Permit Application Status

PRRES20190638


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20190638
Building Permit - Residential
Certificate of Occupancy
D&D BUILDING INC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
03/21/2019
03/26/2019
10/31/2019
Locations
Contacts
D&D BUILDING INC, Address:PO BOX 7014  
D AND D BUILDING INC, Address:PO BOX 7014, Phone:(816) 491-2125  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
TEAGUE ELECTRIC CONSTRUCTION LLC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
DANNELSON@DND@GMAIL.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 03/25/2019 03/22/2019
Kim Brennan
Plot Plan Review Approved 03/25/2019 03/22/2019
Steve Conrick
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $1,054.01 $1,054.01 Paid 03/26/2019
Right of Way Permit Fee $80.00 $80.00 Paid 03/26/2019
8331507-Sewer Connection Fee $480.00 $480.00 Paid 03/26/2019
Water Tap Fee $3,409.00 $3,409.00 Paid 03/26/2019
Water Meter Fee $408.37 $408.37 Paid 03/26/2019
Not Ready Inspection Fee $50.00 $50.00 Paid 10/24/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 4/3/2019 (3:00) 4/3/2019 at 3:00 PM 04/03/2019
Underslab Plumbing Inspection - Residential Failed 4/23/2019 4/23/2019 at 2:35 PM 04/22/2019
Misc
Corrective Action Required
04/22/2019
WALK-UP BASEMENT NOT SHOWN ON PLOT PLAN
Sewer Service Inspection - R Passed 5/3/2019 (10:45) 5/3/2019 at 11:55 AM 05/03/2019
Erosion Control Inspection Residential Failed 5/3/2019 05/03/2019
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/03/2019
DEFICIENT EROSION CONTROL INSTALLATION. CLEAN DIRT OFF THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Erosion Control Inspection Residential Failed 5/6/2019 05/06/2019
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/03/2019
REESTABLISH EROSION CONTROL ALONG THE STREET AND PROPERTY LINE AND CLEAN DIRT OFF THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Water Service Inspection - R Passed 5/6/2019 at 12:45 PM 05/06/2019
Suspended Slab Inspection Passed 5/14/2019 5/14/2019 at 1:45 PM 05/14/2019
Gas Service Inspection - Residential Passed 6/20/2019 6/20/2019 at 1:25 PM 06/20/2019
Electrical Service Inspection Passed 7/9/2019 7/9/2019 07/09/2019
All Rough Inspection - Residential Failed 7/9/2019 7/9/2019 at 8:00 AM 07/09/2019
Misc
Corrective Action Required
07/09/2019
**Shall submit new plan and plot plan with walk-up basement to the city for approval. **Provide city-approved plan on site FRAMING: -Expose framing above the rear porch -Nail garage corner studs per code -Roof support purlins per plan -Remove valley rafter strut from ceiling joist above great room -Firestop all flood&ceiling penetrations; Fb duct chase from roof; Fb space behind bathtub from roof -Frame CSPF walls at rear dining and master bedroom per plan -Master closet and stair exterior wall studs not continuous from floor to ceiling. -Support valley rafter strut to bearing wall at front bedroom closet; support short ridge -Solidblock master bedroom cantilevered joists -Fb basement wall vertically at max ten ft interval; fb basement wall from furdown ceiling and joist space; Fb floor at plumbing traps MECHANICAL: -Fasten fireplace to framing ELECTRICAL: -Provide flood light at rear -Protect AC circuit at master closet PLUMBING: -Loop vent not done per code -Install roof flashing for vents **DO NOT INSULATE
All Rough Inspection - Residential Failed 7/12/2019 7/12/2019 at 9:50 AM 07/12/2019
Misc
Corrective Action Required
07/09/2019
**Shall submit new plan and plot plan with walk-up basement to the city for approval. FRAMING: -Provide CITY-APPROVED plan on site. **Brace interior walls **Support I beam at bar -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability -Remove valley rafter strut from ceiling joist above great room -Frame CSPF walls at rear dining and master bedroom per plan **See the plan for framing detail (strap, nailing, etc) -Solidblock master bedroom cantilevered joists -Fb basement wall from furdown ceiling and joist space **insulation used as fireblocking material shall fill the entire depth of the wall space and min. 16" in height from ceiling level down PLUMBING: -Loop vent not done per code -Install roof flashing for vents **DO NOT INSULATE. SEE BELOW **SHALL PROVIDE THE CITY-APPROVED PLAN ON SITE. (THE ONE WITH THE CITY RED STAMP) **RE-INSPECTION FEE ASSESSED- 7/12
All Rough Inspection - Residential Failed 7/12/2019 07/12/2019
Misc
Corrective Action Required
07/12/2019
**Shall submit new plan and plot plan with walk-up basement to the city for approval. FRAMING: -Provide CITY-APPROVED plan on site. **Brace interior walls **Support I beam at bar -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability -Remove valley rafter strut from ceiling joist above great room -Frame CSPF walls at rear dining and master bedroom per plan **See the plan for framing detail (strap, nailing, etc) -Solidblock master bedroom cantilevered joists -Fb basement wall from furdown ceiling and joist space **insulation used as fireblocking material shall fill the entire depth of the wall space and min. 16" in height from ceiling level down PLUMBING: -Loop vent not done per code -Install roof flashing for vents **DO NOT INSULATE. SEE BELOW **SHALL PROVIDE THE CITY-APPROVED PLAN ON SITE. (THE ONE WITH THE CITY RED STAMP) **RE-INSPECTION FEE ASSESSED- 7/12
All Rough Inspection - Residential Failed 7/18/2019 7/18/2019 at 9:35 AM 07/18/2019
Misc
Corrective Action Required
07/12/2019
**Shall submit plot plan with walk-up basement to the city for approval. FRAMING: -Per city-approved plan: **Brace interior walls **Support I beam at bar -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail. Shall install two 5/8" through bolts at 2x8 connections per plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability -Frame CSPF walls at rear dining and master bedroom per plan **See the plan for framing detail (strap, nailing, etc) -Fb basement wall from furdown ceiling and joist space **insulation used as fireblocking material shall fill the entire depth of the wall space and min. 16" in height from ceiling level down; staple insulation in place **OK TO INSULATE.
All Rough Inspection - Residential Failed 7/26/2019 7/26/2019 at 8:30 AM 07/26/2019
Misc
Corrective Action Required
07/18/2019
**Shall submit plot plan with basement walk-out&walk-up and lower garage to the city for approval. -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail. Shall install two 5/8" through bolts at 2x8 connections per plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability -Frame CSPF walls at rear dining (slide door wall) per plan **See the plan for framing detail (strap, nailing, etc) **OK TO ROCK IF THE CSPF WALLS ARE STRAPPED PER PLAN
Driveway Inspection Failed 9/27/2019 09/27/2019
Misc
Corrective Action Required
09/27/2019
Water at the end of approach also a divot was taken out of the gravel area.
Driveway Inspection Failed 10/1/2019 10/1/2019 10/01/2019
Misc
Corrective Action Required
09/27/2019
Water at the end of approach also a divot was taken out of the gravel area.
Misc
Corrective Action Required
10/01/2019
Corrective Action has not been performed contractor will be fine a fee for not being ready for inspection.
Driveway Inspection Partial 10/01/2019
Misc
Corrective Action Required
10/01/2019
Water at the end of approach also a divot was taken out of the gravel area.
Misc
Corrective Action Required
10/01/2019
Corrective Action has not been performed contractor will be fine a fee for not being ready for inspection.
Misc
Informational
10/01/2019
Contractor made the required changes to driveway approach. Driveway- forms and materials passed pre-inspection.
All Rough Inspection - Residential Failed 10/10/2019 10/10/2019 at 10:00 AM 10/10/2019
Misc
Corrective Action Required
07/26/2019
**Shall submit plot plan with basement walk-out&walk-up and lower garage to the city for approval. -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail. Shall install two 5/8" through bolts at 2x8 connections per plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability
Erosion Control Inspection Residential Failed 10/15/2019 10/15/2019
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/06/2019
REESTABLISH EROSION CONTROL AT REAR OF LOT NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Occupancy Inspection - Codes Residential Failed 10/15/2019 10/15/2019 at 9:50 AM 10/15/2019
Resolved
10/15/2019
Misc
Corrective Action Required
09/17/2019
FROM ALLROUGH: **Shall submit plot plan with basement walk-out&walk-up and lower garage to the city for approval. -Expose framing above the rear porch **Expose the gable end of the porch roof. See the plan detail. Shall install two 5/8" through bolts at 2x8 connections per plan detail **Have engineer address gable support onto the short wall, instead on directly on the post for buckling instability -Re-inspection fee assessed on 7/12 not paid -Driveway not approved on record -Locate the sewer tracer wire and install the tracer terminal -Repair water meter. Water meter well needs replaced and corrected to match grade. Water meter well needs cleaned out of mud and debris. -Final grade per approved plot plan, sod, splash blocks -Seal exterior wall penetrations -Secure AC whip -Install outdoor receptacle near AC -Garage receptacle not tripping -Garage doors shall be self closing -Fb penetrations under garage sink -Install spark rings at kitchen backsplash receptacle boxes recessed more than 1/4” from surface -Where’s the other small appliance circuit gfci? -Wet bar electrical not ready -Provide mean to clean out the furnace condensate drain -Locate and make accessible sewer clean out -Support outer deck joist. Use L bracket -Install breaker lock for out of sight water heater -Shall verify that 2 small appliance circuits are installed for the kitchen countertop receptacles
All Rough Inspection - Residential Failed 10/21/2019 10/21/2019 at 9:05 AM 10/21/2019
Misc
Corrective Action Required
10/10/2019
-COMPLETE INSTALLING STRAPS ON THE INTERIOR SIDES OF BOTH POST&KNEE WALLS PER ENGINEER LETTER DATED OCTOBER 18 -COMPLETE REINFORCE THE OUTER SIDES OF BOTH POST&KNEE WALLS PER ORIGINAL LETTER. INSTALL A SIMPSON LTP5 DEVICE
Underslab Plumbing Inspection - Residential Passed 10/21/2019
Misc
Resolved
10/21/2019
WALK-UP BASEMENT NOT SHOWN ON PLOT PLAN
Driveway Inspection Passed 10/22/2019
Misc
Corrective Action Required
10/01/2019
Water at the end of approach also a divot was taken out of the gravel area.
Misc
Corrective Action Required
10/01/2019
Corrective Action has not been performed contractor will be fine a fee for not being ready for inspection.
Misc
Informational
10/01/2019
Contractor made the required changes to driveway approach. Driveway- forms and materials passed pre-inspection.
Misc
Informational
10/22/2019
Driveway passed final inspection.
Erosion Control Inspection Residential Passed 10/23/2019
DCM2 ESC DEFICIENT INSTALLATION
Resolved
10/23/2019
REESTABLISH EROSION CONTROL AT REAR OF LOT NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Occupancy Inspection - Codes Residential Failed 10/23/2019 10/23/2019 at 1:25 PM 10/23/2019
Misc
Corrective Action Required
10/15/2019
-Reinforcement at the outer side of the hinge-joint not done per 1st engineer letter. Straps on the interior side of the hinge joint are installed per revised engineer letter and is OK. -Re-inspection fee assessed on 7/12 not paid. -Water meter well needs cleaned out of mud and debris. -Provide proper slope away from the basement walk-up stem wall; install downspout splash blocks -Garage receptacle not tripping; or it must be single-plug dedicated receptacle -Provide mean to clean out the furnace condensate drain -Provide battery backup for the outdoor drain outlet sump pump
All Rough Inspection - Residential Passed 10/24/2019
Misc
Resolved
10/24/2019
-COMPLETE INSTALLING STRAPS ON THE INTERIOR SIDES OF BOTH POST&KNEE WALLS PER ENGINEER LETTER DATED OCTOBER 18 -COMPLETE REINFORCE THE OUTER SIDES OF BOTH POST&KNEE WALLS PER ORIGINAL LETTER. INSTALL A SIMPSON LTP5 DEVICE
Occupancy Inspection - Codes Residential Temporary C of O 10/25/2019 10/24/2019 at 1:25 PM 10/24/2019
Misc
Corrective Action Required
10/23/2019
-Provide proper slope away from the basement walk-up stem wall; grading outside of the lower garage with storm inlet connected to the sump pump located inside must be approved by city -Provide battery backup for the outdoor drain outlet sump pump
Occupancy Inspection - Codes Residential Temporary C of O 10/29/2019 10/29/2019 at 10:00 AM 10/29/2019
Misc
Corrective Action Required
10/24/2019
-Final grading must be approved by city
Occupancy Inspection - Codes Residential Full C of O 10/31/2019 10/31/2019
Misc
Resolved
10/31/2019
-Final grading must be approved by city
Documents & Images
Date Uploaded File Type Document Name
03/22/2019 Engineer Report/Study 2019.03.19_Lot 38 Monticello
03/26/2019 Receipt Receipt for transaction: 2019-001065
03/26/2019 Letter Codes Building Permit
03/26/2019 Engineer Report/Study DOC032619-03262019152116
04/22/2019 Letter INSPECTION SUMMARY
05/03/2019 Letter INSPECTION SUMMARY
05/03/2019 Letter INSPECTION SUMMARY
05/06/2019 Letter INSPECTION SUMMARY
05/06/2019 Letter INSPECTION SUMMARY
05/14/2019 Letter INSPECTION SUMMARY
06/20/2019 Letter INSPECTION SUMMARY
07/09/2019 Letter INSPECTION SUMMARY
07/09/2019 Letter INSPECTION SUMMARY
07/12/2019 Letter INSPECTION SUMMARY
07/18/2019 Letter INSPECTION SUMMARY
07/26/2019 Letter INSPECTION SUMMARY
09/27/2019 image
10/10/2019 Letter INSPECTION SUMMARY
10/15/2019 Letter INSPECTION SUMMARY
10/15/2019 Letter INSPECTION SUMMARY
10/18/2019 Plans MONT 38 final rev 3
10/18/2019 Engineer Report/Study Monticello Lot 37, Patio strap and bolts
10/21/2019 Letter INSPECTION SUMMARY
10/21/2019 Letter INSPECTION SUMMARY
10/23/2019 Engineer Report/Study Monticello Lot 37 Patio Fastening
10/23/2019 Letter INSPECTION SUMMARY
10/24/2019 Engineer Report/Study 19-003-28 Lot 37 Patio Fastening - Addendum 10-24-19
10/24/2019 Receipt Receipt for transaction: 2019-006975
10/24/2019 Letter Codes Temporary Certificate of Occupancy
10/31/2019 Letter Codes Final Certificate of Occupancy
10/31/2019 Letter Field Certificate of Occupancy
11/01/2019 MONT 38 final rev 3
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.