Summary
PRCOM20140231
Building Permit - Commercial
Certificate of Occupancy
CITY OF LEES SUMMIT
CHANGE OF TENANT
CHANGE FROM AN OFFICE OCCUPANCY TO AN ASSEMBLY OCCUPANCY
02/25/2014
07/25/2014
09/03/2014
01/16/2015
Locations
Contacts
THE WILSON GROUP, Address:13510 OAK ST, Phone:(816) 537-0212  
THE WILSON GROUP, Address:13510 OAK ST, Phone:(816) 537-0212  
ELECTRIC ONE LLC, Address:7312 N ANTIOCH RD, Phone:(816) 437-9312  
MECHANICAL PIPING, Address:12120 STATE LINE #181, Phone:(816) 797-6368  
THE HOLLIS & MILLER GROUP, Address:1828 WALNUT ST STE 922, Phone:(816) 525-5600  
CITY OF LEES SUMMIT, Address:PO BOX 1600  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 09/03/2014 07/25/2014
Mike Weisenborn
Business License
Resolved
07/25/2014

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.Action required - Either a Class A or Class B license is required. Provide the name of the licensed general contractor. Action required - Provide the name of the licensed general contractor. Either a Class A or B license is required. This information is required for permit approval.
License contractors
Corrective Action Required
03/07/2014

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed mechanical, electrical and plumbing contractors. This information is required for permit approval. Mike Weisenborn 07/25/2014 9:13 AM - Provide the name of the licensed plumbing subcontractor. Inspection on the plumbing alterations will not be performed until the name of the licensed plumber has been provided.
LEE'S SUMMIT HISTORICAL MUSEUM
Building Plan Review Approved with Conditions 03/07/2014 03/07/2014
Mike Weisenborn
Misc
Corrective Action Required
03/07/2014

The door to the safe shall be openable from the safe side. If the door cannot be opened from the safe side the locking mechanism shall be disabled or the door shall be secured in an open position. Action required - This comment is for information purposes.
Misc
Corrective Action Required
03/07/2014

Multi-purpose room 115 on the lower level only has one means of egress and the door swings in. Because of this the room can not facilitate on occupancy greater than 49. Action required - Please post a maximum occupant load sign of 49 on the interior of the room adjacent to the door.
Fire Plan Review Approved with Conditions 03/07/2014 02/27/2014
Brian Austerman
Misc
Corrective Action Required
02/27/2014

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. PROVIDE EXTERIOR EGRESS LIGHTING PER CONDITION 3 AND 5. VERIFIED AT INSPECTION
Portable fire extinguishers - general
Corrective Action Required
02/27/2014

2012 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Misc
Corrective Action Required
02/27/2014

1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf. MARKED EXITS SHALL HAVE APPROVED HARDWARE, VERIFIED AT INSPECTION
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,225.50 $1,225.50 Paid 07/25/2014
$1,225.50
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Passed 8/8/2014 at 12:00 AM 08/08/2014
Above Ceiling Inspection Partial 9/9/2014 9/9/2014 at 12:00 AM 09/09/2014
Misc
Partial Correction
09/09/2014
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 103 AFTER ABANDONED ELECTRICAL CONDUIT AT EAST END ARE REMOVED AND CONDUITS IN USE ARE SECURED TO STRUCTURE; 103b;
In-wall Inspection Partial 9/9/2014 at 12:00 AM 09/09/2014
Misc
Partial Correction
09/09/2014
OK TO TOP-OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT SPACE 103: 5' TOP-OUT @ N WALL; 4' TOP-OUT @ E & W WALLS
In-wall Inspection Partial 9/10/2014 at 12:00 AM 09/10/2014
Misc
Partial Correction
09/09/2014
OK TO TOP-OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT SPACE 103: 5' TOP-OUT DOWN TO EXSTG @ N & S WALLS; 4' TOP-OUT @ E & W WALLS
Above Ceiling Inspection Partial 9/15/2014 9/15/2014 at 12:00 AM 09/15/2014
Misc
Partial Correction
09/09/2014
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 103; 103b INCLUDING HVAC DUCT;
In-wall Inspection Passed 9/16/2014 9/16/2014 at 12:00 AM 09/16/2014
Misc
Resolved
09/16/2014
OK TO TOP-OUT WALLS WITH GWB TO ALLOW INSTALLATION OF HVAC DUCT AND OTHER SYSTEMS AT SPACE 103: 5' TOP-OUT DOWN TO EXSTG @ N & S WALLS; 4' TOP-OUT @ E & W WALLS
Suspended Slab Inspection Failed 10/16/2014 (9:15) 10/16/2014 at 12:00 AM 10/16/2014
Misc
Corrective Action Required
10/16/2014
STAIR SLAB THICKNESS NOT 7" PER DRAWING.
Misc
Corrective Action Required
10/16/2014
RE-BAR CLEARANCE NOT MID-THICKNESS OF SLAB.
Suspended Slab Inspection Passed 10/17/2014 (8:00) 10/17/2014 at 12:00 AM 10/17/2014
Misc
Resolved
10/17/2014
STAIR SLAB THICKNESS NOT 7" PER DRAWING.
Misc
Resolved
10/17/2014
RE-BAR CLEARANCE NOT MID-THICKNESS OF SLAB.
Gas Piping Inspection - Commercial Failed 10/30/2014 10/30/2014 at 12:00 AM 10/30/2014
Misc
Corrective Action Required
10/30/2014
-GAS PIPE SHOULD BE PAINTED TO RESIST CORROSION. WILL CHECK AT FINAL.
Gas Service Inspection - Commercial Passed 10/30/2014 at 12:00 AM 10/30/2014
Foundation Inspection - Commercial Passed 11/6/2014 at 12:00 AM 11/06/2014
Underground Electrical Inspection - Commercial Passed 11/11/2014 11/11/2014 at 12:00 AM 11/11/2014
Rough Mechanical Inspection - Commercial Not Ready 11/25/2014 at 12:00 AM 11/25/2014
Misc
Corrective Action Required
11/25/2014
- NO ONE AVAILABLE FOR INSPECTION
Above Ceiling Inspection Partial 12/1/2014 12/1/2014 at 12:00 AM 12/01/2014
Misc
Partial Correction
09/15/2014
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING 1ST FLR SPACES: 103; 103b; 105; 109 NORTH;
Misc
Corrective Action Required
12/01/2014
ABOVE-CEILING AT BASEMENT: 1) SUPPORT PEX WATER TUBING @ MAX 32" INTERVALS 2) SUPPORT PVC PIPING AT CHANGES OF DIRECTION AND MAX 8' INTERVALS 3) CLOSE ALL ELECTRICAL BOXES AFTER ENSURING ALL CONDUCTOR ENDS ARE WIRE-NUTTED. 4) NEC400.7, 8: CORD & PLUG CANNOT BE ROUTED THROUGH ACT CEILING.
Misc
Corrective Action Required
12/01/2014
NEC400.7, 8: CORD & PLUG WIRING CANNOT BE ROUTED THROUGH ACT CEILING.
Above Ceiling Inspection Passed 12/4/2014 12/4/2014 at 12:00 AM 12/04/2014
Misc
Resolved
12/04/2014
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING 1ST FLR SPACES: 103; 103b; 105; 109 NORTH;
Misc
Resolved
12/04/2014
ABOVE-CEILING AT BASEMENT: 1) SUPPORT PEX WATER TUBING @ MAX 32" INTERVALS 2) SUPPORT PVC PIPING AT CHANGES OF DIRECTION AND MAX 8' INTERVALS 3) CLOSE ALL ELECTRICAL BOXES AFTER ENSURING ALL CONDUCTOR ENDS ARE WIRE-NUTTED. 4) NEC400.7, 8: CORD & PLUG CANNOT BE ROUTED THROUGH ACT CEILING.
Misc
Resolved
12/04/2014
NEC400.7, 8: CORD & PLUG WIRING CANNOT BE ROUTED THROUGH ACT CEILING.
Gas Piping Inspection - Commercial Passed 10/30/2014 at 12:00 AM 12/04/2014
Misc
Resolved
12/04/2014
-GAS PIPE SHOULD BE PAINTED TO RESIST CORROSION. WILL CHECK AT FINAL.
Occupancy Inspection - Fire Not Ready 12/5/2014 12/5/2014 at 12:00 AM 12/05/2014
Occupancy Inspection - Codes Commercial Failed 12/5/2014 12/5/2014 at 12:00 AM 12/05/2014
Misc
Corrective Action Required
12/05/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 2) ALL POWER CIRCUITS MUST BE HOT FOR TEST; LADDER REQUIRED FOR INSPECTION. 3) NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT TIGHT TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE. 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS. 5) ALL SPACES MUST BE ACCESSIBLE FOR INSPECTION. 6) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 7) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS.
Misc
Corrective Action Required
12/05/2014
MAIN FLOOR: 1) LIGHTING GRID IN 103 TO BE INSTALLED. 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 3) MAKE PEX TUBING WATER FEEDS SOLID AT VALVES. 4) PROMINENTLY MARK ABANDONED ELECTRICAL PANEL "NOT IN USE" 5) NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE. SEE AT WALL CABINET AT 109a 6) NEC 380-10; 410-56(f) / IRC E3901.10; E3902.6 SECURING OF ELECTRICAL RECEPTACLES / SWITCHES: SOME NOT TIGHT TO BOX; CHECK ALL AND ENSURE NONE ARE "SOFT" OR LOOSE SIDE-TO-SIDE. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 9) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED 11) SAFETY GLASS ETCHING NOT FOUND ON GLAZING IN DOOR TO 102
Misc
Corrective Action Required
12/05/2014
EXTERIOR: 1) GUARDS AT STAIRS & RAMPS NOT IBC/ANSI COMPLIANT 2) ELECT RECPTS AT SE MUST BE GFCI-PROTECTED. NOT HOT FOR TEST 3) IFGC 404.8: METALLIC PIPING EXPOSED TO WEATHER MUST BE PERMANENTLY PROTECTED WITH PAINT OR BY OTHER APPROVED MEANS. SEE GAS PIPING AT REAR WALL AND ROOFTOP. 4) ACCESS TO ROOF REQUIRED FOR ROOFTOP INSPECTION.
Occupancy Inspection - Fire Temporary C of O 12/11/2014 12/11/2014 at 12:00 AM 12/11/2014
Misc
Corrective Action Required
12/11/2014
mount fire extinguishers: - front entrance area - area of southwest exit (downstairs) - install emergency lighting on exterior of southwest exit (upstairs) - install all light fixtures as needed throughout.
Corrective Action Required
12/11/2014
Occupancy Inspection - Codes Commercial Failed 12/11/2014 12/11/2014 at 12:00 AM 12/11/2014
Misc
Corrective Action Required
12/05/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS. 6) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
12/05/2014
MAIN FLOOR: 1) INSTALLATION OF LIGHTING GRID IN 103 IN PROGRESS. MAINTAIN CONSTRUCTION SAFETY IF STAFF USE OF BUILDING COMMENCES PRIOR TO COMPLETION. 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 3) MAKE PEX TUBING WATER FEEDS SOLID AT VALVES. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 9) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED 11) SAFETY GLASS ETCHING NOT FOUND ON GLAZING IN DOOR TO 102 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/05/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Occupancy Inspection - Codes Commercial Failed 12/11/2014 at 12:00 AM 12/11/2014
Misc
Corrective Action Required
12/11/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS. 6) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
12/11/2014
MAIN FLOOR: 1) INSTALLATION OF LIGHTING GRID IN 103 IN PROGRESS. MAINTAIN CONSTRUCTION SAFETY IF STAFF USE OF BUILDING COMMENCES PRIOR TO COMPLETION. 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 3) MAKE PEX TUBING WATER FEEDS SOLID AT VALVES. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 9) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED 11) SAFETY GLASS ETCHING NOT FOUND ON GLAZING IN DOOR TO 102 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/11/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Misc
Corrective Action Required
12/11/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC BEFORE APPROVAL. MAINTAIN SAFETY CONDITIONS WITH CONSTRUCTION COMPLETION.
Occupancy Inspection - Codes Commercial Partial 12/15/2014 at 12:00 AM 12/15/2014
Misc
Corrective Action Required
12/11/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS. 6) NEC 408.4: LABELING AT ELECTRICAL SWITCHES AND PANELS: MAIN SWITCHES MUST BE DISTINGUISHED AND LABELED. PANEL MUST BE IDENTIFIED ON PANEL FRONT AND AT FEEDER SOURCE. EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
12/11/2014
MAIN FLOOR: 1) INSTALLATION OF LIGHTING GRID IN 103 IN PROGRESS. MAINTAIN CONSTRUCTION SAFETY IF STAFF USE OF BUILDING COMMENCES PRIOR TO COMPLETION. 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 3) SECURE PEX TUBING WATER FEEDS AT VALVES. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: PANEL MUST BE IDENTIFIED ON FRONT AND AT FEEDER SOURCE. EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 9) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS. EXAMPLE: RM 102 10) FLOOR RECEPTACLES AT 102 NOT FINISHED 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/11/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Misc
Corrective Action Required
12/11/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC BEFORE APPROVAL. MAINTAIN SAFETY CONDITIONS WITH CONSTRUCTION COMPLETION.
Occupancy Inspection - Codes Commercial Partial 12/16/2014 at 12:00 AM 12/16/2014
Misc
Corrective Action Required
12/15/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/15/2014
MAIN FLOOR: 1) INSTALLATION OF LIGHTING GRID IN 103 IN PROGRESS. MAINTAIN CONSTRUCTION SAFETY IF STAFF USE OF BUILDING COMMENCES PRIOR TO COMPLETION. 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: PANEL MUST BE IDENTIFIED ON FRONT AND AT FEEDER SOURCE. EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE". 9) TERMINATE AND ENCLOSE ALL UNTERMINATED ELECTRICAL CONDUCTORS. EXAMPLE: RM 102 10) FLOOR RECEPTACLES AT 102 NOT FINISHED 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS. 13) HOLES IN RESTROOM FLOORS MUST BE FILLED TO MAKE NON-ABSORBENT
Misc
Corrective Action Required
12/15/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Misc
Corrective Action Required
12/15/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC BEFORE APPROVAL. MAINTAIN SAFETY CONDITIONS WITH CONSTRUCTION COMPLETION.
Occupancy Inspection - Codes Commercial Partial 12/18/2014 at 12:00 AM 12/18/2014
Misc
Corrective Action Required
12/16/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/16/2014
MAIN FLOOR: 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT MUWT BE SPECIFIC. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED. FULLY COVER HOLE WHERE RECEPT WAS ELIMINATED AT SOUTH WALL. 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS. 13) HOLES IN RESTROOM FLOORS AND WALLS WITHIN 24" OF W.C. MUST BE FILLED TO MAKE NON-ABSORBENT.
Misc
Corrective Action Required
12/16/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Misc
Corrective Action Required
12/16/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC BEFORE APPROVAL. MAINTAIN SAFETY CONDITIONS WITH CONSTRUCTION COMPLETION.
Occupancy Inspection - Codes Commercial Partial 12/18/2014 at 12:00 AM 12/18/2014
Misc
Corrective Action Required
12/18/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 2) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULES AT PANELS "A" AND "B" NOT APPROVED. 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/18/2014
MAIN FLOOR: 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULE AT PANEL "C" NOT APPROVED. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED. FULLY COVER HOLE WHERE RECEPT WAS ELIMINATED AT SOUTH WALL. 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS. 13) HOLES IN RESTROOM FLOORS AND WALLS WITHIN 24" OF W.C. MUST BE FILLED TO MAKE NON-ABSORBENT.
Misc
Corrective Action Required
12/18/2014
EXTERIOR: 1) NEW GUARDS & HANDRAILS AT FRONT & REAR STAIRS NOT IBC/ANSI COMPLIANT. 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Misc
Corrective Action Required
12/18/2014
OCCUPANCY STATUS: OK TO SET UP FOR BUSINESS. NO PUBLIC BEFORE APPROVAL. MAINTAIN SAFETY CONDITIONS WITH CONSTRUCTION COMPLETION.
Occupancy Inspection - Codes Commercial Partial 12/22/2014 at 12:00 AM 12/22/2014
Misc
Corrective Action Required
12/18/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 2) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULES AT PANELS "A" AND "B" NOT APPROVED. 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/18/2014
MAIN FLOOR: 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULE AT PANEL "C" NOT APPROVED. 10) FLOOR RECEPTACLES AT 102 NOT FINISHED. FULLY COVER HOLE WHERE RECEPT WAS ELIMINATED AT SOUTH WALL. 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS. 13) HOLES IN RESTROOM FLOORS AND WALLS WITHIN 24" OF W.C. MUST BE FILLED TO MAKE NON-ABSORBENT.
Misc
Corrective Action Required
12/18/2014
EXTERIOR: 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Occupancy Inspection - Codes Commercial Partial 12/23/2014 at 12:00 AM 12/23/2014
Misc
Corrective Action Required
12/22/2014
BASEMENT: 1) OBTAIN APPROVAL OF FIRE DEPARTMENT 2) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULES AT PANELS "A" AND "B" NOT APPROVED. 4) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/22/2014
MAIN FLOOR: 2) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 7) OBTAIN FIRE DEPARTMENT APPROVAL. 8) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULE AT PANEL "C" NOT APPROVED. 10) FLOOR RECEPTACLES AT 102: FULLY COVER HOLE WHERE RECEPT WAS ELIMINATED AT SOUTH WALL. SOUTH FLOOR DUPLEX @ EAST WALL NOT HOT FOR TEST. 12) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS.
Misc
Corrective Action Required
12/22/2014
EXTERIOR: 2) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 4) ROOFTOP ELECTRICAL RECEPTACLE MUST BE SECURED TO STRUCTURE.
Occupancy Inspection - Fire Passed 1/8/2015 at 12:00 AM 01/08/2015
Occupancy Inspection - Codes Commercial Partial 1/13/2015 at 12:00 AM 01/13/2015
Misc
Corrective Action Required
12/23/2014
1) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH AND NOT CLOSED TO LESS THAN 4" TO AT LEAST 36" HIGH PER IBC. 2) GUARD AT INTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 3) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. 4) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT.
Misc
Resolved
01/13/2015
1) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT; DEEMED ALLOWABLE EXCEPTION. 2) NEC 408.4: LABELING AT ELECTRICAL PANELS: CIRCUIT LABELING MUST BE CURRENT, SPECIFIC, AND CLEAR. PANEL SCHEDULE AT PANEL "C" NOT APPROVED. 3) FLOOR RECEPTACLES AT 102: FULLY COVER HOLE WHERE RECEPT WAS ELIMINATED AT SOUTH WALL. SOUTH FLOOR DUPLEX @ EAST WALL NOT HOT FOR TEST. 4) GUARD AT STAIR TO BASEMENT NOT 42" HIGH PER IBC. CAUTION TO OWNER AND OCCUPANTS.
Misc
Resolved
01/13/2015
EXTERIOR:
Occupancy Inspection - Codes Commercial Partial 1/16/2015 at 12:00 AM 01/16/2015
Misc
Corrective Action Required
01/13/2015
1) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH AND NOT CLOSED TO LESS THAN 4" TO AT LEAST 36" HIGH PER IBC. 2) GUARD AT INTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 3) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. 4) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT.
Misc
Corrective Action Required
01/16/2015
John, I visited the site and looked at items 2, 3 and 4 listed on your inspection report dated Tuesday January 13, 2015. Item #2 deals with an existing guard rail at the interior set of stairs. Since the railing was existing and the building did not change occupancy classifications this guard rail will be allowed to remain as is. If in the future the guard rail becomes structurally unsound or in need of substantial repair a guard rail compliant with current code standards will need to be installed. Item #3 Same logic will be used pertaining to the wire glass as used above. The wire glass will be allowed to remain until something happens to cause the wire glass to be replaced. At that time the glass will be brought up to current standards. Item #4 This issued I believe has been address on the CMR information located in the front page of the construction drawing. The restrooms were brought into compliance with current standards as much as feasible possible. Feel free to attach this document to the permit file. Let me know if you have any additional questions. Thanks! Tracy Deister | Assistant Director of Codes Administration 220 SE Green Street | Lee's Summit, MO 64063
Occupancy Inspection - Codes Commercial Full C of O 1/16/2015 at 12:00 AM 01/16/2015
Misc
Resolved
01/16/2015
1) EXISTING GUARD AROUND EXTERIOR STAIR TO BASEMENT NOT 42" HIGH AND NOT CLOSED TO LESS THAN 4" TO AT LEAST 36" HIGH PER IBC.
Misc
Resolved
01/16/2015
2) GUARD AT INTERIOR STAIR TO BASEMENT NOT 42" HIGH PER IBC. 3) WIRE GLASS VISION PANELS NOT COMPLIANT WITH CURRENT CODE. 4) LAV APRONS AT RESTROOMS NOT ANSI COMPLIANT.
Rough Mechanical Inspection - Commercial Passed 11/25/2014 at 12:00 AM 01/16/2015
Misc
Resolved
01/16/2015
- NO ONE AVAILABLE FOR INSPECTION
Documents & Images
Date Uploaded File Type Document Name
02/27/2014 Letter Fire Building Plan Review
03/07/2014 Letter Codes P/R Corrections Document
07/25/2014 Letter Codes Plan Review Conditions
07/25/2014 Letter Codes Building Permit
09/09/2014 Letter Inspection Summary
09/10/2014 Letter Inspection Summary
09/15/2014 Letter Inspection Summary
09/16/2014 Letter Inspection Summary
10/17/2014 Letter Inspection Summary
10/30/2014 Letter Inspection Summary
11/06/2014 Letter Inspection Summary
11/11/2014 Letter Inspection Summary
12/01/2014 Letter Inspection Summary
12/05/2014 Letter Inspection Summary
12/10/2014 stair guard detail revision
12/11/2014 Letter Inspection Summary
12/16/2014 Letter Inspection Summary
12/18/2014 Letter Inspection Summary
12/18/2014 Letter Inspection Summary
12/23/2014 Letter Inspection Summary
01/13/2015 Letter Inspection Summary
01/16/2015 Letter Inspection Summary
01/21/2015 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home