Permit Application Status

PRCOM20121405


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20121405
Building Permit - Commercial
Certificate of Occupancy
DACUR INVESTMENT COMPANY INC
CHANGE OF TENANT
COMPLETE INTERIOR BUILDOUT AND EXTERIOR FACADE UPDATE
06/21/2012
08/16/2012
10/15/2014
05/14/2013
Locations
Contacts
DARLAND CONSTRUCTION CO, Address:4115 S 133RD ST, Phone:(402) 827-8202  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
WESTERN ENTERPRISE INC, Address:956 OSAGE AVE, Phone:(913) 342-0505  
  
DACUR INVESTMENT COMPANY INC, Address:2700 KENDALLWOOD PKWY # 208  
WESTERN ENTERPRISE INC, Address:956 OSAGE AVE, Phone:(913) 342-0505  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 01/09/2013 01/09/2013
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
01/09/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Revised plans received January 9, 2013
Installation acceptance testing
Corrective Action Required
01/09/2013

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Sprinkler Plan Review Released for Construction 12/14/2012 12/14/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/14/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received for modication of the FDC and back flow vault on November 13, 2012.
Misc
Corrective Action Required
12/14/2012

Provide a one way check valve at the at the base of the riser manifold.
Misc
Corrective Action Required
12/14/2012

The private hydrant shall be painted yellow with a silver bonnet. Verified at inspection.
Installation acceptance testing
Corrective Action Required
12/14/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A flow test of the system shall be completed. Call (816) 969-1300 to schedule a test.
Misc
Corrective Action Required
12/14/2012

The valve and vault shall be secured. Verified at inspection.
Misc
Corrective Action Required
12/14/2012

The FDC shall be marked to indicate the occupancies served by the FDC. Verified at inspections.
Sprinkler Plan Review Released for Construction 10/02/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/02/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received 0ctober 1, 2012.
Installation acceptance testing
Corrective Action Required
10/02/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow tests.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/02/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of a current annual inspection. Verified at inspection.
Misc
Corrective Action Required
10/02/2012

Confirm appropriate temperature settings for the saunas.
Alarm Plan Review Released for Construction 09/05/2012
Brian Austerman
Misc
Corrective Action Required
09/05/2012

OUTSIDE HORN STROBE TO ACTIVATE ON WATERFLOW ALARM ONLY, VERIFIED AT ALARM TESTING
Misc
Corrective Action Required
09/05/2012

DUCT DETECTORS SHALL TRANSMIT A SUPERVISORY SIGNAL TO THE PANEL AND SHUT DOWN THE UNIT, VERIFIED AT ALARM TESTING
Misc
Corrective Action Required
09/05/2012

CALL 816-969-1300 TO SCHEDULE ALARM TESTING PRIOR TO THE FINAL
Internal Plan Review (Res) Approved 08/31/2012 08/15/2012
Mike Weisenborn
True
Fire Plan Review Approved 08/06/2012 08/07/2012
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
08/07/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide plans for approval for any sprinkler modifications
Construction documents for fire alarm systems
Corrective Action Required
08/07/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide plans for approval for any alarm system modifications
Portable fire extinguishers - general
Corrective Action Required
08/07/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum size of 2A10B:C extinguishers, verified at inspection
Address numbers required
Corrective Action Required
08/07/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Provide addressing on all exterior doors, verified at inspection
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
08/07/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: building's sprinkler system must have current certification, verified at final inspection
Misc
Corrective Action Required
08/07/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: Activation of a duct smoke detector shall initiate a supervisory signal and shut down the unit. Verified at alarm testing
Building Plan Review Approved 08/06/2012 08/06/2012
Mike Weisenborn
License contractors
Corrective Action Required
07/31/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing sub-contractors prior to permit issuance.
Misc
Partial Correction
08/06/2012

The application does not indicate which, if any, of the alternates will be included in the project. Action required - Indicate if any of the alternates will be included in the project. Mike Weisenborn 08/06/2012 11:10 AM - The replacement of the storefront is the only alternate accepted.
Misc
Corrective Action Required
07/31/2012

I am unable to locate any structural information regarding the new and relocated rtu's. Action required - Provide documentation from an engineer licensed in the State of Missouri which indicates that the existing roof structure is capable of supporting the new and relocated rtu's or what alterations to the roof structure are required.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
07/31/2012

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Provide emergency lighting on the exterior of the building as required by item 5 above.
License Tax Codes Approved 07/03/2012 07/02/2012
Mike Weisenborn
Internal Plan Review (Res) Rejected 07/03/2012 07/02/2012
Mike Weisenborn
Building Plan Review Rejected 07/03/2012 07/02/2012
Mike Weisenborn
License contractors
Corrective Action Required
07/02/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the licensed mechanical, electrical and plumbing sub-contractors prior to permit issuance.
Misc
Corrective Action Required
07/02/2012

The application does not indicate which, if any, of the alternates will be included in the project. Action required - Indicate if any of the alternates will be included in the project.
Misc
Corrective Action Required
07/02/2012

I am unable to locate any structural information regarding the new and relocated rtu's. Action required - Provide documentation from an engineer licensed in the State of Missouri which indicates that the existing roof structure is capable of supporting the new and relocated rtu's or what alterations to the roof structure are required.
Bldg - Means of egress illumination - Emergency power
Corrective Action Required
07/02/2012

2006 IBC 1006.3 - Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas. 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in building required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in building required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702. Action required - Provide emergency lighting on the exterior of the building as required by item 5 above.
Fire Plan Review Approved 07/03/2012 06/22/2012
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
06/22/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide plans for approval for any sprinkler modifications
Construction documents for fire alarm systems
Corrective Action Required
06/22/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide alarm plans for approval
Misc
Corrective Action Required
06/22/2012

1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. Action Required: For information only. Only panic hardware or thumb throw on egress doors are to be allowed. Verified at inspection
Portable fire extinguishers - general
Corrective Action Required
06/22/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum size of 2A10B:C extinguishers for every 75' of travel distance. Verified at inspection
Address numbers required
Corrective Action Required
06/22/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Provide addressing on all exterior doors, verified at inspection
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/22/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: Sprinkler system is to have current ceritfication tag at time of final, for information only
Misc
Corrective Action Required
06/22/2012

907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Action Required: Activation of a duct detector shall initiate a supervisory signal and shut down the unit. Verified at alarm testing.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $6,625.87 $6,625.87 Paid 08/16/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 8/23/2012 8/23/2012 at 12:00 AM 08/23/2012
Misc
Partial Correction
08/23/2012
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DWV PIPING AT FOLLOWING LOCATIONS: RESTROOM AND WASHER GROUP PER C8/M1.1 + 4" BUILDING DRAIN NORTH TO D.9/10;
Underslab Plumbing Inspection - Commercial Passed 8/27/2012 8/27/2012 at 12:00 AM 08/27/2012
Misc
Resolved
08/27/2012
OK TO COVER WHEN READY UNDER-SLAB PVC SANITARY DWV PLUMBING PIPING.
Underslab Electrical Inspection - Commercial Partial 8/28/2012 8/28/2012 at 12:00 AM 08/28/2012
Misc
Partial Correction
08/28/2012
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP: OK TO COVER WHEN READY FROM NORTH WALL TO WITHIN 20' OF MDP
Water Service Inspection Partial 8/29/2012 08/29/2012
Misc
Partial Correction
08/29/2012
OK TO COVER WHEN READY 2" COPPER WATER SERVICE LINE FROM STUB-UP INSIDE BUILDING TO NE CORNER, THROUGH FOOTING, NORTH TO WITHIN 5' OF METER PIT;
Water Service Inspection Passed 9/7/2012 at 12:00 AM 09/07/2012
Misc
Resolved
09/07/2012
OK TO COVER WHEN READY 2" COPPER WATER SERVICE LINE FROM STUB-UP INSIDE BUILDING TO NE CORNER, THROUGH FOOTING, NORTH TO WITHIN 5' OF METER PIT; COMPLETE TO EXISTING METER
Underslab Electrical Inspection - Commercial Passed 9/13/2012 9/13/2012 at 12:00 AM 09/13/2012
Misc
Resolved
09/13/2012
UNDER-SLAB ELECTRICAL CONDUIT MATERIAL & WORKMANSHIP: OK TO COVER WHEN READY FROM NORTH WALL TO MDP @ WEST WALL
In-wall Inspection Failed 10/2/2012 at 12:00 AM 10/02/2012
Misc
Corrective Action Required
10/02/2012
FOLLOWING APPROVED TO COVER- ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. INSTALL STUD GUARDS ON PLUMBING TOP PLATES AND ON BOTTOM PLATES. RIEINFORCE CUT STUDS WHERE PLUMBING IS INSTALLED
In-wall Inspection Partial 10/3/2012 at 12:00 AM 10/03/2012
Misc
Corrective Action Required
10/02/2012
FOLLOWING APPROVED TO COVER- ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS.
Underslab Electrical Inspection - Commercial Passed 10/8/2012 at 12:00 AM 10/08/2012
Above Ceiling Inspection Partial 10/9/2012 at 12:00 AM 10/09/2012
Misc
Partial Correction
10/09/2012
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS;
In-wall Inspection Partial 10/8/2012 10/9/2012 at 12:00 AM 10/09/2012
Misc
Partial Correction
10/09/2012
FOLLOWING APPROVED TO COVER- ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS. ROOMS NORTH OF DEMISING WALL AT CORR. 114
In-wall Inspection Partial 10/12/2012 10/12/2012 at 12:00 AM 10/12/2012
Misc
Partial Correction
10/09/2012
FOLLOWING APPROVED TO COVER- ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS; ROOMS NORTH OF DEMISING WALL AT CORR; 114; W EXTERIOR WALLS AT 109 & 110;
Above Ceiling Inspection Partial 10/16/2012 at 12:00 AM 10/16/2012
Misc
Partial Correction
10/09/2012
OK TO COVER WHEN READY GWB CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS;
Misc
Partial Correction
10/16/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD FROM 5/B TO 5/D.8;
In-wall Inspection Partial 10/22/2012 10/22/2012 at 12:00 AM 10/22/2012
Misc
Partial Correction
10/12/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYTEMS AT FOLLOWING LOCATIONS: ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS; ROOMS NORTH OF DEMISING WALL AT CORR; 114; W EXTERIOR WALLS AT 109 & 110; 109.2/142; SHORT WALLS @ 105 W&N;
Above Ceiling Inspection Partial 10/22/2012 at 12:00 AM 10/22/2012
Misc
Partial Correction
10/16/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS; 131; 150 151; 161;
Misc
Partial Correction
10/16/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD FROM 5/B TO 5/D.8;
In-wall Inspection Partial 10/23/2012 10/23/2012 at 12:00 AM 10/23/2012
Misc
Partial Correction
10/22/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYTEMS AT FOLLOWING LOCATIONS: ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS; ROOMS NORTH OF DEMISING WALL AT CORR; 114; W EXTERIOR WALLS AT 109 & 110; 109.2/142; SHORT WALLS @ 105 W&N; SHORT WALLS @ 120 W&N;
Above Ceiling Inspection Partial 10/29/2012 at 12:00 AM 10/29/2012
Misc
Partial Correction
10/22/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS; 131; 150 151; 161;
Misc
Partial Correction
10/22/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122 & 123;
Above Ceiling Inspection Partial 10/29/2012 at 12:00 AM 10/29/2012
Misc
Partial Correction
10/29/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS; 131; 150 151; 161;
Misc
Partial Correction
10/29/2012
OK TO COVER WHEN READY FRAMING OF HANGING GWB ULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122, 123, 101, 102, 120
In-wall Inspection Passed 10/29/2012 10/29/2012 at 12:00 AM 10/29/2012
Misc
Resolved
10/29/2012
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYTEMS AT FOLLOWING LOCATIONS: ROOMS SOUTH OF DEMISING WALL AT CORR. 114- BOTH SIDES OF WALL 114(DEMISING WALL) 108,109.1,110,122,121,123,120,114,112,103,102. KIDS RESTROOM AND ADJOINING WALLS; ROOMS NORTH OF DEMISING WALL AT CORR; 114; W EXTERIOR WALLS AT 109 & 110; 109.2/142; SHORT WALLS @ 105 W&N; SHORT WALLS @ 120 W&N;
Above Ceiling Inspection Partial 11/5/2012 11/5/2012 at 12:00 AM 11/05/2012
Misc
Partial Correction
10/29/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS; 131; 150 151; 161;
Misc
Partial Correction
10/29/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122, 123, 101, 102, 120
Misc
Corrective Action Required
11/05/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: MAX 2' BORDERS ONLY AT ALL SPACES EXCEPT 111 & 112
Misc
Corrective Action Required
11/05/2012
REMOVE ALL ABANDONED PIPING AND OTHER SYSTEM COMPONENTS AND HANGERS
Misc
Corrective Action Required
11/05/2012
NEC 300-11 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: SOME NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]
Rough Framing Inspection - Commercial Not Ready 11/5/2012 11/5/2012 at 12:00 AM 11/05/2012
Misc
Corrective Action Required
11/05/2012
FRAMING/BRACING OF FACADE HEIGHT EXTENSION REQUIRES CLARIFICATION BY STRUCTURAL ENGINEER.
Above Ceiling Inspection Partial 11/8/2012 11/8/2012 at 12:00 AM 11/08/2012
Misc
Partial Correction
11/05/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 152, 162 + M/W SHOWERS; 131; 150 151; 161;
Misc
Partial Correction
11/05/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122, 123, 101, 102, 120
Misc
Partial Correction
11/08/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 109 EXCEPT WEST 8' WHERE ABANDONED PIPING IS TO BE REMOVED. NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Misc
Corrective Action Required
11/05/2012
REMOVE ALL ABANDONED PIPING AND OTHER SYSTEM COMPONENTS AND HANGERS @ 109 WEST 8'
Misc
Resolved
11/08/2012
NEC 300-11 & 334-10 INSTALLATION OF MC ELECTRICAL CABLE: SOME NOT SECURELY FASTENED WITHIN 12" OF ENTRY TO BOXES [ALLOWABLE EXCEPTION: FIXTURE WHIPS NOT IN EXCESS OF 6` LONG]
Misc
Corrective Action Required
11/08/2012
GWB CLOUD CEILING AT 102 LOBBY NOT PER DRAWING. SUPPORT NOT APPROVED WITHOUT A/E DIRECTION.
Above Ceiling Inspection Partial 11/9/2012 (8:00 to 5:00) 11/9/2012 at 12:00 AM 11/09/2012
Misc
Partial Correction
11/08/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 131; 150 151; 152, 161; 162; M/W SHOWERS
Misc
Partial Correction
11/08/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122, 123, 101, 102, 120
Misc
Partial Correction
11/08/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 109 EXCEPT WEST 8' WHERE ABANDONED PIPING IS TO BE REMOVED. NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Misc
Corrective Action Required
11/08/2012
REMOVE ALL ABANDONED PIPING AND OTHER SYSTEM COMPONENTS AND HANGERS @ 109 WEST 8'
Misc
Corrective Action Required
11/08/2012
GWB CLOUD CEILING AT 102 LOBBY NOT PER DRAWING. SUPPORT NOT APPROVED WITHOUT A/E DIRECTION.
Gas Piping Inspection - Commercial Not Ready 11/12/2012 11/13/2012 at 12:00 AM 11/13/2012
Above Ceiling Inspection Partial 11/13/2012 at 12:00 AM 11/13/2012
Misc
Resolved
11/13/2012
OK TO COVER WHEN READY GWB CEILING/SOFFIT FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: TWO SAUNA ROOMS; 131; 150 151; 152, 161; 162; M/W SHOWERS
Misc
Resolved
11/13/2012
OK TO COVER WHEN READY FRAMING OF HANGING BULKHEAD: FROM 5/B TO 5/D.8; AT EAST WALL OF SPACES 122, 123, 101, 102, 120
Misc
Partial Correction
11/13/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 150/150.1; 160/160.1; 109 EXCEPT WEST 8' WHERE ABANDONED PIPING IS TO BE REMOVED. NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Misc
Corrective Action Required
11/13/2012
REMOVE ALL ABANDONED PIPING AND OTHER SYSTEM COMPONENTS AND HANGERS @ 109 WEST 8'
Misc
Corrective Action Required
11/13/2012
GWB CLOUD CEILING AT 102 LOBBY NOT PER DRAWING. SUPPORT NOT APPROVED WITHOUT A/E DIRECTION.
Sprinkler - Hydrostatic Test Passed 11/14/2012 at 10:00 AM 11/14/2012
Electrical Service Inspection Not Ready 11/14/2012 11/14/2012 at 12:00 AM 11/14/2012
Misc
Corrective Action Required
11/14/2012
DRAWING REVISION REQUIRED + UNCERTAINTY RE ADDRESSING
Gas Piping Inspection - Commercial Partial 11/14/2012 11/14/2012 at 12:00 AM 11/14/2012
Misc
Partial Correction
11/14/2012
PAINTING OF EXTERIOR EXPOSED PIPE IN PROGRESS
Misc
Partial Correction
11/14/2012
ROOFTOP PIPE SUPPORTS PARTIALLY COMPLETED
Misc
Corrective Action Required
11/14/2012
RTU GAS PIPING ABOVE PHASE 1 AREA NOT COMPLIANT
Above Ceiling Inspection Partial 11/15/2012 11/15/2012 at 12:00 AM 11/15/2012
Misc
Partial Correction
11/13/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 150/150.1; 160/160.1; 101; 109 EXCEPT WEST 8' WHERE ABANDONED PIPE HANGERS ARE TO BE REMOVED. NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Misc
Corrective Action Required
11/13/2012
REMOVE ALL ABANDONED PIPE HANGERS @ 109 WEST 8'
Misc
Resolved
11/15/2012
GWB CLOUD CEILING AT 102 LOBBY NOT PER DRAWING. SUPPORT NOT APPROVED WITHOUT A/E DIRECTION.
Occupancy Inspection - Codes Commercial Failed 11/16/2012 11/16/2012 at 12:00 AM 11/16/2012
Misc
Corrective Action Required
11/16/2012
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
11/16/2012
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Misc
Corrective Action Required
11/16/2012
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY. BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
11/16/2012
COMPLETE ALL CONSTRUCTION ACTIVITY
Misc
Corrective Action Required
11/16/2012
REVISIONS OF ELECTRICAL SERVICE CONFIGURATION PRESENTLY SUBMITTED FOR APPROVAL MUST BE APPROVED BEFORE SERVICE CAN BE INSPECTED.
Misc
Corrective Action Required
11/16/2012
GLAZING AT HAZARDOUS LOCATIONS SUBJECT TO APPROVAL WHEN INSTALLED.
Misc
Corrective Action Required
11/16/2012
COMPLETE ELECTRICAL PANEL SCHEDULES INCLUDING DESIGNATING ALL SPARES
Misc
Corrective Action Required
11/16/2012
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES
Misc
Corrective Action Required
11/16/2012
BUILDING FACADE, SOFFIT BELOW, AND ALL ASSOCIATED REMAINING WORK SUBJECT TO APPROVAL WHEN READY FOR INSPECTION
Misc
Corrective Action Required
11/16/2012
EXPOSED GAS PIPING NOT PAINTED BELOW UPPER ROOF
Misc
Corrective Action Required
11/16/2012
IDENTIFY RTU's: DESIGNATE ADDRESS NUMBER AND RTU NUMBER
Misc
Corrective Action Required
11/16/2012
ELECTRICAL RECEPTACLES AT RTU's NOT HOT FOR TEST
Misc
Corrective Action Required
11/16/2012
REMOVE ALL DEBRIS AND UNUSED MATERIAL FROM ROOFTOP
Misc
Corrective Action Required
11/16/2012
ADDRESS LABELING OF GAS SERVICE ENTRY PIPE: AFFIX PERMANENT TAG/LABEL TO LOAD SIDE PIPE. FELT TIP MARKER NOT APPROVABLE.
Alarm Test Passed 11/16/2012 at 12:00 AM 11/16/2012
Sprinkler - Flow Test Partial 11/16/2012 at 12:00 AM 11/16/2012
Occupancy Inspection - Fire Temporary C of O 11/16/2012 at 12:00 AM 11/16/2012
Misc
Corrective Action Required
11/16/2012
- door access keys to place in the knox box -numeric addressing on exterior of all doors - label sprinkler room door - discontinue all unused wiring A/C wiring and alarm wiring -close elec. panel - close all open j-boxes - remove all const equip, debris, material ** fire line backflow neeeds to be assessment and certified
Above Ceiling Inspection Partial 11/16/2012 at 12:00 AM 11/16/2012
Misc
Partial Correction
11/15/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 150/150.1; 160/160.1; 101; 109: NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Misc
Resolved
11/16/2012
REMOVE ALL ABANDONED PIPE HANGERS @ 109 WEST 8'
Above Ceiling Inspection Not Ready 11/19/2012 at 12:00 AM 11/19/2012
Misc
Partial Correction
11/16/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 150/150.1; 160/160.1; 101; 109: NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Occupancy Inspection - Fire Temporary C of O 11/20/2012 at 12:00 AM 11/20/2012
Misc
Corrective Action Required
11/16/2012
- door access keys to place in the knox box -numeric addressing on exterior of all doors - label sprinkler room door - discontinue all unused wiring A/C wiring and alarm wiring -close elec. panel - close all open j-boxes - remove all const equip, debris, material ** fire line backflow neeeds to be assessment and certified
Occupancy Inspection - Codes Commercial Failed 11/20/2012 11/20/2012 at 12:00 AM 11/20/2012
Misc
Corrective Action Required
11/16/2012
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
11/16/2012
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Misc
Resolved
11/20/2012
LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL LS CODE OF ORDINANCES 17-309: DISPLAY OF "NO SMOKING" SIGN(S) REQUIRED AT PUBLIC ENTRY(IES). SHALL BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY. BE CONSPICOUS AT EACH PUBLIC POINT OF ENTRY.
Misc
Corrective Action Required
11/16/2012
PROTECT PUBLIC FROM CONSTRUCTION ACTIVITY AT FRONT OF BUILDING
Misc
Corrective Action Required
11/16/2012
REVISIONS OF ELECTRICAL SERVICE CONFIGURATION PRESENTLY SUBMITTED FOR APPROVAL MUST BE APPROVED BEFORE SERVICE CAN BE INSPECTED.
Misc
Resolved
11/20/2012
GLAZING AT HAZARDOUS LOCATIONS SUBJECT TO APPROVAL WHEN INSTALLED.
Misc
Resolved
11/20/2012
COMPLETE ELECTRICAL PANEL SCHEDULES INCLUDING DESIGNATING ALL SPARES
Misc
Resolved
11/20/2012
NEC 370-20; IRC E3806.5-6 SET-BACK OF ELECTRICAL RECEPTACLE / SWITCH BOXES: MUST BE FLUSH WITH COMBUSTIBLE WALL SURFACE; 1/4" MAXIMUM SET-BACK @ NON-COMBUSTIBLE SURFACES
Misc
Corrective Action Required
11/16/2012
BUILDING FACADE, SOFFIT BELOW, AND ALL ASSOCIATED REMAINING WORK SUBJECT TO APPROVAL WHEN READY FOR INSPECTION
Misc
Corrective Action Required
11/16/2012
EXPOSED GAS PIPING NOT PAINTED BELOW UPPER ROOF
Misc
Resolved
11/20/2012
IDENTIFY RTU's: DESIGNATE ADDRESS NUMBER AND RTU NUMBER
Misc
Resolved
11/20/2012
ELECTRICAL RECEPTACLES AT RTU's NOT HOT FOR TEST
Misc
Resolved
11/20/2012
REMOVE ALL DEBRIS AND UNUSED MATERIAL FROM ROOFTOP
Misc
Corrective Action Required
11/16/2012
ADDRESS LABELING OF GAS SERVICE ENTRY PIPE: AFFIX PERMANENT TAG/LABEL TO LOAD SIDE PIPE. FELT TIP MARKER NOT APPROVABLE.
Occupancy Inspection - Codes Commercial Temporary C of O 11/21/2012 at 12:00 AM 11/21/2012
Misc
Corrective Action Required
11/20/2012
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Resolved
11/21/2012
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Misc
Resolved
11/21/2012
PROTECT PUBLIC FROM CONSTRUCTION ACTIVITY AT FRONT OF BUILDING
Misc
Resolved
11/21/2012
REVISIONS OF ELECTRICAL SERVICE CONFIGURATION PRESENTLY SUBMITTED FOR APPROVAL MUST BE APPROVED BEFORE SERVICE CAN BE INSPECTED.
Misc
Resolved
11/21/2012
BUILDING FACADE, SOFFIT BELOW, AND ALL ASSOCIATED REMAINING WORK SUBJECT TO APPROVAL WHEN READY FOR INSPECTION
Misc
Resolved
11/21/2012
EXPOSED GAS PIPING NOT PAINTED BELOW UPPER ROOF
Misc
Resolved
11/21/2012
ADDRESS LABELING OF GAS SERVICE ENTRY PIPE: AFFIX PERMANENT TAG/LABEL TO LOAD SIDE PIPE. FELT TIP MARKER NOT APPROVABLE.
Misc
Corrective Action Required
11/21/2012
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
11/21/2012
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
11/21/2012
PHASE 1 AREA IMPROVEMENT WAS PERMITTED, INSPECTED, AND APPROVED FOR TEMPORARY USE ONLY PENDING COMPLETION OF MAIN AREA ENCOMPASSED BY THIS PERMIT SCOPE. NOT APPROVED FOR PERMANENT USE.
Above Ceiling Inspection Passed 11/21/2012 11/21/2012 at 12:00 AM 11/21/2012
Misc
Resolved
11/21/2012
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: 105; 108 AFTER TEMP ELECT WIRING IS REMOVED AND TWO 2x4 LAY-IN LIGHT FIXTURES ARE INSTALLED AND SECURED; 111; 112; 113; 114; 122; 123; 130; 150/150.1; 160/160.1; 101; 109: NOTE THAT SOUTH 15' MAY BE COVERED ON TEMPORARY BASIS ONLY PENDING RESOLUTION OF TIE-IN WITH PHASE 1 TEMPORARY USE AREA.
Miscellaneous Inspection Passed 11/30/2012 11/30/2012 at 12:00 AM 11/30/2012
Occupancy Inspection - Codes Commercial Temporary C of O 12/4/2012 at 12:00 AM 12/04/2012
Misc
Corrective Action Required
11/21/2012
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
11/21/2012
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
11/21/2012
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
11/21/2012
PHASE 1 AREA IMPROVEMENT WAS PERMITTED, INSPECTED, AND APPROVED FOR TEMPORARY USE ONLY PENDING COMPLETION OF MAIN AREA ENCOMPASSED BY THIS PERMIT SCOPE. NOT APPROVED FOR PERMANENT USE.
Occupancy Inspection - Codes Commercial Failed 1/9/2013 1/9/2013 at 12:00 AM 01/09/2013
Misc
Corrective Action Required
12/04/2012
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
12/04/2012
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
12/04/2012
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
12/04/2012
PHASE 1 AREA: A) SW ROOM - PROVIDE SLACK WIRES ON 2x4 LAY-IN LIGHT FIXTURES - SUMP PUMP DUPLEX RECEPTACLE NOT GFI - RECEPTACLE ABOVE SUMP PUMP NOT GFI AND LACKS COVER PLATE B) GENERAL AREA - SUPPORT MC CABLE TO STRUCURE -- NOT ON SPRINKLER PIPE - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES - PLUG UNUSED OPENINGS IN J-BOXES - CHECK ALL CORD & PLUG WIRING AT HIGH BAY LIGHTS; REPAIR/REPLACE ANY DAMAGED C) ELECT RM @ NW: - INSTALL CLOSER @ SW EGRESS DOOR AND CHANGE LOCK TO THUMB TYPE - SUPPORT HVAC FLEX DUCT AND DIFFUSER - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES & PANELS - CLOSE OPEN J-BOX(ES) - UPDATE PANEL SCHEDULES AND MAKE LEGIBLE
Occupancy Inspection - Fire Temporary C of O 1/9/2013 at 12:00 AM 01/10/2013
Misc
Corrective Action Required
11/20/2012
- door access keys to place in the knox box -numeric addressing on exterior of all doors - label sprinkler room door - discontinue all unused wiring A/C wiring and alarm wiring -close elec. panel - close all open j-boxes - remove all const equip, debris, material ** fire line backflow neeeds to be assessment and certified
Misc
Corrective Action Required
01/10/2013
final inspection for occupancy of the temporary work-out area. 2nd exit- provide exit sign over office door, change the keyed lock to thumb latch - intall alarm notification (strobes) in the restrooms - electrical conduit need to be removed from the sprinkler system pipiong - install pull stations at exits
Occupancy Inspection - Codes Commercial Temporary C of O 1/10/2013 at 12:00 AM 01/10/2013
Misc
Corrective Action Required
01/09/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
01/09/2013
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
01/09/2013
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
01/09/2013
PHASE 1 AREA: A) SW ROOM - PROVIDE SLACK WIRES ON 2x4 LAY-IN LIGHT FIXTURES - SUMP PUMP DUPLEX RECEPTACLE NOT GFI - RECEPTACLE ABOVE SUMP PUMP NOT GFI AND LACKS COVER PLATE B) GENERAL AREA - SUPPORT MC CABLE TO STRUCURE -- NOT ON SPRINKLER PIPE - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES - PLUG UNUSED OPENINGS IN J-BOXES - CHECK ALL CORD & PLUG WIRING AT HIGH BAY LIGHTS; REPAIR/REPLACE ANY DAMAGED C) ELECT RM @ NW: - INSTALL CLOSER @ SW EGRESS DOOR AND CHANGE LOCK TO THUMB TYPE - SUPPORT HVAC FLEX DUCT AND DIFFUSER - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES & PANELS - CLOSE OPEN J-BOX(ES) - UPDATE PANEL SCHEDULES AND MAKE LEGIBLE
Occupancy Inspection - Codes Commercial Temporary C of O 3/1/2013 at 12:00 AM 03/01/2013
Misc
Corrective Action Required
01/10/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT
Misc
Corrective Action Required
01/10/2013
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
01/10/2013
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
01/10/2013
PHASE 1 AREA: A) SW ROOM - PROVIDE SLACK WIRES ON 2x4 LAY-IN LIGHT FIXTURES - SUMP PUMP DUPLEX RECEPTACLE NOT GFI - RECEPTACLE ABOVE SUMP PUMP NOT GFI AND LACKS COVER PLATE B) GENERAL AREA - SUPPORT MC CABLE TO STRUCURE -- NOT ON SPRINKLER PIPE - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES - PLUG UNUSED OPENINGS IN J-BOXES - CHECK ALL CORD & PLUG WIRING AT HIGH BAY LIGHTS; REPAIR/REPLACE ANY DAMAGED C) ELECT RM @ NW: - INSTALL CLOSER @ SW EGRESS DOOR AND CHANGE LOCK TO THUMB TYPE - SUPPORT HVAC FLEX DUCT AND DIFFUSER - SECURE MC CABLE WITHIN 12" OF ENTRY TO BOXES & PANELS - CLOSE OPEN J-BOX(ES) - UPDATE PANEL SCHEDULES AND MAKE LEGIBLE
Occupancy Inspection - Codes Commercial Temporary C of O 4/4/2013 4/2/2013 at 12:00 AM 04/02/2013
Misc
Corrective Action Required
03/01/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING.
Misc
Corrective Action Required
03/01/2013
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Corrective Action Required
03/01/2013
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Corrective Action Required
03/01/2013
IN ELECT ROOM AT SIEMANS ELECT PANEL DESIGNATE CIRCUIT BREAKER POSITIONS ON PANEL FRONT 1 THRU 18.
Occupancy Inspection - Codes Commercial Temporary C of O 4/4/2013 4/4/2013 at 12:00 AM 04/04/2013
Misc
Corrective Action Required
04/02/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING.
Misc
Resolved
04/04/2013
PROVIDE ELECTRICAL RECEPTACLE WITHIN 10 METERS OF RTU'S #11 AND #12
Misc
Resolved
04/04/2013
NO CLAMPS AT THREE SUPPORTS FOR GAS PIPING TO RTU #12
Misc
Resolved
04/04/2013
IN ELECT ROOM AT SIEMANS ELECT PANEL DESIGNATE CIRCUIT BREAKER POSITIONS ON PANEL FRONT 1 THRU 18.
Rough Framing Inspection - Commercial Passed 4/18/2013 at 12:00 AM 04/18/2013
Misc
Resolved
04/18/2013
FRAMING/BRACING OF FACADE HEIGHT EXTENSION REQUIRES CLARIFICATION BY STRUCTURAL ENGINEER.
Electrical Service Inspection Passed 4/18/2013 at 12:00 AM 04/18/2013
Misc
Resolved
04/18/2013
DRAWING REVISION REQUIRED + UNCERTAINTY RE ADDRESSING
Gas Piping Inspection - Commercial Passed 4/18/2013 at 12:00 AM 04/18/2013
Misc
Resolved
04/18/2013
PAINTING OF EXTERIOR EXPOSED PIPE IN PROGRESS
Misc
Resolved
04/18/2013
ROOFTOP PIPE SUPPORTS PARTIALLY COMPLETED
Misc
Resolved
04/18/2013
RTU GAS PIPING ABOVE PHASE 1 AREA NOT COMPLIANT
Occupancy Inspection - Codes Commercial Temporary C of O 4/18/2013 at 12:00 AM 04/18/2013
Misc
Corrective Action Required
04/04/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING.
Occupancy Inspection - Codes Commercial Partial 4/25/2013 at 12:00 AM 04/25/2013
Misc
Partial Correction
04/25/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR
Occupancy Inspection - Codes Commercial Partial 4/26/2013 at 12:00 AM 04/26/2013
Misc
Partial Correction
04/25/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR
Occupancy Inspection - Codes Commercial Partial 4/30/2013 at 12:00 AM 04/30/2013
Misc
Partial Correction
04/26/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/30/13: ROCK FILL TO GRADE IN AREA AROUND VAULT; CONTRACTOR NOT ON SITE @ 16:00
Occupancy Inspection - Codes Commercial Temporary C of O 5/2/2013 at 12:00 AM 05/02/2013
Misc
Partial Correction
04/30/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/30/13: ROCK FILL TO GRADE IN AREA AROUND VAULT; CONTRACTOR NOT ON SITE @ 16:00
Occupancy Inspection - Codes Commercial Temporary C of O 5/9/2013 at 12:00 AM 05/09/2013
Misc
Partial Correction
05/02/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT AND WATER DEPARTMENT. eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/30/13: ROCK FILL TO GRADE IN AREA AROUND VAULT; CONTRACTOR NOT ON SITE @ 16:00
Occupancy Inspection - Codes Commercial Temporary C of O 5/9/2013 at 12:00 AM 05/09/2013
Misc
Partial Correction
05/09/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/30/13: ROCK FILL TO GRADE IN AREA AROUND VAULT; CONTRACTOR NOT ON SITE @ 16:00 5/8/13: WU CLEAR PER BEN H. ADVISED ADAM @ DARLAND TO CONTACT J DIR TO GET FD CLEARED.
Occupancy Inspection - Fire Passed 5/13/2013 at 12:00 AM 05/13/2013
Misc
Corrective Action Required
05/13/2013
all of the items for the backflow on the fire line, fire hydrant and the FDC have been completed
Occupancy Inspection - Codes Commercial Full C of O 5/14/2013 at 12:00 AM 05/14/2013
Misc
Resolved
05/14/2013
RESOLVE ISSUES WITH FIRE DEPARTMENT eg, COMPLETE AND OBTAIN APPROVAL ON SPRINKLER F.P. PIPING AND BACKFLOW PREVENTION EQUIPMENT PIT WEST OF BULDING AND SPRINKLER F.P. PIPING AT SPRINKLER ROOM. STATUS CHECK... 4/25/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/26/13: CENTURY PLMBG W/I/P AT WATER SVC @ REAR 4/30/13: ROCK FILL TO GRADE IN AREA AROUND VAULT; CONTRACTOR NOT ON SITE @ 16:00 5/8/13: WU CLEAR PER BEN H. ADVISED ADAM @ DARLAND TO CONTACT J DIR TO GET FD CLEARED.
Documents & Images
Date Uploaded File Type Document Name
07/02/2012 Letter Plan Review Conditions
08/16/2012 Letter Plan Review Conditions
08/16/2012 Letter Building Permit
08/23/2012 Letter Inspection Summary
08/27/2012 Letter Inspection Summary
08/28/2012 Letter Inspection Summary
08/29/2012 Letter Inspection Summary
09/07/2012 Letter Inspection Summary
09/13/2012 Letter Inspection Summary
09/13/2012 Letter Inspection Summary
09/13/2012 Letter Inspection Summary
10/02/2012 Letter Fire (Sprinkler) Plan Review
10/02/2012 Letter Fire (Sprinkler) Plan Review
10/02/2012 Letter Inspection Summary
10/03/2012 Letter Inspection Summary
10/08/2012 Letter Inspection Summary
10/09/2012 Letter Inspection Summary
10/12/2012 Letter Inspection Summary
10/16/2012 Letter Inspection Summary
10/22/2012 Letter Inspection Summary
10/23/2012 Letter Inspection Summary
10/29/2012 Letter Inspection Summary
10/29/2012 Letter Inspection Summary
11/05/2012 Letter Inspection Summary
11/08/2012 Letter Inspection Summary
11/09/2012 Letter Inspection Summary
11/13/2012 Letter Inspection Summary
11/15/2012 Letter Inspection Summary
11/16/2012 Letter Inspection Summary
11/16/2012 Letter Fire Loss Reduction Form
11/20/2012 Letter Inspection Summary
11/21/2012 Letter Temporary Certificate of Occupancy
12/04/2012 Letter Temporary Certificate of Occupancy
12/14/2012 Letter Fire (Sprinkler) Plan Review
01/09/2013 Letter Inspection Summary
01/09/2013 Letter Fire (Sprinkler) Plan Review
01/10/2013 Letter Fire Loss Reduction Form
01/10/2013 Letter Temporary Certificate of Occupancy
03/01/2013 Letter Temporary Certificate of Occupancy
03/28/2013 Letter 10-Day Notice of Violation
04/02/2013 Letter Temporary Certificate of Occupancy
04/04/2013 Letter Temporary Certificate of Occupancy
04/18/2013 Letter Temporary Certificate of Occupancy
05/02/2013 Letter Temporary Certificate of Occupancy
05/09/2013 Letter Temporary Certificate of Occupancy
05/09/2013 Letter Temporary Certificate of Occupancy
05/13/2013 Letter Fire Loss Reduction Form
05/14/2013 Letter Field Certificate of Occupancy
05/16/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
07/05/2013 Letter Final Certificate of Occupancy
08/27/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home