Planning Application Status

PL2019335




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2019335
LION'S CHOICE
Commercial Final Development Plan
Commercial Final Development Plan
Approved
09/27/2019
TOWNSEND SUMMIT LLC
Locations
Contacts
TOWNSEND SUMMIT LLC, Address:1311 MCCORMICK RD STE 470, Phone:(303) 947-2044  
COLE/CHRIS WILSON, Address:401 S. 18TH ST, Phone:(314) 984-9887  
OCULUS INC, Address:1 S MEMORIAL DR, STE 1500, Phone:(314) 367-6100  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review No Comments 02/19/2020 02/14/2020
Mike Weisenborn
Traffic Review No Comments 02/19/2020 02/14/2020
Mike Weisenborn
Building Codes Review No Comments 02/19/2020 02/14/2020
Mike Weisenborn
Engineering Review Approved with Conditions 02/19/2020 02/14/2020
Sue Pyles, P.E.
DE C&O #11 Pavement Thickness
Corrective Action Required
02/14/2020

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
02/14/2020

Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Engineers Estimate
Corrective Action Required
02/14/2020

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $26,518.25
DE Future Repair Work
Corrective Action Required
02/14/2020

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Fire Review Approved with Conditions 02/19/2020 02/13/2020
Jim Eden
Code Statement
Informational
02/13/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Engineering Review Corrections 01/21/2020 01/21/2020
Sue Pyles, P.E.
Corrective Action Required
01/21/2020

Revise asphalt pavement typical sections to include geogrid or stabilized subgrade under the granular base course, as required bt UDO Section 8.620.
Corrective Action Required
01/21/2020

The estimate needs to have a quantity, unit price, and extension for each item. Each item should be for the complete item. For example, the storm sewer 15” HDPE unit price should include all of the cost for material and installation.
Corrective Action Required
01/21/2020

The granular base course and geogrid extend 1’ beyond the back of the curb & gutter, so please verify the estimated quantities for these items match and that they are more than the total pavement quantities.
Building Codes Review No Comments 01/21/2020 01/14/2020
Mike Weisenborn
Fire Review Approved with Conditions 01/21/2020 01/14/2020
Mike Weisenborn
Code Statement
Corrective Action Required
01/13/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Traffic Review No Comments 01/21/2020 01/14/2020
Mike Weisenborn
Planning Review No Comments 01/21/2020 01/14/2020
Victoria Nelson
Fire Review Approved with Conditions 12/20/2019 12/20/2019
Mike Weisenborn
Code Statement
Corrective Action Required
12/20/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Planning Review No Comments 12/20/2019 12/20/2019
Victoria Nelson
Miscellaneous Correction
Corrective Action Required
12/13/2019

C.25. Oil and Gas Wells. Please state on the plan the DNR Well Database information that you referenced in your comments. If the referenced information is on the plan please tell us which page it is on.
Miscellaneous Correction
Corrective Action Required
12/13/2019

C.28-C.30. Photometric Plan. In the manufacturers specification sheets you show two types of flood lights. These flood lights are not shown on the plan nor are the labeled in the Luminaire Schedule. Please show were the flood lights will be installed and there specifications in the table. There are no manufactured specifications for the goose neck lamps that are shown in the elevations. In your Calculation Summary under the heading max/min you have it showing 16.20. Per our UDO this number cannot be greater than 10. Please either increase the Min 0.5 or decrease the Max of 8.1 to make it a 10. This can be found in the UDO under article 8, sec 8.250, letter F.
Miscellaneous Correction
Corrective Action Required
12/13/2019

C.20-Right-of-Way. Please label on the plan ROW measurements vary.
Engineering Review Corrections 12/20/2019 12/20/2019
Sue Pyles, P.E.
Corrective Action Required
12/20/2019

Revise the Sheet Index on the Cover Sheet to match the plan set. The index lists Sheet C4.2, which isn't included, and doesn't list Sheet C8.2, which is included.
Corrective Action Required
12/20/2019

Sheet C8.0 is referenced for Temporary Curb, but nothing on that sheet appears to be any temporary curb detail. Please include the detail.
Corrective Action Required
12/20/2019

Revise the Field Inlet standard detail to remove General Note 9, which refers to the ring and cover which aren't being used. Replace with a note specifying what Grated Top is required or include that information elsewhere on the detail.
Corrective Action Required
12/20/2019

Revise the estimate to show each line item with a quantity and a unit price. Each item shown in the plan set should be included on the estimate and the estimate quantities must match the quantities shown in the plans.
Traffic Review No Comments 12/20/2019 12/19/2019
Michael Park
Building Codes Review No Comments 12/20/2019 12/18/2019
Joe Frogge
Fire Review Approved with Conditions 11/06/2019 11/06/2019
Mike Weisenborn
Code Statement
Corrective Action Required
10/30/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Planning Review Corrections 11/06/2019 11/06/2019
Victoria Nelson
Miscellaneous Correction
Corrective Action Required
10/30/2019

C.25. Oil and Gas Wells. Please state on the plan the DNR Well Database information that you referenced in your comments. If the referenced information is on the plan please tell us which page it is on.
Miscellaneous Correction
Corrective Action Required
10/30/2019

C.28-C.30. Photometric Plan. In the manufacturers specification sheets you show two types of flood lights. These flood lights are not shown on the plan nor are the labeled in the Luminaire Schedule. Please show were the flood lights will be installed and there specifications in the table. There are no manufactured specifications for the goose neck lamps that are shown in the elevations. In your Calculation Summary under the heading max/min you have it showing 16.20. Per our UDO this number cannot be greater than 10. Please either increase the Min 0.5 or decrease the Max of 8.1 to make it a 10. This can be found in the UDO under article 8, sec 8.250, letter F.
Miscellaneous Correction
Corrective Action Required
10/30/2019

C.20-Right-of-Way. Please label on the plan ROW measurements vary.
Building Codes Review No Comments 11/06/2019 11/06/2019
Joe Frogge
Miscellaneous Correction
Resolved
11/06/2019

Water service piping from connection to main to as least 10' past meter must be copper. Action required: Modify design to comply and provide standard detail obtained from water department.
Engineering Review Corrections 11/06/2019 11/05/2019
Sue Pyles, P.E.
Corrective Action Required
11/05/2019

Sheet C3.0: In my previous review I referenced Key Note 3 in error, I meant Key Note 7. Please show the existing storm sewer in the same manner as all other existing storm sewer, with solid lines that are scaled back.
Corrective Action Required
11/05/2019

Sheet C4.0: Temporary curb may be either concrete or asphalt. Include a detail for whichever option is shown.
Corrective Action Required
11/05/2019

Sheet C6.1: • Backfill for storm sewer pipe is typically granular around the pipe with compacted soil the rest of the backfill. If this is preferred to flowable fill, which is typical, there is no need to label as anything specific. Or, if desired, the label could just refer to Section 2104 of the Design and Construction Manual. • Reverse the flowline information for Structure 1 on each profile. The flowline in should be on the upstream side of the structure and the flowline out on the downstream side. • Clarify structure sizes. The grate inlets and curb inlet are labeled as 48” in the Profile views. Are these structures square, 48” x 48” (4’ x 4’)?
Corrective Action Required
11/05/2019

Sheet C8.0: • UDO Section 8.620 requires either 6” granular base course with geogrid OR 6” granular base course with 6” stabilized subgrade. Please revise the “Prepared Subgrade” portion of the detail to meet the UDO requirement. • The pavement sections required by the UDO may only be altered if a modification is requested of and approved by the City Engineer. If a modification is requested, it will require a site specific geotechnical report which directly compares the proposed section to the City’s required section to show that it meets or exceeds the City’s section. If no modicication is requested, please delete the note shown on each detail referencing the geotechnical report.
Corrective Action Required
11/05/2019

Sheet C8.2: • There is an AutoCAD SHX text box shown in the Curb & Gutter detail. Please revise to eliminate. • How will the grate inlets be constructed? Typically the City’s field inlet detail is used with the top modified to show the grate.
Corrective Action Required
11/05/2019

Estimate: Please revise the estimate to list individual items with unit prices. Verify quantities shown on the estimate match quantities shown in the plans.
Traffic Review No Comments 11/06/2019 10/30/2019
Mike Weisenborn
Engineering Review Corrections 10/11/2019 10/15/2019
Sue Pyles, P.E.
Corrective Action Required
10/15/2019

Submit an Engineer's Estimate of Probable Construction Costs, SWPPP and a copy of the MDNR Land Disturbance Permit.
Corrective Action Required
10/15/2019

Sheet C3.0: Show the existing storm sewer, called out as Key Note 3, in the same manner as other existing storm sewer is shown on this sheet and throughout the plan set.
Corrective Action Required
10/15/2019

Sheet C4.0: • Add temporary curb across the future connection to the lot to the west on this sheet and throughout the plan set. Include a detail for the type of curb used. • CG-1 Curb and Gutter is required for all non-integral curb. Revise accordingly.
Corrective Action Required
10/15/2019

Sheet C6.0: • Keyed Note 25 says “Not Used” but is included in the Plan view. Please reconcile. • Key Note 5 shows the domestic water service line connection at the existing gate valve. Service shall be connected with a corporation stop for this size pipe. Revise accordingly. • Include pipe material and length for both water and sanitary sewer service lines. • Include referenced Sheet C6.1 is subsequent submittals. • Clarify how Structure 1 will be constructed. Is it to be a doghouse manhole? • Label structure sizes on either this sheet or C6.1.
Corrective Action Required
10/15/2019

Sheet C6.1: • The drop thru structure 3 does not meet the minimum requirement of Design and Construction Manual Section 5604.5. Please revise accordingly. • Include roof drain flowline information at structure 3. Verify that the 2 pipes shown entering the same wall of the structure will have adequate separation between them. • Revise backfill label to meet the requirements of Design and Construction Manual Section 2100. • Include stationing in the storm sewer profiles.
Corrective Action Required
10/15/2019

Sheet C8.0: • Include the City’s standard detail for curb and gutter. • Pavement sections do not meet the City’s requirements as shown in the UDO Section 8.620. Please revise accordingly. • Revise the pavement sections to show the base extending 1 foot beyond the back of curb. • Remove MoDOT references in the concrete pavement section #7. • Include standard details for all types of storm sewer structures used.
Building Codes Review Corrections 10/11/2019 10/11/2019
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/11/2019

Water service piping from connection to main to as least 10' past meter must be copper. Action required: Modify design to comply and provide standard detail obtained from water department.
Traffic Review No Comments 10/11/2019 10/10/2019
Michael Park
Planning Review Corrections 10/11/2019 10/10/2019
Victoria Nelson
Miscellaneous Correction
Corrective Action Required
10/08/2019

C.20-Right-of-Way. Please label all ROW width on public streets.
Miscellaneous Correction
Corrective Action Required
10/08/2019

C.25. Oil and Gas Wells. Please state whether or not there are active, inactive, or capped wells within the area. Refer to DNR Well Database and reference the site.
Miscellaneous Correction
Corrective Action Required
10/08/2019

C.28-C.30. Photometric Plan. Please submit a Photometric Plan and be sure to include the manufacturer's specification sheets. UDO Requirements can be found in Article 8 subdivision 5.
Miscellaneous Correction
Corrective Action Required
10/08/2019

C.33 Signs. It appears you are proposing five signs for this business. The UDO only allows three wall signs by right. Requesting an approval for five wall signs requires going to the Planning Commission by filing a separate Sign Application. Staff would support the request for a total of five wall signs.
Miscellaneous Correction
Corrective Action Required
10/08/2019

D1. Elevations. The building elevations that you provided shows wood paneling and siding. Is this wood a "true" wood or a wood "composite"? Please label and describe the material on the plans. Staff does not have the administrative authority to approve true wood, but can administratively approve a wood composite. If you request to use true wood on the building exterior, then this will require an approval via the preliminary development plan public hearing process in front of the both the Planning Commission and City Council under separate application. If the material is a wood composite, then a manufacturer specifications is required to be submitted for our review.
Fire Review Approved with Conditions 10/11/2019 10/02/2019
Jim Eden
Code Statement
Corrective Action Required
10/15/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Fees
Paid Fees Amount Paid Owing Date Paid
Final Development Plan fee $600.00 $600.00 Paid 09/27/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
09/27/2019 Receipt Receipt for transaction: 2019-006480
09/27/2019 Letter Routing Sheet - FDP
10/01/2019 Plans 52118-MO01 - Lee's Summit_9-26-19 FDP Elevations
10/01/2019 Plans Combined Signage Drawings - revised 9.24.19 (1)
10/01/2019 Plans Final Development Plan Checklist
10/01/2019 Plans Lighting Specifications
10/01/2019 Plans LION'S CHOICE PHOTO METRIC
10/01/2019 Plans Lion's Choice-Lee's Summit Civil Plans
10/01/2019 Plans Summit Orchards--REA--FULLY RECORDED (00573021xC4CB5)
10/01/2019 Plans Trane RTU Submittal for Review 08-06-2019 (003)
10/01/2019 Plans V_ALTA_18-0136 LIONS CHOICE LEES SUMMIT
10/08/2019 Plans 6.1_IPLAN_UTILITY_18-0136-C6.1
10/15/2019 Letter Applicant Letter - FDP (DFDP)
10/29/2019 LION'S CHOICE - LEE'S SUMMIT, MO Photometric
10/29/2019 Lighting Specifications
10/29/2019 Lee's Summit Lions Choice Full Civil
10/29/2019 Identity Wood Products_Wood Composite_Spec
10/29/2019 52118-MO01 - Lee's Summit_10-18-19 FDP Elevations_Rev1
10/29/2019 2019-10-22 Lion's Choice City Comment Response Letter
10/29/2019 Recorded Summit Orchard corrected plat
10/29/2019 Opinion of Probable Cost
10/29/2019 Lot 4 DNR Land Disturbance Permit
10/30/2019 Letter Resubmittal Routing Sheet - FDP
11/05/2019 Engineer Report/Study 191105 Lot 4-D Stormwater Cert Ltr
11/06/2019 Letter Applicant Letter - FDP (DFDP)
12/11/2019 Lion's Choice Lee's Summit Civil Bid Set
12/11/2019 2019-12-11 City Comment Response Letter
12/11/2019 h-15008-page 3
12/11/2019 Lion's Choice - Lee's Summit MO Photometric Plan
12/11/2019 zur_12_outdoor_wall (2)
12/11/2019 PSL-EnergyLite-GridLite_commercial
12/11/2019 lumark-crosstour-led-td514013en-sss
12/11/2019 Phillco Lions Choice Lee's Summit Site Utility numbers 12-10-19 Revised
12/13/2019 Letter Resubmittal Routing Sheet - FDP
12/20/2019 Letter Applicant Letter - FDP (DFDP)
01/09/2020 Plans 18-0136 Full Set
01/13/2020 Letter Resubmittal Routing Sheet - FDP
01/21/2020 Letter Applicant Letter - FDP (DFDP)
02/06/2020 Activity Document Phillco Lions Choice Lee's Summit Site & Utility numbers 2-3-20 Revised
02/10/2020 Approved Plans Lion's Choice Lee's Summit Civil Bid Set
02/11/2020 Letter Resubmittal Routing Sheet - FDP
02/14/2020 Activity Document Fees PL2019335 Lion's Choice FDP
02/14/2020 Email Lion's Choice
02/14/2020 Activity Document Fees
02/18/2020 Letter Applicant Letter - FDP (DFDP)
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.