Permit Application Status

PRRES20241421


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20241421
Building Permit - Residential
Certificate of Occupancy
CMH PARKS INC
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - UNFINISHED BASEMENT -
03/26/2024
04/03/2024
01/03/2025
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CMH PARKS INC, Address:5000 CLAYTON RD  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
BRUCER@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 04/03/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 04/03/2024
7232302-Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 04/03/2024
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 04/03/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 04/03/2024
9110078-Valuation Fee New Single Family $1,805.59 $1,805.59 Paid 04/03/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 10/03/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 10/03/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 10/03/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/04/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/04/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 5/3/2024 05/03/2024
Sewer Service Inspection - R Passed 5/3/2024 5/3/2024 05/03/2024
Water Service Inspection - R Passed 5/8/2024 5/8/2024 05/08/2024
Underslab Plumbing Inspection - Residential Passed 5/20/2024 5/20/2024 05/20/2024
All Rough Inspection - Residential Partial 6/11/2024 6/11/2024 06/11/2024
Misc
Informational
06/11/2024
Garage portal frame inspection only.
Electrical Service Inspection Failed 7/24/2024 7/24/2024 07/24/2024
Misc
Corrective Action Required
07/24/2024
-Outlets in garage incomplete
Gas Service Inspection - Residential Not Ready 7/24/2024 07/24/2024
Misc
Corrective Action Required
07/24/2024
-No gas line in the house at the time of the inspection
All Rough Inspection - Residential Failed 7/24/2024 7/24/2024 07/24/2024
Misc
Informational
06/11/2024
Garage portal frame inspection only.
Misc
Corrective Action Required
07/24/2024
-Electrical outlets in garage incomplete/insufficient number -Missing fire blocking at top of chase in garage -Several screws aren’t completely sunk in at the truss to top plate connection point (in the garage) -Missing fire blocking at top of chase in powder room -It appears that the doubled manufactured truss assembly at the master bedroom is insufficiently nailed together -The tension bracket at stairs leading to basement is not secured -Exterior siding has insufficient nails at rim joist (west side)
Electrical Service Inspection Passed 7/29/2024 7/29/2024 07/29/2024
Misc
Resolved
07/29/2024
All Rough Inspection - Residential Failed 7/29/2024 7/29/2024 07/29/2024
Misc
Informational
07/24/2024
Garage portal frame inspection only.
Misc
Corrective Action Required
07/24/2024
-Electrical outlets in garage incomplete/insufficient number -Missing fire blocking at top of chase in garage -Several -The tension bracket at stairs leading to basement is not secured completely to stud
All Rough Inspection - Residential Passed 7/31/2024 7/31/2024 07/31/2024
Misc
Resolved
07/31/2024
Garage portal frame inspection only.
Misc
Resolved
07/31/2024
-Electrical outlets in garage incomplete/insufficient number -Missing fire blocking at top of chase in garage -The tension bracket at stairs leading to basement is not secured completely to stud
Driveway Inspection Partial 9/5/2024 09/05/2024
Misc
Informational
09/05/2024
9-5-2024 Dustin A, Dw formed to city specs, Approved to pour
Driveway Inspection Passed 9/12/2024 9/10/2024 09/10/2024
Misc
Informational
09/05/2024
9-5-2024 Dustin A, Dw formed to city specs, Approved to pour 9-10-24 Dustin A, DW is poured to city specs.Passed
Gas Service Inspection - Residential Failed 9/24/2024 9/24/2024 09/24/2024
Misc
Corrective Action Required
07/24/2024
-No gas line in the house at the time of the inspection
G2417.4 Test pressure measurement
Corrective Action Required
09/24/2024
INSPECTION, TESTING AND PURGING. Test pressure shall be measured with a manometer or with a pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure.
G2417.4.1 Test Pressure
Corrective Action Required
09/24/2024
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Gas Service Inspection - Residential Passed 9/27/2024 9/27/2024 09/27/2024
Misc
Resolved
09/27/2024
-No gas line in the house at the time of the inspection
G2417.4 Test pressure measurement
Resolved
09/27/2024
INSPECTION, TESTING AND PURGING. Test pressure shall be measured with a manometer or with a pressure-measuring device designed and calibrated to read, record, or indicate a pressure loss caused by leakage during the pressure test period. The source of pressure shall be isolated before the pressure tests are made. Mechanical gauges used to measure test pressures shall have a range such that the highest end of the scale is not greater than five times the test pressure.
G2417.4.1 Test Pressure
Resolved
09/27/2024
INSPECTION, TESTING AND PURGING. AMENDED 7-945. The test pressure to be used shall be not less than one and one-half times the proposed maximum working pressure, but not less than 10 psig (68.9kPa) irrespective of design pressure. For welded piping, and for piping carrying gas at pressures in excess of fourteen (14) inches water column pressure, the test pressure shall not be less than 60 psig. Where the test pressure exceeds 125 psig (862 kPa gauge), the test pressure shall not exceed a value that produces a hoop stress in the piping greater than 50 percent of the specified minimum yield strength of the pipe.
Plot Plan Inspection Passed 10/1/2024 10/01/2024
Erosion Control Inspection Residential Partial 10/1/2024 10/01/2024
Misc
Corrective Action Required
10/01/2024
- OK AT TIME OF INSPECTION
Occupancy Inspection - Codes Residential Failed 10/1/2024 10/1/2024 10/01/2024
Misc
Corrective Action Required
10/01/2024
Outside only, no access •pay outstanding fees •Final grading and sod •Installation of irrigation system •Provide splash pads •Provide gaurd front porch over 30” above grade •Provide ladder from Egress window basement •Secure electrical whip •With in 12” of disconnect •Sump discharge to be 36” away from foundation
Occupancy Inspection - Codes Residential Ready for Temp CO 10/2/2024 10/2/2024 10/02/2024
Misc
Corrective Action Required
10/01/2024
•pay outstanding fees •Final grading and sod •Installation of irrigation system •Provide splash pads •Provide ladder from Egress window basement •Secure electrical whip •With in 12” of disconnect •Sump discharge to be 36” away from foundation
Occupancy Inspection - Codes Residential Failed 12/2/2024 12/02/2024
Misc
Corrective Action Required
10/02/2024
PERMIT IN NOTICE OF VIOLATION STATUS. TCO EXPIRED •pay outstanding fees •Final grading and sod •Installation of irrigation system •Provide splash pads •Provide ladder from Egress window basement •Secure electrical whip at A/C •With in 12” of disconnect •Sump discharge to be 36” away from foundation
Occupancy Inspection - Codes Residential Full C of O 1/3/2025 01/03/2025
Misc
Resolved
01/03/2025
PERMIT IN NOTICE OF VIOLATION STATUS. TCO EXPIRED •pay outstanding fees •Final grading and sod •Installation of irrigation system •Provide splash pads •Provide ladder from Egress window basement •Secure electrical whip at A/C With in 12” of disconnect •Sump discharge to be 36” away from foundation
Erosion Control Inspection Residential Passed 01/03/2025
Misc
Resolved
01/03/2025
- OK AT TIME OF INSPECTION
Documents & Images
Date Uploaded File Type Document Name
03/26/2024 HT #185 - ENGINEERED PLANS
03/26/2024 Application Form HT #185 - PERMIT APP
03/26/2024 HT #185 - PLOT PLAN
03/26/2024 HT #185 - TRUSS DETAILS
03/26/2024 HT #185 - TRUSS LAYOUT
04/02/2024 Approved Plans APPROVED PLANS
04/02/2024 Plans APPROVED PLOT PLAN
04/02/2024 Approved Plans APPROVED TRUSS LAYOUT
04/02/2024 Approved Plans APPROVED TRUSS PACKAGE
04/02/2024 Permit Codes Residential Plan Review
04/03/2024 Permit DS Building Permit
04/03/2024 Receipt Receipt for transaction:2024-002126
04/15/2024 3RD Party Insp Report THIRD PARTY INSPECTION
04/24/2024 HT #185 - ENGINEERED PLANS
04/24/2024 HT #185 - PLOT PLAN
04/24/2024 HT #185 - TRUSS DETAILS
04/25/2024 HT #185 - TRUSS LAYOUT
04/25/2024 Approved Plans APPROVED REVISED PLANS
04/25/2024 Plot Plan approved revised plot plan
04/25/2024 Approved Plans APPROVED STRUCTUAL PLANS
04/25/2024 Approved Plans APPROVED TRUSS LAYOUT
04/25/2024 Approved Plans APPROVED TRUSS PACKAGE
05/03/2024 Letter INSPECTION SUMMARY
05/03/2024 Letter INSPECTION SUMMARY
05/08/2024 Letter INSPECTION SUMMARY
05/20/2024 Letter INSPECTION SUMMARY
05/24/2024 LOT 185 FINAL 5-23-24
05/28/2024 Plot Plan APPROVED UPDATED PLOT PLAN
06/11/2024 Letter INSPECTION SUMMARY
07/24/2024 Letter INSPECTION SUMMARY
07/24/2024 Letter INSPECTION SUMMARY
07/24/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/31/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/10/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/27/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/01/2024 Letter INSPECTION SUMMARY
10/02/2024 Letter INSPECTION SUMMARY
10/03/2024 Certificate/License Codes Temporary Certificate of Occupancy
10/03/2024 Receipt Receipt for transaction:2024-008076
12/02/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter Codes 10 Day Letter
12/04/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/04/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/04/2024 Receipt Receipt for transaction:2024-009337
01/03/2025 Letter Field Certificate of Occupancy
01/03/2025 Letter Codes Final Certificate of Occupancy
01/03/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home