Permit Application Status

PRRES20236294


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20236294
Building Permit - Residential
Certificate of Occupancy
NEW DUPLEX
NEW DUPLEX. UNFINISHED BASEMENT. ROOF TRUSSES. STOP WORK ORDER generated on 04/19/2024 12:00 AM by username 'Dustin Agcopra'. STOP WORK ORDER removed on 04/23/2024 12:00 AM by username 'Dustin Agcopra'.
11/30/2023
12/13/2023
06/02/2024
09/13/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
JASONH@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Duplex $2,898.02 $2,898.02 Paid 12/13/2023
Water Tap Fee $7,520.00 $7,520.00 Paid 12/13/2023
Water Meter Fee $1,360.92 $1,360.92 Paid 12/13/2023
Sanitary Sewer Development Fee $4,318.00 $4,318.00 Paid 12/13/2023
Right of Way Permit Fee $85.00 $85.00 Paid 12/13/2023
Residential Excise Tax Fee $1,240.32 $1,240.32 Paid 12/13/2023
Not Ready Inspection Fee $75.00 $75.00 Paid 05/28/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 05/30/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 07/30/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 08/01/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 12/20/2023 12/20/2023
Miscellaneous Correction
Informational
12/20/2023
Footing was inspected and passed by a third party. No mention of piers were in the report
Sewer Service Inspection - R Passed 1/26/2024 1/26/2024 01/26/2024
Miscellaneous Correction
Informational
01/26/2024
Both sides of the duplex passed
Water Service Inspection - R Passed 1/29/2024 1/29/2024 01/29/2024
Underslab Plumbing Inspection - Residential Passed 2/1/2024 2/1/2024 02/01/2024
Erosion Control Inspection Residential Partial 2/1/2024 02/01/2024
Miscellaneous Correction
Corrective Action Required
02/01/2024
Full erosion control is in place and needs to be maintained until CofO
Erosion Control Inspection Residential Partial 2/12/2024 02/12/2024
Miscellaneous Correction
Resolved
02/12/2024
Full erosion control is in place and needs to be maintained until CofO
Miscellaneous Correction
Corrective Action Required
02/12/2024
Full erosion control is in place and must be maintained until CofO
All Rough Inspection - Residential Partial 2/29/2024 2/29/2024 02/29/2024
Misc
Corrective Action Required
02/29/2024
- PORTAL FRAME OK TO COVER
Erosion Control Inspection Residential Partial 3/14/2024 03/14/2024
Miscellaneous Correction
Resolved
03/14/2024
Full erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Informational
03/14/2024
Full erosion control is in place and must be maintained until CofO
Electrical Service Inspection Passed 3/27/2024 3/27/2024 03/27/2024
Gas Service Inspection - Residential Failed 3/27/2024 3/27/2024 03/27/2024
Miscellaneous Correction
Corrective Action Required
03/27/2024
Gas line at 2216 (west side) has 0 PSI at inspection
Rated Assembly Inspection Failed 3/27/2024 3/27/2024 03/27/2024
Miscellaneous Correction
Corrective Action Required
03/27/2024
2118 SW Holdbrooks. (East side) Rated assembly -Fire rated plywood deck can not have more than 1/4 inch gap Rated assembly wall in bedroom 1 at south wall ends before reaching the corner 2116 (west side) -Fire rated plywood is chipping and needs replaced or repaired -Caulk gaps where needed at plywood
All Rough Inspection - Residential Failed 3/27/2024 3/27/2024 03/27/2024
Misc
Resolved
03/27/2024
- PORTAL FRAME OK TO COVER
Miscellaneous Correction
Corrective Action Required
03/27/2024
2116 SW Holdbrooks (west side). All rough -LIB in garage is missing nails -Install LIB’s according to plans King studs missing according to plans at patio door -Fire block top plate in bedroom 1 to utility room wrong joist hangers used in two ceiling joist in bedroom 1 -Fire block top and bottom plate in toilet of bathroom 1 -I beam at party wall needs to be fire blocked -I beam at party wall does not set 3 inch on to concrete pocket -Gas line pressure is 0 2118 (east side) -nail garage corners to code Install LIB’s according to plans -King studs missing according to plans at patio door -Fire block top plate in corner of walk in closet -Install correct 2 joist hangers in bedroom one -Fire blocking is broken out above Ibeam in basement -Ibeam in basement west side does not set on 3 inches of concrete -I beam in basement east side was cut short and has three vertical support 2x6’s which were not in the approved set of plans -Top of basement stair stringers do not bear against a full 1 1/2 inches of the double 2x10
Rated Assembly Inspection Partial 4/2/2024 4/2/2024 04/02/2024
Miscellaneous Correction
Resolved
04/02/2024
2118 SW Holdbrooks. (East side) Rated assembly -Fire rated plywood deck can not have more than 1/4 inch gap Rated assembly wall in bedroom 1 at south wall ends before reaching the corner 2116 (west side) -Fire rated plywood is chipping and needs replaced or repaired -Caulk gaps where needed at plywood
Miscellaneous Correction
Informational
04/02/2024
-Party wall passed inspection -Screw pattern will need to be scheduled for a rated assembly inspection. This is a partial pass only
Gas Service Inspection - Residential Failed 4/2/2024 4/2/2024 04/02/2024
Miscellaneous Correction
Resolved
04/02/2024
Gas line at 2216 (west side) has 0 PSI at inspection
Miscellaneous Correction
Corrective Action Required
04/02/2024
Gas pressure gauge at first inspection had 0 PSI Gas pressure gauge is not installed 04/02/24
All Rough Inspection - Residential Failed 4/2/2024 4/2/2024 04/02/2024
Miscellaneous Correction
Resolved
04/02/2024
2116 SW Holdbrooks (west side). All rough -LIB in garage is missing nails -Install LIB’s according to plans King studs missing according to plans at patio door -Fire block top plate in bedroom 1 to utility room wrong joist hangers used in two ceiling joist in bedroom 1 -Fire block top and bottom plate in toilet of bathroom 1 -I beam at party wall needs to be fire blocked -I beam at party wall does not set 3 inch on to concrete pocket -Gas line pressure is 0 2118 (east side) -nail garage corners to code Install LIB’s according to plans -King studs missing according to plans at patio door -Fire block top plate in corner of walk in closet -Install correct 2 joist hangers in bedroom one -Fire blocking is broken out above Ibeam in basement -Ibeam in basement west side does not set on 3 inches of concrete -I beam in basement east side was cut short and has three vertical support 2x6’s which were not in the approved set of plans -Top of basement stair stringers do not bear against a full 1 1/2 inches of the double 2x10
Miscellaneous Correction
Corrective Action Required
04/02/2024
-Gas pressure gauge at 2116 (west side) is missing -Gas pressure gauge on first inspection read 0 PSI All rough can not pass until gas inspection passes 04/02/24. KBEARD
Gas Service Inspection - Residential Passed 4/3/2024 4/3/2024 04/03/2024
Miscellaneous Correction
Resolved
04/03/2024
Gas pressure gauge at first inspection had 0 PSI Gas pressure gauge is not installed 04/02/24
All Rough Inspection - Residential Passed 4/3/2024 4/3/2024 04/03/2024
Miscellaneous Correction
Resolved
04/03/2024
-Gas pressure gauge at 2116 (west side) is missing -Gas pressure gauge on first inspection read 0 PSI All rough can not pass until gas inspection passes 04/02/24. KBEARD
Rated Assembly Inspection Failed 4/8/2024 4/8/2024 04/08/2024
Miscellaneous Correction
Informational
04/02/2024
-Party wall passed inspection -Screw pattern will need to be scheduled for a rated assembly inspection. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
04/08/2024
Screws are missing along wall in bedroom 1 in unit 2218 (east side)
Erosion Control Inspection Residential Failed 4/8/2024 04/08/2024
Miscellaneous Correction
Informational
03/14/2024
Full erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Corrective Action Required
04/08/2024
Silt fence at street is damaged or missing and needs to be repaired or replaced. Full erosion control must be maintained until CofO
Rated Assembly Inspection Passed 4/9/2024 04/09/2024
Miscellaneous Correction
Informational
04/08/2024
-Party wall passed inspection -Screw pattern will need to be scheduled for a rated assembly inspection. This is a partial pass only
Miscellaneous Correction
Corrective Action Required
04/08/2024
Screws are missing along wall in bedroom 1 in unit 2218 (east side)
Erosion Control Inspection Residential Failed 04/12/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/12/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Restroom needs to be removed from sidewalk No silt fence in front
Erosion Control Inspection Residential Partial 4/17/2024 4/17/2024 04/17/2024
Miscellaneous Correction
Informational
04/08/2024
Full erosion control is in place and must be maintained until CofO
Miscellaneous Correction
Corrective Action Required
04/08/2024
Silt fence at street is damaged or missing and needs to be repaired or replaced. Full erosion control must be maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/17/2024
4-17-24 Dustin A. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Remove restroom from Sidewalk or Driveways
Erosion Control Inspection Residential Failed - Stop Work 4/19/2024 4/19/2024 04/19/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/17/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Restroom needs to be removed from sidewalk No silt fence in front
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/19/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. 4-19-24 Dustin A, Restroom was moved but still no erosion control is in place
Erosion Control Inspection Residential Passed 4/23/2024 04/23/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
04/19/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. Restroom needs to be removed from sidewalk No silt fence in front
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/19/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. 4-19-24 Dustin A, Restroom was moved but still no erosion control is in place 4-23-24 Dustin A, Esc is in place and will need to be maintained
Driveway Inspection Partial 4/30/2024 4/30/2024 04/30/2024
Misc
Informational
04/30/2024
4-30-24 PS Driveway pre pour, forms in place and aggregate compacted, approved to pour
Sidewalk Inspection Partial 4/30/2024 4/30/2024 04/30/2024
Misc
Informational
04/30/2024
4-30-24 PS Sidewalk pre pour, forms in place and aggregate compacted, approved to pour
Occupancy Inspection - Codes Residential Not Ready 5/22/2024 5/22/2024 05/22/2024
Miscellaneous Correction
Corrective Action Required
05/22/2024
2118 and 2116 SW Holdbrooks. Occupancy 2118 Front porch has over a 30 inch side drop off and will require a guard rail to be installed Interior of garage needs to have all opens sealed at wall to ceilings First step up at entry to upstairs has a riser height of 8 1/4 inches. Code is no more than a 7 3/4 riser height Basement stair hand rails are not installed Fire block holes in basement to kitchen floor decking at the island Fire blocking is still needed at the electrical service entrance in the basement 2116 Basement handrail is not installed Not a complete list. Walk your property before scheduling an inspection. Not ready
Driveway Inspection Passed 05/22/2024
Misc
Informational
04/30/2024
4-30-24 PS Driveway pre pour, forms in place and aggregate compacted, approved to pour 5-22-24 Dustin A, DW's are poured to city specs. Passed
Sidewalk Inspection Passed 05/22/2024
Misc
Informational
05/22/2024
5-22-24 Dustin A, SW's are poured tp city specs. Passed
Piers/Caissons Inspection - Residential Failed 5/22/2024 5/22/2024 05/22/2024
Miscellaneous Correction
Corrective Action Required
05/22/2024
All piers need to be 36 inches deep.
Occupancy Inspection - Codes Residential Failed 5/23/2024 5/23/2024 05/23/2024
Miscellaneous Correction
Resolved
05/23/2024
2118 and 2116 SW Holdbrooks. Occupancy 2118 Front porch has over a 30 inch side drop off and will require a guard rail to be installed Interior of garage needs to have all opens sealed at wall to ceilings First step up at entry to upstairs has a riser height of 8 1/4 inches. Code is no more than a 7 3/4 riser height Basement stair hand rails are not installed Fire block holes in basement to kitchen floor decking at the island Fire blocking is still needed at the electrical service entrance in the basement 2116 Basement handrail is not installed Not a complete list. Walk your property before scheduling an inspection. Not ready
Miscellaneous Correction
Corrective Action Required
05/23/2024
2118 and 2116 SW Holdbrooks. Occupancy (2) 2118 Front porch has over a 30 inch side drop off and will require a guard rail to be installed Interior of garage needs to have all opens sealed at wall to ceilings First step up at entry to upstairs has a riser height of 8 1/4 inches. Code is no more than a 7 3/4 riser height Basement stair hand rails are not installed Fire block holes in basement to kitchen floor decking at the island Fire blocking is still needed at the electrical service entrance in the basement Seal exterior gas line to siding penetration 2116 guard rail on front porch has more than the 4 inches allowed under the bottom rail to concrete Garage to house door is missing the secondary locking device Seal underneath both chases in the garage Garage steps to house needs guard rails installed. Steps are four or more are req to have guard rails installed Patio slider is missing a secondary lock Basement top step on to main house entry has a riser of more than the code allowed 7 3/4 inches in height Seal penetration in basement ceiling to kitchen floor plywood at kitchen island No code violation but basement humidifier is not hooked up Main entry to up stairs first riser is over the codes allowable 7 3/4 inches in height Both units plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Pay $75 fee associated with this permit
Piers/Caissons Inspection - Residential Passed 5/23/2024 05/23/2024
Miscellaneous Correction
Resolved
05/23/2024
All piers need to be 36 inches deep.
Occupancy Inspection - Codes Residential Failed 5/28/2024 5/28/2024 05/28/2024
Miscellaneous Correction
Corrective Action Required
05/23/2024
2118-OK 2116: -Seal underneath both chases in the garage ** provide 5/8” gypsum underneath garage boxed-out walls Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete
Occupancy Inspection - Codes Residential Failed 5/29/2024 5/29/2024 05/29/2024
Miscellaneous Correction
Resolved
05/29/2024
2118-OK 2116: -Seal underneath both chases in the garage ** provide 5/8” gypsum underneath garage boxed-out walls Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete
Miscellaneous Correction
Corrective Action Required
05/29/2024
2116: -Seal underneath both chases in the garage ** provide 5/8” gypsum underneath garage boxed-out walls (Seal all holes around newly installed gypsum for proper fire blocking) Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Unit 2118 passed for TCO only
Occupancy Inspection - Codes Residential Ready for Temp CO 5/30/2024 5/30/2024 05/30/2024
Miscellaneous Correction
Resolved
05/30/2024
2116: -Seal underneath both chases in the garage ** provide 5/8” gypsum underneath garage boxed-out walls (Seal all holes around newly installed gypsum for proper fire blocking) Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Unit 2118 passed for TCO only
Miscellaneous Correction
Corrective Action Required
05/30/2024
Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Both properties passed for TCO only
Occupancy Inspection - Codes Residential Ready for Temp CO 6/24/2024 06/24/2024
Miscellaneous Correction
Resolved
06/24/2024
Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Both properties passed for TCO only
Miscellaneous Correction
Corrective Action Required
06/24/2024
Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Both properties passed for TCO only
Occupancy Inspection - Codes Residential Ready for Temp CO 7/31/2024 07/31/2024
Miscellaneous Correction
Corrective Action Required
06/24/2024
Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Both properties passed for TCO only Pay TCO Fee
Erosion Control Inspection Residential Failed 8/13/2024 08/13/2024
Miscellaneous Correction
Corrective Action Required
08/13/2024
Erosion control measures are missing at the front and rear of the property. Full erosion control measures my be maintained until CofO
Erosion Control Inspection Residential Partial 9/3/2024 09/03/2024
Miscellaneous Correction
Resolved
09/03/2024
Erosion control measures are missing at the front and rear of the property. Full erosion control measures my be maintained until CofO
Miscellaneous Correction
Informational
09/03/2024
Erosion control measures are in place and must be maintained until CofO
Plot Plan Inspection Failed 9/6/2024 09/06/2024
Miscellaneous Correction
Corrective Action Required
09/06/2024
Plot plan failed due to a retaining wall built on unit 2118
Erosion Control Inspection Residential Passed 9/6/2024 09/06/2024
Miscellaneous Correction
Resolved
09/06/2024
Erosion control measures are in place and must be maintained until CofO
Plot Plan Inspection Passed 9/12/2024 09/12/2024
Miscellaneous Correction
Resolved
09/12/2024
Plot plan failed due to a retaining wall built on unit 2118
Occupancy Inspection - Codes Residential Failed 9/12/2024 09/12/2024
Miscellaneous Correction
Resolved
09/12/2024
Both units: plot has not had it’s final grading for plot plan inspection Sod, splash pads and sump pump extensions are not complete Both properties passed for TCO only Pay TCO Fee
Miscellaneous Correction
Corrective Action Required
09/12/2024
Both units have water meters covered by sod All other corrections have been completed
Occupancy Inspection - Codes Residential Full C of O 9/13/2024 9/13/2024 09/13/2024
Miscellaneous Correction
Resolved
09/13/2024
Both units have water meters covered by sod All other corrections have been completed
Documents & Images
Date Uploaded File Type Document Name
11/30/2023 OS # 76 - PERMIT APP
11/30/2023 OS # 76 - TRUSS DETAILS
11/30/2023 OS # 76 - TRUSS LAYOUT
11/30/2023 OS #76 - CERTIFIED PLANS
12/05/2023 Permit Codes Residential Plan Review
12/13/2023 Approved Plans APPROVED TRUSS LAYOUT
12/13/2023 Approved Plans APPROVED TRUSS PACKAGE
12/13/2023 Approved Plans APPROVED PLANS
12/13/2023 Permit Codes Residential Plan Review
12/13/2023 Permit DS Building Permit
12/13/2023 Receipt Receipt for transaction:2023-009077
12/19/2023 2116 & 2118 SW Holdbrooks Dr LSMO Osage Lot 76 Clayton Properties P 2023-6294 3rd Party Footing Inspection Report 12-18-23
12/20/2023 Letter INSPECTION SUMMARY
01/26/2024 Letter INSPECTION SUMMARY
01/29/2024 Letter INSPECTION SUMMARY
01/30/2024 Plot Plan approved plot plan
02/01/2024 Letter INSPECTION SUMMARY
02/01/2024 Letter INSPECTION SUMMARY
02/12/2024 Letter INSPECTION SUMMARY
02/29/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
03/27/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/02/2024 Letter INSPECTION SUMMARY
04/03/2024 Letter INSPECTION SUMMARY
04/03/2024 Letter INSPECTION SUMMARY
04/08/2024 Letter INSPECTION SUMMARY
04/08/2024 Letter INSPECTION SUMMARY
04/09/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/17/2024 Letter INSPECTION SUMMARY
04/17/2024 Letter INSPECTION SUMMARY
04/19/2024 Letter Stop Work Order
04/19/2024 Letter Stop Work Order
04/23/2024 Letter INSPECTION SUMMARY
04/23/2024 Letter INSPECTION SUMMARY
04/30/2024 Letter INSPECTION SUMMARY
04/30/2024 Letter INSPECTION SUMMARY
05/22/2024 Letter INSPECTION SUMMARY
05/22/2024 Letter INSPECTION SUMMARY
05/22/2024 Letter INSPECTION SUMMARY
05/22/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/23/2024 Letter INSPECTION SUMMARY
05/28/2024 Receipt Receipt for transaction:2024-003988
05/28/2024 Letter INSPECTION SUMMARY
05/29/2024 Letter INSPECTION SUMMARY
05/30/2024 Certificate/License Codes Temporary Certificate of Occupancy
05/30/2024 Receipt Receipt for transaction:2024-004177
06/20/2024 OS #76 - TCO Extension 6_20_24
06/24/2024 Letter INSPECTION SUMMARY
07/30/2024 OS #76 - TCO Extension 7_30_24
07/30/2024 Certificate/License Codes Temporary Certificate of Occupancy
07/30/2024 Receipt Receipt for transaction:2024-006403
08/01/2024 Certificate/License Codes Temporary Certificate of Occupancy
08/01/2024 Receipt Receipt for transaction:2024-006464
08/13/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/22/2024 OS 76 TCOExtension Request Form 8_22
09/03/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/11/2024 Plot Plan APPROVED AS BUILT PLOT PLAN
09/12/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/13/2024 Letter Field Certificate of Occupancy
09/13/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.