Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
05/16/2024
|
05/09/2024
|
|
Brandon Kalwei
|
|
Miscellaneous Correction
Corrective Action Required
The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources.
Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
06/12/2023- No response.
7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs.
05/1/2024- Petroleum tank plan from MAC does not match approved FDP tank plan. How many tanks will there be and what is the quantity of gasoline and diesel fuel?
2303.2 Emergency disconnect switches. An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Suchdevices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
5/6/2024- Provide exterior shut-off. Verified at inspection
|
|
Miscellaneous Correction
Corrective Action Required
Water service and Site plans still show the building as being sprinklered.
Amend the plans.
|
|
|
Building Plan Review
|
Approved with Conditions
|
05/16/2024
|
05/09/2024
|
|
Brandon Kalwei
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
Miscellaneous Correction
Corrective Action Required
The License Tax shall be paid prior to receiving any type of occupancy.
|
|
Miscellaneous Correction
Corrective Action Required
The turn lane improvements on Hamblen Rd shall be issued a Substantial Completion, at a minimum, prior to issuance of any type of occupancy for the convenience store.
|
|
|
Licensed Contractors
|
Approved
|
05/09/2024
|
05/09/2024
|
|
Brandon Kalwei
|
|
|
Licensed Contractors
|
Approved
|
05/01/2024
|
05/07/2024
|
|
Joe Frogge
|
|
LC - General Contractor
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor.
6/9/23 - not addressed
|
|
LC - MEP Subs
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
6/9/23 - not addressed
|
|
|
Fire Plan Review
|
Approved with Conditions
|
05/01/2024
|
05/06/2024
|
|
Jim Eden
|
|
Miscellaneous Correction
Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
5/1/2024- Indicate the quantity of gasoline and diesel fuel to be stored. The MAC tank plans do not match the tank plan on the FDC. Per Robert Andrew the most current submittal is correct for tank size with quantities less than 75,000-gallons.
|
|
Misc
5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1
Action required- Confirm size of CO2 tank.
7.3.2023- Comfirmed 300-pound cylinder.Per IFC 5307.1- Provide ventilation in accordance with IFC 5004.3 or detection in accordance with 5307.3.2. Drawing M! does not show an exhaust system.
|
|
Miscellaneous Correction
Corrective Action Required
The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources.
Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
06/12/2023- No response.
7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs.
05/1/2024- Petroleum tank plan from MAC does not match approved FDP tank plan. How many tanks will there be and what is the quantity of gasoline and diesel fuel?
2303.2 Emergency disconnect switches. An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Suchdevices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
5/6/2024- Provide exterior shut-off. Verified at inspection
|
|
Miscellaneous Correction
Corrective Action Required
Water service and Site plans still show the building as being sprinklered.
Amend the plans.
|
|
|
Building Plan Review
|
Approved with Conditions
|
05/01/2024
|
04/30/2024
|
|
Joe Frogge
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
Miscellaneous Correction
Corrective Action Required
The License Tax shall be paid prior to receiving any type of occupancy.
|
|
Miscellaneous Correction
Corrective Action Required
The turn lane improvements on Hamblen Rd shall be issued a Substantial Completion, at a minimum, prior to issuance of any type of occupancy for the convenience store.
|
|
|
Building Plan Review
|
Approved with Conditions
|
07/05/2023
|
03/20/2024
|
|
Joe Frogge
|
|
Final Development Plan
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
SEC - CPTED
Code of Ordinances Section 8.330. CPTED Review Requirement.
All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”.
Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space.
1. Bank/Financial Services
2. Bank Drive-Thru Facility
3. Check Cashing and Payday Loan Business
4. Convenience Store (C-Store)
5. Financial Services with Drive-up Window or Drive-Thru Facility
6. Pawn Shop
7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand
8. Unattended self-serve gas pumps
9. Unsecured Loan Business
10. Other similar uses shall meet the same standards as the above
Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved.
6/9/23 - Revisions inadequate. Provide response to each line item listed in ordinance.
|
|
Gen - Plan submittals 2018 codes
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Revise Design Criteria on S1.1 to show correct code year.
6/9/23 - not addressed- still shows 2015
|
|
IBC 1008.3 Emergency power for illumination - at exit discharge
2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps.
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1.
5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge.
1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas:
1. Electrical equipment rooms.
2. Fire command centers.
3. Fire pump rooms.
4. Generator rooms.
5. Public restrooms with an area greater than 300 square feet.
Action required: Provide emergency lighting at landing side of main double door exit.
6/9/23 - not found in design
|
|
Miscellaneous Correction
Insufficient information to complete review at raised cashier area.
Clarify/modify the following?
- How high is platform? (see IBC 1103.2.2 & 1011.5.2)
- Materials to be per IBC 410.3.
- Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf)
- Ramps require handrails on each side.
- Ramps require landings per IBC 1012.6.
6/9/23:
- 6" step means that entire cashier area must be accessible. (ramp rqd, turning radius, reach ranges, etc)
|
|
IPC 604.9 Water hammer
2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010.
Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed.
6/9/23 - air chambers still noted in spec.
|
|
|
Final Development Plan Review
|
Approved
|
02/16/2024
|
03/14/2024
|
|
Mike Weisenborn
|
|
LION PETROLEUM CONVENIENCE STORE
|
Fire Plan Review
|
Rejected
|
07/05/2023
|
07/06/2023
|
|
Jim Eden
|
|
Miscellaneous Correction
2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
Action required: Provide emergency lighting at landing side of main double door exit.
06/12/2023- No correction provided.
|
|
Miscellaneous Correction
Corrective Action Required
Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
|
|
Misc
Corrective Action Required
5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1
Action required- Confirm size of CO2 tank.
7.3.2023- Comfirmed 300-pound cylinder.Per IFC 5307.1- Provide ventilation in accordance with IFC 5004.3 or detection in accordance with 5307.3.2. Drawing M! does not show an exhaust system.
|
|
Miscellaneous Correction
Corrective Action Required
The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources.
Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
06/12/2023- No response.
7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs.
|
|
Miscellaneous Correction
The Final Development Plan calls the building out as fully sprinklered.
Action required- Provide revised civil plans.
6/12/2023- No response
7/3/2023- Removed.
|
|
Duct smoke detectors
2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM.
6/12/2023- No response.
7/3/2023- Provide remote reset//test/annunciators if a fire alarm is not provided. Verified at inspection.
|
|
|
Licensed Contractors
|
Rejected
|
07/05/2023
|
06/29/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor.
6/9/23 - not addressed
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
6/9/23 - not addressed
|
|
|
Fire Plan Review
|
Rejected
|
06/07/2023
|
06/12/2023
|
|
Jim Eden
|
|
Address numbers required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Paction required- Provide fire extinguishers for the store and fuel dispensing area (IFC Chapter 23)
|
|
Miscellaneous Correction
Corrective Action Required
2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
Action required: Provide emergency lighting at landing side of main double door exit.
06/12/2023- No correction provided.
|
|
Miscellaneous Correction
Corrective Action Required
Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
|
|
Misc
Corrective Action Required
5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1
Action required- Confirm size of CO2 tank.
|
|
Miscellaneous Correction
Corrective Action Required
The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources.
Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
06/12/2023- No response.
|
|
Miscellaneous Correction
Corrective Action Required
The Final Development Plan calls the building out as fully sprinklered.
Action required- Provide revised civil plans.
6/12/2023- No response
|
|
Duct smoke detectors
Corrective Action Required
2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM.
6/12/2023- No response.
|
|
|
Building Plan Review
|
Rejected
|
06/07/2023
|
06/12/2023
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
Health Dept Review
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is informational.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
6/9/23 - not addressed
|
|
SEC - CPTED
Corrective Action Required
Code of Ordinances Section 8.330. CPTED Review Requirement.
All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”.
Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space.
1. Bank/Financial Services
2. Bank Drive-Thru Facility
3. Check Cashing and Payday Loan Business
4. Convenience Store (C-Store)
5. Financial Services with Drive-up Window or Drive-Thru Facility
6. Pawn Shop
7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand
8. Unattended self-serve gas pumps
9. Unsecured Loan Business
10. Other similar uses shall meet the same standards as the above
Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved.
6/9/23 - Revisions inadequate. Provide response to each line item listed in ordinance.
|
|
Misc
Remove references to car wash in Code Block.
|
|
ICC A117.1 604.6 Flush Controls
ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet.
Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet.
Action required: Modify designs to demonstrate compliance. Flush lever must be on open side of stall.
6/9/23 - not changed
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Revise Design Criteria on S1.1 to show correct code year.
6/9/23 - not addressed- still shows 2015
|
|
IBC 1803.1 General - geotech
2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional.
Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
6/9/23 - not found in submittal
|
|
NEC Article 210.8 (B) Other than dwelling units GFCI
2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Kitchens
(3) Rooftops
(4) Outdoors
(5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms.
(9) Crawl spaces – at or below grade level.
(10) Unfinished portions or areas of the basement not intended as habitable rooms.
(refer to code for exceptions)
Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
|
|
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps.
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1.
5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge.
1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas:
1. Electrical equipment rooms.
2. Fire command centers.
3. Fire pump rooms.
4. Generator rooms.
5. Public restrooms with an area greater than 300 square feet.
Action required: Provide emergency lighting at landing side of main double door exit.
6/9/23 - not found in design
|
|
NEC Article 250.50 Grounding electrode system
2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception)
Action required: Provide ground concrete encased electrode. ("Ufer" ground)
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide receptacle(s) within 25' of rooftop equipment.
|
|
Miscellaneous Correction
Corrective Action Required
Insufficient information to complete review at raised cashier area.
Clarify/modify the following?
- How high is platform? (see IBC 1103.2.2 & 1011.5.2)
- Materials to be per IBC 410.3.
- Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf)
- Ramps require handrails on each side.
- Ramps require landings per IBC 1012.6.
6/9/23:
- 6" step means that entire cashier area must be accessible. (ramp rqd, turning radius, reach ranges, etc)
|
|
IPC 604.9 Water hammer
Corrective Action Required
2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010.
Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed.
6/9/23 - air chambers still noted in spec.
|
|
IPC 502.1 Water heater manufacturers installation instructions
2018 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code.
Action required: Provide expansion tank at water heater or provide verification that water heater installed will not require expansion tank in the manufacturer's written instructions.
|
|
IPC 802.1 Indirect/special waste
2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7.
Action required: Amend designs to demonstrate compliance.
|
|
Miscellaneous Correction
Provide water service entry detail/diagram.
|
|
|
Licensed Contractors
|
Rejected
|
06/07/2023
|
06/09/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor.
6/9/23 - not addressed
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
6/9/23 - not addressed
|
|
|
Health Department Review
|
Approved
|
03/23/2023
|
06/08/2023
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Rejected
|
03/23/2023
|
03/26/2023
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Paction required- Provide fire extinguishers for the store and fuel dispensing area (IFC Chapter 23)
|
|
Miscellaneous Correction
2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps.
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1.
5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge.
1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas:
1. Electrical equipment rooms.
2. Fire command centers.
3. Fire pump rooms.
4. Generator rooms.
5. Public restrooms with an area greater than 300 square feet.
Action required: Provide emergency lighting at landing side of main double door exit.
|
|
Miscellaneous Correction
Corrective Action Required
Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
|
|
Misc
Corrective Action Required
5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1
Action required- Confirm size of CO2 tank.
|
|
Miscellaneous Correction
Corrective Action Required
The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri DEpartment of Natural Resources.
Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
|
|
Miscellaneous Correction
The Final Development Plan calls the building out as fully sprinklered.
Action required- Provide revised civil plans.
|
|
Duct smoke detectors
Corrective Action Required
2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM.
|
|
|
Building Plan Review
|
Rejected
|
03/23/2023
|
03/17/2023
|
|
Joe Frogge
|
|
Final Development Plan
Corrective Action Required
The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan.
Action required: Comment is informational.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required: Comment is informational.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required: Comment is informational.
|
|
SEC - CPTED
Corrective Action Required
Code of Ordinances Section 8.330. CPTED Review Requirement.
All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”.
Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space.
1. Bank/Financial Services
2. Bank Drive-Thru Facility
3. Check Cashing and Payday Loan Business
4. Convenience Store (C-Store)
5. Financial Services with Drive-up Window or Drive-Thru Facility
6. Pawn Shop
7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand
8. Unattended self-serve gas pumps
9. Unsecured Loan Business
10. Other similar uses shall meet the same standards as the above
Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved.
|
|
Misc
Corrective Action Required
Remove references to car wash in Code Block.
|
|
ICC A117.1 604.6 Flush Controls
Corrective Action Required
ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet.
Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet.
Action required: Modify designs to demonstrate compliance. Flush lever must be on open side of stall.
|
|
Gen - Plan submittals 2018 codes
Corrective Action Required
All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit.
Action required: Revise Design Criteria on S1.1 to show correct code year.
|
|
IBC 1803.1 General - geotech
Corrective Action Required
2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional.
Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
|
|
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel.
(1) Bathrooms
(2) Kitchens
(3) Rooftops
(4) Outdoors
(5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink.
(6) Indoor wet locations
(7) Locker rooms with associated showering facilities
(8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms.
(9) Crawl spaces – at or below grade level.
(10) Unfinished portions or areas of the basement not intended as habitable rooms.
(refer to code for exceptions)
Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
|
|
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply.
1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Aisles.
2. Corridors.
3. Exit access stairways and ramps.
1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas:
1. Interior exit access stairways and ramps.
2. Interior and exterior exit stairways and ramps.
3. Exit passageways.
4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1.
5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge.
1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas:
1. Electrical equipment rooms.
2. Fire command centers.
3. Fire pump rooms.
4. Generator rooms.
5. Public restrooms with an area greater than 300 square feet.
Action required: Provide emergency lighting at landing side of main double door exit.
|
|
NEC Article 250.50 Grounding electrode system
Corrective Action Required
2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception)
Action required: Provide ground concrete encased electrode. ("Ufer" ground)
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide receptacle(s) within 25' of rooftop equipment.
|
|
Miscellaneous Correction
Corrective Action Required
Insufficient information to complete review at raised cashier area.
Clarify/modify the following?
- How high is platform? (see IBC 1103.2.2 & 1011.5.2)
- Materials to be per IBC 410.3.
- Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf)
- Ramps require handrails on each side.
- Ramps require landings per IBC 1012.6.
|
|
IPC 604.9 Water hammer
Corrective Action Required
2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010.
Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed.
|
|
IPC 502.1 Water heater manufacturers installation instructions
Corrective Action Required
2018 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code.
Action required: Provide expansion tank at water heater or provide verification that water heater installed will not require expansion tank in the manufacturer's written instructions.
|
|
IPC 802.1 Indirect/special waste
Corrective Action Required
2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7.
Action required: Amend designs to demonstrate compliance.
|
|
Miscellaneous Correction
Corrective Action Required
Provide water service entry detail/diagram.
|
|
|
Licensed Contractors
|
Rejected
|
03/23/2023
|
03/17/2023
|
|
Joe Frogge
|
|
LC - General Contractor
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor.
|
|
LC - MEP Subs
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt)
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section.
Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
|
|
|