Permit Application Status

PRRES20204351


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20204351
Building Permit - Residential
Certificate of Occupancy
MCFARLAND CUSTOM BUILDERS INC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED DECK STOP WORK ORDER generated on 02/23/2021 12:00 AM by username 'John Morris'. STOP WORK ORDER removed on 02/26/2021 12:00 AM by username 'John Morris'. HOLD PUT ON PERMIT UNTIL PLUMBER IS ADDED Brandon Kalwei 09/13/2021 3:51 PM
11/17/2020
12/03/2020
05/23/2021
11/11/2022
Locations
Contacts
MCFARLAND CUSTOM BUILDERS INC, Address:9601 NE BARRY RD STE 130  
MCFARLAND CUSTOM BUILDERS, Address:P O BOX 25285, Phone:(816) 215-1660  
MARISA@MCFARLANDKC.COM  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
JOE KILOWATT INC, Address:6506 ROYAL, Phone:(816) 792-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 11/30/2020 12/03/2020
Dylan Eppert
06 Designate use of each room or space
Corrective Action Required
11/24/2020

Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space. PLEASE LABEL ALL LUMBING FIXTURES i.e(SINKS, TOILETS, SHOWERS, UTILITEY SINKS, WET BARS ECT.) THINGS OF THAT NATURE AS WE CHARGE $30.00 A TRAP AND DON'T WANT TO OVER/UNDER CHARGE YOU. OPTIONAL GENERAL IS NOT ACCEPTED AS THE HOUSE PLANS MUST MATCH THE PLOT PLAN. PLEASE ENSURE THAT EVERYTHING ON THE PLAN IS SOMETHING YOU WILL BE CONSTRUCTING.
Miscellaneous Correction
Corrective Action Required
11/24/2020

ALL PAGES OF THE HOUSE PLAN MUST REFERENCE THE 2018 IRC BUILD CODE NOT THE 2012 IRC BUILDING CODE.
Miscellaneous Correction
Corrective Action Required
11/24/2020

YOUR PLUMBER MUST HAVE AN ACTIVE BUSINESS LICENSE THROUGH THE CITY OF LEE'S SUMMIT BEFORE I CAN ISSUE THE BUILDING PERMIT.
Plot Plan Review Approved 11/30/2020 11/24/2020
Dylan Eppert
Signed and sealed
Corrective Action Required
11/24/2020

Plot plan must drawn, signed, and sealed by a licensed surveyor or engineer.
Building elevations
Corrective Action Required
11/24/2020

Existing and finished elevations at building footprint corners must be provided on the plot plan.
Lot elevations
Corrective Action Required
11/24/2020

Existing and finish elevations at all property corners must be provided on the plot plan.
Curb elevation
Corrective Action Required
11/24/2020

The elevation at top of curb at end of driveway and at lot corners adjacent to street must be provided on the plot plan.
Garage elevation
Corrective Action Required
11/24/2020

The garage floor elevation must be provided on the plot plan.
Spot elevations
Corrective Action Required
11/24/2020

Spot elevations and/or drainage flow arrows shall be provided throughout the lot.
Basement opening elevations
Corrective Action Required
11/24/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan.
Contours, spot elevations and arrows
Corrective Action Required
11/24/2020

Contours, spot elevations and drainage flow arrows (as required) shall be provided on the lot.
Basement egress
Corrective Action Required
11/24/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Plot Plan Review Rejected 11/20/2020 11/20/2020
Dylan Eppert
Signed and sealed
Corrective Action Required
11/20/2020

Plot plan must drawn, signed, and sealed by a licensed surveyor or engineer.
Building elevations
Corrective Action Required
11/20/2020

Existing and finished elevations at building footprint corners must be provided on the plot plan.
Lot elevations
Corrective Action Required
11/20/2020

Existing and finish elevations at all property corners must be provided on the plot plan.
Curb elevation
Corrective Action Required
11/20/2020

The elevation at top of curb at end of driveway and at lot corners adjacent to street must be provided on the plot plan.
Garage elevation
Corrective Action Required
11/20/2020

The garage floor elevation must be provided on the plot plan.
Spot elevations
Corrective Action Required
11/20/2020

Spot elevations and/or drainage flow arrows shall be provided throughout the lot.
Basement opening elevations
Corrective Action Required
11/20/2020

Minimum Building Opening Elevation (MBOE) and location on structure must be provided on the plot plan.
Contours, spot elevations and arrows
Corrective Action Required
11/20/2020

Contours, spot elevations and drainage flow arrows (as required) shall be provided on the lot.
Basement egress
Corrective Action Required
11/20/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Rejected 11/20/2020 11/20/2020
Dylan Eppert
06 Designate use of each room or space
Corrective Action Required
11/20/2020

Designate use of each room or space including but not limited to; basement storage, garages, and attic areas intended for storage space. PLEASE LABEL ALL PLUMBING FIXTURES i.e(SINKS, TOILETS, SHOWERS, UTILITEY SINKS, WET BARS ECT.) THINGS OF THAT NATURE AS WE CHARGE $30.00 A TRAP AND DON'T WANT TO OVER/UNDER CHARGE YOU. OPTIONAL GENERAL IS NOT ACCEPTED AS THE HOUSE PLANS MUST MATCH THE PLOT PLAN. PLEASE ENSURE THAT EVERYTHING ON THE PLAN IS SOMETHING YOU WILL BE CONSTRUCTING.
Miscellaneous Correction
Corrective Action Required
11/20/2020

ALL PAGES OF THE HOUSE PLAN MUST REFERENCE THE 2018 IRC BUILD CODE NOT THE 2012 IRC BUILDING CODE.
Miscellaneous Correction
Corrective Action Required
11/20/2020

YOUR PLUMBER MUST HAVE AN ACTIVE BUSINESS LICENSE THROUGH THE CITY OF LEE'S SUMMIT BEFORE I CAN ISSUE THE BUILDING PERMIT.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,415.76 $1,415.76 Paid 12/03/2020
8331507-Sewer Connection Fee $540.00 $540.00 Paid 12/03/2020
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 12/03/2020
8350015-Water Meter Fee $455.54 $455.54 Paid 12/03/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 12/03/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/03/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 08/05/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 08/05/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 08/05/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 08/08/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 11/04/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 11/04/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 12/8/2020 12/08/2020
Misc
Corrective Action Required
12/08/2020
Immediate street cleanup required
Footing Inspection - Residential Passed 12/23/2020 12/23/2020
Erosion Control Inspection Residential Failed 2/21/2021 02/03/2021
Misc
Corrective Action Required
12/08/2020
-Establish erosion control methods within 48 hours -remove debris from curb/gutter -post site address -no further inspections until issues are resolved
Erosion Control Inspection Residential Failed - Stop Work 2/23/2021 02/23/2021
Misc
Corrective Action Required
02/03/2021
-Establish erosion control methods around lot perimeter -remove debris from curb/gutter -post site address -establish and maintain gravel filter -no further inspections until issues are resolved STOP WORK ORDER ISSUED 02/23/2021 FOR LACK OF COMPLIANCE WITH EROSION CONTROL INSPECTION REPORTS
Erosion Control Inspection Residential Passed 2/3/2021 02/26/2021
Misc
Resolved
02/26/2021
-Establish erosion control methods around lot perimeter -remove debris from curb/gutter -post site address -establish and maintain gravel filter -no further inspections until issues are resolved STOP WORK ORDER ISSUED 02/23/2021 FOR LACK OF COMPLIANCE WITH EROSION CONTROL INSPECTION REPORTS
Miscellaneous Inspection Failed 2/26/2021 02/26/2021
Misc
Corrective Action Required
02/26/2021
Post site address
Sewer Service Inspection - R Passed 3/2/2021 (1:00) 3/2/2021 03/02/2021
Water Service Inspection - R Partial 3/2/2021 3/2/2021 03/02/2021
Misc
Informational
03/02/2021
From structure to metallic connection customer side of meter approved
Water Service Inspection - R Passed 3/4/2021 (1:00) 3/4/2021 03/04/2021
Misc
Resolved
03/04/2021
From structure to metallic connection customer side of meter approved
Underslab Plumbing Inspection - Residential Failed 3/5/2021 3/5/2021 03/04/2021
Misc
Corrective Action Required
03/04/2021
Complete installation of under slab interior drain tile around perimeter of foundation and connect to sump pit
Erosion Control Inspection Residential Failed 3/3/2021 03/05/2021
Misc
Corrective Action Required
03/05/2021
Excavation spoils from foundation installation is being removed by ABI corporation. Trucks are traveling through the green space behind the property, any damage to the green space will require restoration to original condition. Mud and debris are being tracked from river trail road through the subdivision nearly to Pryor Road, I have notified Carla with ABI that immediate Street clean up is required
Underslab Plumbing Inspection - Residential Passed 3/17/2021 3/17/2021 03/17/2021
Misc
Resolved
03/17/2021
Complete installation of under slab interior drain tile around perimeter of foundation and connect to sump pit
Erosion Control Inspection Residential Failed 5/18/2021 05/18/2021
Misc
Corrective Action Required
03/05/2021
Excavation spoils from foundation installation is being removed by ABI corporation. Trucks are traveling through the green space behind the property, any damage to the green space will require restoration to original condition. Mud and debris are being tracked from river trail road through the subdivision nearly to Pryor Road, I have notified Carla with ABI that immediate Street clean up is required
Misc
Corrective Action Required
05/18/2021
Erosion control requires continuous maintenance. Repair damaged areas within 48 hours no further inspections until issues are resolved
Erosion Control Inspection Residential Failed 8/6/2021 8/6/2021 08/06/2021
Misc
Resolved
08/06/2021
Misc
Resolved
08/06/2021
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/06/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. EROSION CONTROL REQUIRED AT FRONT OF LOT, SILT FENCE REQUIRES CONTINUOUS MAINTENANCE MAINTAIN OVERGROWN WEEDS AND VEGETATION ON LOT
Erosion Control Inspection Residential Failed 9/9/2021 9/9/2021 09/09/2021
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/06/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. EROSION CONTROL REQUIRED AT FRONT OF LOT, SILT FENCE REQUIRES CONTINUOUS MAINTENANCE MAINTAIN OVERGROWN WEEDS AND VEGETATION ON LOT
All Rough Inspection - Residential Not Ready 1/7/2022 1/7/2022 01/07/2022
Misc
Corrective Action Required
01/07/2022
INSPECTION DENIED DUE TO DEFICIENT EROSION CONTROL AND NO PREMISES IDENTIFICATION POSTED Mitchell Schwarz 01/07/2022 10:31 AM
Erosion Control Inspection Residential Failed 1/7/2022 01/07/2022
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
09/09/2021
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. EROSION CONTROL REQUIRED AT FRONT OF LOT, SILT FENCE REQUIRES CONTINUOUS MAINTENANCE MAINTAIN OVERGROWN WEEDS AND VEGETATION ON LOT
Misc
Corrective Action Required
01/07/2022
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
01/07/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM5 ESC INSP DENIED
Corrective Action Required
01/07/2022
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
Gas Service Inspection - Residential Failed 1/7/2022 01/07/2022
Misc
Corrective Action Required
01/07/2022
Inspection denied due to insufficient erosion control and no premise identification.
All Rough Inspection - Residential Failed 1/11/2022 1/11/2022 01/11/2022
Misc
Resolved
01/11/2022
Miscellaneous Correction
Corrective Action Required
01/11/2022
- Nail straps on portal framing per code - Fb penetration double side sill - Nail exterior sheeting per code, bay window - Nail off joist hangers at I-beam in pantry - Through bolts on I- beam not to plan’s - Provide joist hanger for double LVL over island - Nail off corner dining room - Land all electrical wiring - Nail off corner pantry - Security blocking back door, strike plate - Fur out DWV at back door - Address over bored joist living room - Nail off corner by fire place - Address over bored studs right of fire place - Provide joist hangers at foyer and hearth room - Provide 2 1200 lb straps bay window per plan - Complete though bolts above formal dining - Fire block chase above dining room window - Address over bored joist front closet - Fur out pipes in front closet - Strap stud breaks sides windows stair landing - Snow block front bathroom by stairs - Address siding gaps bedroom 4 at WIC - Snow block owner suite and bedroom 2 - Provide joist hangers for joist over 4’ basement - Insulate and block cantilevers in basement
Gas Service Inspection - Residential Passed 1/11/2022 1/11/2022 01/11/2022
Misc
Corrective Action Required
01/07/2022
Inspection denied due to insufficient erosion control and no premise identification.
All Rough Inspection - Residential Failed 1/18/2022 1/18/2022 01/18/2022
Miscellaneous Correction
Corrective Action Required
01/11/2022
- Nail exterior sheeting per code, bay window - Nail off joist hangers at I-beam in pantry - Through bolts on I- beam not to plan’s - Nail off corner dining room - Land all electrical wiring - Nail off corner pantry - Security blocking back door, strike plate - Fur out DWV at back door - Address over bored joist living room - Nail off corner by fire place - Address over bored studs right of fire place - Provide 2 1200 lb straps bay window per plan - Complete though bolts above formal dining - Address over bored joist front closet - Fur out pipes in front closet - Strap stud breaks sides windows stair landing - Address siding gaps bedroom 4 at WIC - Provide joist hangers for joist over 4’ basement - Insulate and block cantilevers in basement
All Rough Inspection - Residential Failed 1/24/2022 1/24/2022 01/24/2022
Miscellaneous Correction
Corrective Action Required
01/18/2022
NO FURTHER INSPECTIONS UNTIL PLUMBER ADDED TO PERMIT Mitchell Schwarz 1/24/22 - Nail exterior sheeting per code/plans, back windows - Through bolts on I- beam not tightened -fireblock furr outs for in garage - Land all electrical wiring upstairs master bedroom - Address over bored joist living room - Address over bored studs right of fire place - Provide 2 1200 lb straps bay window per plan - Complete though bolts above formal dining (tighten) - Address over bored joist front closet - fireblock Fur out pipes in front closet -repair broken window back of house - Provide stud pack at basement stairs per plan
Electrical Service Inspection Passed 1/24/2022 1/24/2022 01/24/2022
All Rough Inspection - Residential Not Ready 2/3/2022 2/3/2022 02/03/2022
Miscellaneous Correction
Corrective Action Required
01/24/2022
- Nail exterior sheeting per code/plans, back windows cs-pf - Through bolts on I- beam not tightened -fireblock furr outs for in garage - Address over bored joist living room - Address over bored studs right of fire place - Provide 2 1200 lb straps bay window per plan (cs-pf) - Complete though bolts above formal dining (tighten) - Address over bored joist front closet - fireblock Fur out pipes in front closet -repair broken window back of house - Provide stud pack at basement stairs per plan
All Rough Inspection - Residential Failed 2/7/2022 2/7/2022 02/07/2022
Miscellaneous Correction
Corrective Action Required
02/03/2022
- Nail exterior sheeting per code/plans, back windows cs-pf -fireblock furr outs for in garage - Address over bored joist living room - Address over bored studs right of fire place - Provide 2 1200 lb straps bay window per plan (cs-pf) - Address over bored joist front closet - fireblock Fur out pipes in front closet
All Rough Inspection - Residential Failed 2/17/2022 2/17/2022 02/17/2022
Miscellaneous Correction
Corrective Action Required
02/07/2022
-provide 2x6 stud wall at rear hearth room exterior wall per plan (curve wall) -provide stud support per plan 8 2x6 left side and 4 2x6 right exterior corner -provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 -rear dining room provide cspf per plan (frame, nail, strap) -fireblock furr outs for in garage - Address over bored joist living room (fix per engineer and provide nailing schedule - Address over bored studs right of fire place (install stud shoe) - Address over bored joist front closet - fireblock Fur out pipes in front closet
All Rough Inspection - Residential Failed 2/23/2022 2/23/2022 02/23/2022
Miscellaneous Correction
Corrective Action Required
02/17/2022
-provide 2x6 stud wall at rear hearth room exterior wall per plan (curve wall) -provide stud support per plan 8 2x6 left side and 4 2x6 right exterior corner -provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 -rear dining room provide cspf per plan (frame, nail, strap) -fireblock furr outs for in garage - Address over bored joist living room (fix per engineer and provide nailing schedule - Address over bored studs right of fire place (install stud shoe)
All Rough Inspection - Residential Failed 2/28/2022 2/28/2022 03/01/2022
Miscellaneous Correction
Corrective Action Required
02/23/2022
-provide 2x6 stud wall at rear hearth room exterior wall per plan (curve wall) -provide stud support per plan 8 2x6 left side and 4 2x6 right exterior corner -provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 -rear dining room provide cspf nailing per plan. Wood struct -fireblock furr outs for in garage - Address over bored joist living room (fix per engineer and provide nailing schedule - Address over bored studs right of fire place (install stud shoe)
All Rough Inspection - Residential Failed 3/1/2022 3/1/2022 03/01/2022
Miscellaneous Correction
Corrective Action Required
02/28/2022
-provide 2x6 stud wall at rear hearth room exterior wall per plan (curve wall) -provide stud support per plan 8 2x6 left side and 4 2x6 right exterior corner -provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 -CSPF EXTERIOR NAIL PATTERN WOOD STRUCTRUL SHEATHING TO BAND/RIM JOIST -INSPECTION FOR GB BRACED WALL METHOD -OKAY TO INSULATE DO NOT COVER ITEMS STILL NEEDING INSPECTION
All Rough Inspection - Residential Failed 3/30/2022 3/30/2022 03/30/2022
Miscellaneous Correction
Corrective Action Required
03/01/2022
-provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 have engineer address this -provide outlets per code at hearth room wall -OKAY TO INSULATE DO NOT COVER ITEMS STILL NEEDING INSPECTION
All Rough Inspection - Residential Passed 4/14/2022 4/14/2022 04/14/2022
Miscellaneous Correction
Resolved
04/14/2022
Upload engineer letter for approval -provide strapping per plans for beam -hearth room windows need to be framed per 3/S505 have engineer address this -provide outlets per code at hearth room wall -OKAY TO INSULATE DO NOT COVER ITEMS STILL NEEDING INSPECTION
Erosion Control Inspection Residential Failed 6/20/2022 6/20/2022 06/20/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
06/20/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. EROSION CONTROL REQUIRED AT FRONT OF LOT, SILT FENCE REQUIRES CONTINUOUS MAINTENANCE MAINTAIN OVERGROWN WEEDS AND VEGETATION ON LOT
Misc
Resolved
06/20/2022
DCM2 ESC DEFICIENT INSTALLATION
Resolved
06/20/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM5 ESC INSP DENIED
Resolved
06/20/2022
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/20/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -maintain gravel filter and overgrown vegetation Mitchell Schwarz 06/20/2022 2:23 PM
Driveway Inspection Partial 6/22/2022 6/22/2022 06/22/2022
Misc
Informational
06/22/2022
On Wednesday 6.22.2022 I performed a driveway inspection and pass the sub-grade to pour concrete
Sidewalk Inspection Partial 6/22/2022 6/22/2022 06/22/2022
Misc
Informational
06/22/2022
On 6.22.2022 Wednesday i performed a sidewalk inspection and pass the sub-grade to pour concrete.
Occupancy Inspection - Codes Residential Not Ready 8/3/2022 8/3/2022 08/03/2022
Misc
Corrective Action Required
08/03/2022
inspection denied conplete all trades for inspection no address posted no erosion control
Erosion Control Inspection Residential Failed 8/3/2022 08/03/2022
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/20/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -maintain gravel filter and overgrown vegetation Mitchell Schwarz 06/20/2022 2:23 PM
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
08/03/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. Mitchell Schwarz 08/03/2022 9:54 AM
Miscellaneous Inspection Passed 08/05/2022
Misc
Resolved
08/05/2022
Post site address
Occupancy Inspection - Codes Residential Failed 8/5/2022 08/05/2022
Misc
Resolved
08/05/2022
inspection denied conplete all trades for inspection no address posted no erosion control
Misc
Corrective Action Required
08/05/2022
-sod -as graded plot plan -address pending driveway and sidewalk inspections -gutters, splash block and sump pump discharge to extend 36” from foundation -address piers poured without inspection -pay all fees -add to be properly illuminated -attic access cover in garage -spark rings at kitchen outlets as required by code -complete lighting fixture in dining -face plates for island outlets -security screws at rear door -GFCI protection for laundry -install window in master bath -GFCI protection for dishwasher -open junction box at front stoop -guard rail at front stoop where required by code -address steps at front stoop greater than 3/8 difference -check water meter and all other exterior items at time of final grade and sod
Driveway Inspection Passed 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
06/22/2022
On Wednesday 6.22.2022 I performed a driveway inspection and pass the sub-grade to pour concrete 8.8.2022 Driveway appears to be compliant
Sidewalk Inspection Passed 8/8/2022 8/8/2022 08/08/2022
Misc
Informational
08/08/2022
8.8.2022 Sidewalk appears to be compliant
Piers/Caissons Inspection - Residential Passed 08/08/2022
Occupancy Inspection - Codes Residential Ready for Temp CO 8/8/2022 8/8/2022 08/08/2022
Misc
Corrective Action Required
08/05/2022
TCO until 9/8/22 -sod -as graded plot plan -gutters, splash block and sump pump discharge to extend 36” from foundation -pay all fees -spark rings at kitchen outlets as required by code -check water meter and all other exterior items at time of final grade and sod
Occupancy Inspection - Codes Residential Temporary C of O 08/08/2022
Misc
Corrective Action Required
08/08/2022
TCO until 9/8/22 -sod -obtain lawn irrigation permit -as graded plot plan -gutters, splash block and sump pump discharge to extend 36” from foundation -pay all fees -spark rings at kitchen outlets as required by code -check water meter and all other exterior items at time of final grade and sod
Plot Plan Inspection Passed 8/25/2022 08/25/2022
Occupancy Inspection - Codes Residential Ready for Temp CO 11/4/2022 11/4/2022 11/04/2022
Misc
Corrective Action Required
08/08/2022
-raise water meter well to grade -water meter to be 14-18" from meter to lid
Erosion Control Inspection Residential Passed 11/4/2022 11/04/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
11/04/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. -maintain gravel filter and overgrown vegetation Mitchell Schwarz 06/20/2022 2:23 PM
DCM2 ESC DEFICIENT INSTALLATION
Resolved
11/04/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. Mitchell Schwarz 08/03/2022 9:54 AM
Occupancy Inspection - Codes Residential Full C of O 11/11/2022 11/11/2022
Misc
Resolved
11/11/2022
-raise water meter well to grade -water meter to be 14-18" from meter to lid
Documents & Images
Date Uploaded File Type Document Name
11/17/2020 Application Form New Lee's Summit
11/18/2020 THE LEXINGTON II 2529 SW Rivertrail Rd
11/18/2020 Eagle Creek 673 Plot Plan
11/20/2020 Letter Codes Residential Plan Review
11/24/2020 Plot Plan APPROVED PLOT PLAN
12/03/2020 Plans APPROVED HOUSE PLAN
12/03/2020 Receipt Receipt for transaction:2020-007856
12/03/2020 Letter DS Building Permit
12/08/2020 Letter INSPECTION SUMMARY
12/23/2020 Letter INSPECTION SUMMARY
02/03/2021 Letter INSPECTION SUMMARY
02/23/2021 Letter Stop Work Order
02/26/2021 Letter INSPECTION SUMMARY
02/26/2021 Letter INSPECTION SUMMARY
03/02/2021 Letter INSPECTION SUMMARY
03/02/2021 Letter INSPECTION SUMMARY
03/04/2021 Letter INSPECTION SUMMARY
03/04/2021 Letter INSPECTION SUMMARY
03/05/2021 Letter INSPECTION SUMMARY
03/17/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
08/06/2021 Letter INSPECTION SUMMARY
09/09/2021 Letter INSPECTION SUMMARY
01/07/2022 Letter INSPECTION SUMMARY
01/07/2022 Letter INSPECTION SUMMARY
01/07/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
01/11/2022 Letter INSPECTION SUMMARY
01/18/2022 Letter INSPECTION SUMMARY
01/24/2022 Letter INSPECTION SUMMARY
01/24/2022 Letter INSPECTION SUMMARY
02/03/2022 Letter INSPECTION SUMMARY
02/07/2022 Letter INSPECTION SUMMARY
02/17/2022 Letter INSPECTION SUMMARY
02/23/2022 2529 SE River Trail Rd
02/23/2022 Letter INSPECTION SUMMARY
02/28/2022 Letter INSPECTION SUMMARY
03/01/2022 Letter INSPECTION SUMMARY
03/01/2022 Letter INSPECTION SUMMARY
03/30/2022 Letter INSPECTION SUMMARY
04/14/2022 Eagle Creek, Lot 673
04/28/2022 Letter INSPECTION SUMMARY
06/20/2022 Letter INSPECTION SUMMARY
06/22/2022 Letter INSPECTION SUMMARY
06/22/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/05/2022 Receipt Receipt for transaction:2022-006423
08/08/2022 Eagle Creek, Lot 673 - deck piers
08/08/2022 Receipt Receipt for transaction:2022-006498
08/08/2022 Letter Codes Temporary Certificate of Occupancy
08/24/2022 Plot Plan APPROVED AS GRADED PLOT PLAN
10/12/2022 Letter Codes 10 Day Letter
10/31/2022 Letter Codes 10 Day Letter
11/04/2022 Certificate/License Codes Temporary Certificate of Occupancy
11/04/2022 Certificate/License Codes Temporary Certificate of Occupancy
11/04/2022 Receipt Receipt for transaction:2022-008718
11/11/2022 Letter Codes Final Certificate of Occupancy
11/11/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home