Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved with Conditions
|
09/27/2024
|
09/24/2024
|
|
Craig Hill
|
|
|
Building Plan Review
|
Approved
|
09/27/2024
|
09/20/2024
|
|
Joe Frogge
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is informational. Fee will be $17,094.00
4/10/24 - Acknowledged in letter.
|
|
Misc
Corrective Action Required
Condensing unit not shown.
Actions required: Specify location and all relevant code related designs. (electrical, screening, etc)
4/10/24
- Height and species of screening vegetation not specified. Proceed at your own risk. To be verified at inspections.
|
|
Misc
Corrective Action Required
**comment added 4/10/24**
I missed the required convenience receptacle within 25' of new condensing unit. To be field verified.
|
|
|
Alarm Plan Review
|
Released for Construction
|
06/17/2024
|
06/24/2024
|
|
Craig Hill
|
|
Misc
Corrective Action Required
Provide tenant finish drawings and storage plan for the production are.
|
|
Duct smoke detectors
Corrective Action Required
2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is rquired by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with theis code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection.
|
|
Miscellaneous Correction
Corrective Action Required
High volume low spped (HVLS) fans shall be interlocked to shut down immediately upon fire alarm activation.
|
|
Duct smoke detection
Corrective Action Required
907.2.12.1.2 Duct smoke detection. Duct smoke
detectors complying with Section 907.3.1 shall be
located as follows:
1. In the main return air and exhaust air plenum
of each air-conditioning system having a
capacity greater than 2,000 cubic feet per minute
(cfm) (0.94 m3/s). Such detectors shall be
located in a serviceable area downstream of
the last duct inlet.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
05/17/2024
|
05/16/2024
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans for the office only received 3/5/2024.
|
|
Installation acceptance testing
Corrective Action Required
2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule hydrostatic and flow tests.
|
|
|
Building Plan Review
|
Approved with Conditions
|
04/10/2024
|
04/10/2024
|
|
Joe Frogge
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is informational. Fee will be $17,094.00
4/10/24 - Acknowledged in letter.
|
|
IBC 2902.3.1 Access - access to public toilet
1109.2.1 Family or assisted-use toilet and bathing rooms.
In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required.
Action required: Provide additional water closet and lavatory. (numbers to be rounded up)
|
|
IBC 1010.1.10 Panic and fire exit hardware
2018 IBC 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware.
Exceptions:
1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.1.9.4, Item 2.
2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancy shall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10.
Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.
Action required: Provide panic hardware on door 100.
|
|
IBC 706.1 Fire and Smoke Protection - General
2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply.
Action required: Construction details of wall type D-1 do not match UL details. Select alternate UL# or clarify. (ref: stud size and different framing at top of wall)
|
|
IBC 505.3.3 - platform guards
2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2.
Action required: Provide guards at equipment platform.
|
|
IMC 307.2.3 Auxiliary condensate disposal
2018 IMC 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options)
Action required: Specify method of auxiliary drainage for furnace and water heater.
|
|
IBC 1013.1 Where required - exit sign
2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Actions required:
- Relocate exit sign on sheet E-2 to Production Area side of door into office. (Not allowed to exit a B occupancy through an F)
- Provide exit sign and external emergency light at front door 100.
|
|
Misc
Corrective Action Required
Condensing unit not shown.
Actions required: Specify location and all relevant code related designs. (electrical, screening, etc)
4/10/24
- Height and species of screening vegetation not specified. Proceed at your own risk. To be verified at inspections.
|
|
Misc
Corrective Action Required
**comment added 4/10/24**
I missed the required convenience receptacle within 25' of new condensing unit. To be field verified.
|
|
|
Licensed Contractors
|
Approved
|
04/10/2024
|
04/10/2024
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved
|
04/10/2024
|
04/09/2024
|
|
Jim Eden
|
|
Address numbers required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Post unit address on front and rear doors. Verified at inspection.
|
|
Miscellaneous Correction
Confirm use of the space. Is it manufacturing, or storage of pre-manufactured merchandise. What materials are used if it is manufacturing?
|
|
Construction documents for fire alarm systems
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide shop drawings for review and approval.
|
|
Construction documents - Fire protection systems
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide shop drawings for review and approval.
|
|
|
Fire Plan Review
|
Approved with Conditions
|
03/22/2024
|
03/27/2024
|
|
Jim Eden
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Post unit address on front and rear doors. Verified at inspection.
|
|
Miscellaneous Correction
Corrective Action Required
Confirm use of the space. Is it manufacturing, or storage of pre-manufactured merchandise. What materials are used if it is manufacturing?
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide shop drawings for review and approval.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide shop drawings for review and approval.
|
|
|
Building Plan Review
|
Rejected
|
03/22/2024
|
03/21/2024
|
|
Joe Frogge
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is informational. Fee will be $17,094.00
|
|
IBC 2902.3.1 Access - access to public toilet
Corrective Action Required
1109.2.1 Family or assisted-use toilet and bathing rooms.
In assembly and mercantile occupancies, an accessible family or assisted-use toilet room shall be provided where an aggregate of six or more male and female water closets is required. In buildings of mixed occupancy, only those water closets required for the assembly or mercantile occupancy shall be used to determine the family or assisted-use toilet room requirement. In recreational facilities where separate-sex bathing rooms are provided, an accessible family or assisted-use bathing room shall be provided. Fixtures located within family or assisted-use toilet and bathing rooms shall be included in determining the number of fixtures provided in an occupancy.
Exception: Where each separate-sex bathing room has only one shower or bathtub fixture, a family or assisted-use bathing room is not required.
Action required: Provide additional water closet and lavatory. (numbers to be rounded up)
|
|
IBC 1010.1.10 Panic and fire exit hardware
Corrective Action Required
2018 IBC 1010.1.10 Panic and fire exit hardware. Swinging doors serving a Group H occupancy and swinging doors serving rooms or spaces with an occupant load of 50 or more in a Group A or E occupancy shall not be provided with a latch or lock other than panic hardware or fire exit hardware.
Exceptions:
1. A main exit of a Group A occupancy shall be permitted to have locking devices in accordance with Section 1010.1.9.4, Item 2.
2. Doors provided with panic hardware or fire exit hardware and serving a Group A or E occupancy shall be permitted to be electrically locked in accordance with Section 1010.1.9.9 or 1010.1.9.10.
Electrical rooms with equipment rated 1,200 amperes or more and over 6 feet wide that contains over current devices, switching devices or control devices with exit or exit access doors shall be equipped with panic hardware or fire exit hardware. The doors shall swing in the direction of egress travel.
Action required: Provide panic hardware on door 100.
|
|
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply.
Action required: Construction details of wall type D-1 do not match UL details. Select alternate UL# or clarify. (ref: stud size and different framing at top of wall)
|
|
IBC 505.3.3 - platform guards
Corrective Action Required
2018 IBC 505.3.3 Guards. Equipment platforms shall have guards where required by Section 1013.2.
Action required: Provide guards at equipment platform.
|
|
IMC 307.2.3 Auxiliary condensate disposal
Corrective Action Required
2018 IMC 307.2.3 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options)
Action required: Specify method of auxiliary drainage for furnace and water heater.
|
|
IBC 1013.1 Where required - exit sign
Corrective Action Required
2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions)
Actions required:
- Relocate exit sign on sheet E-2 to Production Area side of door into office. (Not allowed to exit a B occupancy through an F)
- Provide exit sign and external emergency light at front door 100.
|
|
Misc
Corrective Action Required
Condensing unit not shown.
Actions required: Specify location and all relevant code related designs. (electrical, screening, etc)
|
|
|
Zoning Review
|
Approved
|
03/22/2024
|
03/14/2024
|
|
Joe Frogge
|
|
|
Licensed Contractors
|
Approved
|
03/12/2024
|
03/14/2024
|
|
Joe Frogge
|
|
|