002: 003: -Fc gap at top 004: -Fc penetration of corridor wall behind tub **Pump more firecaulk into gap -Mud&tape elevator FW seams 005: 006: -Squash block above doorway to bathroom 007: 008:
FIRST FLOOR
Corrective Action Required
06/30/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 102: 103: 104: 105: 106: 107: 108: 109: 110: -Not ready
SECOND FLOOR
Corrective Action Required
06/30/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
06/30/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
06/30/2025
Dwelling units-OK Corridor- OK
All Rough Inspection - Commercial Partial 7/16/2025 7/16/2025 07/16/2025
Misc
Corrective Action Required
07/14/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
07/14/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
07/14/2025
OK: -Pre-rock behind tubs and showers **Check all -Nail balcony joist hangers -Repair trusses per engineer letter -Extend dryer and bath fans duct to patio ceiling level -Fb opening at top plates between the two 2x4 (space adjacent to tub) 004: -Mud&tape elevator FW seams
FIRST FLOOR
Corrective Action Required
07/14/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
07/14/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
07/14/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
07/14/2025
Dwelling units-OK Corridor- OK
Above Ceiling Inspection Partial 7/16/2025 07/16/2025
Misc
Corrective Action Required
07/03/2025
**Area at accessible garages/IT closet/Storage not ready
CORRIDORS
Corrective Action Required
07/03/2025
Lower level, 2->4th floors-OK 1st floor not inspected
All Rough Inspection - Commercial Partial 7/18/2025 7/18/2025 07/18/2025
Misc
Corrective Action Required
07/16/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
07/16/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
07/16/2025
OK: -Pre-rock behind tubs and showers **Check all -Nail balcony joist hangers -Repair trusses per engineer letter (002, 004, 007) 004: -Mud&tape seam at elevator wall; fb gap at top of laundry wall
FIRST FLOOR
Corrective Action Required
07/16/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
07/16/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Check all -Nail hanger at balcony 211: -Squashed blocks above windows not having min 1.5” of bearing
THIRD FLOOR
Corrective Action Required
07/16/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
07/16/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 7/18/2025 07/18/2025
LOWER LEVEL
Corrective Action Required
07/09/2025
-Tub&shower walls -mud&taped
FIRST FLOOR
Corrective Action Required
07/09/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
07/09/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/09/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling demising walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/09/2025
-Tub&shower walls -mud&taped -Dwelling demising walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/09/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
07/09/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/09/2025
STAIR TOWER 1
Corrective Action Required
07/09/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/09/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 7/21/2025 7/21/2025 07/21/2025
Misc
Corrective Action Required
07/18/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
07/18/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
07/18/2025
OK: -Pre-rock behind tubs and showers -Nail balcony joist hangers -Mud&tape seam at elevator wall at unit 004
FIRST FLOOR
Corrective Action Required
07/18/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
07/18/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall -202 cantilevered beam and trusses repair **Corrections: -201 cantilevered beam not fully bear on wall -Nail hanger at balcony -Squashed blocks above windows not having min 1.5” of bearing. Repair truss
THIRD FLOOR
Corrective Action Required
07/18/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
07/18/2025
Dwelling units-OK Corridor- OK
All Rough Inspection - Commercial Partial 7/28/2025 7/28/2025 07/28/2025
Misc
Corrective Action Required
07/21/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
07/21/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
07/21/2025
OK: -Pre-rock behind tubs and showers -Nail balcony joist hangers -Mud&tape seam at elevator wall at unit 004
FIRST FLOOR
Corrective Action Required
07/21/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
07/21/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall -202 cantilevered beams and trusses repair **Corrections: -Nail hanger at balcony
THIRD FLOOR
Corrective Action Required
07/21/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
07/21/2025
Dwelling units-OK Corridor- OK
Rated Assembly Inspection Partial 7/28/2025 7/28/2025 07/28/2025
LOWER LEVEL
Corrective Action Required
07/18/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling
FIRST FLOOR
Corrective Action Required
07/18/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
07/18/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/18/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/18/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/18/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
07/18/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/18/2025
STAIR TOWER 1
Corrective Action Required
07/18/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/18/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
Rated Assembly Inspection Partial 7/30/2025 7/30/2025 07/30/2025
LOWER LEVEL
Corrective Action Required
07/28/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor
FIRST FLOOR
Corrective Action Required
07/28/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
07/28/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/28/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/28/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/28/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
07/28/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/28/2025
STAIR TOWER 1
Corrective Action Required
07/28/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/28/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer -corridor side 1st layer -above ceiling space 1st layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
All Rough Inspection - Commercial Partial 8/5/2025 8/5/2025 08/05/2025
Misc
Corrective Action Required
07/28/2025
Front garage PFH walls only: -Provide 2 anchors per wall sill plate -Nail wall top plate to header w/ 2 rows of 16d @ 3" oc
Misc
Corrective Action Required
07/28/2025
Interior and exterior sheathed shearwalls: -lower level, 1st, and 2nd fl -exterior shearwalls
LOWER LEVEL
Corrective Action Required
07/28/2025
OK: -Pre-rock behind tubs and showers -Nail balcony joist hangers -Mud&tape seam at elevator wall at unit 004
FIRST FLOOR
Corrective Action Required
07/28/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall **Dwelling units only **Check all: -Nail balcony hanger 101: -Missing stud at closet wall -Damaged trusses near entry door and at kitchen 110: -Not ready
SECOND FLOOR
Corrective Action Required
07/28/2025
OK: -Pre-rock behind tubs ad showers -Demising/shearwall in-wall -202 cantilevered beams and trusses repair **Corrections: -Nail hanger at balcony
THIRD FLOOR
Corrective Action Required
07/28/2025
-Access to roof space above end units -Frame the cantilevered balcony roof per 2/S3.42 -1st layer inside ceiling space at stair towers wall needs more work. Add blockings where required and nail GB 302: -Tie down trusses to balcony beam; tie down beam 301: -Tie down trusses to balcony beam; tie down beam Corridor: -Secure EM light wiring at max 4.5 ft intervals
FOURTH FLOOR
Corrective Action Required
07/28/2025
Dwelling units-OK Corridor- OK
ELEVATOR 1
Corrective Action Required
08/05/2025
shaft-okay
STAIR TOWER 1
Corrective Action Required
08/05/2025
ceiling okay to cover
STAIR TOWER 2
Corrective Action Required
08/05/2025
ceiling okay to cover
Rated Assembly Inspection Failed 8/6/2025 8/6/2025 08/06/2025
LOWER LEVEL
Corrective Action Required
07/30/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor
FIRST FLOOR
Corrective Action Required
07/30/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
07/30/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
07/30/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
07/30/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
07/30/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
07/30/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
07/30/2025
STAIR TOWER 1
Corrective Action Required
07/30/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
STAIR TOWER 2
Corrective Action Required
07/30/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer -corridor side 1st layer -above ceiling space 1st layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer
Rated Assembly Inspection Partial 8/8/2025 8/8/2025 08/08/2025
LOWER LEVEL
Corrective Action Required
08/06/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor
FIRST FLOOR
Corrective Action Required
08/06/2025
-Tub&shower walls -mud&taped -Corridor ceiling nailing **Dwelling demising walls and ceiling OK, except units 101, 110
SECOND FLOOR
Corrective Action Required
08/06/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
THIRD FLOOR
Corrective Action Required
08/06/2025
-Tub&shower walls -mud&taped -Firestop of floor&ceiling penetrations -Dwelling walls and ceiling -Corridor walls and ceiling
FOURTH FLOOR
Corrective Action Required
08/06/2025
-Tub&shower walls -mud&taped -Dwelling walls and ceiling -Corridor walls and ceiling
STAIR TOWER 3
Corrective Action Required
08/06/2025
**THIS IS REAR STAIR B** -Wall protected inside floor space in units 004&005
ELEVATOR 1
Corrective Action Required
08/06/2025
Lower floor: -004 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 1st floor: -104 dwelling side 2nd layer -corridor side 1st layer -stair side 2nd layer 2nd floor: -207/209 dwelling side 2nd layer -corridor side 2nd layer 3rd floor: -307/309 dwelling side 2nd layer -corridor side 2nd layer -inner side 1st layer 4th floor: -405/407 dwelling side 2nd layer -inner side 1st layer -corridor side 2nd layer -Top lid-complete
Misc
Corrective Action Required
08/06/2025
STAIR TOWER 1
Corrective Action Required
08/06/2025
**THIS IS NORTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer -1st layer and rc ceiling
STAIR TOWER 2
Corrective Action Required
08/06/2025
**THIS IS SOUTH STAIR A** Lower floor: -stair side 2nd layer -outer side 1st layer 1st floor: -stair side 2nd layer -corridor side 1st layer -above ceiling space 1st layer 2nd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 3rd floor: -stair side 2nd layer -outer side 2nd layer -Fc wall penetrations and along edge in floor space 4th floor: -outer side 2nd layer -1st layer and rc ceiling
Documents & Images
Date Uploaded File Type Document Name
10/16/2023 Receipt Receipt for transaction: 2023-007795
10/16/2023 Letter DS Building Permit
04/01/2024 Letter INSPECTION SUMMARY
04/04/2024 Letter INSPECTION SUMMARY
04/04/2024 Letter INSPECTION SUMMARY
04/08/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
05/03/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
06/05/2024 Letter INSPECTION SUMMARY
06/14/2024 Letter INSPECTION SUMMARY
06/19/2024 RB-0B_LH-Calc-06-18-2024 Stamped
06/19/2024 RB-04-13RCalc-06-18-2024 Stamped
06/19/2024 RB-FP1-06-18-2024 Model Stamped
06/19/2024 RB-FP2-06-18-2024 Model Stamped
06/19/2024 RB-FP3-06-18-2024 Model Stamped
06/19/2024 RB-ST-Calc-06-18-2024 Stamped
07/03/2024 Letter Fire (Sprinkler) Plan Review
08/01/2024 Letter INSPECTION SUMMARY
08/02/2024 Letter INSPECTION SUMMARY
08/07/2024 Alliance Fire Protection Combined FP drawings 8-7-24
08/12/2024 Receipt Receipt for transaction: 2024-006799
08/12/2024 Letter DS Building Permit
09/12/2024 Letter INSPECTION SUMMARY
09/17/2024 24050258 Blackwell product data (apts only)
09/17/2024 24050258 Blackwell CH & apartments-FA-set-rev sealed
09/17/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/26/2024 Letter INSPECTION SUMMARY
09/26/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter Fire (Alarm) Plan Review Notice
10/03/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter Fire (Alarm) Plan Review Notice
12/19/2024 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
01/28/2025 Letter INSPECTION SUMMARY
01/29/2025 Letter INSPECTION SUMMARY
01/30/2025 24050258 Blackwell apartment only- FA-set rev_1(sealed)
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/07/2025 24050258 Blackwell apartment only- FA-set rev_1(sealed) RFC
02/07/2025 Letter Fire (Alarm) Plan Review Notice
02/11/2025 Letter INSPECTION SUMMARY
02/18/2025 Letter INSPECTION SUMMARY
02/26/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/11/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/14/2025 Letter INSPECTION SUMMARY
03/18/2025 Letter INSPECTION SUMMARY
03/20/2025 Letter INSPECTION SUMMARY
03/20/2025 Letter INSPECTION SUMMARY
03/24/2025 Letter INSPECTION SUMMARY
03/26/2025 Letter INSPECTION SUMMARY
04/01/2025 Letter INSPECTION SUMMARY
04/03/2025 Letter INSPECTION SUMMARY
04/08/2025 Letter INSPECTION SUMMARY
04/08/2025 Letter INSPECTION SUMMARY
04/17/2025 Letter INSPECTION SUMMARY
04/25/2025 Letter INSPECTION SUMMARY
04/25/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/12/2025 Letter INSPECTION SUMMARY
05/15/2025 Letter INSPECTION SUMMARY
05/19/2025 Letter INSPECTION SUMMARY
05/22/2025 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
05/30/2025 Letter INSPECTION SUMMARY
06/02/2025 Letter INSPECTION SUMMARY
06/03/2025 Letter INSPECTION SUMMARY
06/03/2025 Letter INSPECTION SUMMARY
06/04/2025 Letter INSPECTION SUMMARY
06/04/2025 Letter INSPECTION SUMMARY
06/05/2025 Letter INSPECTION SUMMARY
06/09/2025 Letter INSPECTION SUMMARY
06/09/2025 Letter INSPECTION SUMMARY
06/10/2025 Letter INSPECTION SUMMARY
06/10/2025 Letter INSPECTION SUMMARY
06/11/2025 Letter INSPECTION SUMMARY
06/13/2025 Letter INSPECTION SUMMARY
06/16/2025 Letter INSPECTION SUMMARY
06/17/2025 Letter INSPECTION SUMMARY
06/18/2025 Letter INSPECTION SUMMARY
06/20/2025 Letter INSPECTION SUMMARY
06/23/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/24/2025 Letter INSPECTION SUMMARY
06/26/2025 Letter INSPECTION SUMMARY
06/30/2025 Letter INSPECTION SUMMARY
06/30/2025 Letter INSPECTION SUMMARY
07/01/2025 Letter INSPECTION SUMMARY
07/01/2025 Letter INSPECTION SUMMARY
07/03/2025 Blackwell Building 3 - Lower Level Truss Repair
07/03/2025 Letter INSPECTION SUMMARY
07/03/2025 Letter INSPECTION SUMMARY
07/14/2025 Letter INSPECTION SUMMARY
07/14/2025 Letter INSPECTION SUMMARY
07/14/2025 Letter INSPECTION SUMMARY
07/16/2025 Letter INSPECTION SUMMARY
07/16/2025 Letter INSPECTION SUMMARY
07/18/2025 Letter INSPECTION SUMMARY
07/18/2025 Letter INSPECTION SUMMARY
07/28/2025 Letter INSPECTION SUMMARY
07/28/2025 Letter INSPECTION SUMMARY
07/30/2025 Letter INSPECTION SUMMARY
07/30/2025 Letter INSPECTION SUMMARY
07/13/2023 Approved Plans approved - volume 1
07/13/2023 Approved Plans approved - volume 2
08/05/2025 Letter INSPECTION SUMMARY
08/06/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents