Permit Application Status

PRCOM20235681


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20235681
Building Permit - Commercial
Issued
JEFFREY E SMITH INV CO LC
NEW MULTI-FAMILY
NEW AGE RESTRICTED APARTMENT BUILDING
10/31/2023
04/15/2025
09/25/2024
Locations
Contacts
Fairway Construction Co., Inc., Address:3290 NORTHSIDE PKWY NW  
Eric Brundick - Fairway Construction, Phone:(573) 476-8264  
BENCHMARK MECHANICAL LLC, Address:5 SW 4TH ST, Phone:(816) 524-5616  
KASA ELECTRIC LLC, Address:1206 NW VALLEY RIDGE DR, Phone:(816) 228-4886  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
ROSEMANN & ASSOCIATES, Address:1526 GRAND BLVD, Phone:(816) 472-1448  
ENGINEERING SURVEYS & SERVICES, Address:1113 FAY ST, Phone:(573) 449-2646  
JEFFREY E SMITH INV CO LC, Address:PO BOX 7688  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Rejected 06/06/2025 06/02/2025
Craig Hill
Misc
Corrective Action Required
06/02/2025

Action Required: Change fire department connection to a 4" with a 30 degree elbow.
Alarm Plan Review Rejected 12/24/2024 12/24/2024
Craig Hill
Alarms connected to automatic sprinkler system
Corrective Action Required
12/16/2024

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Information Only
Alarm testing.
Corrective Action Required
12/16/2024

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Action Required: Call (816) 969-1300 for testing.
Misc
Corrective Action Required
12/19/2024

No business license on file for the alarm company. A call was placed to the alarm company and a message was left.
Fire Plan Review Approved with Conditions 10/18/2024 10/18/2024
Craig Hill
Construction documents for fire alarm systems
Informational
10/10/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Acknowledged
Construction documents - Fire protection systems
Informational
10/10/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Miscellaneous Correction
Corrective Action Required
10/10/2024

Hydrants and the base asphalt layer of the parking lot shall be in place before going vertical with combustible construction or storage of combustible building materials on site. This comment refers to fire hydrants, not wall hydrants.
Building Plan Review Approved with Conditions 10/18/2024 10/14/2024
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/10/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $13,600.00 3/25/24 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
10/10/2024

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
10/10/2024

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Certificate of Inspection
Corrective Action Required
10/10/2024

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Building Plan Review Approved with Conditions 04/26/2024 08/27/2024
Joe Frogge
Final Development Plan
Resolved
08/27/2024

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Miscellaneous Correction
Corrective Action Required
04/19/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $13,600.00 3/25/24 - acknowledged in letter
Elevator Equipment Permit
Corrective Action Required
04/19/2024

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
04/19/2024

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Certificate of Inspection
Corrective Action Required
04/19/2024

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is informational. 3/25/24 - acknowledged in letter
IBC 706.1 Fire and Smoke Protection - General
Resolved
04/26/2024

2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. Actions required: - - Specify fire ratings for doors 1004, 1006, 1007, 2002, 3001, 3002, 3003 3/25/24 - Ratings not found for doors 1007, 2002, 3001, 3002, 3003
IBC 1209.2 Finish materials
Resolved
04/26/2024

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Amend designs to demonstrate compliance at public restrooms and at mop sink. 3/25/24 - Provide description/spec for R.V.S. We are not familiar with this material. (Google searches show me nothing but recreation vehicle walls)
Licensed Contractors Approved 04/26/2024 08/27/2024
Joe Frogge
LC - General Contractor
Resolved
08/27/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 3/25/24 - acknowledged in letter
LC - MEP Subs
Resolved
08/27/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/25/24 - acknowledged in letter
Final Development Plan Review Approved 08/09/2024 07/31/2024
Daniel Fernandez
Fire Plan Review Approved with Conditions 04/26/2024 04/25/2024
Craig Hill
Construction documents for fire alarm systems
Informational
04/19/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Acknowledged
Construction documents - Fire protection systems
Informational
04/19/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Miscellaneous Correction
Corrective Action Required
04/19/2024

Hydrants and the base asphalt layer of the parking lot shall be in place before going vertical with combustible construction or storage of combustible building materials on site. This comment refers to fire hydrants, not wall hydrants.
Fire Plan Review Approved with Conditions 03/27/2024 03/28/2024
Jim Eden
Construction documents for fire alarm systems
Informational
03/28/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Acknowledged
Address numbers required
Resolved
03/28/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Construction documents - Fire protection systems
Informational
03/28/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Miscellaneous Correction
Resolved
03/28/2024

The range hood suppression system in the community room shall be connected to the building fire alarm. Confirmed at inspection and life safety testing.
Miscellaneous Correction
Resolved
03/28/2024

Confirm meeting room 3001 will have tables and chairs (OL43) to meet the egress configuration for the room.
Miscellaneous Correction
Corrective Action Required
03/20/2024

Hydrants and the base asphalt layer of the parking lot shall be in place before going vertical with combustible construction or storage of combustible building materials on site. This comment refers to fire hydrants, not wall hydrants.
Knox box required
Resolved
03/28/2024

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required- Provide a Knox box 6' AFF over the FDC.
Key boxes for non-standardized fire service elevator keys
Resolved
03/28/2024

2018 IFC 506.1.2 Key boxes for non-standardized fire service elevator keys. Key boxes provided for non-standardized fire service elevator keys shall comply with Section 506.1 and 506.2 or as approved by the fire code official. Action required- Provide a KNox elevator key box on the first floor at the elevator.
Building Plan Review Rejected 03/27/2024 03/25/2024
Joe Frogge
Final Development Plan
Corrective Action Required
03/20/2024

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Miscellaneous Correction
Corrective Action Required
03/20/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $13,600.00 3/25/24 - acknowledged in letter
IBC 1704.2 Special Inspections
Resolved
03/25/2024

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Elevator Equipment Permit
Corrective Action Required
03/20/2024

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Equipment Inspection
Corrective Action Required
03/20/2024

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is informational. 3/25/24 - acknowledged in letter
Elevator Certificate of Inspection
Corrective Action Required
03/20/2024

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is informational. 3/25/24 - acknowledged in letter
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
03/20/2024

2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. Actions required: - - Specify fire ratings for doors 1004, 1006, 1007, 2002, 3001, 3002, 3003 3/25/24 - Ratings not found for doors 1007, 2002, 3001, 3002, 3003
IBC 1704.2 Special Inspections
Resolved
03/25/2024

2018 IBC 1705.1 General. Special inspections and tests of elements and non-structural components of buildings and structures shall meet the applicable requirements of this section. Action required: Amend Special Inspection Criteria on sheet S-001 to cover truss inspections per 2018 IBC 1705.5.2.
ICC A117.1 604.3.1 Water closet width
Resolved
03/25/2024

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clear behind Restrooms RR 1007, RR 2002, and RR 3003.
IBC 602.1 Type of Construction - general
Resolved
04/19/2024

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Amend designs to show how structural elements of front canopy are protected per Table 601. 3/25/24 - Either amend as requested or rate walls per IBC Table 602.
IBC 1107.6.1.1 Accessible units - accessibility
Resolved
03/25/2024

2018 IBC 1107.6.1.1 Accessible units. Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1. On a multiple-building site, where structures contain more than 50 dwelling units or sleeping units, the number of Accessible units shall be determined per structure. On a multiple-building site, where structures contain 50 or fewer dwelling units or sleeping units, all dwelling units and sleeping units on a site shall be considered to determine the total number of accessible units. Accessible units shall be dispersed among the various classes of units. Action required: Provide complete bedroom unit plans for accessible units. (ICC/ANSI Type A)
IBC 1209.2 Finish materials
Corrective Action Required
03/20/2024

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Amend designs to demonstrate compliance at public restrooms and at mop sink. 3/25/24 - Provide description/spec for R.V.S. We are not familiar with this material. (Google searches show me nothing but recreation vehicle walls)
IMC 504.8.4 Domestic Dryer duct length
Resolved
03/25/2024

2018 IMC 504.8.5 Length Identification. Where the exhaust duct equivalent length exceeds 35 feet, the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet of the exhaust duct connection. Action required: Provide signs to comply.
IPC 916.3 Island vent installation below flood level rim
Resolved
03/25/2024

2018 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting to show required cleanout(s).
NEC Article 230.2 (E) Identification of multiple services
Resolved
03/25/2024

2017 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Add "..of 3" to services #1 and #2.
Licensed Contractors Rejected 03/27/2024 03/25/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
03/20/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 3/25/24 - acknowledged in letter
LC - MEP Subs
Corrective Action Required
03/20/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/25/24 - acknowledged in letter
Special Inspections Review Approved 03/25/2024
Joe Frogge
Fire Plan Review Approved with Conditions 12/06/2023 12/07/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
12/06/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Address numbers required
Corrective Action Required
12/06/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Construction documents - Fire protection systems
Corrective Action Required
12/06/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Miscellaneous Correction
Corrective Action Required
12/06/2023

The range hood suppression system in the community room shall be connected to the building fire alarm. Confirmed at inspection and life safety testing.
Miscellaneous Correction
Corrective Action Required
12/06/2023

Confirm meeting room 3001 will have tables and chairs (OL43) to meet the egress configuration for the room.
Miscellaneous Correction
Corrective Action Required
12/06/2023

Hydrants and the base asphalt layer of the parking lot shall be in place before going vertical with combustible construction or storage of combustible building materials on site.
Knox box required
Corrective Action Required
12/06/2023

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required- Provide a Knox box 6' AFF over the FDC.
Key boxes for non-standardized fire service elevator keys
Corrective Action Required
12/06/2023

2018 IFC 506.1.2 Key boxes for non-standardized fire service elevator keys. Key boxes provided for non-standardized fire service elevator keys shall comply with Section 506.1 and 506.2 or as approved by the fire code official. action required- Provide a KNox elevator key box on the first floor at the elevator.
Building Plan Review Rejected 11/14/2023 11/06/2023
Joe Frogge
Final Development Plan
Corrective Action Required
11/06/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Miscellaneous Correction
Corrective Action Required
11/06/2023

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. The fee will be $13,600.00
IBC 1704.2 Special Inspections
Corrective Action Required
11/06/2023

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Elevator Equipment Permit
Corrective Action Required
11/06/2023

Prior to the installation or construction of any elevator equipment, an elevator equipment permit shall be obtained from the Missouri Department of Public Safety or its authorized representative. Action required: Comment is informational.
Elevator Equipment Inspection
Corrective Action Required
11/06/2023

Prior to the operation of any new elevator equipment or the issuance of the operating certificate, such elevator equipment shall be inspected by a licensed inspector. Testing must be performed in accordance with these rules and regulations. The testing must be witnessed by a licensed inspector. Action required: Comment is informational.
Elevator Certificate of Inspection
Corrective Action Required
11/06/2023

Elevator Safety Act and Rules 701.361 - Each privately owned or operated installation and each installation owned or operated by the state of Missouri or any political subdivision of the state shall have a certificate of inspection and meet the safety code promulgated pursuant to sections 701.350 to 701.380. Action required: Comment is informational.
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
11/06/2023

2018 IBC 703.2 Fire-resistance ratings. The fire-resistance rating of building elements, components or assemblies shall be determined in accordance with the test procedures set forth in ASTM E 119 or UL 263 or in accordance with Section 703.3. The fire-resistance rating of penetrations and fire-resistant joint systems shall be determined in accordance Sections 714 and 715, respectively. Actions required: - Provide UL assembly details for U356 (wall designation P30) - Specify fire ratings for doors 1004, 1006, 1007, 2002, 3001, 3002, 3003
IBC 1704.2 Special Inspections
Corrective Action Required
11/06/2023

2018 IBC 1705.1 General. Special inspections and tests of elements and non-structural components of buildings and structures shall meet the applicable requirements of this section. Action required: Amend Special Inspection Criteria on sheet S-001 to cover truss inspections per 2018 IBC 1705.5.2.
ICC A117.1 604.3.1 Water closet width
Corrective Action Required
11/06/2023

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clear behind Restrooms RR 1007, RR 2002, and RR 3003.
IBC 602.1 Type of Construction - general
Corrective Action Required
11/06/2023

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Action required: Amend designs to show how structural elements of front canopy are protected per Table 601.
IBC 1107.6.1.1 Accessible units - accessibility
Corrective Action Required
11/06/2023

2018 IBC 1107.6.1.1 Accessible units. Accessible dwelling units and sleeping units shall be provided in accordance with Table 1107.6.1.1. On a multiple-building site, where structures contain more than 50 dwelling units or sleeping units, the number of Accessible units shall be determined per structure. On a multiple-building site, where structures contain 50 or fewer dwelling units or sleeping units, all dwelling units and sleeping units on a site shall be considered to determine the total number of accessible units. Accessible units shall be dispersed among the various classes of units. Action required: Provide complete bedroom unit plans for accessible units. (ICC/ANSI Type A)
IBC 1209.2 Finish materials
Corrective Action Required
11/06/2023

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) Action required: Amend designs to demonstrate compliance at public restrooms and at mop sink.
IMC 504.8.4 Domestic Dryer duct length
Corrective Action Required
11/06/2023

2018 IMC 504.8.5 Length Identification. Where the exhaust duct equivalent length exceeds 35 feet, the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet of the exhaust duct connection. Action required: Provide signs to comply.
IPC 916.3 Island vent installation below flood level rim
Corrective Action Required
11/08/2023

2018 IPC 916.3 Vent installation below the fixture flood level rim. The vent located below the flood level rim of the fixture being vented shall be installed as required for drainage piping in accordance with Chapter 7, except for sizing. The vent shall be sized in accordance with Section 906.2. The lowest point of the island fixture vent shall connect full size to the drainage system. The connection shall be to a vertical drain pipe or to the top half of a horizontal drain pipe. Cleanouts shall be provided in the island fixture vent to permit rodding of all vent piping located below the flood level rim of the fixtures. Rodding in both directions shall be permitted through a cleanout. Action required: Modify island fixture vent venting to show required cleanout(s).
NEC Article 230.2 (E) Identification of multiple services
Corrective Action Required
11/08/2023

2017 NEC Article 230.2 (E) Identification. Where a building or structure is supplied by more than one service, or any combination of branch circuits, feeders, and services, a permanent plaque or directory shall be installed at each service disconnect location denoting all other services, feeders, and branch circuits supplying that building or structure and the area served by each. See 225.37. Action required: Add "..of 3" to services #1 and #2.
Licensed Contractors Rejected 11/14/2023 11/06/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
11/06/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
11/06/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Multi-Family $35,000.00 $35,000.00 Paid 08/28/2024
7232302-Residential Excise Tax Fee $13,600.00 $13,600.00 Paid 08/28/2024
91100C8-Sanitary Sewer Insp Fees $419.52 $419.52 Paid 09/20/2024
9110081-Paved Surface Inspection Fee $12,464.30 $12,464.30 Paid 09/20/2024
91100C9-Water Insp Fee $2,862.09 $2,862.09 Paid 09/20/2024
9110068-Storm Sewer Inspection Fee $5,305.75 $5,305.75 Paid 09/20/2024
9110071-Site Grading Fee $4,214.96 $4,214.96 Paid 09/20/2024
8331507-Sanitary Sewer Development Fee $24,381.00 $24,381.00 Paid 04/02/2025
9110072-Water Test Fee $200.00 $200.00 Paid 09/20/2024
8331401-Water Tap Fee $68,865.00 $68,865.00 Paid 04/02/2025
8350015-Water Meter Fee $8,300.07 $8,300.07 Paid 04/02/2025
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 04/02/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Sewer Service Inspection Pending
Water Service Inspection Pending
Gas Piping Inspection - Commercial Pending
Gas Service Inspection - Commercial Pending
Above Ceiling Inspection Pending
Rated Assembly Inspection Pending
Underslab Electrical Inspection - Commercial Pending
Misc
Informational
02/27/2025
Building underslab electrical-OK **Call for footing inspection when the shear wall footing is ready
Footing Inspection - Commercial Pending
Misc
Informational
03/06/2025
Exterior footing OK to pour: -Exterior wall footing -Elevator footing and foundation wall Interior shearwall footing-OK
Grading/Excavation/Fill Inspection Pending
Water Line - Construction Inspection Pending
Sanitary - Material Verification Pending
Sanitary Sewer Construction Inspection Pending
Sanitary Sewer - Air Test Pending
Sanitary Sewer - Mandrel Pending
Sanitary Sewer - Vacuum Pending
Pavement-Proof Roll Pending
Pavement-Surface Pending
Install Street and Stop Signs Pending
Pavement-Aggregate Base Pending
Pavement-Curb Construction Pending
Pavement-Stabilized Subgrade Pending
Storm Sewer Construction Inspection Pending
Sidewalk Inspection Pending
Misc
Informational
05/13/2025
5-13-25 NS Site visited, and it appears sidewalk has not yet started.
Erosion Control Inspection Pending
Misc
Informational
05/14/2025
Wilshire retirement homes 3-08-25 NS Site visited and asked to have some fence fixed 3-19-25 NS Site visited, and fence has been fixed 3-26-25 NS no erosion control problems 4-2-25 NS erosion control appears to be in compliance 4-16-25 NS site visited and it appears that everything appears to be fine 4-24-25 NS I went by and saw workers walking the erosion control fence.
Sprinkler - Hydrostatic Test Pending
Sprinkler - Flow Test Pending
Electrical Service Inspection Pending 4/4/2025
Rated Assembly Inspection Pending 4/18/2025
All Rough Inspection - Commercial Pending 6/9/2025 6/9/2025
Misc
Corrective Action Required
05/29/2025
Interior shearwall: -1st floor
FIRST FLOOR
Corrective Action Required
05/29/2025
-Corridor ceiling pre-rock OK
SECOND FLOOR
Corrective Action Required
05/29/2025
-Corridor ceiling pre-rock OK
Footing Inspection - Commercial Partial 12/3/2024 12/3/2024 12/03/2024
Misc
Informational
12/03/2024
Exterior footing OK to pour: -from NE corner of rm 116 to NW corner of stair 1
Footing Inspection - Commercial Partial 12/6/2024 12/6/2024 12/06/2024
Misc
Informational
12/03/2024
Exterior footing OK to pour: -from NE corner of rm 116 to NW corner of stair 1 -From SE corner of 209 to NE corner of 213
Footing Inspection - Commercial Partial 12/6/2024 12/6/2024 12/06/2024
Misc
Informational
12/06/2024
Exterior footing OK to pour: -From NE corner of rm 116 to NW corner of stair 1; continue to sprinkler rm; -NE corner of sprinkler rm to NE corner of 213
Footing Inspection - Commercial Partial 12/9/2024 12/9/2024 12/09/2024
Misc
Informational
12/06/2024
Exterior footing OK to pour: -From NE corner of rm 116 to NW corner of stair 1; continue to sprinkler rm; -NE corner of sprinkler rm to NE corner of 213 -Elevator footing and foundation wall
Footing Inspection - Commercial Partial 12/10/2024 12/10/2024 12/10/2024
Misc
Informational
12/06/2024
Exterior footing OK to pour: -From NE corner of rm 116 to NW corner of stair 1; continue to sprinkler rm; -NE corner of sprinkler rm to NE corner of 213; continue remaining footing to NE of rm 116 -Elevator footing and foundation wall
Footing Inspection - Commercial Partial 12/11/2024 12/11/2024 12/11/2024
Misc
Informational
12/10/2024
Exterior footing OK to pour: -Exterior wall footing -Elevator footing and foundation wall
Underslab Plumbing Inspection - Commercial Failed 12/13/2024 12/13/2024 12/13/2024
Misc
Corrective Action Required
12/13/2024
Not ready for inspection
Underslab Plumbing Inspection - Commercial Not Ready 12/16/2024 12/16/2024 12/16/2024
Misc
Corrective Action Required
12/13/2024
12/13-Not ready for inspection 12/16-Again, underslab plumbing not ready for inspection. Underslab plumbing shall be tested for leakage. Reinspection fee is assessed.
Underslab Plumbing Inspection - Commercial Partial 12/20/2024 12/20/2024 12/20/2024
Misc
Corrective Action Required
12/16/2024
-Underslab plumbing OK, except the floor drain inside sprinkler rm
Underslab Plumbing Inspection - Commercial Passed 12/30/2024 12/30/2024 12/30/2024
Misc
Resolved
12/30/2024
-Underslab plumbing OK, except the floor drain inside sprinkler rm
Underslab Electrical Inspection - Commercial Partial 2/27/2025 2/27/2025 02/27/2025
Misc
Informational
02/27/2025
Building underslab electrical-OK **Call for footing inspection when the shear wall footing is ready
Footing Inspection - Commercial Partial 3/6/2025 3/6/2025 03/06/2025
Misc
Informational
12/11/2024
Exterior footing OK to pour: -Exterior wall footing -Elevator footing and foundation wall Interior shearwall footing-OK
Electrical Service Inspection Failed 4/2/2025 4/2/2025 04/02/2025
Misc
Corrective Action Required
04/02/2025
Obtain separate permit for the temporary electric service
Electrical Service Inspection Passed 4/4/2025 4/4/2025 04/04/2025
Misc
Resolved
04/04/2025
Obtain separate permit for the temporary electric service
All Rough Inspection - Commercial Failed 4/17/2025 4/17/2025 04/17/2025
Misc
Corrective Action Required
04/17/2025
Shearwall-Nail sheathing @ 6" oc
All Rough Inspection - Commercial Partial 4/18/2025 04/18/2025
Misc
Corrective Action Required
04/17/2025
Interior shearwall: -1st floor
Erosion Control Inspection Partial 4/23/2025 04/24/2025
Misc
Informational
04/24/2025
Wilshire retirement homes 3-08-25 NS Site visited and asked to have some fence fixed 3-19-25 NS Site visited, and fence has been fixed 3-26-25 NS no erosion control problems 4-2-25 NS erosion control appears to be in compliance 4-16-25 NS site visited and it appears that everything appears to be fine 4-24-25 NS I went by and saw workers walking the erosion control fence.
Sidewalk Inspection Partial 5/14/2025 05/13/2025
Misc
Informational
05/13/2025
5-13-25 NS Site visited, and it appears sidewalk has not yet started.
Erosion Control Inspection Partial 5/15/2025 05/14/2025
Misc
Informational
04/24/2025
Wilshire retirement homes 3-08-25 NS Site visited and asked to have some fence fixed 3-19-25 NS Site visited, and fence has been fixed 3-26-25 NS no erosion control problems 4-2-25 NS erosion control appears to be in compliance 4-16-25 NS site visited and it appears that everything appears to be fine 4-24-25 NS I went by and saw workers walking the erosion control fence.
All Rough Inspection - Commercial Partial 5/27/2025 5/27/2025 05/27/2025
Misc
Corrective Action Required
04/18/2025
Interior shearwall: -1st floor
FIRST FLOOR
Corrective Action Required
05/27/2025
-Corridor ceiling pre-rock OK
SECOND FLOOR
Corrective Action Required
05/27/2025
All Rough Inspection - Commercial Partial 5/29/2025 5/29/2025 05/29/2025
Misc
Corrective Action Required
05/27/2025
Interior shearwall: -1st floor
FIRST FLOOR
Corrective Action Required
05/27/2025
-Corridor ceiling pre-rock OK
SECOND FLOOR
Corrective Action Required
05/27/2025
-Corridor ceiling pre-rock OK
Documents & Images
Date Uploaded File Type Document Name
10/31/2023 Application Form APPLICATION
10/31/2023 Plans 23-1030_Wilshire Hills III_Permit Submittal - FULL SET sm
10/31/2023 Specifications 23-1030 Wilshire Hills III Specifications sm
10/31/2023 Letter License Tax Bill
11/01/2023 Email cpted info from PD
12/07/2023 Letter DS P/R Corrections Document
03/19/2024 Engineer Report/Study Wilshire Hills Phase 3 - Special Inspection Letter-signed
03/19/2024 Letter 23-1207 Response Letter - Wilshire Hills III - Plan Review Comments
03/19/2024 Plans 24-0313_Wilshire Hills III_ADD1 - FULL SET sm
03/29/2024 Letter DS P/R Corrections Document
04/19/2024 Plans 24-0419_Wilshire Hills III_ADD3
04/19/2024 Letter 24-0419 Response Letter - Wilshire Hills III - Plan Review Comments
07/25/2024 Approved Plans Approved FDP Stamped Plan Set_PL2023163
08/28/2024 Receipt Receipt for transaction:2024-007310
08/28/2024 Letter DS Building Permit
08/29/2024 Plans 24-0716_Wilshire Hills III_ADD4 - FULL SET
08/30/2024 Plans previousle approved building permit set
09/20/2024 Receipt Receipt for transaction:2024-007804
10/10/2024 Plans 24-1004_Wilshire Hills III_ASI001
10/10/2024 Letter 24-1004 Wilshire Hills III ASI 001
10/21/2024 Plans 24-1004_Wilshire Hills III_ASI001 - RACK SET - sm
10/21/2024 Approved Plans Approved construction plans
12/03/2024 Letter INSPECTION SUMMARY
12/06/2024 Letter INSPECTION SUMMARY
12/06/2024 Letter INSPECTION SUMMARY
12/09/2024 Letter INSPECTION SUMMARY
12/10/2024 191240913 Wilshire Hills - AOR Drawings
12/10/2024 191240912 Wilshire Hills - FA Drawings
12/10/2024 Wilshire Cutsheets
12/10/2024 Plans Area of Rescue cutsheets
12/10/2024 Letter INSPECTION SUMMARY
12/11/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/20/2024 Letter INSPECTION SUMMARY
12/24/2024 Letter Fire (Alarm) Plan Review Notice
12/30/2024 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
04/02/2025 Letter INSPECTION SUMMARY
04/04/2025 Letter INSPECTION SUMMARY
04/15/2025 Letter DS Building Permit
04/17/2025 Letter INSPECTION SUMMARY
04/18/2025 Letter INSPECTION SUMMARY
05/23/2025 AFP PE STAMP CALC PACKAGE Wilshire 5-23-25
05/23/2025 AFP PE STAMP Wilshire FP 5-23-25
05/27/2025 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
06/02/2025 Letter Fire (Sprinkler) Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home