Permit Application Status

PRCOM20241128


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20241128
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
WALLFLOWER MERCH - NEW TENANT FOR SCREEN PRINTING BUSINESS **Invite Planner to final to verify screening of new ground mounted hvac
03/12/2024
04/19/2024
09/23/2024
10/10/2024
Locations
Contacts
North Oak Safety Storage LLC, Address:1120 NW Eagle Ridge Blvd.  
CLAYTON@SAFETYMINISTORAGE.COM  
F & G MECHANICAL SERVICES INC, Address:17219 BEL RAY PLACE, Phone:(816) 322-0810  
VELOCITY ELECTRIC AND AUTOMATION LLC, Address:1704 SW RED FOX CIR, Phone:(816) 215-1514  
R2 PLUMBING LLC, Address:1705 A SE COUNTY RD AA, Phone:(816) 215-8098  
MIDWEST ARCHITECTS, Address:1120 NW EAGLE RIDGE BLVD, Phone:(816) 229-8115  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved with Conditions 09/27/2024 09/24/2024
Craig Hill
Building Plan Review Approved 09/27/2024 09/20/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
09/20/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. Fee will be $17,094.00 4/10/24 - Acknowledged in letter.
Misc
Corrective Action Required
09/20/2024

Condensing unit not shown. Actions required: Specify location and all relevant code related designs. (electrical, screening, etc) 4/10/24 - Height and species of screening vegetation not specified. Proceed at your own risk. To be verified at inspections.
Misc
Corrective Action Required
09/20/2024

**comment added 4/10/24** I missed the required convenience receptacle within 25' of new condensing unit. To be field verified.
Alarm Plan Review Released for Construction 06/17/2024 06/24/2024
Craig Hill
Misc
Corrective Action Required
06/17/2024

Provide tenant finish drawings and storage plan for the production are.
Duct smoke detectors
Corrective Action Required
06/17/2024

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
Miscellaneous Correction
Corrective Action Required
06/17/2024

High volume low spped (HVLS) fans shall be interlocked to shut down immediately upon fire alarm activation.
Duct smoke detection
Corrective Action Required
06/17/2024

907.2.12.1.2 Duct smoke detection. Duct smoke detectors complying with Section 907.3.1 shall be located as follows: 1. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.
Sprinkler Plan Review Released for Construction 05/17/2024 05/16/2024
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
05/16/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans for the office only received 3/5/2024.
Installation acceptance testing
Corrective Action Required
05/16/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow tests.
Building Plan Review Approved with Conditions 04/10/2024 04/10/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
04/03/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. Fee will be $17,094.00 4/10/24 - Acknowledged in letter.
IBC 2902.3.1 Access - access to public toilet
Resolved
04/10/2024

1109.2.1 Family or assisted-use toilet and bathing rooms. In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy. Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required. Action required: Provide additional water closet and lavatory. (numbers to be rounded up)
IBC 1010.1.10 Panic and fire exit hardware
Resolved
04/10/2024

2018 IBC 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Exceptions: 1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.1.9.4, Item 2. 2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancy shall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Provide panic hardware on door 100.
IBC 706.1 Fire and Smoke Protection - General
Resolved
04/10/2024

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Construction details of wall type D-1 do not match UL details. Select alternate UL# or clarify. (ref: stud size and different framing at top of wall)
IBC 505.3.3 - platform guards
Resolved
04/10/2024

2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2. Action required: Provide guards at equipment platform.
IMC 307.2.3 Auxiliary condensate disposal
Resolved
04/10/2024

2018 IMC 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options) Action required: Specify method of auxiliary drainage for furnace and water heater.
IBC 1013.1 Where required - exit sign
Resolved
04/10/2024

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Actions required: - Relocate exit sign on sheet E-2 to Production Area side of door into office. (Not allowed to exit a B occupancy through an F) - Provide exit sign and external emergency light at front door 100.
Misc
Corrective Action Required
04/03/2024

Condensing unit not shown. Actions required: Specify location and all relevant code related designs. (electrical, screening, etc) 4/10/24 - Height and species of screening vegetation not specified. Proceed at your own risk. To be verified at inspections.
Misc
Corrective Action Required
04/10/2024

**comment added 4/10/24** I missed the required convenience receptacle within 25' of new condensing unit. To be field verified.
Licensed Contractors Approved 04/10/2024 04/10/2024
Joe Frogge
Fire Plan Review Approved 04/10/2024 04/09/2024
Jim Eden
Address numbers required
Resolved
04/09/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post unit address on front and rear doors. Verified at inspection.
Miscellaneous Correction
Resolved
04/09/2024

Confirm use of the space. Is it manufacturing, or storage of pre-manufactured merchandise. What materials are used if it is manufacturing?
Construction documents for fire alarm systems
Informational
04/09/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Construction documents - Fire protection systems
Informational
04/09/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Fire Plan Review Approved with Conditions 03/22/2024 03/27/2024
Jim Eden
Address numbers required
Corrective Action Required
03/27/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Post unit address on front and rear doors. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
03/27/2024

Confirm use of the space. Is it manufacturing, or storage of pre-manufactured merchandise. What materials are used if it is manufacturing?
Construction documents for fire alarm systems
Corrective Action Required
03/27/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
03/27/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Building Plan Review Rejected 03/22/2024 03/21/2024
Joe Frogge
License Tax - Payment
Corrective Action Required
03/21/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is informational. Fee will be $17,094.00
IBC 2902.3.1 Access - access to public toilet
Corrective Action Required
03/21/2024

1109.2.1 Family or assisted-use toilet and bathing rooms. In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy. Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required. Action required: Provide additional water closet and lavatory. (numbers to be rounded up)
IBC 1010.1.10 Panic and fire exit hardware
Corrective Action Required
03/21/2024

2018 IBC 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware. Exceptions: 1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.1.9.4, Item 2. 2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancy shall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10. Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel. Action required: Provide panic hardware on door 100.
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
03/21/2024

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Construction details of wall type D-1 do not match UL details. Select alternate UL# or clarify. (ref: stud size and different framing at top of wall)
IBC 505.3.3 - platform guards
Corrective Action Required
03/21/2024

2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2. Action required: Provide guards at equipment platform.
IMC 307.2.3 Auxiliary condensate disposal
Corrective Action Required
03/21/2024

2018 IMC 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options) Action required: Specify method of auxiliary drainage for furnace and water heater.
IBC 1013.1 Where required - exit sign
Corrective Action Required
03/21/2024

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Actions required: - Relocate exit sign on sheet E-2 to Production Area side of door into office. (Not allowed to exit a B occupancy through an F) - Provide exit sign and external emergency light at front door 100.
Misc
Corrective Action Required
03/21/2024

Condensing unit not shown. Actions required: Specify location and all relevant code related designs. (electrical, screening, etc)
Zoning Review Approved 03/22/2024 03/14/2024
Joe Frogge
Licensed Contractors Approved 03/12/2024 03/14/2024
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $1,128.00 $1,128.00 Paid 04/19/2024
7232302-Industrial/Warehouse License Tax Fee $17,094.00 $17,094.00 Paid 07/17/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 09/10/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 09/10/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 4/22/2024 04/22/2024
Rated Assembly Inspection Partial 4/25/2024 4/25/2024 04/25/2024
Misc
Informational
04/25/2024
1-hr demising wall-east side 1st layer screw pattern OK
Rated Assembly Inspection Passed 4/29/2024 4/29/2024 04/29/2024
Misc
Informational
04/25/2024
1-hr demising wall-both sides screw pattern OK
In-wall Inspection Passed 5/6/2024 5/6/2024 05/06/2024
Above Ceiling Inspection Failed 6/3/2024 6/3/2024 06/03/2024
Misc
Corrective Action Required
06/03/2024
-Fire caulk along firewall vertical edge at north side of building
Above Ceiling Inspection Passed 6/5/2024 6/5/2024 06/05/2024
Misc
Resolved
06/05/2024
-Fire caulk along firewall vertical edge at north side of building
Electrical Service Inspection Passed 6/5/2024 06/05/2024
Rough Electrical Inspection - Commercial Passed 6/6/2024 6/7/2024 06/07/2024
Gas Service Inspection - Commercial Passed 6/28/2024 06/28/2024
Occupancy Inspection - Codes Commercial Failed 7/17/2024 7/17/2024 07/17/2024
Misc
Corrective Action Required
07/17/2024
-License tax fee has not been paid -Fire and Planning approval required -Fire caulk penetrations of fire wall -Install breaker cover for rear panel -Label all breakers and panels; identify all circuits per NEC 210.5 -Door threshold shall not exceed 1/2”. Threshold more than 1/4” shall be beveled -Operation of all doors cannot require twisting of the wrists
Occupancy Inspection - Codes Commercial Ready for Temp CO 7/22/2024 7/22/2024 07/22/2024
Misc
Corrective Action Required
07/17/2024
-Planning approval required -Support water line vertically at max 10 ft intervals
Occupancy Inspection - Fire Passed 7/17/2024 7/17/2024 07/22/2024
Occupancy Inspection - Codes Commercial Ready for Temp CO 8/21/2024 8/21/2024 08/21/2024
Misc
Corrective Action Required
07/22/2024
-Planning approval required. Replace dead trees around AC unit
Occupancy Inspection - Codes Commercial Full C of O 10/10/2024 10/10/2024
Misc
Resolved
10/10/2024
-Planning approval required.
Miscellaneous Inspection Passed 10/14/2024 10/14/2024
Misc
Informational
10/14/2024
Rack system inspected and is in compliance with submit documentation
Documents & Images
Date Uploaded File Type Document Name
03/14/2024 Plans 24_03_11 Wallflower Merch Permit Submittal PRCOM20241128
03/14/2024 Application Form Wallfower Merch Commercial Permit Application Signed
03/14/2024 Letter License Tax Bill
03/27/2024 Letter DS P/R Corrections Document
04/03/2024 Letter 24_04_01 Plan Review Response Letter PRCOM20241128
04/03/2024 Plans 24_04_01 Wallflower Merch Complete Revised Set PRCOM20241128
04/05/2024 Letter 24_04_05 Design Change Narrative Letter PRCOM20241128
04/05/2024 Drawing MP-1 Revised 24_04_05
04/05/2024 Drawing E-1 Revised 24_04_05
04/10/2024 Approved Plans Approved Wallflower plans
04/16/2024 Letter 24_04_16 Design Change Narrative Letter PRCOM20241128
04/16/2024 Drawing E-1 Revised 24_04_16
04/16/2024 Drawing E-2 Revised 24_04_16
04/16/2024 Drawing E-3 Revised 24_04_16
04/17/2024 Approved Plans Approved Elec Rev
04/19/2024 Receipt Receipt for transaction: 2024-002530
04/19/2024 Letter DS Building Permit
04/25/2024 Letter INSPECTION SUMMARY
04/25/2024 Letter INSPECTION SUMMARY
04/29/2024 Letter INSPECTION SUMMARY
05/03/2024 Wallflower FP
05/06/2024 Letter INSPECTION SUMMARY
05/16/2024 Wallflower FP APPROVED
05/16/2024 Letter Fire (Sprinkler) Plan Review
06/03/2024 Fire Alarm for Spiritus-Wallflower
06/03/2024 Fire Alarm Data Sheets
06/03/2024 Letter INSPECTION SUMMARY
06/04/2024 Fire Alarm Data Sheets
06/04/2024 Fire Alarm Front Page for Spiritus-Wallflower
06/04/2024 Spiritus-Wall Flower Fire Alarm_STAMPED
06/05/2024 Letter INSPECTION SUMMARY
06/05/2024 Letter INSPECTION SUMMARY
06/07/2024 Letter INSPECTION SUMMARY
06/17/2024 Letter Fire (Alarm) Plan Review Notice
06/28/2024 Letter INSPECTION SUMMARY
07/17/2024 Letter INSPECTION SUMMARY
07/17/2024 Receipt Receipt for transaction: 2024-005927
07/22/2024 Letter INSPECTION SUMMARY
09/10/2024 Certificate/License Codes Temporary Certificate of Occupancy
09/10/2024 Certificate/License Codes Temporary Certificate of Occupancy
09/10/2024 Receipt Receipt for transaction:2024-007571
09/20/2024 Plans 24-2416 (Wallflower Merchandise), Dtls (Digitally Signed 09-18-2024 LE)
09/20/2024 Engineer Report/Study 24-2416 (Wallflower Merchandise),Calcs - 09-18-2024 (Digitally Signed 09-18-2024 LE)
09/25/2024 Approved Plans Approved Racking Plans
10/10/2024 Letter Codes Final Certificate of Occupancy
10/10/2024 Letter Field Certificate of Occupancy
10/10/2024 Letter INSPECTION SUMMARY
10/14/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home