Permit Application Status

PRCOM20230994


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20230994
Building Permit - Commercial
Issued
NEW COMMERCIAL
LP Mart - NEW CONVENIENCE STORE WITH 16 PUMP CANOPY **Invite Police to final
03/09/2023
05/14/2024
10/29/2024
Locations
Contacts
MID-WEST ASSOCIATED CONTRACTORS CORPORATION, Address:900 NW HUNTER DR STE 25, Phone:(816) 229-6090  
C RENFROW, Phone:(816) 729-8046  
MALIK HEATING & COOLING, Address:6403 W 158TH ST, Phone:(816) 813-1338  
ROZIER ELECTRIC, Address:1608 SW JEFFERSON ST, Phone:(816) 246-9000  
R2 PLUMBING LLC, Address:1705 A SE COUNTY RD AA, Phone:(816) 215-8098  
Rangwala Architects, Address:201 S Central Ave. Unit 203, Phone:(314) 863-6661  
NEIGHBORS CONSTRUCTION COMPANY INC, Address:1708 E 123RD ST, Phone:(913) 422-5555  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 05/16/2024 05/09/2024
Brandon Kalwei
Miscellaneous Correction
Corrective Action Required
05/09/2024

The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources. Action required- Provide plans and specifications for the fuel dispensing operation and the canopy. 06/12/2023- No response. 7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs. 05/1/2024- Petroleum tank plan from MAC does not match approved FDP tank plan. How many tanks will there be and what is the quantity of gasoline and diesel fuel? 2303.2 Emergency disconnect switches. An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Suchdevices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations. 5/6/2024- Provide exterior shut-off. Verified at inspection
Miscellaneous Correction
Corrective Action Required
05/09/2024

Water service and Site plans still show the building as being sprinklered. Amend the plans.
Building Plan Review Approved with Conditions 05/16/2024 05/09/2024
Brandon Kalwei
Health Dept Inspection
Corrective Action Required
05/09/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/9/23 - not addressed
Miscellaneous Correction
Corrective Action Required
05/09/2024

The License Tax shall be paid prior to receiving any type of occupancy.
Miscellaneous Correction
Corrective Action Required
05/09/2024

The turn lane improvements on Hamblen Rd shall be issued a Substantial Completion, at a minimum, prior to issuance of any type of occupancy for the convenience store.
Licensed Contractors Approved 05/09/2024 05/09/2024
Brandon Kalwei
Licensed Contractors Approved 05/01/2024 05/07/2024
Joe Frogge
LC - General Contractor
Resolved
04/30/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor. 6/9/23 - not addressed
LC - MEP Subs
Resolved
05/07/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/9/23 - not addressed
Fire Plan Review Approved with Conditions 05/01/2024 05/06/2024
Jim Eden
Miscellaneous Correction
Resolved
05/06/2024

Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages. 5/1/2024- Indicate the quantity of gasoline and diesel fuel to be stored. The MAC tank plans do not match the tank plan on the FDC. Per Robert Andrew the most current submittal is correct for tank size with quantities less than 75,000-gallons.
Misc
Resolved
05/06/2024

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1 Action required- Confirm size of CO2 tank. 7.3.2023- Comfirmed 300-pound cylinder.Per IFC 5307.1- Provide ventilation in accordance with IFC 5004.3 or detection in accordance with 5307.3.2. Drawing M! does not show an exhaust system.
Miscellaneous Correction
Corrective Action Required
04/24/2024

The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources. Action required- Provide plans and specifications for the fuel dispensing operation and the canopy. 06/12/2023- No response. 7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs. 05/1/2024- Petroleum tank plan from MAC does not match approved FDP tank plan. How many tanks will there be and what is the quantity of gasoline and diesel fuel? 2303.2 Emergency disconnect switches. An approved emergency disconnect switch shall be provided at an approved location to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. The emergency disconnect switch for exterior fuel dispensers shall be provided with ready access and shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be provided with ready access and be installed at an approved location. Suchdevices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations. 5/6/2024- Provide exterior shut-off. Verified at inspection
Miscellaneous Correction
Corrective Action Required
05/02/2024

Water service and Site plans still show the building as being sprinklered. Amend the plans.
Building Plan Review Approved with Conditions 05/01/2024 04/30/2024
Joe Frogge
Health Dept Inspection
Corrective Action Required
04/24/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/9/23 - not addressed
Miscellaneous Correction
Corrective Action Required
05/06/2024

The License Tax shall be paid prior to receiving any type of occupancy.
Miscellaneous Correction
Corrective Action Required
05/06/2024

The turn lane improvements on Hamblen Rd shall be issued a Substantial Completion, at a minimum, prior to issuance of any type of occupancy for the convenience store.
Building Plan Review Approved with Conditions 07/05/2023 03/20/2024
Joe Frogge
Final Development Plan
Resolved
03/14/2024

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 6/9/23 - not addressed
Health Dept Inspection
Corrective Action Required
06/27/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/9/23 - not addressed
SEC - CPTED
Resolved
06/29/2023

Code of Ordinances Section 8.330. CPTED Review Requirement. All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”. Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convenience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended self-serve gas pumps 9. Unsecured Loan Business 10. Other similar uses shall meet the same standards as the above Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved. 6/9/23 - Revisions inadequate. Provide response to each line item listed in ordinance.
Gen - Plan submittals 2018 codes
Resolved
06/29/2023

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise Design Criteria on S1.1 to show correct code year. 6/9/23 - not addressed- still shows 2015
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
06/29/2023

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at landing side of main double door exit. 6/9/23 - not found in design
Miscellaneous Correction
Resolved
06/29/2023

Insufficient information to complete review at raised cashier area. Clarify/modify the following? - How high is platform? (see IBC 1103.2.2 & 1011.5.2) - Materials to be per IBC 410.3. - Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf) - Ramps require handrails on each side. - Ramps require landings per IBC 1012.6. 6/9/23: - 6" step means that entire cashier area must be accessible. (ramp rqd, turning radius, reach ranges, etc)
IPC 604.9 Water hammer
Resolved
06/29/2023

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed. 6/9/23 - air chambers still noted in spec.
Final Development Plan Review Approved 02/16/2024 03/14/2024
Mike Weisenborn
LION PETROLEUM CONVENIENCE STORE
Fire Plan Review Rejected 07/05/2023 07/06/2023
Jim Eden
Miscellaneous Correction
Resolved
07/03/2023

2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. Action required: Provide emergency lighting at landing side of main double door exit. 06/12/2023- No correction provided.
Miscellaneous Correction
Corrective Action Required
06/27/2023

Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
Misc
Corrective Action Required
06/27/2023

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1 Action required- Confirm size of CO2 tank. 7.3.2023- Comfirmed 300-pound cylinder.Per IFC 5307.1- Provide ventilation in accordance with IFC 5004.3 or detection in accordance with 5307.3.2. Drawing M! does not show an exhaust system.
Miscellaneous Correction
Corrective Action Required
06/27/2023

The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources. Action required- Provide plans and specifications for the fuel dispensing operation and the canopy. 06/12/2023- No response. 7/3/2013- Provide plans for the tanks, pumps, awning and shut-offs.
Miscellaneous Correction
Resolved
07/03/2023

The Final Development Plan calls the building out as fully sprinklered. Action required- Provide revised civil plans. 6/12/2023- No response 7/3/2023- Removed.
Duct smoke detectors
Resolved
07/03/2023

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM. 6/12/2023- No response. 7/3/2023- Provide remote reset//test/annunciators if a fire alarm is not provided. Verified at inspection.
Licensed Contractors Rejected 07/05/2023 06/29/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
06/27/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor. 6/9/23 - not addressed
LC - MEP Subs
Corrective Action Required
06/27/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/9/23 - not addressed
Fire Plan Review Rejected 06/07/2023 06/12/2023
Jim Eden
Address numbers required
Resolved
06/12/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Portable fire extinguishers - general
Resolved
06/12/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Paction required- Provide fire extinguishers for the store and fuel dispensing area (IFC Chapter 23)
Miscellaneous Correction
Corrective Action Required
05/31/2023

2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. Action required: Provide emergency lighting at landing side of main double door exit. 06/12/2023- No correction provided.
Miscellaneous Correction
Corrective Action Required
05/31/2023

Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
Misc
Corrective Action Required
05/31/2023

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1 Action required- Confirm size of CO2 tank.
Miscellaneous Correction
Corrective Action Required
05/31/2023

The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri Department of Natural Resources. Action required- Provide plans and specifications for the fuel dispensing operation and the canopy. 06/12/2023- No response.
Miscellaneous Correction
Corrective Action Required
05/31/2023

The Final Development Plan calls the building out as fully sprinklered. Action required- Provide revised civil plans. 6/12/2023- No response
Duct smoke detectors
Corrective Action Required
05/31/2023

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM. 6/12/2023- No response.
Building Plan Review Rejected 06/07/2023 06/12/2023
Joe Frogge
Final Development Plan
Corrective Action Required
05/31/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 6/9/23 - not addressed
Health Dept Review
Resolved
06/08/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
05/31/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 6/9/23 - not addressed
SEC - CPTED
Corrective Action Required
05/31/2023

Code of Ordinances Section 8.330. CPTED Review Requirement. All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”. Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convenience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended self-serve gas pumps 9. Unsecured Loan Business 10. Other similar uses shall meet the same standards as the above Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved. 6/9/23 - Revisions inadequate. Provide response to each line item listed in ordinance.
Misc
Resolved
06/09/2023

Remove references to car wash in Code Block.
ICC A117.1 604.6 Flush Controls
Resolved
06/09/2023

ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet. Action required: Modify designs to demonstrate compliance. Flush lever must be on open side of stall. 6/9/23 - not changed
Gen - Plan submittals 2018 codes
Corrective Action Required
05/31/2023

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise Design Criteria on S1.1 to show correct code year. 6/9/23 - not addressed- still shows 2015
IBC 1803.1 General - geotech
Resolved
06/16/2023

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf. 6/9/23 - not found in submittal
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
06/09/2023

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
05/31/2023

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at landing side of main double door exit. 6/9/23 - not found in design
NEC Article 250.50 Grounding electrode system
Resolved
06/09/2023

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide ground concrete encased electrode. ("Ufer" ground)
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Resolved
06/09/2023

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of rooftop equipment.
Miscellaneous Correction
Corrective Action Required
05/31/2023

Insufficient information to complete review at raised cashier area. Clarify/modify the following? - How high is platform? (see IBC 1103.2.2 & 1011.5.2) - Materials to be per IBC 410.3. - Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf) - Ramps require handrails on each side. - Ramps require landings per IBC 1012.6. 6/9/23: - 6" step means that entire cashier area must be accessible. (ramp rqd, turning radius, reach ranges, etc)
IPC 604.9 Water hammer
Corrective Action Required
05/31/2023

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed. 6/9/23 - air chambers still noted in spec.
IPC 502.1 Water heater manufacturers installation instructions
Resolved
06/09/2023

2018 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code. Action required: Provide expansion tank at water heater or provide verification that water heater installed will not require expansion tank in the manufacturer's written instructions.
IPC 802.1 Indirect/special waste
Resolved
06/09/2023

2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Amend designs to demonstrate compliance.
Miscellaneous Correction
Resolved
06/09/2023

Provide water service entry detail/diagram.
Licensed Contractors Rejected 06/07/2023 06/09/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
05/31/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor. 6/9/23 - not addressed
LC - MEP Subs
Corrective Action Required
05/31/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 6/9/23 - not addressed
Health Department Review Approved 03/23/2023 06/08/2023
Joe Frogge
Fire Plan Review Rejected 03/23/2023 03/26/2023
Jim Eden
Address numbers required
Corrective Action Required
03/26/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Portable fire extinguishers - general
Resolved
07/03/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Paction required- Provide fire extinguishers for the store and fuel dispensing area (IFC Chapter 23)
Miscellaneous Correction
Resolved
07/03/2023

2018 IFC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at landing side of main double door exit.
Miscellaneous Correction
Corrective Action Required
03/26/2023

Complete a Hazardous Materials Permit Application- Include a site plan, tank and dispensing equipment information. A Hazardous Materials Permit is also required for propane cylinder exchange. If provided, show the location of exchange cages.
Misc
Corrective Action Required
03/26/2023

5307.3 Insulated liquid carbon dioxide systems used in beverage dispensing applications. Insulated liquid carbon dioxide systems with more than 100 pounds (45.4 kg) of carbon dioxide used in beverage dispensing applications shall comply with Section 5307.3.1 Action required- Confirm size of CO2 tank.
Miscellaneous Correction
Corrective Action Required
03/26/2023

The dispensing of fuel shall be in accordance with IFC Chapter 23 and the Missouri DEpartment of Natural Resources. Action required- Provide plans and specifications for the fuel dispensing operation and the canopy.
Miscellaneous Correction
Resolved
07/03/2023

The Final Development Plan calls the building out as fully sprinklered. Action required- Provide revised civil plans.
Duct smoke detectors
Corrective Action Required
03/26/2023

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. Action required- Provide duct detection with remote annunciators and resets for HVAC unit greater than 2000 CFM.
Building Plan Review Rejected 03/23/2023 03/17/2023
Joe Frogge
Final Development Plan
Corrective Action Required
03/17/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Health Dept Review
Corrective Action Required
03/17/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
03/17/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
SEC - CPTED
Corrective Action Required
03/17/2023

Code of Ordinances Section 8.330. CPTED Review Requirement. All development applications shall be subject to CPTED review and recommendations. The application of CPTED concepts and strategies is site specific and the level of review shall be determined on a case by case basis. Some requests during development review will require mandatory compliance. Others will be strongly encouraged but compliance will be voluntary. Mandatory compliance elements will be addressed in Article 9 “Uses with Conditions”. Section 8.340. CPTED Uses Specified The following uses have been classified as “Uses with Conditions” per Article 9 of this Chapter, having been determined with a tendency toward an increased risk of crime,. Specific conditions for such uses are found in Article 9 and shall be required to be met prior to receiving any zoning approval, business license or approval to occupy any commercial space. 1. Bank/Financial Services 2. Bank Drive-Thru Facility 3. Check Cashing and Payday Loan Business 4. Convenience Store (C-Store) 5. Financial Services with Drive-up Window or Drive-Thru Facility 6. Pawn Shop 7. Title Loan Business, if performing on site cash transactions with $500 or more in cash on hand 8. Unattended self-serve gas pumps 9. Unsecured Loan Business 10. Other similar uses shall meet the same standards as the above Action required: Submit drawings or detailed report/spec to demonstrate compliance. A separate review for CPTED requirements must be performed. Permit will not be issued until CPTED review is approved.
Misc
Corrective Action Required
03/17/2023

Remove references to car wash in Code Block.
ICC A117.1 604.6 Flush Controls
Corrective Action Required
03/17/2023

ICC A117.1 Section 604.6 Flush Controls. Flush controls shall be hand operated or automatic. Hand operated flush controls shall comply with Section 309. Flush controls shall be located on the open side of the water closet. Exception: In ambulatory accessible compartments complying with Section 604.10, flush controls shall be permitted to be located on either side of the water closet. Action required: Modify designs to demonstrate compliance. Flush lever must be on open side of stall.
Gen - Plan submittals 2018 codes
Corrective Action Required
03/17/2023

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Revise Design Criteria on S1.1 to show correct code year.
IBC 1803.1 General - geotech
Corrective Action Required
03/17/2023

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf.
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
03/17/2023

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
03/17/2023

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at landing side of main double door exit.
NEC Article 250.50 Grounding electrode system
Corrective Action Required
03/17/2023

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide ground concrete encased electrode. ("Ufer" ground)
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
03/17/2023

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) within 25' of rooftop equipment.
Miscellaneous Correction
Corrective Action Required
03/17/2023

Insufficient information to complete review at raised cashier area. Clarify/modify the following? - How high is platform? (see IBC 1103.2.2 & 1011.5.2) - Materials to be per IBC 410.3. - Is ramp necessary? (it can be avoided if exactly 7" tall and cashier area remains less than 300sf) - Ramps require handrails on each side. - Ramps require landings per IBC 1012.6.
IPC 604.9 Water hammer
Corrective Action Required
03/17/2023

2018 IPC 604.9 Water hammer. The flow velocity of the water distribution system shall be controlled to reduce the possibility of water hammer. A water-hammer arrestor shall be installed where quick-closing valves are utilized. Water-hammer arrestors shall be installed in accordance with the manufacturer’s instructions. Water-hammer arrestors shall conform to ASSE 1010. Action required: Amend Plumbing Specification to provide water hammer arrestors. Air chambers not allowed.
IPC 502.1 Water heater manufacturers installation instructions
Corrective Action Required
03/17/2023

2018 IPC 502.1 General. Water heaters shall be installed in accordance with the manufacturer’s installation instructions. Oil-fired water heaters shall conform to the requirements of this code and the International Mechanical Code. Electric water heaters shall conform to the requirements of this code and provisions of NFPA 70. Gas-fired water heaters shall conform to the requirements of the International Fuel Gas Code. Action required: Provide expansion tank at water heater or provide verification that water heater installed will not require expansion tank in the manufacturer's written instructions.
IPC 802.1 Indirect/special waste
Corrective Action Required
03/17/2023

2018 IPC 802.1 Where required. Food-handling equipment, in other than dwelling units, clear-water waste, humidifiers, dish-washing machines and utensils, pots, pans and dishwashing sinks shall discharge though an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. Fixtures not required to be indirectly connected by this section and the exception to Section 301.6 shall be directly connected to the plumbing system in accordance with Chapter 7. Action required: Amend designs to demonstrate compliance.
Miscellaneous Correction
Corrective Action Required
03/17/2023

Provide water service entry detail/diagram.
Licensed Contractors Rejected 03/23/2023 03/17/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
03/17/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor.
LC - MEP Subs
Corrective Action Required
03/17/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $6,000.00 $6,000.00 Paid 05/14/2024
8331401-Water Tap Fee $12,535.00 $12,535.00 Paid 05/14/2024
8350015-Water Meter Fee $3,663.86 $3,663.86 Paid 05/14/2024
8331507-Sanitary Sewer Development Fee $7,189.00 $7,189.00 Paid 05/14/2024
9110071-Site Grading Fee $2,498.25 $2,498.25 Paid 05/14/2024
9110081-Paved Surface Inspection Fee $5,538.86 $5,538.86 Paid 05/14/2024
91100C9-Water Insp Fee $475.32 $475.32 Paid 05/14/2024
9110068-Storm Fee $790.87 $790.87 Paid 05/14/2024
91100C8-Sanitary Sewer Insp Fees $184.51 $184.51 Paid 05/14/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 05/14/2024
Outstanding Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $195,426.00 $0.00 $195,426.00 Not Paid
9110069-After Hours Inspections (Public Works)(Per Hour) $75.00 $0.00 $75.00 Not Paid


$195,501.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Install Street and Stop Signs Pending
Pavement-Aggregate Base Pending
Pavement-Stabilized Subgrade Pending
Erosion Control Inspection Pending
Rough Electrical Inspection - Commercial Pending
Water Service Inspection Pending
Misc
Informational
08/28/2024
8-28-24 BR Contractor excavated for water main to give access to water dept. ready for tap on water main.
Site Visit Pending
Misc
Informational
09/03/2024
5-20-24 BR No work is being done on site. 7-8-24 PS No activity on site 9-3-2024 Dustin A, Building work
Sewer Service Inspection Pending
Misc
Informational
09/09/2024
8-30-24 BR Contractor installed 50' of service wye from building with clean out installed next to the building. 09/09/24 Monday JMJ Contractor performed tie-in to the 8" existing sanitary main with two max adapters and 8"X6" tee. Contractor bored 70' of 6" sanitary main across the road of SE Hamblen RD on Friday 09/06/24. Cleanout was already set (possibly done on Friday) on the Eastside of SE Hamblen RD . Contractor will install approximately 70' more of sanitary were sanitary was stub out from building site.
Sidewalk Inspection Pending
Misc
Informational
09/10/2024
9-9-24 BR Contractor took out one panel of sidewalk to connect water service to water main.
Pavement-Curb Construction Pending
Misc
Corrective Action Required
10/07/2024
10-7-24 BR Contractor start forming for curbs on north side of parking lot. Contractor need to add aggregate and be compacted before ready to pour concrete.
Storm Sewer Construction Inspection Pending
Misc
Informational
10/10/2024
10-9-24 BR Contractor started working on installing storm box south side of building to connect to existing 36'' RCP pipe.
Footing Inspection - Commercial Pending
Misc
Informational
10/16/2024
-Building perimeter footings complete -(8) of (8) canopy piers complete
Pavement-Proof Roll Pending
Misc
Informational
10/21/2024
10-21-24 BR Contractor preformed a poof roll on east parking lot section to entrance to LS specifications. pass
Pavement-Surface Pending
Misc
Informational
11/05/2024
11-5-24 BR Contractor poured 1st driveway entrance approach on east side of building and parking lot along with poured driveway next to islands on west side of parking lot.
Verify Final Inspection Status - New Com Development Pending
Erosion Control Inspection Residential Pending
Misc
Corrective Action Required
12/16/2024
-Install gravel filter at site entrance and clean mud from streets. No further inspections will be performed until in compliance
Driveway Inspection Pending
Misc
Informational
12/19/2024
12-19-24 BR Contractor installed aggregate base on driveway entrance on south side of property to store front entrance.
Above Ceiling Inspection Pending
Misc
Corrective Action Required
04/22/2025
Bathroom hard lids ok to cover inspection canceled for 4/22/25 no GC is listed, new GC needs to be added to the permit and verified MARK HARDING 04/22/2025 8:10 AM
Underground Plumbing Inspection - Commercial Pending 7/17/2024
Grading/Excavation/Fill Inspection Partial 5/24/2024 05/24/2024
Misc
Informational
05/17/2024
5-17-24 BR Contractor (MAC) is grading the area. 5-21-24 BR Contractor (MAC) is grading the area. 5-24-24 BR Contractor (MAC) is grading the area 5-29-24 BR Contractor (MAC) is grading the area.
Footing Inspection - Commercial Passed 6/19/2024 6/20/2024 06/20/2024
Misc
Informational
06/20/2024
-Copper grounding cable located on south side of building.
Site Visit Partial 7/16/2024 7/16/2024 07/16/2024
Misc
Informational
05/20/2024
5-20-24 BR No work is being done on site. 7-8-24 PS No activity on site 7-16-24 BR Contractor is working on installing electrical conduct in building floor and brick layers are installing building walls.
Underslab Plumbing Inspection - Commercial Failed 07/17/2024
Misc
Corrective Action Required
07/17/2024
**CITY STAMPED PLANS REQUIRED ON SITE FOR ALL INSPECTIONS -Air test approved -DO NOT COVER
Underslab Plumbing Inspection - Commercial Passed 7/18/2024 7/18/2024 07/18/2024
Misc
Resolved
07/18/2024
Underslab Electrical Inspection - Commercial Passed 7/26/2024 7/26/2024 07/26/2024
Miscellaneous Inspection Passed 8/7/2024 08/07/2024
Misc
Informational
08/07/2024
Referred contractor to Jim Eden to inspect underground fuel tanks
Site Visit Partial 8/15/2024 8/15/2024 08/15/2024
Misc
Informational
05/20/2024
5-20-24 BR No work is being done on site. 5-22-24 BR Contractor placed aggregate and compacted rock for the base of retaining wall on the east side of build pad. 5-23-24 BR Contractor installed 2nd and 3rd layer of retaining wall. 5-29-24 BR Contractor installed 4th layer on retaining wall. 6-6-24 BR Contractor is working on building pad. 6-17-24 BR Contractor is working on building pad and digging for fuel pump silos. 6-25-24 BR Contractor is working on digging for fuel tanks placement. 7-2-24 BR No work is being done do to site is to wet do to rain events. 8-9-24 BR Contractor putting in fuel tanks on south west of building. 8-15-24 BR No work is being done on site.
Sewer Service Inspection Passed 09/10/2024
Misc
Informational
08/30/2024
8-30-24 BR Contractor installed 50' of service wye from building with clean out installed next to the building. 09/09/24 Monday JMJ Contractor performed tie-in to the 8" existing sanitary main with two max adapters and 8"X6" tee. Contractor bored 70' of 6" sanitary main across the road of SE Hamblen RD on Friday 09/06/24. Cleanout was already set (possibly done on Friday) on the Eastside of SE Hamblen RD . Contractor will install approximately 70' more of sanitary were sanitary was stub out from building site. 9-10-24 BR Contractor installed 40' of 6'' SDR-26 from boring connection under SE Hamblen Rd to 2nd clean out in middle of parking lot.
Sewer Service Inspection Passed 9/6/2024 9/6/2024 09/10/2024
Misc
Informational
08/30/2024
8-30-24 BR Contractor installed 50' of service wye from building with clean out installed next to the building. 9-6-24 BR Contractor installed 40' of 6'' DIP pipe under SE Hamblen Rd to get ready for connection to existing sewer main. 09/09/24 Monday JMJ Contractor performed tie-in to the 8" existing sanitary main with two max adapters and 8"X6" tee. Contractor bored 70' of 6" sanitary main across the road of SE Hamblen RD on Friday 09/06/24. Cleanout was already set (possibly done on Friday) on the Eastside of SE Hamblen RD . Contractor will install approximately 70' more of sanitary were sanitary was stub out from building site. 9-10-24 BR Contractor installed 40' of 6'' SDR-26 from boring connection under SE Hamblen Rd to 2nd clean out in middle of parking lot.
Water Service Inspection Passed 8/28/2024 8/28/2024 09/10/2024
Misc
Informational
08/28/2024
8-28-24 BR Contractor excavated for water main to give access to water dept. ready for tap on water main. 9-10-24 BR City water dept installed tap on water main. Contractor installed 1'' cooper line to water meter and 10' after water meter heading to building.
Underground Electrical Inspection - Commercial Partial 10/7/2024 10/7/2024 10/07/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/07/2024
-UE to junction near trash enclosure
Underground Electrical Inspection - Commercial Partial 10/8/2024 10/08/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/07/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone
Underground Electrical Inspection - Commercial Partial 10/10/2024 10/10/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/08/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power
Electrical Service Inspection Failed 10/10/2024 10/10/2024 10/10/2024
Misc
Corrective Action Required
10/10/2024
Not ready for service inspection
Underground Electrical Inspection - Commercial Partial 10/15/2024 10/15/2024 10/15/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/10/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner to NE storm drain location for compressor and HD sign
Underground Electrical Inspection - Commercial Partial 10/16/2024 10/16/2024 10/16/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/15/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner to NE storm drain location for compressor and HD sign, from NE corner north to car chargers and light pole
Footing Inspection - Commercial Partial 10/16/2024 10/16/2024
Misc
Informational
10/16/2024
-Building perimeter footings complete -(8) of (8) canopy piers complete
Underground Electrical Inspection - Commercial Partial 10/17/2024 10/17/2024 10/17/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/16/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner to NE storm drain location for compressor and HD sign, -UE from NE corner north to car chargers and light pole at north drive
Underground Electrical Inspection - Commercial Partial 10/21/2024 10/21/2024 10/21/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/17/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner to NE storm drain location for compressor and HD sign, -UE from NE corner north to car chargers and light pole at north drive -UE stubbed out from (3) light pole bases at north, south and southwest
Underground Electrical Inspection - Commercial Partial 10/21/2024 10/21/2024 10/21/2024
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
10/21/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner for compressor and vac at NW and HD sign, -UE from NE corner north to car chargers and light pole at north drive -UE stubbed out from (4) light pole bases at north, northeast, south and southwest
Piers/Caissons Inspection - Commercial Failed 10/22/2024 10/22/2024 10/22/2024
Misc
Corrective Action Required
10/22/2024
-Pier depth to be 8' per details -Secure rebar at tops of piers to maintain 3" clearance
Underground Electrical Inspection - Commercial Passed 10/23/2024 10/23/2024 10/23/2024
THE FOLLOWING AREAS ARE APPROVED
Resolved
10/23/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner for compressor and vac at NW and HD sign, -UE from NE corner north to car chargers and light pole at north drive -UE stubbed out from (4) light pole bases at north, northeast, south and southwest
Pavement-Proof Roll Partial 11/12/2024 11/12/2024 11/14/2024
Misc
Informational
10/21/2024
10-21-24 BR Contractor preformed a poof roll on east parking lot section to entrance to LS specifications. pass 11-12-24 BR Contractor preformed a poof roll on east side of fuel island of property. pass
Pavement-Curb Construction Partial 11/14/2024 11/14/2024
Misc
Corrective Action Required
10/07/2024
10-7-24 BR Contractor start forming for curbs on north side of parking lot. Contractor need to add aggregate and be compacted before ready to pour concrete. 10-8-24 BR Contractor installed aggregate and compacted on north side of parking lot. Ready for concrete. 10-10-24 BR Contractor start forming for curbs on west side of parking lot and aggregate and compacted ready for concrete. 10-11-24 BR Contractor poured concrete curbs on west side and south side of parking lot. 10-14-24 BR Contractor start forming for curbs on south side of parking lot to 2nd entrance and aggregate and compacted ready for concrete. 11-12-24 BR Contractor recompacted aggregate and concrete was poured on south side of parking lot 2nd entrance.
Erosion Control Inspection Residential Partial 12/2/2024 12/2/2024 12/02/2024
Misc
Informational
05/14/2024
5-14-24 BR Erosion control is up and working order 5-23-24 BR Grass needs to be trim down so that public fire hydrant is visible and silt fence is visible and work properly. Also need to use approve gutter buddy's on erosion control plans for inlet protection. 5-29-24 BR Erosion control is up and working order. Grass is trim down and public fire hydrant is visible. 6-4-24 BR Erosion control is up and working order. 6-11-24 BR Erosion control is up and working order. 6-17-24 BR Erosion control is up and working order. 6-26-24 BR Erosion control is up and working order. 7-3-34 BR Erosion control is up and working order. 7-10-24 Erosion control is up and working order. 7-17-24 BR Erosion control is up and working order. 7-26-24 BR Erosion control is up and working order. 8-9-24 BR Erosion control is up and working order. 8-15-24 BR Erosion control is up and working order. 8-30-24 BR Erosion control is up and working order. 9-4-24 BR Erosion control is up and working order. 9-24-24 BR Silt fence needs to be repaired on west side of property next to SE Hamblen Rd 10-7-24 BR Silt fence needs to be repaired on west side of property next to SE Hamblen Rd 10-14-24 BR Erosion control is up and working order. 10-21-24 BR Erosion control is up and working order. 11-4-24 BR Need to repaired silt fence around property. Also need to clean up debris on site and clean up plus add gutter buddies on all storm boxes. 11-8-24 BR Silt fence has been repaired around of property and debris is clean up. 11-14-24 BR Erosion control is up and working order. 12-2-24 BR Erosion control is up and working order.
Piers/Caissons Inspection - Commercial Passed 12/03/2024
Misc
Resolved
12/03/2024
-Pier depth to be 8' per details -Secure rebar at tops of piers to maintain 3" clearance
Underground Electrical Inspection - Commercial Partial 12/3/2024 12/3/2024 12/03/2024
Misc
Corrective Action Required
12/03/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner for compressor and vac at NW and HD sign, -UE from NE corner north to car chargers and light pole at north drive -UE stubbed out from (4) light pole bases at north, northeast, south and southwest -UE at NE drive for future
Underground Electrical Inspection - Commercial Passed 12/12/2024 12/12/2024 12/12/2024
Misc
Resolved
12/12/2024
-UE to junction near trash enclosure - UE to light pole at South West corner - UE to light pole West side - UE to moument sign South West corner - UE to hamblen rd. for phone and future power -UE from NE corner for compressor and vac at NW and HD sign, -UE from NE corner north to car chargers and light pole at north drive -UE stubbed out from (4) light pole bases at north, northeast, south and southwest -UE at NE drive for future
Underground Electrical Inspection - Commercial Passed 12/16/2024 12/16/2024 12/16/2024
Storm Sewer Construction Inspection Passed 10/24/2024 10/24/2024 12/19/2024
Misc
Informational
10/10/2024
10-9-24 BR Contractor started working on installing storm box south side of building to connect to existing 36'' RCP pipe. 10-14-24 BR Contractor installed rebar on storm boxes bottom on storm box 1-1, 1-2, & 1-3. Also poured concrete footings to all 3 storm boxes. 10-15-24 BR Contactor install rebar to concrete bases for framing walls on storm boxes 1-2, 1-3 which these boxes are ready for concrete. 10-16-24 BR Contractor poured concrete walls on storm box 1-2, & 1-3 with installing 15'' HDPE pipe to box 1-2 & 1-3. 10-18-24 BR Contractor poured inverts in storm box 1-3, & 1-2. Also installed 150' of 15'' HDPE pipe from storm box 1-2 to box 1-1. 10-21-24 BR Contractor installed 100' of 15'' HDPE pipe from storm box 1-2 to box 1-1 and tee at Sta. 0+40 to connect roof drains line 1. 10-23-24 BR Contractor installed roof drains on west side and east side of fuel island to connect to 15'' HDPE storm pipe. 10-24-24 BR Contractor poured lid for storm box 1-1 and inverts inside storm box.
Pavement-Surface Partial 1/2/2025 1/2/2025 01/02/2025
Misc
Informational
11/05/2024
11-5-24 BR Contractor poured concrete 1st driveway entrance approach on east side of building and parking lot along with poured driveway next to islands on west side of parking lot. 11-14-24 BR Contractor poured concrete driveway on east side of fuel island. 1-2-25 BR Contractor poured concrete pavement surface on the fuel island, building entrance, & parking stalls.
Electrical Service Inspection Failed 1/6/2025 1/7/2025 01/07/2025
Misc
Corrective Action Required
10/10/2024
600 amp electrical service is per code; however, the electrical service plan must to be updated to reflect service installation
Gas Service Inspection - Commercial Passed 1/22/2025 1/22/2025 01/22/2025
Driveway Inspection Partial 1/30/2025 1/30/2025 01/30/2025
Misc
Informational
12/19/2024
12-19-24 BR Contractor installed aggregate base on driveway entrance on south side of property to store front entrance. 1-30-25 BR Contractor poured concrete on south side driveway and entrance approach of building.
Electrical Service Inspection Passed 2/3/2025 2/3/2025 02/03/2025
Misc
Resolved
02/03/2025
600 amp electrical service is per code; however, the electrical service plan must to be updated to reflect service installation
Above Ceiling Inspection Partial 02/06/2025
Misc
Corrective Action Required
02/06/2025
Bathroom hard lids ok to cover
In-wall Inspection Passed 2/6/2025 2/6/2025 02/06/2025
Sidewalk Inspection Passed 2/27/2025 2/27/2025 02/27/2025
Misc
Informational
09/10/2024
9-9-24 BR Contractor took out one panel of sidewalk to connect water service to water main. 10-23-24 BR Contractor has formed up for sidewalk section on west side of parking lot without any aggregate being place not ready for concrete. 10-25-24 BR Contractor added aggregate with compaction to formed up sidewalk section on west side of parking lot ready for concrete. 10-28-24 BR Contractor poured concrete sidewalk on west side of parking lot to ADA section on SE Hamblen Rd which is not to LS specifications. The ADA section fail and need to be installed to ADA specifications. 2-4-25 BR Contractor has reformed up ADA section on south & north end of property. Contractor needs to add aggregate to both ADA sections of sidewalk before pouring concrete. 2-7-25 BR Contractor has added aggregate to formed up ADA section ready for concrete. 2-27-25 BR ADA ramp and sidewalk is constructed to LS specification.
Site Visit Partial 3/19/2025 3/19/2025 03/19/2025
Misc
Informational
07/08/2024
5-20-24 BR No work is being done on site. 7-8-24 PS No activity on site 9-3-2024 Dustin A, Building work 9-4-24 BR Contractor is working on building. 9-17-24 BR Contractor is working on building. 9-24-24 BR No activity on site. 1-14-25 BR No activity on site. 2-21-25 BR No activity on site do to weather conditions. 3-19-25 BR Work is being done on building outside and inside.
Erosion Control Inspection Residential Failed 3/28/2025 3/28/2025 03/28/2025
Misc
Corrective Action Required
02/28/2025
-Install gravel filter at site entrance and clean mud from streets. No further inspections will be performed until in compliance 1-2-25 BR Contractor installed gravel on south entrance of site and clean up mud off street. 2-3-25 BR Erosion control is up and working order. 2-17-25 BR Erosion control is up and working order. 2-28-25 BR Silt fence has several cut and rips in silt fence around entire property. Need to repair silt fence control erosion properly. 3-4-25 BR Erosion control is up and working order. 3-19-24 BR Erosion control is up and working order. 3-28-25 BR Silt fence is down on west side of property with several cuts and rips in silt fence around entire property. Need to repair silt fence and bring erosion control back to compliance.
Above Ceiling Inspection Failed 4/22/2025 4/22/2025 04/22/2025
Misc
Corrective Action Required
02/06/2025
Bathroom hard lids ok to cover inspection canceled for 4/22/25 no GC is listed, new GC needs to be added to the permit and verified MARK HARDING 04/22/2025 8:10 AM
Documents & Images
Date Uploaded File Type Document Name
03/09/2023 Application Form APPLICATION
03/09/2023 Plans Lee's Summit C-Store - full set of constuction drawings 03-09-23
03/27/2023 Letter DS P/R Corrections Document
05/31/2023 Plans Lee's Summit C-Store -REVISED full set of Permit drawings 05-16-23
06/08/2023 Letter Plan Review - health dept
06/13/2023 Letter DS P/R Corrections Document
06/16/2023 Engineer Report/Study 22-5625 Lion C-Store Geotech Report
06/18/2023 Letter Jackson County Health Dept Plan Review
06/27/2023 Plans Lee's Summit C-Store -REVISED full set of Permit drawings 06-26-23
07/06/2023 Letter DS P/R Corrections Document
03/14/2024 Approved Plans APPROVED LP MART FDP_REV 0_PL2022386
03/14/2024 Approved Plans Approved permit set
03/22/2024 Letter License Tax Bill
04/24/2024 Plans Petroleum Plans T1_Rev 0_PRCOM20230994
04/24/2024 Plans Petrolium Plans 2_Rev 0_PRCOM20230994
05/02/2024 Letter DS P/R Corrections Document
05/14/2024 Receipt Receipt for transaction: 2024-003321
05/14/2024 Letter DS Building Permit
05/14/2024 Letter INSPECTION SUMMARY
05/17/2024 Letter INSPECTION SUMMARY
05/20/2024 Letter INSPECTION SUMMARY
05/21/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/24/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
06/06/2024 Letter INSPECTION SUMMARY
06/11/2024 Letter INSPECTION SUMMARY
06/17/2024 Letter INSPECTION SUMMARY
06/17/2024 Letter INSPECTION SUMMARY
06/20/2024 Letter INSPECTION SUMMARY
06/25/2024 Letter INSPECTION SUMMARY
06/26/2024 Letter INSPECTION SUMMARY
07/02/2024 Letter INSPECTION SUMMARY
07/08/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
07/17/2024 Letter INSPECTION SUMMARY
07/17/2024 Letter INSPECTION SUMMARY
07/17/2024 Letter INSPECTION SUMMARY
07/18/2024 Letter INSPECTION SUMMARY
07/22/2024 Drawing E1_Rev 4
07/22/2024 Drawing P1_Rev 4
07/23/2024 Approved Plans Approved E1 revision
07/26/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter INSPECTION SUMMARY
08/07/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/12/2024 Plans LP MART, LSMO 240805
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
08/28/2024 Letter INSPECTION SUMMARY
08/30/2024 Letter INSPECTION SUMMARY
08/30/2024 Letter INSPECTION SUMMARY
08/30/2024 Letter INSPECTION SUMMARY
09/03/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter Fire Building Plan Review
10/07/2024 Letter Fire Building Plan Review
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/07/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/10/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/14/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/16/2024 Letter INSPECTION SUMMARY
10/16/2024 Letter INSPECTION SUMMARY
10/16/2024 Letter INSPECTION SUMMARY
10/16/2024 Letter INSPECTION SUMMARY
10/17/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/22/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
10/24/2024 Letter INSPECTION SUMMARY
10/24/2024 Letter INSPECTION SUMMARY
10/25/2024 Letter INSPECTION SUMMARY
10/28/2024 Letter INSPECTION SUMMARY
10/29/2024 Plans LP Mart_Lee's Summit C-Store -REVISED Arch & Struct drawings 05-01-24 with Rev5 Sht S5_1 06-27-24
10/29/2024 Approved Plans Approved LP revisions
11/04/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
11/06/2024 Drawing 22032-S4-1 WITH CLARIFICATION#7_Submitted 11-6-2024
11/07/2024 Approved Plans Approved S4-1 revisions
11/08/2024 Approved Plans APPROVED LP MART FDP_REV 1_PL2022386
11/08/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/03/2024 Letter INSPECTION SUMMARY
12/11/2024 Drawing Sealed T1 Rev_ 4 Petroleum Piping Plan Added Gas Line
12/12/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/07/2025 Letter INSPECTION SUMMARY
01/14/2025 Letter INSPECTION SUMMARY
01/14/2025 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/29/2025 Drawing Revised E5 Electrical Service Drawing
01/29/2025 Approved Plans Approved E-5
01/30/2025 Letter INSPECTION SUMMARY
01/30/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/04/2025 Letter INSPECTION SUMMARY
02/04/2025 Letter INSPECTION SUMMARY
02/06/2025 Letter INSPECTION SUMMARY
02/06/2025 Letter INSPECTION SUMMARY
02/07/2025 Letter INSPECTION SUMMARY
02/07/2025 Letter INSPECTION SUMMARY
02/21/2025 Letter INSPECTION SUMMARY
02/21/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
02/27/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
03/04/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/28/2025 Letter INSPECTION SUMMARY
04/22/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home