Review Type |
Outcome |
Est. Completion Date |
Completed |
Alarm Plan Review
|
Released for Construction
|
06/22/2011
|
05/18/2012
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Revised plans received on May 18, 2012.
|
|
Misc
Corrective Action Required
Duct detection shall be supervisory only and shall not activate interior horn/strobes.
Verified at inspection.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule alarm testing.
|
|
|
Alarm Plan Review
|
Rejected
|
06/22/2011
|
05/07/2012
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans received on May 1, 2012.
|
|
Misc
The FACP is shown mounted in a doorway. Clarify the location of the panel.
|
|
Misc
A pull station is shown mounted on a window behind shelving. Clarify location or relocate to central counter area.
For information only- A manual fire alarm is NOT required for this project.
|
|
Misc
Corrective Action Required
Duct detection shall be supervisory only and shall not activate interior horn/strobes.
Verified at inspection.
|
|
Misc
IFC 1008.1.3.4 Access-controlled egress doors.
The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria:
1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset.
5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Indicate how the electronic door locks will meet this requirement.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule alarm testing.
|
|
|
Internal Plan Review (Res)
|
Approved
|
04/20/2012
|
04/18/2012
|
|
Mike Weisenborn
|
|
|
Final Development Plan Review
|
Approved
|
04/06/2012
|
04/06/2012
|
|
Mike Weisenborn
|
|
|
CPTED Plan Review
|
Approved
|
04/06/2012
|
04/06/2012
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
01/27/2012
|
01/31/2012
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Final Development Plan
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
Mike Weisenborn August 29, 2011 - The final development plan has not been approved.
|
|
Security Code
The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances)
Action required - Contact the Planning and Development Department at 816-969-1600 for additional information.
Mike Weisenborn August 29, 2011 - We have not yet received an approval of the security review.
|
|
Misc
Plans and specifications for the construction of the fuelling island have not been provided.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Misc
Details and specifications for the installation of the fuel pumps and underground fuel storage tanks and their associated services has not been provided.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Mech - Outdoor air required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - I am unable to locate the calculations for the outdoor air. Please provide additional information.
Mike Weisenborn August 05, 2011 - The resubmittal letter states that the calculations are attached but I am unable to locate them. Please provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Misc
I am unable to locate details for the grease interceptor being installed.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
|
Fire Plan Review
|
Approved
|
10/12/2011
|
10/24/2011
|
|
Brian Austerman
|
|
Misc
2006 IFC 907.2.12.1 Automatic fire detection.
Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows:
...
2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.
2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
...
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
ACTION REQUIRED: PROVIDE DUCT DETECTION FOR RTU 1 TO SEND A SUPERVISORY SIGNAL TO A REMOTE AUDIO/LED TEST AND RESET STATION
Additional Information: Duct detector shall be located on the return air side, verified at inspection
|
|
Address numbers required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: INFORMATION ONLY, VERIFIED AT INSPECTION
|
|
Misc
Fire Department- Underground fuel tank placement and testing shall be witnessed by the Fire Department, and shall conform to chapters 22 and 34 of the IFC 2006 as well as NFPA chapters 30 and 70. Call 969-1300 to schedule inspections.
|
|
Misc
Corrective Action Required
Fire Department- A Hazardous Materials Permit will be required, call (816) 969-1300 to obtain a HMP application from the Fire Department.
Provide specifications on the tanks, pumps and piping.
|
|
Misc
Corrective Action Required
2203.2 Emergency disconnect switches.
An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Action Required: Distance from emergency shutoffs not shown on plans, needs to be within 100' but no closer than 20', verified at inspection
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action Required: Submit a minimum of 3 copies of the fire alarm construction documents, including the contractor information who will be installing the system
|
|
|
Fire Plan Review
|
Released for Construction
|
06/22/2011
|
10/24/2011
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
2203.2 Emergency disconnect switches.
An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. For interior fuel-dispensing operations, the emergency disconnect switch shall be installed at an approved location. Such devices shall be distinctly labeled as: EMERGENCY FUEL SHUTOFF. Signs shall be provided in approved locations.
Action Required: Distance from emergency shutoffs to fuel pumps not shown on plans, must be within 100' but no closer than 20', verified at inspection
|
|
Misc
Corrective Action Required
Duct smoke detector shall be located on the return air side, verified at inspection
|
|
|
Internal Plan Review (Res)
|
Rejected
|
08/30/2011
|
09/06/2011
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Rejected
|
08/30/2011
|
09/01/2011
|
|
Jim Eden
|
|
Misc
2006 IFC 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
ACTION REQUIRED: DOOR 1 SHOWS AS DOUBLE KEYED DEADBOLT (SHEET A1.0) NEEDS TO BE PANIC HARDWARE OR THUMB SYTLE LATCH ON THE EGRESS SIDE. VERIFIED AT INSPECTION
|
|
Misc
2006 IFC 907.2.12.1 Automatic fire detection.
Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows:
...
2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.
2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
...
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
ACTION REQUIRED: PROVIDE DUCT DETECTION FOR RTU 1 TO SEND A SUPERVISORY SIGNAL TO A REMOTE AUDIO/LED TEST AND RESET STATION
|
|
Address numbers required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: INFORMATION ONLY, VERIFIED AT INSPECTION
|
|
Misc
Fire Department- Underground fuel tank placement and testing shall be witnessed by the Fire Department, and shall conform to chapters 22 and 34 of the IFC 2006 as well as NFPA chapters 30 and 70. Call 969-1300 to schedule inspections.
|
|
Misc
Corrective Action Required
Fire Department- A Hazardous Materials Permit will be required, call (816) 969-1300 to obtain a HMP application from the Fire Department.
Provide specifications on the tanks, pumps and piping.
|
|
|
Building Plan Review
|
Rejected
|
08/30/2011
|
08/29/2011
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit issuance but shall be provided prior to inspection.
Mike Weisenborn August 05, 2011 - The truss details have been provided but I am unable to locate the layout and installation details. Please provide addtional information.
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
Mike Weisenborn August 29, 2011 - The final development plan has not been approved.
|
|
Security Code
Corrective Action Required
The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances)
Action required - Contact the Planning and Development Department at 816-969-1600 for additional information.
Mike Weisenborn August 29, 2011 - We have not yet received an approval of the security review.
|
|
Misc
Corrective Action Required
Plans and specifications for the construction of the fuelling island have not been provided.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Misc
Corrective Action Required
Details and specifications for the installation of the fuel pumps and underground fuel storage tanks and their associated services has not been provided.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Mech - Outdoor air required
Corrective Action Required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - I am unable to locate the calculations for the outdoor air. Please provide additional information.
Mike Weisenborn August 05, 2011 - The resubmittal letter states that the calculations are attached but I am unable to locate them. Please provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
Misc
Corrective Action Required
I am unable to locate details for the grease interceptor being installed.
Action required - Provide additional information.
Mike Weisenborn August 29, 2011 - this information has not yet been provided.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
08/05/2011
|
08/05/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
08/05/2011
|
08/05/2011
|
|
Mike Weisenborn
|
|
Health Dept Review
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of approval from the Health Department.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit issuance but shall be provided prior to inspection.
Mike Weisenborn August 05, 2011 - The truss details have been provided but I am unable to locate the layout and installation details. Please provide addtional information.
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
|
|
Security Code
Corrective Action Required
The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances)
Action required - Contact the Planning and Development Department at 816-969-1600 for additional information.
|
|
Mech - Access to elevated appliances
2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
Action required - I am unable to locate information on the roof access. Please provide additional information.
|
|
Misc
Corrective Action Required
Plans and specifications for the construction of the fuelling island have not been provided.
Action required - Provide additional information.
|
|
Misc
Corrective Action Required
Details and specifications for the installation of the fuel pumps and underground fuel storage tanks and their associated services has not been provided.
Action required - Provide additional information.
|
|
Plumb - Backflow general 608.3
2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Action required - I am unable to locate information on the backflow device to the ice machine. Please provide additional information.
|
|
Misc
2006 IPC 608.16.10 - Coffee machines and noncarbonated beverage dispensers. The water supply connection to coffee machines and noncarbonated beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022 or by an air gap.
Action required - I am unable to locate information showing compliance with this code section. Please provide additional information.
|
|
Plumb - Indirect waste for food handling fixtures
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Please indicate this on the plans.
|
|
Bldg - Exit signage - Where required
2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Action required - Provide additional exit signage in area 107 at the entrance to corridor 108 to indicate the location of the second exit.
|
|
Mech - Outdoor air required
Corrective Action Required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - I am unable to locate the calculations for the outdoor air. Please provide additional information.
Mike Weisenborn August 05, 2011 - The resubmittal letter states that the calculations are attached but I am unable to locate them. Please provide additional information.
|
|
Misc
Corrective Action Required
I am unable to locate details for the grease interceptor being installed.
Action required - Provide additional information.
|
|
|
Fire Plan Review
|
Rejected
|
08/05/2011
|
08/02/2011
|
|
Jim Eden
|
|
Misc
2006 IFC 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
ACTION REQUIRED: DOOR 1 SHOWS AS DOUBLE KEYED DEADBOLT (SHEET A1.0) NEEDS TO BE PANIC HARDWARE OR THUMB SYTLE LATCH ON THE EGRESS SIDE. VERIFIED AT INSPECTION
|
|
Misc
2006 IFC 907.2.12.1 Automatic fire detection.
Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows:
...
2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.
2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
...
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
ACTION REQUIRED: PROVIDE DUCT DETECTION FOR RTU 1 TO SEND A SUPERVISORY SIGNAL TO A REMOTE AUDIO/LED TEST AND RESET STATION
|
|
Address numbers required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: INFORMATION ONLY, VERIFIED AT INSPECTION
|
|
Misc
Fire Department- Underground fuel tank placement and testing shall be witnessed by the Fire Department, and shall conform to chapters 22 and 34 of the IFC 2006 as well as NFPA chapters 30 and 70. Call 969-1300 to schedule inspections.
|
|
Misc
Corrective Action Required
Fire Department- A Hazardous Materials Permit will be required, call (816) 969-1300 to obtain a HMP application from the Fire Department.
Provide specifications on the tanks, pumps and piping.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
07/22/2011
|
08/02/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
|
|
|
Fire Plan Review
|
Rejected
|
06/22/2011
|
08/02/2011
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
2006 IFC 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
ACTION REQUIRED: DOOR 1 SHOWS AS DOUBLE KEYED DEADBOLT (SHEET A1.0) NEEDS TO BE PANIC HARDWARE OR THUMB SYTLE LATCH ON THE EGRESS SIDE. VERIFIED AT INSPECTION
|
|
Misc
Corrective Action Required
2006 IFC 907.2.12.1 Automatic fire detection.
Smoke detectors shall be provided in accordance with this section. Smoke detectors shall be connected to an automatic fire alarm system. The activation of any detector required by this section shall operate the emergency voice/alarm communication system. Smoke detectors shall be located as follows:
...
2. In the main return air and exhaust air plenum of each air-conditioning system having a capacity greater than 2,000 cubic feet per minute (cfm) (0.94 m3/s). Such detectors shall be located in a serviceable area downstream of the last duct inlet.
2006 IFC 907.12 Duct smoke detectors.
Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection.
Exceptions:
...
2. In occupancies not required to be equipped with a fire alarm system, actuation of a smoke detector shall activate a visible and an audible signal in an approved location. Smoke detector trouble conditions shall activate a visible or audible signal in an approved location and shall be identified as air duct detector trouble.
ACTION REQUIRED: PROVIDE DUCT DETECTION FOR RTU 1 TO SEND A TROUBLE SIGNAL TO A REMOTE AUDIO/LED TEST AND RESET STATION
|
|
Address numbers required
Corrective Action Required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
ACTION REQUIRED: INFORMATION ONLY, VERIFIED AT INSPECTION
|
|
Misc
Corrective Action Required
Fire Department- Underground fuel tank placement and testing shall be witnessed by the Fire Department, and shall conform to chapters 22 and 34 of the IFC 2006 as well as NFPA chapters 30 and 70. Call 969-1300 to schedule inspections.
|
|
Misc
Corrective Action Required
Fire Department- A Hazardous Materials Permit (HMP)will be required, call 969-1300 to obtain a HMP application from the Fire Department. Provide tank and feul system component specifications.
|
|
|
Building Plan Review
|
Rejected
|
06/22/2011
|
06/22/2011
|
|
Mike Weisenborn
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of approval from the Health Department.
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Engineered truss package
Corrective Action Required
Copies of the engineered truss package were not provided at the time of permit application.
Action required - Provide two (2) copies of the engineered truss package which have been signed and sealed by an engineer licensed in the State of Missouri. This information is not required for permit issuance but shall be provided prior to inspection.
|
|
Final Development Plan
Corrective Action Required
The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department.
Action required - This comment is for information purposes.
|
|
Security Code
Corrective Action Required
The work authorized by this permit shall be constructed to comply with the Security Code provisions. (Chapter 7, Article 14 of the Lees Summit Code of Ordinances)
Action required - Contact the Planning and Development Department at 816-969-1600 for additional information.
|
|
Mech - Access to elevated appliances
Corrective Action Required
2006 IMC 306.5 - Equipment and appliances on roofs or elevated structures. Where equipment and appliances requiring access are installed on roofs or elevated structures at a height exceeding 16 feet, such access shall be provided by a permanent approved means of access, the extent of which shall be from grade or floor level to the equipment and appliances level service space. Such access shall not require climbing over obstructions greater than 30 inches high or walking on roofs having a slope greater than 4 units vertical in 12 units horizontal. Permanent ladders installed to provide the required access shall comply with the following minimum design criteria: 1. The side railing shall extend above the parapet or roof edge not less than 30 inches. 2. Ladders shall have rung spacing not to exceed 14 inches on center. 3. Ladders shall have a toe spacing not less than 6 inches deep. 4. There shall be a minimum of 18 inches between rails. 5. Rungs shall have a minimum 0.75-inch diameter and be capable of withstanding a 300-pound load. 6. Ladders over 30 feet in height shall be provided with offset sections and landings capable of withstanding 100 pound per square foot. 7. Ladders shall be protected against corrosion by approved means. Catwalks installed to provide the required access shall be not less than 24 inches wide and shall have railing as required for service platforms.
Action required - I am unable to locate information on the roof access. Please provide additional information.
|
|
Misc
Corrective Action Required
Plans and specifications for the construction of the fuelling island have not been provided.
Action required - Provide additional information.
|
|
Misc
Corrective Action Required
Details and specifications for the installation of the fuel pumps and underground fuel storage tanks and their associated services has not been provided.
Action required - Provide additional information.
|
|
Plumb - Backflow general 608.3
Corrective Action Required
2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination.
Action required - I am unable to locate information on the backflow device to the ice machine. Please provide additional information.
|
|
Misc
Corrective Action Required
2006 IPC 608.16.10 - Coffee machines and noncarbonated beverage dispensers. The water supply connection to coffee machines and noncarbonated beverage dispensers shall be protected against backflow by a backflow preventer conforming to ASSE 1022 or by an air gap.
Action required - I am unable to locate information showing compliance with this code section. Please provide additional information.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - Please indicate this on the plans.
|
|
Bldg - Exit signage - Where required
Corrective Action Required
2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Action required - Provide additional exit signage in area 107 at the entrance to corridor 108 to indicate the location of the second exit.
|
|
Mech - Outdoor air required
Corrective Action Required
2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design.
Action required - I am unable to locate the calculations for the outdoor air. Please provide additional information.
|
|
Misc
Corrective Action Required
I am unable to locate details for the grease interceptor being installed.
Action required - Provide additional information.
|
|
|
License Tax Codes
|
Approved
|
06/22/2011
|
06/21/2011
|
|
Mike Weisenborn
|
|
|