Permit Application Status

PRCOM20246376


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20246376
Building Permit - Commercial
Issued - Partial
LSMO TUDOR APARTMENTS LLC
NEW COMMERCIAL
EVREN - CLUBHOUSE AND LEASING OFICE FOR EVREN APARTMENT COMPLEX, PRIVATE SITE DEVELOPMENT Mike Weisenborn 01/02/2025 1:09 PM - ISSUED A PARTIAL PERMIT FOR THE PRIVATE SITE DEVELOPMENT. STRUCTURES ARE NOT PERMITTED AT THIS TIME **Approved plans are in PRCOM20244879**
12/12/2024
07/22/2025
Locations
Contacts
CITYSCAPE CONSTRUCTION - TUDOR LLC, Address:10 W CARMEL DRIVE STE 200, Phone:(317) 574-1600  
Shawn Bartholomew, Address:114 DOUGLAS ST SE, Phone:(714) 944-0215  
M & S INC, Address:21947 W 230TH ST, Phone:(913) 915-0520  
STANDARD ELECTRIC TOO LLC, Address:2006 E PRAIRIE CIRCLE, Phone:(913) 782-5409  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
Mitsch Design, Address:200 S Rangeline Rd, Phone:(317) 805-1159  
LSMO TUDOR APARTMENTS LLC, Address:10 W CARMEL DR STE 200  
  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 02/05/2025 01/29/2025
Joe Frogge
Planning - Screening of ground mounted equipment
Corrective Action Required
01/29/2025

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (must be either masonry or approved evergreen plantings) 1/17/2025 - Designs are approvable assuming grass is at least as tall as the equipment to be screened. To be field verified during inspections.
IPC 604.9 Water hammer
Resolved
01/29/2025

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Air chambers not allowed. Remove general notes that give that option. 1/17/2025 - Not addressed. P-series sheets not found in uploads.
Fire Plan Review Approved with Conditions 02/05/2025 01/29/2025
Joe Frogge
Hazardous material identification
Corrective Action Required
01/29/2025

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Action Required: Provide 704 placard for storage of pool chemicals.
Licensed Contractors Approved 01/29/2025 01/29/2025
Joe Frogge
LC - MEP Subs
Resolved
01/29/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 1/17/2025 - Standard Electric is not currently licensed with us.
Fire Plan Review Approved with Conditions 01/23/2025 01/22/2025
Craig Hill
Hazardous material identification
Corrective Action Required
01/15/2025

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Action Required: Provide 704 placard for storage of pool chemicals.
Building Plan Review Rejected 01/23/2025 01/17/2025
Joe Frogge
Planning - Screening of ground mounted equipment
Corrective Action Required
01/15/2025

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (must be either masonry or approved evergreen plantings) 1/17/2025 - Designs are approvable assuming grass is at least as tall as the equipment to be screened. To be field verified during inspections.
IBC 1803.1 General - geotech
Resolved
01/17/2025

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
IPC 604.8 Water pressure reducing valve
Resolved
01/17/2025

2018 IPC 604.8 Water Pressure reducing valve or regulator. Where water pressure within a building exceeds 80 psi static, an approved water-pressure reducing valve conforming to ASSE 1003 or CSA B356 with strainer shall be installed to reduce the pressure in the building water distribution piping to not greater than 80 psi static. Action required: Provide pressure reducing valve at water entry. i.e. remove "if" statement from detail 5/MP101. (Our Water Department requires PRV installation in all locations regardless of pressure)
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
01/17/2025

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Provide GFCI protection at Kitchenette island.
NEC Article 250.66 Size of AC Grounding electrode conductor
Resolved
01/17/2025

2017 NEC Article 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). Action required: Provide conductor sizes for entire grounding electrode system.
IPC 604.9 Water hammer
Corrective Action Required
01/29/2025

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Air chambers not allowed. Remove general notes that give that option. 1/17/2025 - Not addressed. P-series sheets not found in uploads.
Misc
Resolved
01/17/2025

Unable to verify pipe materials. Action required: Provide pipe material schedule for all water and sanitary systems.
Licensed Contractors Rejected 01/23/2025 01/17/2025
Joe Frogge
LC - MEP Subs
Corrective Action Required
01/17/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 1/17/2025 - Standard Electric is not currently licensed with us.
Final Development Plan Review Approved 12/30/2024 01/02/2025
Daniel Fernandez
Fire Plan Review Approved with Conditions 12/30/2024 12/30/2024
Craig Hill
Hazardous material identification
Corrective Action Required
12/30/2024

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. Action Required: Provide 704 placard for storage of pool chemicals.
Building Plan Review Rejected 12/30/2024 12/20/2024
Joe Frogge
Planning - Screening of ground mounted equipment
Corrective Action Required
12/19/2024

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO section. (must be either masonry or approved evergreen plantings)
IBC 1803.1 General - geotech
Corrective Action Required
12/19/2024

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
IPC 604.8 Water pressure reducing valve
Corrective Action Required
12/20/2024

2018 IPC 604.8 Water Pressure reducing valve or regulator. Where water pressure within a building exceeds 80 psi static, an approved water-pressure reducing valve conforming to ASSE 1003 or CSA B356 with strainer shall be installed to reduce the pressure in the building water distribution piping to not greater than 80 psi static. Action required: Provide pressure reducing valve at water entry. i.e. remove "if" statement from detail 5/MP101. (Our Water Department requires PRV installation in all locations regardless of pressure)
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
12/20/2024

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Provide GFCI protection at Kitchenette island.
NEC Article 250.66 Size of AC Grounding electrode conductor
Corrective Action Required
12/20/2024

2017 NEC Article 250.66 Size of Alternating-Current Grounding Electrode Conductor. The size of the grounding electrode conductor at the service, at each building or structure where supplied by a feeder(s) or branch circuit(s), or at a separately derived system of a grounded or ungrounded ac system shall not be less than given in Table 250.66, except as permitted in 250.66(A) through (C). Action required: Provide conductor sizes for entire grounding electrode system.
IPC 604.9 Water hammer
Corrective Action Required
12/20/2024

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Air chambers not allowed. Remove general notes that give that option.
Misc
Corrective Action Required
12/20/2024

Unable to verify pipe materials. Action required: Provide pipe material schedule for all water and sanitary systems.
Licensed Contractors Rejected 12/30/2024 12/19/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
12/19/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
LC - MEP Subs
Corrective Action Required
12/19/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $4,984.22 $4,984.22 Paid 02/27/2025
8331401-Water Tap Fee $10,595.00 $10,595.00 Paid 02/27/2025
8331507-Sanitary Sewer Development Fee $6,101.00 $6,101.00 Paid 02/27/2025
8350015-Water Meter Fee $1,066.76 $1,066.76 Paid 02/27/2025
9110068-Storm Fee $8,817.93 $8,817.93 Paid 12/31/2024
9110071-Site Grading Fee $14,367.75 $14,367.75 Paid 12/31/2024
9110072-Water Test Fee $400.00 $400.00 Paid 12/31/2024
9110081-Paved Surface Inspection Fee $42,645.33 $42,645.33 Paid 12/31/2024
91100C9-Water Insp Fee $9,193.44 $9,193.44 Paid 12/31/2024
91100C8-Sanitary Sewer Insp Fees $2,846.70 $2,846.70 Paid 12/31/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/31/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Underslab Plumbing Inspection - Commercial Pending
Water Service Inspection Pending
Electrical Service Inspection Pending
Gas Service Inspection - Commercial Pending
In-wall Inspection Pending
Above Ceiling Inspection Pending
Grading/Excavation/Fill Inspection Pending
Sanitary - Material Verification Pending
Sanitary Sewer - Air Test Pending
Sanitary Sewer - Mandrel Pending
Sanitary Sewer - Vacuum Pending
Pavement-Proof Roll Pending
Pavement-Surface Pending
Install Street and Stop Signs Pending
Pavement-Aggregate Base Pending
Pavement-Curb Construction Pending
Pavement-Stabilized Subgrade Pending
Erosion Control Inspection Pending
Sidewalk Inspection Pending
Footing Inspection - Commercial Pending
Misc
Corrective Action Required
04/17/2025
4/17/25 -Footings for building 5 scheduled on clubhouse permit. Obtain proper, issued permit
Storm Sewer Construction Inspection Pending
Misc
Informational
05/05/2025
05/05/25 Monday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 60' of 24" HDPE storm pipe & cored into existing storm structure 05/02/25. 05/05/25 Monday JMJ (Gen. Cityscape, CP Excavating) Contractor poured collars and installed encasement of storm pipe as per project. Concrete block was poured at out going nyoplast structure to prevent floatation C49.
Sanitary Sewer Construction Inspection Pending
Misc
Informational
05/07/2025
05/01/25 Thursday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 49' of 6" SDR-26 sanitary pipe for building #7 & 147' of 6" SDR-26 sanitary pipe for building #8. 05/02/25 Friday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 90' of 6" SDR-26 sanitary pipe for building #4, 94' of 6" SDR-26 sanitary pipe for Maintenance building as per project plans. 05/07/25 Wednesday JMJ (Gen. Cityscape, CP Excavating) Private sanitary building #1 stub 54ft of 6" SDR-26 pipe.
Water Line - Construction Inspection Pending
Misc
Informational
05/07/2025
05/01/25 Thursday JMJ (Gen. Cityscape, Sub. CP Excavation) Contractor bored installed casing under South NW Commerce Dr. for the Combination water meter & backflow valve vault. Contractor waited on locator to help explain markings on the North and South end boring on street. 50' casing was completed on the South end going running East to West, and the Eastside of the road was backfilled. The contractor may start to bore the North end along NW Commerce & Tudor Road. 05/06/25 Wednesday JMJ (Gen. Cityscape, Sub. CP Excavation) Contractor installed approximate 60' of private water with 2-45 deg bends.
Erosion Control Inspection Residential Pending
Misc
Informational
05/08/2025
05/07/25 Wednesday JMJ Erosion control appears to be functioning properly.
Underground Electrical Inspection - Commercial Pending
Misc
Informational
05/09/2025
Conduit for (3) light poles South of building 5 and (1) SE of building 8
Footing Inspection - Commercial Failed 4/17/2025 4/17/2025 04/17/2025
Misc
Corrective Action Required
04/17/2025
4/17/25 -Footings for building 5 scheduled on clubhouse permit. Obtain proper, issued permit
Water Line - Construction Inspection Partial 05/01/2025
Misc
Informational
05/01/2025
05/01/25 Thursday JMJ ( Gen. Cityscape, Sub. CP Excavation) Contractor bored installed casing under NW Commerce Dr. for the Combination water meter & backflow valve vault. Contractor waited on locator to help explain maker on the North and South end boring on street.(04/30/25).
Water Line - Construction Inspection Partial 5/1/2025 5/1/2025 05/01/2025
Misc
Informational
05/01/2025
05/01/25 Thursday JMJ ( Gen. Cityscape, Sub. CP Excavation) Contractor bored installed casing under South NW Commerce Dr. for the Combination water meter & backflow valve vault. Contractor waited on locator to help explain markings on the North and South end boring on street. 50' casing was completed on the South end going running East to West, and the Eastside of the road was backfilled. The contractor may start to bore the North end along NW Commerce & Tudor Road.
Sanitary Sewer Construction Inspection Partial 5/1/2025 5/1/2025 05/01/2025
Misc
Informational
05/01/2025
05/01/25 Thursday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 49' of 6" SDR-26 sanitary pipe for building #7 & 147' of 6" SDR-26 sanitary pipe for building #8.
Storm Sewer Construction Inspection Partial 5/5/2025 5/5/2025 05/05/2025
Misc
Informational
05/05/2025
05/05/25 Monday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 60' of 24" HDPE storm pipe & cored into existing storm structure 05/02/25.
Sanitary Sewer Construction Inspection Partial 5/5/2025 5/5/2025 05/05/2025
Misc
Informational
05/01/2025
05/01/25 Thursday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 49' of 6" SDR-26 sanitary pipe for building #7 & 147' of 6" SDR-26 sanitary pipe for building #8. 05/02/25 Friday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 90' of 6" SDR-26 sanitary pipe for building #4, 94' of 6" SDR-26 sanitary pipe for Maintenance building as per project plans.
Storm Sewer Construction Inspection Partial 5/5/2025 5/5/2025 05/05/2025
Misc
Informational
05/05/2025
05/05/25 Monday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 60' of 24" HDPE storm pipe & cored into existing storm structure 05/02/25. 05/05/25 Monday JMJ (Gen. Cityscape, CP Excavating) Contractor poured collars and installed encasement of storm pipe as per project. Concrete block was poured at out going nyoplast structure to prevent floatation C49.
Sanitary Sewer Construction Inspection Partial 5/7/2025 5/7/2025 05/07/2025
Misc
Informational
05/05/2025
05/01/25 Thursday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 49' of 6" SDR-26 sanitary pipe for building #7 & 147' of 6" SDR-26 sanitary pipe for building #8. 05/02/25 Friday JMJ (Gen. Cityscape, CP Excavating) Contractor installed 90' of 6" SDR-26 sanitary pipe for building #4, 94' of 6" SDR-26 sanitary pipe for Maintenance building as per project plans. 05/07/25 Wednesday JMJ (Gen. Cityscape, CP Excavating) Private sanitary building #1 stub 54ft of 6" SDR-26 pipe.
Water Line - Construction Inspection Partial 5/6/2025 5/6/2025 05/07/2025
Misc
Informational
05/01/2025
05/01/25 Thursday JMJ (Gen. Cityscape, Sub. CP Excavation) Contractor bored installed casing under South NW Commerce Dr. for the Combination water meter & backflow valve vault. Contractor waited on locator to help explain markings on the North and South end boring on street. 50' casing was completed on the South end going running East to West, and the Eastside of the road was backfilled. The contractor may start to bore the North end along NW Commerce & Tudor Road. 05/06/25 Wednesday JMJ (Gen. Cityscape, Sub. CP Excavation) Contractor installed approximate 60' of private water with 2-45 deg bends.
Erosion Control Inspection Residential Partial 5/7/2025 5/7/2025 05/08/2025
Misc
Informational
05/08/2025
05/07/25 Wednesday JMJ Erosion control appears to be functioning properly.
Underground Electrical Inspection - Commercial Partial 5/9/2025 5/9/2025 05/09/2025
Misc
Informational
05/09/2025
Conduit for (3) light poles South of building 5 and (1) SE of building 8
Documents & Images
Date Uploaded File Type Document Name
12/12/2024 Application Form APPLICATION
12/13/2024 Plans Evren Apart CH_Arch Permit Set
12/13/2024 Engineer Report/Study Evren Apart CH_Comcheck - Elec
12/13/2024 Engineer Report/Study Evern Apr CH_Comcheck Arc
12/13/2024 Plans Evren Apart CH_Permit Set MEP
12/13/2024 Engineer Report/Study Evren Apart CH-ST Calc Binder
12/13/2024 Plans Evren Clubhouse Structural - Permit
12/30/2024 Letter DS P/R Corrections Document
12/31/2024 Receipt Receipt for transaction:2024-009723
01/02/2025 Letter DS Building Permit
01/15/2025 Letter 2024-10-29_Evren Response
01/15/2025 Engineer Report/Study 02225125 Tudor Road Apartments Geotech Report_signed
01/15/2025 Plans Cityscape Tudor Club - Delta 2 City Response 01-10-2025_MEP
01/15/2025 Plans Evren Clubhouse Landscape Plans 25 0107
01/15/2025 Drawing Evren_CH-A103
01/15/2025 Specifications Piping Specification
01/23/2025 Letter DS P/R Corrections Document
01/29/2025 Letter 2025-01-29_Evren Response
01/29/2025 Certificate/License Lees Summit License Certificate
01/29/2025 Drawing P101
01/29/2025 Drawing P102
02/06/2025 Plans 2025-02-06_CH Permit Set_Combined_City Response
02/07/2025 Approved Plans Approved construction plans
02/27/2025 Receipt Receipt for transaction:2025-001145
04/17/2025 Letter INSPECTION SUMMARY
05/01/2025 Stamped Approved Plans_PL2024210 (Clubhouse)
05/01/2025 Letter INSPECTION SUMMARY
05/01/2025 Letter INSPECTION SUMMARY
05/01/2025 4-10 INSPECTION SUMMARY1
05/01/2025 4-14 INSPECTION SUMMARY1
05/01/2025 4-14 INSPECTION SUMMARY2
05/01/2025 4-14 INSPECTION SUMMARY3
05/01/2025 4-14 INSPECTION SUMMARY4
05/01/2025 4-14 INSPECTION SUMMARY5
05/01/2025 4-16 INSPECTION SUMMARY1
05/01/2025 4-16 INSPECTION SUMMARY2
05/01/2025 4-16 INSPECTION SUMMARY3
05/01/2025 4-16 INSPECTION SUMMARY4
05/01/2025 4-21 INSPECTION SUMMARY
05/01/2025 4-23 INSPECTION SUMMARY1
05/01/2025 4-23 INSPECTION SUMMARY2
05/01/2025 4-25 INSPECTION SUMMARY3
05/01/2025 4-28 INSPECTION SUMMARY
05/01/2025 4-29 INSPECTION SUMMARY1
05/01/2025 4-29 INSPECTION SUMMARY2
05/01/2025 4-29 INSPECTION SUMMARY3
05/01/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/05/2025 Letter INSPECTION SUMMARY
05/07/2025 Letter INSPECTION SUMMARY
05/07/2025 Letter INSPECTION SUMMARY
05/08/2025 Letter INSPECTION SUMMARY
05/09/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home