Permit Application Status

PRRES20240573


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20240573
Building Permit - Residential
Certificate of Occupancy
NEW DUPLEX
NEW DUPLEX. UNFINISHED BASEMENT. ROOF TRUSSES. STOP WORK ORDER generated on 04/25/2024 12:00 AM by username 'Dustin Agcopra'. STOP WORK ORDER removed on 04/25/2024 12:00 AM by username 'Dustin Agcopra'.
02/09/2024
02/16/2024
08/13/2024
10/16/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
JASONH@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Duplex $2,905.65 $2,905.65 Paid 02/16/2024
Water Tap Fee $7,520.00 $7,520.00 Paid 02/16/2024
Water Meter Fee $1,360.92 $1,360.92 Paid 02/16/2024
Sanitary Sewer Development Fee $4,318.00 $4,318.00 Paid 02/16/2024
Right of Way Permit Fee $85.00 $85.00 Paid 02/16/2024
Residential Excise Tax Fee $1,240.32 $1,240.32 Paid 02/16/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 07/24/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 07/25/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 08/19/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 09/25/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 10/08/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 10/14/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 3/20/2024 03/20/2024
Miscellaneous Correction
Informational
03/20/2024
Erosion control is in place and must be maintained until CofO
Footing Inspection - Residential Passed 3/21/2024 03/21/2024
Miscellaneous Correction
Informational
03/21/2024
Footing was passed by a third party. Piers were not mentioned in the footing report
Sewer Service Inspection - R Passed 4/5/2024 04/05/2024
Water Service Inspection - R Passed 4/8/2024 4/8/2024 04/08/2024
Underslab Plumbing Inspection - Residential Passed 4/12/2024 4/12/2024 04/12/2024
Erosion Control Inspection Residential Passed 04/25/2024
Miscellaneous Correction
Informational
03/20/2024
Erosion control is in place and must be maintained until CofO
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/25/2024
4-25-24 Dustin A, EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Failed 5/2/2024 5/2/2024 05/02/2024
Miscellaneous Correction
Corrective Action Required
05/02/2024
Garage 5/8 inch anchor bolts are not installed. Ok to cover exterior of garage with siding only. This inspection was for garage portal only This is a partial inspection
Rated Assembly Inspection Partial 5/14/2024 5/14/2024 05/14/2024
Miscellaneous Correction
Corrective Action Required
05/14/2024
Rated assembly passed for both units. This is a partial pass. Screw pattern will need to be scheduled under rated assembly inspection
Electrical Service Inspection Passed 5/14/2024 5/14/2024 05/14/2024
Gas Service Inspection - Residential Passed 5/14/2024 5/14/2024 05/14/2024
All Rough Inspection - Residential Failed 5/14/2024 5/14/2024 05/14/2024
Miscellaneous Correction
Resolved
05/14/2024
Garage 5/8 inch anchor bolts are not installed. Ok to cover exterior of garage with siding only. This inspection was for garage portal only This is a partial inspection
Miscellaneous Correction
Corrective Action Required
05/14/2024
3737 and 3735 SW Knoxville. All rough 3737 -Garage 5/8 anchor bolts are not installed -Mechanical vent pipe in garage ceiling is not completed -Fire block the top of chase in garage better -Garage S/E corner is not completed -Fire block top of chase between pantry and dining room -Fire block hole in entry closet at sole plate -Address cut joist above entry closet -Have engineer address where ceiling/floor joist have been cut on the ends where attached to the Ibeam in the dining room -Mechanical needs to have nail protection two inches above and below the top and sole plate -Double 2x4 studs are not installed at the door of garage to owners entry -Install all LSTA straps -Electrical box at patio is not fully installed -Fire blocking is broken out above the wall dining room to refrigerator -Joist hanger above basement north window is not installed correctly 3735 -Garage 5/8 anchors bolts are not installed -Garage North side sole plate does not completely rest on the concrete foundation wall -Nail garage S/W corner to code Fire block top of chase between pantry and dining room -Protection all mechanical two inches up and down from sole and top plate -Fire block hole in floor sheathing at kitchen sink -Electrical is not properly attached at great room S/E window -Install all LSTA straps -Basement south wall needs anchors to be in the middle 1/3 of sole plate -One nail is missing in the double joist hanger by the basement stairs
All Rough Inspection - Residential Failed 5/17/2024 5/17/2024 05/17/2024
Miscellaneous Correction
Resolved
05/17/2024
3737 and 3735 SW Knoxville. All rough 3737 -Garage 5/8 anchor bolts are not installed -Mechanical vent pipe in garage ceiling is not completed -Fire block the top of chase in garage better -Garage S/E corner is not completed -Fire block top of chase between pantry and dining room -Fire block hole in entry closet at sole plate -Address cut joist above entry closet -Have engineer address where ceiling/floor joist have been cut on the ends where attached to the Ibeam in the dining room -Mechanical needs to have nail protection two inches above and below the top and sole plate -Double 2x4 studs are not installed at the door of garage to owners entry -Install all LSTA straps -Electrical box at patio is not fully installed -Fire blocking is broken out above the wall dining room to refrigerator -Joist hanger above basement north window is not installed correctly 3735 -Garage 5/8 anchors bolts are not installed -Garage North side sole plate does not completely rest on the concrete foundation wall -Nail garage S/W corner to code Fire block top of chase between pantry and dining room -Protection all mechanical two inches up and down from sole and top plate -Fire block hole in floor sheathing at kitchen sink -Electrical is not properly attached at great room S/E window -Install all LSTA straps -Basement south wall needs anchors to be in the middle 1/3 of sole plate -One nail is missing in the double joist hanger by the basement stairs
Miscellaneous Correction
Corrective Action Required
05/17/2024
3737 and 3735 SW Knoxville. All rough (2) 3737 Garage S/E corner is not completed (corners must consist of three studs and bare on the sole plate and up against the top plate) Garage to house doors needs electrical next to it to be replaced and secured Fire block hole in entry closet at sole plate Have engineer address where ceiling/floor joist have been cut on the ends where attached to the Ibeam in the dining room Electrical at kitchen wall and above kitchen are not fully installed 3735 Garage North side sole plate does not completely rest on the concrete foundation wall
Erosion Control Inspection Residential Failed 5/17/2024 05/17/2024
Miscellaneous Correction
Informational
04/25/2024
Erosion control is in place and must be maintained until CofO
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/17/2024
4-25-24 Dustin A, EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Miscellaneous Correction
Corrective Action Required
05/17/2024
Some silt fence at the front of the lot has been damaged and needs to be replaced or repaired. Full erosion control must be maintained until CofO
All Rough Inspection - Residential Passed 5/21/2024 5/21/2024 05/21/2024
Miscellaneous Correction
Corrective Action Required
05/17/2024
3737 and 3735 SW Knoxville. All rough (2) 3737 Garage S/E corner is not completed (corners must consist of three studs and bare on the sole plate and up against the top plate) Garage to house doors needs electrical next to it to be replaced and secured Fire block hole in entry closet at sole plate Have engineer address where ceiling/floor joist have been cut on the ends where attached to the Ibeam in the dining room Electrical at kitchen wall and above kitchen are not fully installed 3735 Garage North side sole plate does not completely rest on the concrete foundation wall
Rated Assembly Inspection Failed 5/24/2024 5/24/2024 05/24/2024
Miscellaneous Correction
Corrective Action Required
05/14/2024
Rated assembly passed for both units. This is a partial pass. Screw pattern will need to be scheduled under rated assembly inspection
Miscellaneous Correction
Corrective Action Required
05/24/2024
3735 as numbered on the exterior of the dwelling -Kitchen screw pattern was not complete. -Screw pattern inspection was stopped at the kitchen This was a partial screw pattern only and was intended for unit 3735 as stated on the exterior of the dwelling Not ready for inspection
Rated Assembly Inspection Passed 5/28/2024 5/28/2024 05/28/2024
Miscellaneous Correction
Resolved
05/28/2024
Rated assembly passed for both units. This is a partial pass. Screw pattern will need to be scheduled under rated assembly inspection
Miscellaneous Correction
Resolved
05/28/2024
3735 as numbered on the exterior of the dwelling -Kitchen screw pattern was not complete. -Screw pattern inspection was stopped at the kitchen This was a partial screw pattern only and was intended for unit 3735 as stated on the exterior of the dwelling Not ready for inspection
Driveway Inspection Partial 6/5/2024 06/05/2024
Misc
Informational
06/05/2024
6-5-24 Dustin A, DW is formed and compacted to city specs. Approved to pour
Sidewalk Inspection Partial 6/5/2024 06/05/2024
Misc
Informational
06/05/2024
6-5-24 Dustin A, SW has been formed and compacted to city specs. Approved to pour
Sidewalk Inspection Passed 6/12/2024 6/12/2024 06/12/2024
Misc
Informational
06/12/2024
6-12-24 Dustin A, SW is poured to city specs and slopes are in compliance. Passed
Driveway Inspection Passed 6/12/2024 6/12/2024 06/12/2024
Misc
Informational
06/05/2024
6-5-24 Dustin A, DW is formed and compacted to city specs. Approved to pour 6-12-24 Dustin A, Dw is poured to city specs and slopes are in compliance. Passed
Erosion Control Inspection Residential Partial 7/10/2024 07/10/2024
Miscellaneous Correction
Resolved
07/10/2024
Erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Resolved
07/10/2024
Some silt fence at the front of the lot has been damaged and needs to be replaced or repaired. Full erosion control must be maintained until CofO
Miscellaneous Correction
Informational
07/10/2024
Full erosion control measures are in place and must be maintained until CofO
Piers/Caissons Inspection - Residential Not Ready 7/10/2024 07/10/2024
Miscellaneous Correction
Corrective Action Required
07/10/2024
Only one of the two units on the permit were ready for inspection. Unit 3735 back deck piers passed If you only need one unit inspection done please specify which one is ready Not ready fee added
Piers/Caissons Inspection - Residential Passed 7/12/2024 07/12/2024
Miscellaneous Correction
Resolved
07/12/2024
Only one of the two units on the permit were ready for inspection. Unit 3735 back deck piers passed If you only need one unit inspection done please specify which one is ready Not ready fee added
Erosion Control Inspection Residential Partial 7/18/2024 07/18/2024
Miscellaneous Correction
Resolved
07/18/2024
Full erosion control measures are in place and must be maintained until CofO
Miscellaneous Correction
Informational
07/18/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 7/19/2024 7/19/2024 07/19/2024
Miscellaneous Correction
Corrective Action Required
07/19/2024
3735 and 3737 SW Knoxville. Occupancy 3735 security light not installed on backyard side of the property Landing pad not installed at the bottom of the stairwell in backyard Light switch cover in 1/2 bathroom is not installed Can not verify fire blocking at south chase in garage due to trash being in the way Fire block gaps in north side chase in garage Breaker #20 in panel is not marked Hot water heater breaker needs a lock out installed First to second riser going upstairs from the main entry has a greater height than the code 3/8 of an inch difference 3737 Landing pad not installed at the bottom of the stairwell in backyard Check slope on first step up from the main entry (no more than 2% by code)going up stairs Fire block hole in floor to basement under kitchen island Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Seal top of a/c disconnects Final grade is not ready for plot plan inspection Pay $75 fee associated with this permit
Erosion Control Inspection Residential Partial 7/19/2024 07/19/2024
Miscellaneous Correction
Resolved
07/19/2024
Full erosion control measures are in place and must be maintained until CofO
Miscellaneous Correction
Informational
07/19/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 7/23/2024 7/23/2024 07/23/2024
Miscellaneous Correction
Resolved
07/23/2024
3735 and 3737 SW Knoxville. Occupancy 3735 security light not installed on backyard side of the property Landing pad not installed at the bottom of the stairwell in backyard Light switch cover in 1/2 bathroom is not installed Can not verify fire blocking at south chase in garage due to trash being in the way Fire block gaps in north side chase in garage Breaker #20 in panel is not marked Hot water heater breaker needs a lock out installed First to second riser going upstairs from the main entry has a greater height than the code 3/8 of an inch difference 3737 Landing pad not installed at the bottom of the stairwell in backyard Check slope on first step up from the main entry (no more than 2% by code)going up stairs Fire block hole in floor to basement under kitchen island Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Seal top of a/c disconnects Final grade is not ready for plot plan inspection Pay $75 fee associated with this permit
Miscellaneous Correction
Corrective Action Required
07/23/2024
3735 and 3737 SW Knoxville. Occupancy (2) 3735 Landing pad not installed at the bottom of the stairway in backyard Fire block gaps in north side chase in garage First to second riser going upstairs from the main entry has a greater height than the code 3/8 of an inch difference (check slope of first riser since alternating tread height) 3737 Landing pad not installed at the bottom of the stairway in backyard Fire block hole in floor to basement under kitchen island Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing Final grading needs to be completed before plot plan inspection can be conducted Pay $75 fee associated with this permit
Occupancy Inspection - Codes Residential Ready for Temp CO 7/24/2024 7/24/2024 07/24/2024
Miscellaneous Correction
Resolved
07/24/2024
3735 and 3737 SW Knoxville. Occupancy (2) 3735 Landing pad not installed at the bottom of the stairway in backyard Fire block gaps in north side chase in garage First to second riser going upstairs from the main entry has a greater height than the code 3/8 of an inch difference (check slope of first riser since alternating tread height) 3737 Landing pad not installed at the bottom of the stairway in backyard Fire block hole in floor to basement under kitchen island Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing Final grading needs to be completed before plot plan inspection can be conducted Pay $75 fee associated with this permit
Miscellaneous Correction
Corrective Action Required
07/24/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted Pay $75 fee associated with this permit TCO passed for both units
Erosion Control Inspection Residential Failed 8/19/2024 08/19/2024
Miscellaneous Correction
Resolved
08/19/2024
Full erosion control measures are in place and must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/19/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -Storm drain located at the S/E corner needs to be protected -Install erosion control along the south side up against sod
Occupancy Inspection - Codes Residential Ready for Temp CO 8/19/2024 08/19/2024
Miscellaneous Correction
Resolved
08/19/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted Pay $75 fee associated with this permit TCO passed for both units
Miscellaneous Correction
Corrective Action Required
08/19/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted
Occupancy Inspection - Codes Residential Ready for Temp CO 8/23/2024 08/23/2024
Miscellaneous Correction
Corrective Action Required
08/19/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted Second TCO extension request was sent in by the builder. On site field inspection notes that progress is being made to finish the exterior.
Erosion Control Inspection Residential Partial 9/5/2024 09/05/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
09/05/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -Storm drain located at the S/E corner needs to be protected -Install erosion control along the south side up against sod
Miscellaneous Correction
Informational
09/05/2024
Full erosion control measures are in place and must be maintained until CofO
Plot Plan Inspection Passed 9/5/2024 09/05/2024
Occupancy Inspection - Codes Residential Not Ready 9/27/2024 09/27/2024
Miscellaneous Correction
Corrective Action Required
08/23/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted Second TCO extension request was sent in by the builder. 10 day notice of violation was sent to the builder because no response to a TCO extension request was received 09/27/24 KBEARD
Erosion Control Inspection Residential Passed 10/9/2024 10/09/2024
Miscellaneous Correction
Resolved
10/09/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Ready for Temp CO 10/11/2024 10/11/2024
Miscellaneous Correction
Resolved
10/11/2024
Both units sod, splash pads and sump pump extensions are not installed Deck is missing a joist hanger Deck joist hanger is missing nails Final grading needs to be completed before plot plan inspection can be conducted Second TCO extension request was sent in by the builder. 10 day notice of violation was sent to the builder because no response to a TCO extension request was received 09/27/24 KBEARD
Miscellaneous Correction
Corrective Action Required
10/11/2024
3735 and 3737 SW Knoxville. Occupancy (2) 3737 uncover water meter lid Both units Deck is missing a joist hanger Deck joist hanger is missing Tighten 1/2 inch bolts on cedar beam to rim joist connection
Occupancy Inspection - Codes Residential Full C of O 10/16/2024 10/16/2024 10/16/2024
Miscellaneous Correction
Resolved
10/16/2024
3735 and 3737 SW Knoxville. Occupancy (2) 3737 uncover water meter lid Both units Deck is missing a joist hanger Deck joist hanger is missing Tighten 1/2 inch bolts on cedar beam to rim joist connection
Documents & Images
Date Uploaded File Type Document Name
02/09/2024 OS # 83 - PERMIT APP
02/15/2024 Approved Plans APPROVED PLANS
02/15/2024 Permit Codes Residential Plan Review
02/16/2024 Plot Plan APPROVED PLOT PLAN
02/16/2024 Approved Plans APPROVED TRUSS PACKAGE
02/16/2024 Approved Plans APPROVED TRUSS LAYOUT
02/16/2024 Permit Codes Residential Plan Review
02/16/2024 Permit DS Building Permit
02/16/2024 Receipt Receipt for transaction:2024-000919
03/20/2024 Letter INSPECTION SUMMARY
03/20/2024 M L Crose 3735 & 3737 SW Knoxville Ct LSMO Osage Lot 83 Clayton P 2024-0573 3rd Party Footing Inspection Report 3-20-24
03/21/2024 Letter INSPECTION SUMMARY
04/05/2024 Letter INSPECTION SUMMARY
04/08/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/25/2024 Letter Stop Work Order
04/25/2024 Letter Stop Work Order
04/25/2024 Letter INSPECTION SUMMARY
05/02/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/17/2024 Letter INSPECTION SUMMARY
05/17/2024 Letter INSPECTION SUMMARY
05/21/2024 Engineer Report/Study ENGINEER FRAMING REPORT
05/21/2024 Letter INSPECTION SUMMARY
05/24/2024 Letter INSPECTION SUMMARY
05/28/2024 Letter INSPECTION SUMMARY
06/05/2024 Letter INSPECTION SUMMARY
06/05/2024 Letter INSPECTION SUMMARY
06/12/2024 Letter INSPECTION SUMMARY
06/12/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/12/2024 Letter INSPECTION SUMMARY
07/18/2024 Letter INSPECTION SUMMARY
07/19/2024 Letter INSPECTION SUMMARY
07/19/2024 Letter INSPECTION SUMMARY
07/23/2024 Letter INSPECTION SUMMARY
07/24/2024 Receipt Receipt for transaction:2024-006143
07/24/2024 Letter INSPECTION SUMMARY
07/25/2024 Certificate/License Codes Temporary Certificate of Occupancy
07/25/2024 Receipt Receipt for transaction:2024-006203
08/19/2024 OS #83 - TCO Extension App
08/19/2024 Letter INSPECTION SUMMARY
08/19/2024 Letter INSPECTION SUMMARY
08/19/2024 Letter INSPECTION SUMMARY
08/19/2024 Certificate/License Codes Temporary Certificate of Occupancy
08/19/2024 Receipt Receipt for transaction:2024-006994
08/22/2024 OS 83 TCOExtension Request Form 8_22
08/23/2024 Letter INSPECTION SUMMARY
09/04/2024 Plot Plan approved as graded plot plan
09/05/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/25/2024 OS 83 TCOExtension Request Form 9_25
09/25/2024 Certificate/License Codes Temporary Certificate of Occupancy
09/25/2024 Receipt Receipt for transaction:2024-007899
09/27/2024 Letter Codes 10 Day Letter
09/27/2024 Letter INSPECTION SUMMARY
10/08/2024 OS 83 TCOExtension Request Form 10_8_24
10/08/2024 Receipt Receipt for transaction:2024-008194
10/08/2024 OS 83 ASBUILT
10/08/2024 Plot Plan approved as graded plot plan
10/09/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/14/2024 Certificate/License Codes Temporary Certificate of Occupancy
10/14/2024 Receipt Receipt for transaction:2024-008307
10/16/2024 Letter Field Certificate of Occupancy
10/16/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home