Permit Application Status

PRCOM20223975


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20223975
Building Permit - Commercial
Certificate of Occupancy
HFI 463 WARD LLC
NEW COMMERCIAL
NEW FAST FOOD RESTAURANT WITH DRIVE-THRU
08/18/2022
08/30/2023
09/26/2023
07/26/2024
Locations
Contacts
HFI 463 WARD LLC, Address:463 SW WARD RD  
WHATABURGER, Address:300 CONCORD PLAZA DR, Phone:(210) 309-7957  
MS CONSULTANTS, INC., Address:300 CORPORATE CENTER DRIVE, SUITE 200  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
SCHWARTZ ELECTRIC, Address:112 SE PRINCETON PL, Phone:(816) 977-9970  
TAYLOR MECHANICAL INC, Address:23700 E 189th st, Phone:(816) 743-9900  
Kyle Murtfeld - Pinnacle Construction  
PINNACLE CONSTRUCTION GROUP LLC, Address:8355 MELROSE DR, Phone:(816) 412-5855  
Gensler, Address:229 E. Houston St., Suite 200, Phone:(210) 222-8059  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 09/01/2022 04/03/2024
Jim Eden
Miscellaneous Correction
Corrective Action Required
04/03/2024

The system shall be tied to the buildings fire alarm system.
Construction documents - Fire protection systems
Corrective Action Required
04/03/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide supporting design documents (pre-engineered) documents prior to scheduling a test.
Installation acceptance testing
Corrective Action Required
04/03/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule test.
Licensed Contractors Approved 04/25/2023 08/30/2023
Joe Frogge
LC - General Contractor
Resolved
04/24/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 9/20/22 - referred to G1.0 but unable to locate info
LC - MEP Subs
Resolved
08/30/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/20/22 - Acknowledged in letter. 4/24/23 - Acknowledged in letter.
Building Plan Review Approved with Conditions 04/25/2023 07/25/2023
Joe Frogge
Final Development Plan
Resolved
05/08/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 9/20/22 - Acknowledged in letter. 4/24/23 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
04/18/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 9/20/22 - Acknowledged in letter. 4/24/23 - Acknowledged in letter.
Engineered truss package
Corrective Action Required
04/18/2023

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/20/22 - Deferred per request
Health Dept Review
Resolved
07/25/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational. 4/24/23 - Acknowledged in letter.
IBC 1809.5 Frost protection - foundation
Resolved
04/24/2023

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Modify footing sections to show that bottoms of all footings will be protected by at least 36" of soil.
Misc
Resolved
04/24/2023

Site lighting design incomplete. Action required: Provide light pole base detail.
Final Development Plan Review Approved 12/19/2022 05/08/2023
Dawn Bell
Fire Plan Review Approved with Conditions 04/25/2023 04/24/2023
Jim Eden
Door operations
Resolved
04/24/2023

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Action required- The front entry door shall be provided with a thumb latch. Double keyed deadbolts are not allowed.
Installation acceptance testing
Informational
04/24/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing of the hood.
Miscellaneous Correction
Corrective Action Required
04/18/2023

Provide specifications for the hoods and Ansul system, including location of controls/pull stations .
Emergency power for illumination
Resolved
04/24/2023

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required- Provide exterior emergency lighting at the exits.
Fire Plan Review Rejected 04/10/2023 04/10/2023
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
04/10/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Hood supression plans.
Door operations
Corrective Action Required
04/10/2023

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Action required- The front entry door shall be provided with a thumb latch. Double keyed deadbolts are not allowed.
Knox box required
Resolved
04/10/2023

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required- Order from Knoxbox.com and mount 6' AFF above the FDC.
Installation acceptance testing
Corrective Action Required
04/10/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing of the hood.
Miscellaneous Correction
Corrective Action Required
04/10/2023

Provide specifications for the hoods and Ansul system, including location of controls/pull stations .
Emergency power for illumination
Corrective Action Required
04/10/2023

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required- Provide exterior emergency lighting at the exits.
Fire Plan Review Rejected 03/30/2023 03/29/2023
Jim Eden
Miscellaneous Correction
Resolved
04/10/2023

Recalculate the occupant load. For assembly occupancies, non-fixed seating is calulated at 15 sq. ft/person and waiting/standing areas at 5 sq.ft./person. The calculated occupant using these factors will exceed 100 occupants. 4/10/2023- The revised occupant load is 96.
Miscellaneous Correction
Resolved
04/10/2023

903.2.1.2 Group A-2. An automatic sprinkler system shall be provided throughout stories containing Group A-2 occupancies and throughout all stories from the Group A-2 occupancy to and including the levels of exit discharge serving that occupancy where one of the following conditions exists: 2. The fire area has an occupant load of 100 or more. 4/10/2023- No longer required by occupant load.
Construction documents for fire alarm systems
Resolved
04/10/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Corrective Action Required
04/10/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Hood supression plans.
Door operations
Corrective Action Required
03/29/2023

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Action required- The front entry door shall be provided with a thumb latch. Double keyed deadbolts are not allowed.
Knox box required
Corrective Action Required
03/29/2023

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action required- Order from Knoxbox.com and mount 6' AFF above the FDC.
Installation acceptance testing
Corrective Action Required
03/29/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Miscellaneous Correction
Corrective Action Required
03/29/2023

Provide specifications for the hoods and Ansul system, including location of controls/pull stations .
Emergency power for illumination
Corrective Action Required
03/29/2023

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required- Provide exterior emergency lighting at the exits.
Building Plan Review Rejected 03/30/2023 03/27/2023
Joe Frogge
Final Development Plan
Corrective Action Required
03/17/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 9/20/22 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
03/17/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 9/20/22 - Acknowledged in letter.
Engineered truss package
Corrective Action Required
03/17/2023

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/20/22 - Deferred per request
Health Dept Review
Corrective Action Required
03/24/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
IBC 1809.5 Frost protection - foundation
Corrective Action Required
03/24/2023

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Modify footing sections to show that bottoms of all footings will be protected by at least 36" of soil.
Misc
Corrective Action Required
03/24/2023

Site lighting design incomplete. Action required: Provide light pole base detail.
Building Plan Review Rejected 09/22/2022 09/20/2022
Joe Frogge
Final Development Plan
Corrective Action Required
09/15/2022

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 9/20/22 - Acknowledged in letter.
Health Dept Inspection
Corrective Action Required
09/15/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 9/20/22 - Acknowledged in letter.
Gen - Plan submittals 2018 codes
Resolved
09/20/2022

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Modify code analysis to show correct code dates. Multiple references to 2012 & 2015 found.
Engineered truss package
Corrective Action Required
09/15/2022

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/20/22 - Deferred per request
IBC 1803.1 General - geotech
Resolved
09/20/2022

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf. (2,500 listed in Foundation Notes on sheet S0.2)
IBC 1809.5 Frost protection - foundation
Resolved
09/20/2022

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Minimum frost depth in this area is 36". Modify designs to comply.
ICC A117.1 604.5.1 Fixed side wall grab bars
Resolved
09/20/2022

ICC A117.1 604.5.1 Fixed side wall grab bars. Fixed side-wall grab bars shall include a horizontal bar complying with Section 604.5.1.1 and a vertical grab bar complying with Section 604.5.12. The vertical grab bar at water closets primarily for children’s use shall comply with Section 609.4.2. ICC A117.1 604.5.1.1 Horizontal grab bar. A horizontal grab bar 42 inches minimum in length shall be located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. ICC A117.1 604.5.1.2 Vertical grab bar. A vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide vertical side grab bars at accessible water closets.
IPC 305.4 Freezing - protection of potable water
Resolved
09/20/2022

Protection of Potable Water System 2018 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Move water entry into conditioned space to prevent freezing. (or other approved method - currently shown in exterior wall which is problematic in this area)
IPC 1003.1 Interceptors and separators required
Resolved
09/20/2022

2018 IPC 1003.3.1 Grease interceptors and automatic grease removal devices required. A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. Fixtures and equipment shall include pot sinks, pre-rinse sinks; soup kettles or similar devices; work stations; floor drains or sinks into which kettles are drained; automatic hood wash units and dishwashers without pre-rinse sinks. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged. Where lack of space or other constraints prevent the installation or replacement of a grease interceptor, one or more grease interceptors shall be permitted to be installed on or above the floor and upstream of an existing grease interceptor. Action required: Modify plumbing design. Hand sinks and restrooms not allowed to be routed through grease trap.
Licensed Contractors Rejected 09/22/2022 09/20/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
09/15/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 9/20/22 - referred to G1.0 but unable to locate info
LC - MEP Subs
Corrective Action Required
09/15/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/20/22 - Acknowledged in letter.
Fire Plan Review Approved with Conditions 09/22/2022 09/20/2022
Ben Hicks
Posting of occupant load
Corrective Action Required
09/15/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Alarm testing.
Corrective Action Required
09/15/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.
Construction documents for fire alarm systems
Corrective Action Required
09/15/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Corrective Action Required
09/15/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Fire Plan Review Approved with Conditions 09/01/2022 09/01/2022
Ben Hicks
Posting of occupant load
Corrective Action Required
09/01/2022

2018 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Alarm testing.
Corrective Action Required
09/01/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.
Construction documents for fire alarm systems
Corrective Action Required
09/01/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Corrective Action Required
09/01/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Health Department Review Approved 08/30/2022
Joe Frogge
Building Plan Review Rejected 09/01/2022 08/24/2022
Joe Frogge
Final Development Plan
Corrective Action Required
08/24/2022

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
08/24/2022

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
Gen - Plan submittals 2018 codes
Corrective Action Required
08/24/2022

All plans submitted for review on or after April 1, 2019 shall be designed to the requirements of the 2018 International Building Code, 2018 International Mechanical Code, 2018 International Plumbing Code, 2018 International Fuel Gas Code, 2018 International Fire Code, 2017 National Electric Code and the ICC/ANSI A117.1-2009 as amended and adopted by the City of Lee’s Summit. Action required: Modify code analysis to show correct code dates. Multiple references to 2012 & 2015 found.
Engineered truss package
Corrective Action Required
08/24/2022

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral.
IBC 1803.1 General - geotech
Corrective Action Required
08/24/2022

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Provide soils report to justify design assumption of soil bearing capacity greater than 2,000psf. (2,500 listed in Foundation Notes on sheet S0.2)
IBC 1809.5 Frost protection - foundation
Corrective Action Required
08/24/2022

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Minimum frost depth in this area is 36". Modify designs to comply.
ICC A117.1 604.5.1 Fixed side wall grab bars
Corrective Action Required
08/24/2022

ICC A117.1 604.5.1 Fixed side wall grab bars. Fixed side-wall grab bars shall include a horizontal bar complying with Section 604.5.1.1 and a vertical grab bar complying with Section 604.5.12. The vertical grab bar at water closets primarily for children’s use shall comply with Section 609.4.2. ICC A117.1 604.5.1.1 Horizontal grab bar. A horizontal grab bar 42 inches minimum in length shall be located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. ICC A117.1 604.5.1.2 Vertical grab bar. A vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located 39 inches minimum and 41 inches maximum above the floor, and with the center line of the bar located 39 inches minimum and 41 inches maximum from the rear wall. Action required: Provide vertical side grab bars at accessible water closets.
IPC 305.4 Freezing - protection of potable water
Corrective Action Required
08/24/2022

Protection of Potable Water System 2018 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Move water entry into conditioned space to prevent freezing. (or other approved method - currently shown in exterior wall which is problematic in this area)
IPC 1003.1 Interceptors and separators required
Corrective Action Required
08/24/2022

2018 IPC 1003.3.1 Grease interceptors and automatic grease removal devices required. A grease interceptor or automatic grease removal device shall be required to receive the drainage from fixtures and equipment with grease-laden waste located in food preparation areas, such as in restaurants, hotel kitchens, hospitals, school kitchens, bars, factory cafeterias and clubs. Fixtures and equipment shall include pot sinks, pre-rinse sinks; soup kettles or similar devices; work stations; floor drains or sinks into which kettles are drained; automatic hood wash units and dishwashers without pre-rinse sinks. Grease interceptors and automatic grease removal devices shall receive waste only from fixtures and equipment that allow fats, oils or grease to be discharged. Where lack of space or other constraints prevent the installation or replacement of a grease interceptor, one or more grease interceptors shall be permitted to be installed on or above the floor and upstream of an existing grease interceptor. Action required: Modify plumbing design. Hand sinks and restrooms not allowed to be routed through grease trap.
Licensed Contractors Rejected 09/01/2022 08/24/2022
Joe Frogge
LC - General Contractor
Corrective Action Required
08/24/2022

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
08/24/2022

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $11,286.69 $11,286.69 Paid 05/09/2023
7232302-Commercial License Tax Fee $45,045.00 $45,045.00 Paid 05/09/2023
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 03/29/2023
8331401-Water Tap Fee $34,810.00 $34,810.00 Paid 03/29/2023
8350015-Water Meter Fee $3,986.37 $3,986.37 Paid 03/29/2023
8331507-Sanitary Sewer Development Fee $9,230.00 $9,230.00 Paid 03/29/2023
91100C8-Sanitary Sewer Insp Fees $461.04 $461.04 Paid 03/29/2023
91100C9-Water Insp Fee $1,268.41 $1,268.41 Paid 03/29/2023
9110068-Storm Fee $9,395.72 $9,395.72 Paid 03/29/2023
9110071-Site Grading Fee $5,460.36 $5,460.36 Paid 03/29/2023
9110081-Paved Surface Inspection Fee $6,530.12 $6,530.12 Paid 03/29/2023
9110072-Water Test Fee $200.00 $200.00 Paid 03/29/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 9/25/2023 09/25/2023
Miscellaneous Correction
Informational
09/25/2023
Erosion control is in place at the time of lot clearing of brush. Erosion control is required throughout the entire construction process.
Grading/Excavation/Fill Inspection Partial 11/3/2023 11/3/2023 11/03/2023
Misc
Informational
11/03/2023
11-3-23 PS Contractor hauling spoils pile from site
Footing Inspection - Commercial Partial 11/7/2023 (2:00) 11/8/2023 11/08/2023
Miscellaneous Correction
Informational
11/08/2023
The Ufer is located on the west side of the footing near the Southwest corner. This is a partial footing pass only. The footing for the building itself passed and other footings will be call in for inspection at a later date 11/08/23 KBEARD
Site Visit Partial 11/20/2023 11/20/2023 11/17/2023
Site Visit Partial 11/20/2023 11/20/2023 11/20/2023
Misc
Informational
11/20/2023
11-20-23 Dustin A, No work being performed today due to rain 11-21-23 Dustin A, No work today due to muddy conditions 11-22-23 Dustin A , No work being done.
Site Visit Partial 11/27/2023 11/27/2023
Misc
Informational
11/20/2023
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us.
Site Visit Partial 11/28/2023 11/28/2023
Misc
Informational
11/27/2023
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us.
Underslab Plumbing Inspection - Commercial Passed 12/4/2023 12/4/2023 12/04/2023
Site Visit Partial 12/7/2023 12/07/2023
Misc
Informational
11/28/2023
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us. 12-7-23 Dustin A, No Activity for us today 12-11-23 Dustin A, lumber dropped off, no activity for us. Hoping to start sewer in a week 12-12-23 Dustin A, no activity for us today. 12-19-23 Dustin A, Visit with Dutch. Asked for a footing inspection for later today. Informed him that would need to be scheduled with building codes. May start on some service line work for the sewer pending on delivery of grease trap. 1-19-23 Dustin A, No activity today due to frigid temperatures. 1-23-24 Dustin A, No activity for us today. Hoping to start excavating next week after thaw 2-16-24 Dustin A, Talked with Dutch on some issues on site. Road needed to be cleaned , restrooms off the roads, and they are using another construction entrance that has no construction entrance gravel. All needs to be addressed by the end of the day.
Underslab Electrical Inspection - Commercial Partial 12/12/2023 12/12/2023 12/12/2023
Miscellaneous Correction
Informational
12/12/2023
Underslab electric passed.
Erosion Control Inspection Residential Partial 12/12/2023 12/12/2023
Miscellaneous Correction
Informational
12/12/2023
Erosion control is in place. Full erosion control must be maintained throughout until CofO
Sanitary Sewer Construction Inspection Partial 1/2/2024 1/2/2024 01/02/2024
Misc
Informational
01/02/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on.
Erosion Control Inspection Residential Partial 1/8/2024 01/08/2024
Misc
Corrective Action Required
01/08/2024
1-8-24 Dustin A, Silt fence needs to repaired in some areas on summitcrest dr, and on hollywood dr. Summitcrest dr needs dirt cleaned off
Storm Sewer Construction Inspection Partial 1/30/2024 01/30/2024
Misc
Informational
01/30/2024
1-30-24 Dustin A, Contractor on site working on storm on south side of building. MH 2 and 5A is installed at the correct slopes .
All Rough Inspection - Commercial Failed 2/2/2024 2/2/2024 02/02/2024
Miscellaneous Correction
Corrective Action Required
02/02/2024
204 SW M 150. All rough (1) -All plastic plumbing lines need BOCA plates installed at the sole plate and nail guards at fire blocking -Double trusses need to be nailed together every two feet on center -Electrical lines in PVC at sole plate needs to have nail guards installed -Fire block top plate holes on north side of bathroom where electrical penetrates the wall sheeting -Install joist hangers in bathroom ceilings where the span exceeds 4 feet -Exterior sheeting was cover prior to inspection Plumbing and electrical is not finished at the time of all rough. This is not a complete list
Underslab Electrical Inspection - Commercial Passed 2/5/2024 02/05/2024
Miscellaneous Correction
Resolved
02/05/2024
Underslab electric passed.
All Rough Inspection - Commercial Passed 2/5/2024 02/05/2024
Miscellaneous Correction
Resolved
02/05/2024
204 SW M 150. All rough (1) -All plastic plumbing lines need BOCA plates installed at the sole plate and nail guards at fire blocking -Double trusses need to be nailed together every two feet on center -Electrical lines in PVC at sole plate needs to have nail guards installed -Fire block top plate holes on north side of bathroom where electrical penetrates the wall sheeting -Install joist hangers in bathroom ceilings where the span exceeds 4 feet -Exterior sheeting was cover prior to inspection Plumbing and electrical is not finished at the time of all rough. This is not a complete list
Miscellaneous Correction
Informational
02/05/2024
-Exterior sheeting was covered prior to all rough inspection. -All rough was inspected and passed by a third party. -Electrical panel is located on the exterior west side and will be inspected at a later date. Interior electrical passed Okay to insulate. No screw pattern inspection needed. Call for above ceiling inspection prior to hard lid for Sheetrock
Sanitary Sewer Construction Inspection Partial 2/5/2024 02/05/2024
Misc
Informational
01/02/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10),
Sanitary Sewer Construction Inspection Partial 2/6/2024 2/6/2024 02/06/2024
Misc
Informational
02/05/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line.
Sanitary Sewer Construction Inspection Partial 2/7/2024 02/07/2024
Misc
Informational
02/06/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-9-24 Dustin A, Continued work on the sewer main extension.
Sanitary Sewer Construction Inspection Partial 2/19/2024 2/19/2024 02/14/2024
Misc
Informational
02/07/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-10-24 Dustin A, Last manhole set sewer tied in. Backfilled 30 day starts today will be up on march 12th
Above Ceiling Inspection Partial 2/20/2024 2/20/2024 02/20/2024
Miscellaneous Correction
Informational
02/20/2024
All above ceiling hard lid areas passed. Okay to cover hard lid areas. All other above ceiling inspections will be scheduled at a later date. This is a partial above ceiling inspection only
Storm Sewer Construction Inspection Partial 02/26/2024
Misc
Informational
01/30/2024
1-30-24 Dustin A, Contractor on site working on storm on south side of building. MH 2 and 5A is installed at the correct slopes . 2-23-24 Dustin A, Started working on underground retention.
Piers/Caissons Inspection - Commercial Passed 2/27/2024 2/27/2024 02/27/2024
Erosion Control Inspection Residential Failed 03/07/2024
Misc
Corrective Action Required
03/07/2024
1-8-24 Dustin A, Silt fence needs to repaired in some areas on summitcrest dr, and on hollywood dr. Summitcrest dr needs dirt cleaned off 3-7-24 Dustin A, Silt fence is down near job trailer, mud on street an dirt along both curbs. Will give 2 days to address
Erosion Control Inspection Passed 03/07/2024
Sanitary Sewer - Air Test Passed 03/14/2024
Misc
Informational
03/14/2024
3-13-24 Dustin A, Air test has Passed 5-1-24 Dustin A, New Air test performed due to having to fix section of pipe. New test Passed
Sanitary Sewer - Mandrel Passed 03/14/2024
Misc
Informational
03/14/2024
3-13-24 Dustin A, Mandrel test has Passed 5-1-24 Dustin A, New mandrel test performed due to having to fix section of pipe . Passed.
Sanitary Sewer - Vacuum Passed 03/14/2024
Misc
Informational
03/14/2024
3-13-24 Dustin A, Vacuum test has Passed
Underground Electrical Inspection - Commercial Partial 3/14/2024 3/14/2024 03/14/2024
Miscellaneous Correction
Informational
03/14/2024
Underground electrical from power pole to the structures west southwest corner passed. This is a partial pass only. Okay to cover.
Erosion Control Inspection Residential Passed 3/18/2024 3/18/2024 03/18/2024
Misc
Corrective Action Required
03/07/2024
1-8-24 Dustin A, Silt fence needs to repaired in some areas on summitcrest dr, and on hollywood dr. Summitcrest dr needs dirt cleaned off 3-7-24 Dustin A, Silt fence is down near job trailer, mud on street an dirt along both curbs. Will give 2 days to address 3-18-24 Dustin A, Issues have been resolved
Water Service Inspection Partial 3/18/2024 3/18/2024 03/18/2024
Misc
Informational
03/18/2024
3-18-24 Dustin A, water line installed from building to vault, then vault to main. meter will need to be raised
Underground Electrical Inspection - Commercial Partial 3/18/2024 3/18/2024 03/18/2024
Miscellaneous Correction
Informational
03/14/2024
Underground electrical from power pole to the structures west southwest corner passed. This is a partial pass only. Okay to cover.
Miscellaneous Correction
Informational
03/18/2024
Underground electrical from main disconnect to panels passed. Ok to cover Underground electrical from panels to trash compactor passed. Ok to cover This is a partial pass only
Sanitary - Material Verification Passed 03/18/2024
Pavement-Stabilized Subgrade Passed 03/19/2024
Misc
Informational
03/19/2024
3-19-24 Dustin A, Passed
Curb - Proof Roll Partial 03/20/2024
Misc
Informational
03/20/2024
3-19-24 Dustin A, Performed proof roll on outside edge of parking lot. Side next to arbys did not pass, and section near west side approach near job trailer did not pass.
Sanitary Sewer Construction Inspection Failed 03/20/2024
Misc
Informational
02/14/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-10-24 Dustin A, Last manhole set sewer tied in. Backfilled 30 day starts today will be up on march 12th
Miscellaneous Correction
Corrective Action Required
03/20/2024
3-15-24 Dustin A, Sewer did not pass camera test from water dept . Talked with Dutch and contractor on issues that need to be addressed. Will need to be fixed and 30 day will need to be restarted.
Site Visit Partial 03/25/2024
Misc
Informational
12/07/2023
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us. 12-7-23 Dustin A, No Activity for us today 12-29-23 Dustin A, No activity today for our department. 1-8-24 Dustin A, no work due to rain 1-25-24 Dustin A, No work being done due to rain. Did inform Dutch that silt fence needed to be reestablished in some areas and needed to maintain his approach and get rid of mud in the street. 1-29-24 Dustin , Contractor started working on the detention system 3-25-24 Dustin A, No activity today
Underground Electrical Inspection - Commercial Partial 3/27/2024 03/27/2024
Miscellaneous Correction
Informational
03/18/2024
Underground electrical from power pole to the structures west southwest corner passed. This is a partial pass only. Okay to cover.
Miscellaneous Correction
Informational
03/18/2024
Underground electrical from main disconnect to panels passed. Ok to cover Underground electrical from panels to trash compactor passed. Ok to cover This is a partial pass only
Miscellaneous Correction
Corrective Action Required
03/27/2024
Underground electrical to outside light post south, west and north sides and trash compactor passed. Ok to cover East side has been run under ground but not to the piers. Do not cover until inspected This is a partial pass only
Miscellaneous Inspection Passed 3/27/2024 03/27/2024
Miscellaneous Correction
Informational
03/27/2024
Talked to the electrician about the Ufer.
Underground Electrical Inspection - Commercial Partial 3/29/2024 3/29/2024 03/29/2024
Miscellaneous Correction
Informational
03/27/2024
Underground electrical from power pole to the structures west southwest corner passed. This is a partial pass only. Okay to cover.
Miscellaneous Correction
Informational
03/27/2024
Underground electrical from main disconnect to panels passed. Ok to cover Underground electrical from panels to trash compactor passed. Ok to cover This is a partial pass only
Miscellaneous Correction
Corrective Action Required
03/27/2024
Underground electrical to outside light post south, west and north sides and trash compactor passed. Ok to cover East side has been run under ground but not to the piers. Do not cover until inspected This is a partial pass only
Miscellaneous Correction
Informational
03/29/2024
Ufer to #4 copper has been inspected and approved. Okay to pour concrete to cover This is a partial under ground electrical inspection pass only
Sanitary Sewer Construction Inspection Partial 04/01/2024
Misc
Informational
03/20/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-10-24 Dustin A, Last manhole set sewer tied in. Backfilled 30 day starts today will be up on march 12th
Miscellaneous Correction
Corrective Action Required
03/20/2024
3-15-24 Dustin A, Sewer did not pass camera test from water dept . Talked with Dutch and contractor on issues that need to be addressed. Will need to be fixed and 30 day will need to be restarted. 4-1-24 Dustin A, Sewer was dug up and issues have been corrected. Sewer cannot still be used until 30 day period has passed and all testing redone.
Site Visit Partial 04/02/2024
Misc
Informational
03/25/2024
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us. 12-7-23 Dustin A, No Activity for us today 12-29-23 Dustin A, No activity today for our department. 1-8-24 Dustin A, no work due to rain 1-25-24 Dustin A, No work being done due to rain. Did inform Dutch that silt fence needed to be reestablished in some areas and needed to maintain his approach and get rid of mud in the street. 1-29-24 Dustin , Contractor started working on the detention system 3-25-24 Dustin A, No activity today 4-2-24 Dustin A, no activity for us .
Curb - Proof Roll Passed 04/11/2024
Misc
Informational
03/20/2024
3-19-24 Dustin A, Performed proof roll on outside edge of parking lot. Side next to arbys did not pass, and section near west side approach near job trailer did not pass. 3-20-24 Dustin A, section along arbys and drive through lane has been approved 4-5-24 Dustin A, reproof roll performed for curb north side of parking lot due to being rained on. Section failed. Contractor attempting to fix. 4-11-24 rest of curb has passed proof roll.
Electrical Service Inspection Failed 4/19/2024 4/19/2024 04/19/2024
Miscellaneous Correction
Corrective Action Required
04/19/2024
Service line needs to be KC350 MIL copper of 500 MIL aluminum
Electrical Service Inspection Passed 4/23/2024 4/23/2024 04/23/2024
Miscellaneous Correction
Resolved
04/23/2024
Service line needs to be KC350 MIL copper of 500 MIL aluminum
Miscellaneous Correction
Informational
04/23/2024
Electrical service passed. Okay to release to Evergy
Piers/Caissons Inspection - Commercial Partial 4/23/2024 4/23/2024 04/23/2024
Miscellaneous Correction
Informational
04/23/2024
All piers passed except for pier #7 on the south side of the property. This is a partial pass only. Okay to pour for signs and piers except for #7
Piers/Caissons Inspection - Commercial Passed 4/24/2024 4/24/2024 04/24/2024
Miscellaneous Correction
Resolved
04/24/2024
All piers passed except for pier #7 on the south side of the property. This is a partial pass only. Okay to pour for signs and piers except for #7
Hood/Duct Inspection Passed 4/24/2024 4/24/2024 04/24/2024
Gas Service Inspection - Commercial Passed 5/6/2024 5/6/2024 05/06/2024
Above Ceiling Inspection Passed 5/8/2024 5/8/2024 05/08/2024
Miscellaneous Correction
Resolved
05/08/2024
All above ceiling hard lid areas passed. Okay to cover hard lid areas. All other above ceiling inspections will be scheduled at a later date. This is a partial above ceiling inspection only
Site Visit Partial 05/13/2024
Misc
Informational
04/02/2024
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us. 12-7-23 Dustin A, No Activity for us today 12-29-23 Dustin A, No activity today for our department. 1-8-24 Dustin A, no work due to rain 1-25-24 Dustin A, No work being done due to rain. Did inform Dutch that silt fence needed to be reestablished in some areas and needed to maintain his approach and get rid of mud in the street. 1-29-24 Dustin , Contractor started working on the detention system 3-25-24 Dustin A, No activity today 4-2-24 Dustin A, no activity for us . 5-13-24 Dustin A, Waiting for re proof roll of approaches , no activity today
Pavement-Curb Construction Partial 05/28/2024
Misc
Informational
05/28/2024
5-28-24 Dustin A, Curb is all poured to city specs. Informed Dutch there was 2 areas that washed out underneath that would need to be filled in.
Sewer Service Inspection Passed 2/9/2024 05/28/2024
Storm Sewer Construction Inspection Passed 05/28/2024
Misc
Informational
02/26/2024
1-30-24 Dustin A, Contractor on site working on storm on south side of building. MH 2 and 5A is installed at the correct slopes . 2-23-24 Dustin A, Started working on underground retention. 3-20-24 Dustin A, Storm retention manhole was knocked off. There is gravel that will need to be cleaned out and mastic reapplied. 5-28-24 Dustin A, all storm has been installed.
Water Line - Construction Inspection Passed 05/28/2024
Misc
Informational
05/28/2024
Water line was installed per city specs. Passed
Water Line - Hydrostatic Test Passed 05/28/2024
Misc
Informational
05/28/2024
Passed
Water Line - Coliform Test 1 Passed 05/28/2024
Water Line - Coliform Test 2 Passed 05/28/2024
Water Service Inspection Passed 05/28/2024
Misc
Informational
05/28/2024
5-28-24 Dustin A, water service was installed per city specs. Passed
Pavement-Curb Construction Partial 5/29/2024 5/29/2024 05/29/2024
Misc
Informational
05/28/2024
5-28-24 Dustin A, Curb is all poured to city specs. Informed Dutch there was 2 areas that washed out underneath that would need to be filled in. 5-29-24 Dustin A, few cracks in curb 5-30-24 Dustin A, Started pouring base asphalt in parking lot 5-31-24 Dustin A, Most of base is poured. Due to weather probably will not be working on it today
Pavement-Aggregate Base Passed 05/29/2024
Misc
Informational
05/29/2024
5-29-24 Dustin A, base is installed to city specs
Curb - Proof Roll Passed 05/29/2024
Misc
Informational
03/20/2024
3-19-24 Dustin A, Performed proof roll on outside edge of parking lot. Side next to arbys did not pass, and section near west side approach near job trailer did not pass. 3-20-24 Dustin A, section along arbys and drive through lane has been approved 5-29-24 Dustin A, All curbs have been proof rolled and passed
Pavement-Proof Roll Passed 05/31/2024
Misc
Informational
05/28/2024
5-28-24 Dustin A, performed proof roll on approach closest to arbys, as well as rest of parking lot . Passed
Alternate Protection Systems Inspection Passed 6/3/2024 06/03/2024
Pavement-Proof Roll Passed 6/4/2024 6/4/2024 06/04/2024
Misc
Informational
05/28/2024
5-28-24 Dustin A, performed proof roll on approach closest to arbys, as well as rest of parking lot . Passed
Sidewalk Inspection Partial 6/10/2024 6/10/2024 06/10/2024
Misc
Corrective Action Required
06/10/2024
6-10-24 Dustin A, SW's Are poured. There is a crack across the street that will need to be replaced. There is a chip in sidewalk that panel that will need to be replaced.
In-wall Inspection Passed 1/24/2024 1/24/2024 06/19/2024
Miscellaneous Correction
Informational
01/24/2024
Freezer south and west walls passed. Okay to insulate those two walls only. This is just a partial for in wall inspection. This inspection has to fail for accounting purposes only.
Grading/Excavation/Fill Inspection Passed 06/19/2024
Misc
Informational
11/03/2023
11-3-23 PS Contractor hauling spoils pile from site 4-1-24 Dustin A, Tap hole on hollywood needs to be cleaned up. Talked to contractor and they said they would 6-19-24 Dustin A, Tap hole is cleaned up ready for seed, as well as the ditch where main extension was.
Pavement-Curb Construction Passed 6/19/2024 06/19/2024
Misc
Informational
05/29/2024
5-28-24 Dustin A, Curb is all poured to city specs. Informed Dutch there was 2 areas that washed out underneath that would need to be filled in. 5-29-24 Dustin A, few cracks in curb 6-10-24 Dustin A, 2 curbs are cracked 6-19-24 Dustin A, after reviewing the cracks , they are hairlines and have not separated any.
Pavement-Surface Passed 06/19/2024
Misc
Informational
06/19/2024
6-19-24 Dustin A, All pavement has been installed
Sanitary Sewer Construction Inspection Passed 06/19/2024
Misc
Informational
04/01/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-10-24 Dustin A, Last manhole set sewer tied in. Backfilled 30 day starts today will be up on march 12th
Miscellaneous Correction
Corrective Action Required
04/01/2024
3-15-24 Dustin A, Sewer did not pass camera test from water dept . Talked with Dutch and contractor on issues that need to be addressed. Will need to be fixed and 30 day will need to be restarted. 4-1-24 Dustin A, Sewer was dug up and issues have been corrected. Sewer cannot still be used until 30 day period has passed and all testing redone.
Misc
Corrective Action Required
05/03/2024
5-3-24 Dustin A, Sewer camera inspection has been redone. There is a sag, but it is within the limit to allow. The only thing of note to repair is the grouting of the lifting lugs in manhole 57-136. Contractor and Dutch has been informed ans will let me know when corrections have been made. 6-19-24 Dustin A, Lugs has been grouted and was ok'd by water dept
Sanitary Sewer - Camera Test Passed 6/19/2024 06/19/2024
Misc
Informational
06/19/2024
6-19-24 Dustin A, Camera test was passed on 5-2-24
Sidewalk Inspection Partial 06/19/2024
Misc
Corrective Action Required
06/10/2024
6-10-24 Dustin A, SW's Are poured. There is a crack across the street that will need to be replaced. There is a chip in sidewalk that panel that will need to be replaced. 6-19-24 Dustin A, last 2 panels are being poured today
Sidewalk Inspection Passed 6/25/2024 6/25/2024 06/25/2024
Misc
Corrective Action Required
06/19/2024
6-10-24 Dustin A, SW's Are poured. There is a crack across the street that will need to be replaced. There is a chip in sidewalk that panel that will need to be replaced. 6-19-24 Dustin A, last 2 panels are being poured today 6-25-24 Dustin A. All sidewalks have been poured to city specs. Passed
Footing Inspection - Commercial Passed 6/19/2024 06/25/2024
Miscellaneous Correction
Informational
11/08/2023
The Ufer is located on the west side of the footing near the Southwest corner. This is a partial footing pass only. The footing for the building itself passed and other footings will be call in for inspection at a later date 11/08/23 KBEARD
Miscellaneous Inspection Passed 6/25/2024 06/25/2024
Miscellaneous Correction
Informational
06/25/2024
Talked to the job superintendent about building final and answered miscellaneous questions he had.
Site Visit Complete 6/25/2024 6/25/2024 06/25/2024
Misc
Informational
05/13/2024
11-20-23 Dustin A, No work being performed today due to rain 11-27-23 Dustin A, Ground rough plumbing only thing going on. Nothing for us. 11-28-23 Dustin A, No work for us. 12-7-23 Dustin A, No Activity for us today 12-29-23 Dustin A, No activity today for our department. 1-8-24 Dustin A, no work due to rain 1-25-24 Dustin A, No work being done due to rain. Did inform Dutch that silt fence needed to be reestablished in some areas and needed to maintain his approach and get rid of mud in the street. 1-29-24 Dustin , Contractor started working on the detention system 3-25-24 Dustin A, No activity today 4-2-24 Dustin A, no activity for us . 5-13-24 Dustin A, Waiting for re proof roll of approaches , no activity today 6-25-24 Dustin A. Last of Sw's is poured and passed. Only thing that is left for us to look at is vegetation.
Underground Electrical Inspection - Commercial Passed 6/28/2024 06/28/2024
Miscellaneous Correction
Resolved
06/28/2024
Underground electrical from power pole to the structures west southwest corner passed. This is a partial pass only. Okay to cover.
Miscellaneous Correction
Resolved
06/28/2024
Underground electrical from main disconnect to panels passed. Ok to cover Underground electrical from panels to trash compactor passed. Ok to cover This is a partial pass only
Miscellaneous Correction
Resolved
06/28/2024
Underground electrical to outside light post south, west and north sides and trash compactor passed. Ok to cover East side has been run under ground but not to the piers. Do not cover until inspected This is a partial pass only
Miscellaneous Correction
Resolved
06/28/2024
Ufer to #4 copper has been inspected and approved. Okay to pour concrete to cover This is a partial under ground electrical inspection pass only
Piers/Caissons Inspection - Commercial Passed 6/28/2024 06/28/2024
Erosion Control Inspection Residential Failed 7/1/2024 7/1/2024 07/01/2024
Misc
Informational
07/01/2024
7-1-24 Dustin A, Met with PM kyle with pinnacle. Informed him erosion control is needed across the street and SW cleaned . He said he would get it corrected
ESC - (Vegetation/Ground Cover) Partial 07/03/2024
Misc
Informational
07/03/2024
7-3-24 Dustin A, some sod is installed. Still need some on west and south sides and seed across street
Grading/Excavation/Fill Inspection Partial 07/03/2024
Misc
Informational
04/01/2024
11-3-23 PS Contractor hauling spoils pile from site 4-1-24 Dustin A, Tap hole on hollywood needs to be cleaned up. Talked to contractor and they said they would 7-3-24 Dustin A, some grading still needs to be done on west and south sides of lot
ESC - (Vegetation/Ground Cover) Partial 07/03/2024
Misc
Informational
07/03/2024
7-3-24 Dustin A, some sod is installed. Still need some on west and south sides and seed across street
Pavement-Curb Construction Passed 7/3/2024 7/3/2024 07/03/2024
Misc
Informational
06/10/2024
5-28-24 Dustin A, Curb is all poured to city specs. Informed Dutch there was 2 areas that washed out underneath that would need to be filled in. 5-29-24 Dustin A, few cracks in curb 6-10-24 Dustin A, 2 curbs are cracked 7-3-24 Dustin A, Cracks are hairline and have not separated so still in compliance.
Sanitary Sewer - Mandrel Passed 7/3/2024 07/03/2024
Sanitary Sewer - Vacuum Passed 07/03/2024
Sanitary Sewer Construction Inspection Passed 07/03/2024
Misc
Informational
05/03/2024
1-2-24 DP. Sewer contractor was on site today. They set the Manhole (sampling manhole). They had the 4" pipe ran to the manhole and 4" coming out. They were trying to get to the 4x6 tee today but are going to leave it uncovered. They didn't have tracer wire installed when I was there, but said they would get it on. 2-5-24 Dustin A, Started sewer out of proposed sewer service manhole (#10), 2-6-24 Dustin A, Continued work on service line. 2-7-24 Dustin A, Part of manhole near y is set, y is installed 2-10-24 Dustin A, Last manhole set sewer tied in. Backfilled 30 day starts today will be up on march 12th
Miscellaneous Correction
Corrective Action Required
05/03/2024
3-15-24 Dustin A, Sewer did not pass camera test from water dept . Talked with Dutch and contractor on issues that need to be addressed. Will need to be fixed and 30 day will need to be restarted. 4-1-24 Dustin A, Sewer was dug up and issues have been corrected. Sewer cannot still be used until 30 day period has passed and all testing redone.
Misc
Corrective Action Required
05/03/2024
5-3-24 Dustin A, Sewer camera inspection has been redone. There is a sag, but it is within the limit to allow. The only thing of note to repair is the grouting of the lifting lugs in manhole 57-136. Contractor and Dutch has been informed ans will let me know when corrections have been made.
Sanitary Sewer - Mandrel Passed 07/03/2024
Sanitary Sewer - Vacuum Passed 07/03/2024
Storm Sewer Construction Inspection Passed 07/03/2024
Misc
Informational
03/20/2024
1-30-24 Dustin A, Contractor on site working on storm on south side of building. MH 2 and 5A is installed at the correct slopes . 2-23-24 Dustin A, Started working on underground retention. 3-20-24 Dustin A, Storm retention manhole was knocked off. There is gravel that will need to be cleaned out and mastic reapplied.
Sanitary Sewer - Air Test Passed 07/03/2024
Occupancy Inspection - Engineering Temporary C of O 7/8/2024 7/3/2024 07/03/2024
Misc
Informational
07/03/2024
7-3-24 Dustin A, Granted TCO due to no life threatening possibilities on site. Punch List Attached Punch List: Needs 75% vegetation Seeded and matted on north side of SW SummitCrest DR Seeded and matted west side of Hollywood DR Grading and removal of excess dirt on west and south side of lot. South and west side still need sod
Sanitary Sewer - Air Test Passed 7/3/2024 7/3/2024 07/03/2024
Occupancy Inspection - Codes Commercial Failed 7/8/2024 7/8/2024 07/08/2024
Miscellaneous Correction
Corrective Action Required
07/08/2024
Whataburger. Occupancy -Secure MC cable’s under warming table -Back door exit discharge light is not working -Dining room GFCI needs to be tamper resistant -Protect Ptrap in bathrooms -Hood reservoir on roof is not installed -Protect grounding wire outside at grounding buss bar -Roof top cooler amps do not correspond with panel breaker -Strap MC cable and metal conduit at L2 panel -Bond water copper line 250.104 (a) -Installed bushings in transformer box in back room -Grease warmer needs a shutoff valve to be accessible -Soda machine back flow device needs to be code approved -Exit discharge lighting is not correct for passage -Guard rail at roof edge for hood system is only 31 vertical inches high (mechanical code 304.11) -Max freezer amps are 25 and 15 -Fire, planning and water must pass inspection
Occupancy Inspection - Fire Failed 7/8/2024 7/8/2024 07/08/2024
Miscellaneous Inspection Passed 7/9/2024 07/09/2024
Miscellaneous Correction
Informational
07/09/2024
Job superintendent and I went over their corrective action list
Occupancy Inspection - Planning Failed 7/8/2024 7/8/2024 07/09/2024
Corrective Action Required
07/08/2024
The bollards at the head of the ADA stall have been installed into the parking surface causing them to be to short. Minimum depth of a parking stall shall be 19’. As constructed the stalls are 18’. Please move the bollards back (similar to the bollards in front of the non-ADA stalls).
Corrective Action Required
07/08/2024
The east ADA stall is only 7’ wide. The minimum width shall be 8’. Parking stall widths are measured exclusive of the curb and guttering. Please restripe the ADA stall the meet the minimum widths.
Corrective Action Required
07/08/2024
There was no ground cover along Mo-150. Please install the required groundcover.
Miscellaneous Inspection Passed 7/11/2024 07/11/2024
Miscellaneous Correction
Informational
07/11/2024
Job site superintendent wanted to discuss roof top fall protection Superintendent was advised to talk to commercial plan reviewer
Miscellaneous Inspection Passed 7/18/2024 07/18/2024
Miscellaneous Correction
Informational
07/18/2024
Talked to site superintendent about corrective actions for Occupancy
Occupancy Inspection - Water Utilities Passed 7/8/2024 7/8/2024 07/19/2024
Miscellaneous Inspection Passed 7/23/2024 07/23/2024
Miscellaneous Correction
Informational
07/23/2024
Talked with job site superintendent about the building final set for 07/26/2024
ESC - (Vegetation/Ground Cover) Passed 07/25/2024
Misc
Informational
07/03/2024
7-3-24 Dustin A, some sod is installed. Still need some on west and south sides and seed across street 7-25-24 Dustin A, All sod and seed has been installed
Grading/Excavation/Fill Inspection Passed 07/25/2024
Misc
Informational
07/03/2024
11-3-23 PS Contractor hauling spoils pile from site 4-1-24 Dustin A, Tap hole on hollywood needs to be cleaned up. Talked to contractor and they said they would 7-3-24 Dustin A, some grading still needs to be done on west and south sides of lot 7-25-24 Dustin A, All grading completed
Sanitary Sewer - Camera Test Passed 8/2/2024 07/25/2024
Occupancy Inspection - Engineering Passed 7/25/2024 7/25/2024 07/25/2024
Misc
Informational
07/03/2024
7-3-24 Dustin A, Granted TCO due to no life threatening possibilities on site. Punch List Attached Punch List: Needs 75% vegetation Seeded and matted on north side of SW SummitCrest DR Seeded and matted west side of Hollywood DR Grading and removal of excess dirt on west and south side of lot. South and west side still need sod 7-25-24 Dustin A, All gradng and sod has been installed. Seed and matting has been installed where it was needed. It has 75% vegetation installed
Occupancy Inspection - Planning Passed 7/26/2024 7/26/2024 07/26/2024
Occupancy Inspection - Codes Commercial Full C of O 7/26/2024 7/26/2024 07/26/2024
Miscellaneous Correction
Resolved
07/26/2024
Whataburger. Occupancy -Secure MC cable’s under warming table -Back door exit discharge light is not working -Dining room GFCI needs to be tamper resistant -Protect Ptrap in bathrooms -Hood reservoir on roof is not installed -Protect grounding wire outside at grounding buss bar -Roof top cooler amps do not correspond with panel breaker -Strap MC cable and metal conduit at L2 panel -Bond water copper line 250.104 (a) -Installed bushings in transformer box in back room -Grease warmer needs a shutoff valve to be accessible -Soda machine back flow device needs to be code approved -Exit discharge lighting is not correct for passage -Guard rail at roof edge for hood system is only 31 vertical inches high (mechanical code 304.11) -Max freezer amps are 25 and 15 -Fire, planning and water must pass inspection
Documents & Images
Date Uploaded File Type Document Name
08/23/2022 Plans WB - Lees Summit Market MO - Building Permit Plans
08/23/2022 Application Form Updated Commercial Permit Application_220823
08/30/2022 Email Health Dept review
09/01/2022 Letter Fire Building Plan Review
09/01/2022 Letter DS P/R Corrections Document
09/19/2022 220908 WB Lees Summit Building Comment Response
09/19/2022 A4-1 - WALL SECTIONS
09/19/2022 A4-2 - WALL SECTIONS
09/19/2022 A4-3 - WALL SECTIONS
09/19/2022 A4-4 - WALL SECTIONS
09/19/2022 F0_1 - SITE PLAN
09/19/2022 G1-0 - CODE ANALYSIS AND LIFE SAFETY PLANS
09/19/2022 Geotechnical Report
09/19/2022 I0-1 - FINISH PLAN
09/19/2022 I1-2 - ENLARGED PLAN AND INTERIOR ELEVATIONS
09/19/2022 P1_1 - PLUMBING DOMESTIC WATER PLAN
09/19/2022 P4_2 - PLUMBING DETAILS
09/19/2022 S0_2 - GENERAL NOTES
09/19/2022 S3_1 - FOUNDATION DETAILS
09/19/2022 S5_1 - TYPICAL DETAILS
09/20/2022 Letter Fire Building Plan Review
03/17/2023 Plans 20230317_WB_LEESSUMMIT MO_PT22M
03/29/2023 Receipt Receipt for transaction: 2023-001775
03/29/2023 Letter Fire Building Plan Review
03/30/2023 Letter DS P/R Corrections Document
04/10/2023 Letter Fire Building Plan Review
04/18/2023 Plans 20230417_LEESSUMMIT MO_REV 1
04/18/2023 Letter 20230417_WB Lees Summit_Building Permit Comment Response
04/24/2023 Letter Fire Building Plan Review
05/08/2023 Approved Plans Approved 5.8.2023 WB150 FDP
05/09/2023 Receipt Receipt for transaction:2023-003005
05/09/2023 Receipt Receipt for transaction:2023-003010
07/25/2023 Email jackson county health dept approval
08/30/2023 Plans 20230830_LEESSUMMIT MO_COMBINED
08/30/2023 Approved Plans approved - 20230830_LEESSUMMIT MO_COMBINED
08/30/2023 Letter DS Building Permit
09/25/2023 Letter INSPECTION SUMMARY
11/03/2023 Letter INSPECTION SUMMARY
11/08/2023 Letter INSPECTION SUMMARY
11/17/2023 Letter INSPECTION SUMMARY
11/20/2023 Letter INSPECTION SUMMARY
11/21/2023 Letter INSPECTION SUMMARY
11/27/2023 Letter INSPECTION SUMMARY
11/28/2023 Letter INSPECTION SUMMARY
12/04/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/11/2023 Letter INSPECTION SUMMARY
12/12/2023 Letter INSPECTION SUMMARY
12/12/2023 Letter INSPECTION SUMMARY
01/02/2024 Letter INSPECTION SUMMARY
01/03/2024 whataburger Sanitary 1-3-24
01/04/2024 Whataburger sewer and storm
01/04/2024 Whataburger sewer and storm0
01/04/2024 Whataburger sewer
01/04/2024 whataburgersew
01/04/2024 whatburgersew1
01/08/2024 Letter INSPECTION SUMMARY
01/24/2024 Letter INSPECTION SUMMARY
01/30/2024 Letter INSPECTION SUMMARY
02/02/2024 whataburger storm south side MH5
02/02/2024 what aburger storm MH5 2
02/02/2024 Letter INSPECTION SUMMARY
02/05/2024 Letter INSPECTION SUMMARY
02/05/2024 Letter INSPECTION SUMMARY
02/05/2024 Letter INSPECTION SUMMARY
02/06/2024 Whataburger 6in out of proposed sewer service manhole ( #10)
02/06/2024 Letter INSPECTION SUMMARY
02/06/2024 Letter INSPECTION SUMMARY
02/07/2024 Letter INSPECTION SUMMARY
02/09/2024 sewer 2
02/09/2024 sewer 1
02/09/2024 sewer 3
02/09/2024 Whataburger sewer0
02/09/2024 whataburgersew0
02/09/2024 whatburgersew2
02/09/2024 what aburger storm MH5 3
02/09/2024 whataburger storm south side MH6
02/09/2024 Letter INSPECTION SUMMARY
02/14/2024 Letter INSPECTION SUMMARY
02/20/2024 Letter INSPECTION SUMMARY
02/26/2024 Letter INSPECTION SUMMARY
02/27/2024 Letter INSPECTION SUMMARY
03/07/2024 Letter INSPECTION SUMMARY
03/07/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/18/2024 Letter INSPECTION SUMMARY
03/18/2024 Letter INSPECTION SUMMARY
03/18/2024 Letter INSPECTION SUMMARY
03/18/2024 Letter INSPECTION SUMMARY
03/19/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Engineer Report/Study pier report
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 Letter INSPECTION SUMMARY
03/21/2024 Plans Whataburger plans
03/25/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter Codes Residential Plan Review
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter Fire Building Plan Review
03/27/2024 Letter Fire Building Plan Review
03/27/2024 Letter Fire Building Plan Review
03/27/2024 Letter Fire Building Plan Review
03/27/2024 Letter Fire Building Plan Review
03/29/2024 Letter INSPECTION SUMMARY
03/29/2024 Letter Fire Building Plan Review
03/29/2024 Letter Fire Building Plan Review
04/01/2024 Letter INSPECTION SUMMARY
04/01/2024 Letter INSPECTION SUMMARY
04/01/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/03/2024 Letter Fire (Sprinkler) Plan Review
04/11/2024 Letter INSPECTION SUMMARY
04/11/2024 Letter INSPECTION SUMMARY
04/19/2024 Letter INSPECTION SUMMARY
04/23/2024 Letter INSPECTION SUMMARY
04/23/2024 Letter INSPECTION SUMMARY
04/24/2024 Letter INSPECTION SUMMARY
04/24/2024 Letter INSPECTION SUMMARY
05/01/2024 Letter INSPECTION SUMMARY
05/01/2024 Letter INSPECTION SUMMARY
05/03/2024 Letter INSPECTION SUMMARY
05/06/2024 Letter INSPECTION SUMMARY
05/08/2024 Letter INSPECTION SUMMARY
05/13/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/31/2024 Letter INSPECTION SUMMARY
05/31/2024 Letter INSPECTION SUMMARY
05/31/2024 Letter INSPECTION SUMMARY
06/04/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/10/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/19/2024 Letter INSPECTION SUMMARY
06/25/2024 Letter INSPECTION SUMMARY
06/25/2024 Letter INSPECTION SUMMARY
06/25/2024 Letter INSPECTION SUMMARY
06/25/2024 Letter INSPECTION SUMMARY
06/28/2024 Letter INSPECTION SUMMARY
06/28/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/03/2024 Letter INSPECTION SUMMARY
07/08/2024 Letter INSPECTION SUMMARY
07/08/2024 whataburger health dept doc
07/09/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/17/2024 Specifications Leading Edge Safety Est 071524-0003
07/17/2024 Approved Plans Approved - Rail mounting detail
07/18/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/25/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter INSPECTION SUMMARY
07/26/2024 Letter Codes Final Certificate of Occupancy
07/26/2024 Letter Field Certificate of Occupancy
07/26/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home