Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Plan Review
|
Approved
|
08/19/2024
|
08/19/2024
|
|
Craig Hill
|
|
Miscellaneous Correction
Corrective Action Required
The west space of the office has an occupant load of 63 and requires a second remote egress. IFC Section 1016.2 does not allow egress into the warehouse, except under certain circumstances.
Action needed: Provide exit signage from the west side of the space to hallway 117 and change the door swing of door 118A.
07/05/2024- provide exit signage over the west side of the hallway. Verified at inspection.
|
|
|
Building Plan Review
|
Approved
|
08/19/2024
|
08/12/2024
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
08/08/2024
|
08/08/2024
|
|
Jim Eden
|
|
Miscellaneous Correction
Corrective Action Required
The west space of the office has an occupant load of 63 and requires a second remote egress. IFC Section 1016.2 does not allow egress into the warehouse, except under certain circumstances.
Action needed: Provide exit signage from the west side of the space to hallway 117 and change the door swing of door 118A.
07/05/2024- provide exit signage over the west side of the hallway. Verified at inspection.
|
|
|
Alarm Plan Review
|
Released for Construction
|
07/29/2024
|
07/29/2024
|
|
Craig Hill
|
|
Miscellaneous Correction
Corrective Action Required
Any high-volume large-diameter fans shall shutdown upon any activation of the fire alarm.
|
|
Alarms connected to automatic sprinkler system
Corrective Action Required
2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
|
|
Alarm testing.
Corrective Action Required
2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation.
|
|
|
Building Plan Review
|
Approved
|
05/24/2024
|
07/25/2024
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
07/22/2024
|
07/22/2024
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide tenant finish alarm notification plans.
|
|
Construction documents - Fire protection systems
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans as a seperate submittal.
|
|
Miscellaneous Correction
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Provide rack storage plans for the warehouse.
|
|
Miscellaneous Correction
Corrective Action Required
The west space of the office has an occupant load of 63 and requires a second remote egress. IFC Section 1016.2 does not allow egress into the warehouse, except under certain circumstances.
Action needed: Provide exit signage from the west side of the space to hallway 117 and change the door swing of door 118A.
07/05/2024- provide exit signage over the west side of the hallway. Verified at inspection.
|
|
|
Building Plan Review
|
Approved
|
07/22/2024
|
07/22/2024
|
|
Joe Frogge
|
|
|
Fire Plan Review
|
Approved with Conditions
|
07/03/2024
|
07/05/2024
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide tenant finish alarm notification plans.
|
|
Address numbers required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Provide suite numbers on all exterior doors.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans as a seperate submittal.
|
|
Portable fire extinguishers - general
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Show the location of extinguishers in the warehouse.
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Provide rack storage plans for the warehouse.
|
|
Miscellaneous Correction
Corrective Action Required
The west space of the office has an occupant load of 63 and requires a second remote egress. IFC Section 1016.2 does not allow egress into the warehouse, except under certain circumstances.
Action needed: Provide exit signage from the west side of the space to hallway 117 and change the door swing of door 118A.
07/05/2024- {rovide exit signage over the west side of the hallway. Verified at inspection.
|
|
|
Building Plan Review
|
Approved
|
07/03/2024
|
07/03/2024
|
|
Joe Frogge
|
|
Suite address
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required: Comment is informational. This tenant has been assigned the address of 1220 NW Main St, Unit:E. Please update your records and inform your client.
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. The fee will be $7,128.00
7/3/2024 - acknowledged in letter.
|
|
IBC 1606.2 Design dead load - structural
2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official.
Action required: Provide verification that roof structure will support new roof mounted equipment.
|
|
Misc
2 sheets are blank.
Action required: Upon resubmittal verify that sheets E1.10 and E2.00 are printed correctly. (we were able to review the sheets based on supplemental electrical set uploaded after original set)
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide convenience receptacle near condensing unit CU-01. (re: hvac serving offices 201 & 202)
|
|
|
Licensed Contractors
|
Approved
|
07/03/2024
|
07/03/2024
|
|
Joe Frogge
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
06/27/2024
|
07/01/2024
|
|
Craig Hill
|
|
Misc
Corrective Action Required
25.2.1.4.1 Where modification is made to an existing system affecting more than 20 sprinklers, the new portion shall be isolated and tested at not less than 200 psi (13.8 bar) for 2 hours.
|
|
|
Fire Plan Review
|
Rejected
|
06/06/2024
|
06/08/2024
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide tenant finish alarm notification plans.
|
|
Address numbers required
Corrective Action Required
2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Provide suite numbers on all exterior doors.
|
|
Construction documents - Fire protection systems
Corrective Action Required
2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide sprinkler plans as a seperate submittal.
|
|
Portable fire extinguishers - general
Corrective Action Required
2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Show the location of extinguishers in the warehouse.
|
|
Miscellaneous Correction
Corrective Action Required
3201.3 Construction documents. At the time of building
permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International
Building Code, the storage permit submittal shall
include the information specified in this section. The construction documents shall include all of the following:
1. Floor plan of the building showing locations and
dimensions of high-piled storage areas.
2. Usable storage height for each storage area.
3. Number of tiers within each rack, if applicable.
4. Commodity clearance between top of storage and the
sprinkler deflector for each storage arrangement.
5. Aisle dimensions between each storage array.
6. Maximum pile volume for each storage array.
7. Location and classification of commodities in accordance with Section 3203.
8. Location of commodities that are banded or encapsulated.
9. Location of required fire department access doors.
10. Type of fire suppression and fire detection systems.
11. Location of valves controlling the water supply of
ceiling and in-rack sprinklers.
12. Type, location and specifications of smoke removal
and curtain board systems.
13. Dimension and location of transverse and longitudinal flue spaces.
14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area
shall be provided at the time of permit, where required
by the fire code official.
Provide rack storage plans for the warehouse.
|
|
Miscellaneous Correction
Corrective Action Required
The west space of the office has an occupant load of 63 and requires a second remote egress. IFC Section 1016.2 does not allow egress into the warehouse, except under certain circumstances.
Action needed: Provide exit signage from the west side of the space to hallway 117 and change the door swing of door 118A.
|
|
|
Building Plan Review
|
Rejected
|
06/06/2024
|
06/05/2024
|
|
Joe Frogge
|
|
Suite address
Corrective Action Required
This structure has been assigned one address. All suites/apartments shall be assigned an address by the owner which can be numeric, alphabetic or a combination of both. If the building has multiple stories the suite/apartment number shall start with a number representing the floor on which the unit is located.
Action required: Comment is informational. This tenant has been assigned the address of 1220 NW Main St, Unit:E. Please update your records and inform your client.
|
|
License Tax - Payment
Corrective Action Required
A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process.
Action required: Comment is for informational purposes. The fee will be $7,128.00
|
|
IBC 1606.2 Design dead load - structural
Corrective Action Required
2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official.
Action required: Provide verification that roof structure will support new roof mounted equipment.
|
|
Misc
Corrective Action Required
2 sheets are blank.
Action required: Upon resubmittal verify that sheets E1.10 and E2.00 are printed correctly. (we were able to review the sheets based on supplemental electrical set uploaded after original set)
|
|
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means.
Action required: Provide convenience receptacle near condensing unit CU-01. (re: hvac serving offices 201 & 202)
|
|
|
Licensed Contractors
|
Approved
|
06/06/2024
|
06/04/2024
|
|
Joe Frogge
|
|
|