Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
02/06/2024
|
02/02/2024
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Received stamped plans 1/30/2024. Indicate the contractor installing the system.
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule a hydrostatic test.
|
|
Miscellaneous Correction
Corrective Action Required
It is the resposibility of the sprinkler installer and building contractor to ensure the system is adequately insulated and protected from freezing.
|
|
|
Sprinkler Plan Review
|
Rejected
|
10/09/2023
|
10/09/2023
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required- Unstamped plans received 9/29/2023. Provide PE stamped plans.
Indicate the sprinkler contractor installing the system.
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule a hydrostatic test.
|
|
Miscellaneous Correction
Corrective Action Required
The 2016 Edition of NFPA 13 D is adopted as the referenced code per the 2018 Edition of the IFC.
Call out any exceptions taken from the 2019 Edition and correct the code information.
|
|
|
Zoning Review
|
Approved
|
07/07/2023
|
07/05/2023
|
|
Hector Soto Jr.
|
|
Misc
Corrective Action Required
EXTERIOR MATERIAL.
- The proposed change in exterior material from brick along the rear elevations of Buildings 1 and 2 depicted on Sheets A121 and A221 lists "Siding or Stucco". Which material will be used on the buildings? The elevations shall list the actual material to be used for staff review.
- Label the color of the proposed material(s) to be used along the rear elevations for review. Also provide a color elevation.
|
|
|
Zoning Review
|
Rejected
|
06/19/2023
|
06/21/2023
|
|
Hector Soto Jr.
|
|
Misc
Corrective Action Required
EXTERIOR MATERIAL.
- The proposed change in exterior material from brick along the rear elevations of Buildings 1 and 2 depicted on Sheets A121 and A221 lists "Siding or Stucco". Which material will be used on the buildings? The elevations shall list the actual material to be used for staff review.
- Label the color of the proposed material(s) to be used along the rear elevations for review. Also provide a color elevation.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
06/19/2023
|
06/19/2023
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action Required: Submit sprinkler plans (13 D) for review and approval. Acknowledged deffered submittal on letter
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action Required: Call 816-969-1300 to schedule hydrostatic pressure test.
|
|
|
Building Plan Review
|
Approved with Conditions
|
06/19/2023
|
06/15/2023
|
|
Joe Frogge
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Comment is informational. Truss packages deferred per request.
2/1/2023 - acknowledged in letter.
|
|
|
Building Plan Review
|
Approved with Conditions
|
02/06/2023
|
05/24/2023
|
|
Joe Frogge
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Comment is informational. Truss packages deferred per request.
2/1/2023 - acknowledged in letter.
|
|
Project cost
The project cost, which is used to establish the permit fee, has not been provided.
Action required: Provide construction cost breakdown for each structure. Townhomes attached to garages via covered walkway are considered a single structure.
2/1/2023 - acknowledged in letter.
|
|
IBC 706.1 Fire and Smoke Protection - General
2018 IRC 302.2 Townhouses.
Action required: Provide complete UL details for separation walls. Must include nail/screw patterns.
|
|
IBC 706.6 Fire and Smoke Protection - Vertical Continuity
2018 IRC 302.2.3 Continuity.
Action required: Amend designs to demonstrate compliance. Must be continuous through floor/ceiling assemblies. Unclear how to attach at roof deck.
|
|
IBC 706.1 Fire and Smoke Protection - General
2018 IRC 302.2.3 Parapets for townhouses.
Action required: Amend drawings to demonstrate compliance. How is parapet exception being met?
|
|
Misc
2018 IRC 302.5 Dwelling-garage opening and penetration protection.
thru
2018 IRC 302.7 Under-stair protection.
Action required: Amend drawings to demonstrate compliance. Must address:
- Mechanical rooms/door (where and how is separation accomplished? Back wall? Front wall with rated doors?)
- Door ratings
- Door closers
- Garage ceilings (whether or not living space above)
|
|
IBC 1010.1.2 Door swing - direction of swing egress travel
2018 IRC 311.2 Egress door.
Actions required:
- Provide information as to how the doubled 3/6 doors comply. Floor and/or top jamb slide locks, or similar, will make these non-compliant.
- Edit door label on sheet A111. (2/8 not allowed)
|
|
IPC 405.3.1 fixture clearance to obstruction
2018 IRC 307.1 Space required.
Figure 307.1
Action required: Modifications required. All toilets require minimum 21" front clearance.
|
|
IBC 1030.2 Minimum size - emergency escape and rescue
2018 IRC 310.1 Emergency escape and rescue opening required.
Action required: Modify designs. All basements required to have egress direct to exterior. Some are missing, some have egress wells that lead to nowhere.
|
|
IBC 706.8.4.2 Fire and Smoke Protection - Fireblocks and Firestops
2018 IRC 302.12 Draftstopping.
Action required: Specify draftstopping in floors and attics.
|
|
Misc
2018 IRC 302.2.2 Common walls.
Action required: Revise plumbing drawings to comply. Piping not allowed in common walls.
|
|
IFGC 303.3 Prohibited locations for gas fired appliance
2018 IRC 1307.3 Elevation of ignition source.
Action required: Amend drawings to demonstrate compliance at water heaters.
|
|
NEC Article 210.11 (C) (3) Bathroom branch circuits
2018 IRC 3703.4 Bathroom circuits.
Action required: Bathroom circuits are required to be dedicated. This includes lighting and power.
|
|
IBC 915.1.1 Fire Protection - carbon monoxide detect
2018 IRC 315 Carbon Monoxide Alarms.
2018 IRC 315.2 Where required.
2018 IRC 315.3 Location.
Action required: Provide carbon monoxide detection at all required locations.
|
|
NEC Article 250.50 Grounding electrode system
2018 IRC 3608.1 Grounding electrode system.
Action required: Revise grounding detail to show connection to concrete-encased electrode per 3608.1.2.
|
|
NEC Article 230.2 Number of services
2018 IRC 3601.3 One building or other structure not to be supplied through another.
Action required: SE cables are not to be routed through dwelling units. (each townhouse is considered a separate building at fire separation wall) To be field verified.
|
|
|
Licensed Contractors
|
Approved
|
02/06/2023
|
05/08/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
2/1/2023 - acknowledged in letter.
|
|
|
Licensed Contractors
|
Approved
|
01/20/2023
|
05/08/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
02/06/2023
|
02/01/2023
|
|
Ben Hicks
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action Required: Submit sprinkler plans (13 D) for review and approval. Acknowledged deffered submittal on letter
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action Required: Call 816-969-1300 to schedule hydrostatic pressure test.
|
|
|
Building Plan Review
|
Rejected
|
01/20/2023
|
01/18/2023
|
|
Joe Frogge
|
|
IBC 1103.1 Where required - accessibility
2018 IRC 320.1 Scope Accessibility. Where there are four or more dwelling units or sleeping units in a single structure, the provisions of Chapter 11 of the International Building Code for Group R-3 shall apply.
1107.6.3 Group R-3. In Group R-3 occupancies where there are four or more dwelling units or sleeping units intended to be occupied as a residence in a single structure, every dwelling unit and sleeping unit intended to be occupied as a residence shall be a Type B unit. Bedrooms within congregate living facilities, dormitories, sororities, fraternities, and boarding houses shall be counted as sleeping units for the purpose of determining the number of units.
Exception: The number of Type B units is permitted to be reduced in accordance with Section 1107.7.
Action required: Amend designs and code analysis to demonstrate compliance.
1/24/23 - per architect's analysis and review of commentary comment removed.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required: Comment is informational. Truss packages deferred per request.
|
|
Project cost
Corrective Action Required
The project cost, which is used to establish the permit fee, has not been provided.
Action required: Provide construction cost breakdown for each structure. Townhomes attached to garages via covered walkway are considered a single structure.
|
|
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
2018 IRC 302.2 Townhouses.
Action required: Provide complete UL details for separation walls. Must include nail/screw patterns.
|
|
IBC 706.6 Fire and Smoke Protection - Vertical Continuity
Corrective Action Required
2018 IRC 302.2.3 Continuity.
Action required: Amend designs to demonstrate compliance. Must be continuous through floor/ceiling assemblies. Unclear how to attach at roof deck.
|
|
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
2018 IRC 302.2.3 Parapets for townhouses.
Action required: Amend drawings to demonstrate compliance. How is parapet exception being met?
|
|
Misc
Corrective Action Required
2018 IRC 302.5 Dwelling-garage opening and penetration protection.
thru
2018 IRC 302.7 Under-stair protection.
Action required: Amend drawings to demonstrate compliance. Must address:
- Mechanical rooms/door (where and how is separation accomplished? Back wall? Front wall with rated doors?)
- Door ratings
- Door closers
- Garage ceilings (whether or not living space above)
|
|
IBC 1010.1.2 Door swing - direction of swing egress travel
Corrective Action Required
2018 IRC 311.2 Egress door.
Actions required:
- Provide information as to how the doubled 3/6 doors comply. Floor and/or top jamb slide locks, or similar, will make these non-compliant.
- Edit door label on sheet A111. (2/8 not allowed)
|
|
IPC 405.3.1 fixture clearance to obstruction
Corrective Action Required
2018 IRC 307.1 Space required.
Figure 307.1
Action required: Modifications required. All toilets require minimum 21" front clearance.
|
|
IBC 1030.2 Minimum size - emergency escape and rescue
Corrective Action Required
2018 IRC 310.1 Emergency escape and rescue opening required.
Action required: Modify designs. All basements required to have egress direct to exterior. Some are missing, some have egress wells that lead to nowhere.
|
|
IBC 706.8.4.2 Fire and Smoke Protection - Fireblocks and Firestops
Corrective Action Required
2018 IRC 302.12 Draftstopping.
Action required: Specify draftstopping in floors and attics.
|
|
Misc
Corrective Action Required
2018 IRC 302.2.2 Common walls.
Action required: Revise plumbing drawings to comply. Piping not allowed in common walls.
|
|
IFGC 303.3 Prohibited locations for gas fired appliance
Corrective Action Required
2018 IRC 1307.3 Elevation of ignition source.
Action required: Amend drawings to demonstrate compliance at water heaters.
|
|
NEC Article 210.11 (C) (3) Bathroom branch circuits
Corrective Action Required
2018 IRC 3703.4 Bathroom circuits.
Action required: Bathroom circuits are required to be dedicated. This includes lighting and power.
|
|
IBC 915.1.1 Fire Protection - carbon monoxide detect
Corrective Action Required
2018 IRC 315 Carbon Monoxide Alarms.
2018 IRC 315.2 Where required.
2018 IRC 315.3 Location.
Action required: Provide carbon monoxide detection at all required locations.
|
|
NEC Article 250.50 Grounding electrode system
Corrective Action Required
2018 IRC 3608.1 Grounding electrode system.
Action required: Revise grounding detail to show connection to concrete-encased electrode per 3608.1.2.
|
|
NEC Article 230.2 Number of services
Corrective Action Required
2018 IRC 3601.3 One building or other structure not to be supplied through another.
Action required: SE cables are not to be routed through dwelling units. (each townhouse is considered a separate building at fire separation wall) To be field verified.
|
|
|
Building Plan Review
|
Rejected
|
01/20/2023
|
01/18/2023
|
|
Joe Frogge
|
|
|
Final Development Plan Review
|
Approved
|
12/13/2022
|
01/18/2023
|
|
Scott Ready
|
|
NLV Townhomes
|
Fire Plan Review
|
Approved with Conditions
|
01/20/2023
|
01/06/2023
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Submit sprinkler plans (13 D) for review and approval.
|
|
|