Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
11/02/2023
|
10/31/2023
|
|
Joe Frogge
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Action required- Provide the information needed for the rack storage.
9/25/2023
Provide details on racking type.
10/26/2023- The unstamped drawing submitted 10/11/2023 from the contractor did not show rack design, or provide a plan for emergency or exit lighting in the rack storage area.
|
|
Miscellaneous Correction
Corrective Action Required
Show exit and emergency lighting in the warehouse (New and existing).
9/25/2023- Provide exit signage on the north wall to the east of the rack storage directing to the exit north of the racking.
|
|
|
Building Plan Review
|
Approved
|
11/02/2023
|
10/27/2023
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Plans must be stamped by licensed architect or engineer and must show floor connection methods.
|
|
|
Building Plan Review
|
Rejected
|
09/11/2023
|
10/24/2023
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Plans must be stamped by licensed architect or engineer and must show floor connection methods.
|
|
|
Fire Plan Review
|
Rejected
|
10/30/2023
|
10/24/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Action required- Provide the information needed for the rack storage.
9/25/2023
Provide details on racking type.
10/26/2023- The unstamped drawing submitted 10/11/2023 from the contractor did not show rack design, or provide a plan for emergency or exit lighting in the rack storage area.
|
|
Miscellaneous Correction
Corrective Action Required
Show exit and emergency lighting in the warehouse (New and existing).
9/25/2023- Provide exit signage on the north wall to the east of the rack storage directing to the exit north of the racking.
|
|
Construction documents - Fire protection systems
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
9/25/2023-Provide a complete set of shop drawings for the ENTIRE space.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
10/26/2023
|
10/24/2023
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Call(816) 969-1303 to schedule a hydrostatic test. A visual inspection will be completed at occupany. A flow test will be conducted on the shell building inspection.
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Revised plans recieved 10/19/2023. Plans indicated approximately where the demising wall will go, but the wall was not shown. Verified at inspection.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
09/25/2023
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Stamped plans received 9/19/2023.
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call 816-969-1300 to schedule alarm testing. Coordinate with sprinkler testing.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
09/20/2023
|
09/25/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Action required- Provide the information needed for the rack storage.
9/25/2023
Provide details on racking type racking type.
|
|
Miscellaneous Correction
Corrective Action Required
Show exit and emergency lighting in the warehouse (New and existing).
9/25/2023- Provide exit signage on the north wall to the east of the rack storage directing to the exit north of the racking.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
9/25/2023-Provide a complete set of shop drawings for the ENTIRE space.
|
|
|
Building Plan Review
|
Approved
|
09/20/2023
|
09/14/2023
|
|
Joe Frogge
|
|
IBC 1016.2 Egress through intervening spaces
2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section.
Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions)
Action required: Egress not to be directed out of office area through warehouse. Remove path reference on Life Safety Plan A100.
|
|
Miscellaneous Correction
Key Plan references incorrect building.
Action required: Modify Key Plans to comply.
|
|
|
Licensed Contractors
|
Approved
|
09/20/2023
|
09/14/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
|
Fire Plan Review
|
Rejected
|
09/11/2023
|
09/12/2023
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required- Provide shop drawings for the alrm system.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required- Provide a layout of fire extinguishers.
|
|
Miscellaneous Correction
Corrective Action Required
510.1 Emergency responder radio coverage in new buildings. New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems.
Exceptions:
1. Where approved by the building official and the fire
code official, a wired communication system in
accordance with Section 907.2.12.2 shall be permitted
to be installed or maintained instead of an
approved radio coverage system.
2. Where it is determined by the fire code official that
the radio coverage system is not needed.
3. In facilities where emergency responder radio coverage is required and such systems, components or
equipment required could have a negative impact on
the normal operations of that facility, the fire code
official shall have the authority to accept an automatically activated emergency responder radio coverage system.-
Action required- Provide a study of radio signal coverage in the building and provide the necessary equipment to maintain appropriate signal strength.
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Action required- Provide the information needed for the rack storage.
|
|
MISC
Corrective Action Required
The location of the building on the Key Notes is incorrect.
|
|
Miscellaneous Correction
Corrective Action Required
309.1 General. Powered industrial trucks and similar equipment including, but not limited to, floor scrubbers and floorbuffers, shall be operated and maintained in accordance 309.2 through 309.7.Provide information on the power supply for lift trucks to be used in the warehouse.
Action required- Provide information on the type of industrial trucks and equipment to be used and how this section will be met.
|
|
Miscellaneous Correction
Corrective Action Required
Show exit and emergency lighting in the warehouse (New and existing).
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required- All fire access doors shall be posted with the suite designation for the space. Verified at inspection.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide a complete set of shop drawings for the space.
|
|
|
Building Plan Review
|
Rejected
|
09/11/2023
|
09/07/2023
|
|
Joe Frogge
|
|
IBC 1016.2 Egress through intervening spaces
Corrective Action Required
2018 IBC 1016.2 Egress through intervening spaces. Egress through intervening spaces shall comply with this section.
Item 5. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes. (See code section for additional items and exceptions)
Action required: Egress not to be directed out of office area through warehouse. Remove path reference on Life Safety Plan A100.
|
|
Miscellaneous Correction
Corrective Action Required
Key Plan references incorrect building.
Action required: Modify Key Plans to comply.
|
|
IBC 1606.2 Design dead load - structural
2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official.
Provide the following:
- Engineer’s report (or design) to verify that existing roof structure will support additional load imposed by roof mounted equipment.
- Detailed roof curb construction information.
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2017 as amended and adopted by the City of Lee’s Summit.
|
|
|
Licensed Contractors
|
Rejected
|
09/11/2023
|
09/07/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Provide an email address & phone number for the on-site contact which is where inspection reports will be sent.
|
|
|