Permit Application Status

PRRES20215067


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20215067
Building Permit - Residential
Certificate of Occupancy
CLAYTON PROPERTIES GROUP INC
NEW 3 OR 4 FAMILY
NEW FOUR PLEX - FINISHED BASEMENT - UNCOVERED DECK STOP WORK ORDER generated on 03/10/2022 12:00 AM by username 'Patrick Schonfeldt'. STOP WORK ORDER removed on 03/11/2022 12:00 AM by username 'Patrick Schonfeldt'.
09/28/2021
10/11/2021
03/27/2022
03/17/2023
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
LLOYD@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $3,047.99 $3,047.99 Paid 10/11/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 10/11/2021
7232302-Residential Excise Tax Fee $4,308.48 $4,308.48 Paid 10/11/2021
8331507-Sewer Connection Fee $1,440.00 $1,440.00 Paid 10/11/2021
8331401-Water Tap Fee $14,620.00 $14,620.00 Paid 10/11/2021
8350015-Water Meter Fee $1,916.96 $1,916.96 Paid 10/11/2021
8331504-EFHB Middle Big Creek, Full $1,607.04 $1,607.04 Paid 10/11/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 02/22/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/22/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/22/2023
9110080-3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 02/22/2023
9110080-3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 02/22/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/22/2023
9110080-3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 02/22/2023
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 02/22/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Not Ready 3/10/2022 3/10/2022 03/10/2022
Misc
Corrective Action Required
03/10/2022
INSPECTION DENIED -FOOTING POURED WITHOUT INSPECTION - POST ADDRESSES -SNOW COVER PREVENT INSPECTION
Footing Inspection - Residential Failed - Stop Work 3/10/2022 3/10/2022 03/10/2022
Misc
Corrective Action Required
03/10/2022
FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE UPLOADED TO PERMIT WITHIN 48 HOURS OF INSPECTION STOP WORK ISSUED
Footing Inspection - Residential Passed 3/11/2022 3/11/2022 03/11/2022
Misc
Corrective Action Required
03/10/2022
APPROVED PER DAVID P AINSWORTH 1/15/22
Underslab Plumbing Inspection - Residential Failed 3/15/2022 3/15/2022 03/15/2022
Misc
Corrective Action Required
03/10/2022
-ALL PLUMBING NEEDS TO BE BEDDED IN GRAVEL
Erosion Control Inspection Residential Failed 3/30/2022 03/30/2022
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
03/30/2022
STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. MAINTAIN SILT FENCE SPREAD & MAINTAIN GRAVEL FILTER CLEAN STREET OF MUD< GRAVEL & DEBRIS
Underslab Plumbing Inspection - Residential Passed 3/30/2022 3/30/2022 03/30/2022
Misc
Informational
03/30/2022
2038,2036,2034,2032
Sewer Service Inspection - R Partial 5/16/2022 (1:00) 5/16/2022 05/16/2022
Misc
Corrective Action Required
05/16/2022
UNIT 2036 OK
Sewer Service Inspection - R Partial 5/17/2022 05/17/2022
Misc
Corrective Action Required
05/16/2022
UNIT 2036,2032,2034 OK
Sewer Service Inspection - R Passed 5/18/2022 05/18/2022
Misc
Corrective Action Required
05/17/2022
UNIT 2036,2032,2034,2038 OK
Water Service Inspection - R Partial 5/20/2022 05/20/2022
Misc
Corrective Action Required
05/20/2022
2032, 2034, 2036 OK
Water Service Inspection - R Passed 5/26/2022 (8:30) 5/26/2022 05/26/2022
Misc
Corrective Action Required
05/20/2022
2032, 2034, 2036,2038 OK
Erosion Control Inspection Residential Failed 5/26/2022 05/26/2022
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
05/26/2022
STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. MAINTAIN SILT FENCE SPREAD & MAINTAIN GRAVEL FILTER CLEAN STREET OF MUD< GRAVEL & DEBRIS
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/26/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Failed 10/11/2022 10/11/2022 10/11/2022
Misc
Corrective Action Required
10/11/2022
10/11/22 - NO ALL ROUGH INSPECTION PERFORMED, INSPECTED ALL UNITS GARAGE PORTAL PFH NAIL PATTERN AND ALL UNITS REAR CS-PF NAIL PATTERN ON ZIP BOARD, OK FOR SIDING ON ZIP BOARD
All Rough Inspection - Residential Not Ready 11/28/2022 11/28/2022 11/28/2022
Misc
Corrective Action Required
10/11/2022
10/11/22 - NO ALL ROUGH INSPECTION PERFORMED, INSPECTED ALL UNITS GARAGE PORTAL PFH NAIL PATTERN AND ALL UNITS REAR CS-PF NAIL PATTERN ON ZIP BOARD, OK FOR SIDING ON ZIP BOARD
Misc
Corrective Action Required
11/28/2022
11/28/22 - INSPECTION DENIED, NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Electrical Service Inspection Failed 11/28/2022 11/28/2022 11/28/2022
Misc
Corrective Action Required
11/28/2022
11/28/22 - INSPECTION DENIED, NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Gas Service Inspection - Residential Failed 11/28/2022 11/28/2022 11/28/2022
Misc
Corrective Action Required
11/28/2022
11/28/22 - INSPECTION DENIED, NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Rated Assembly Inspection Failed 11/28/2022 11/28/2022 11/28/2022
Misc
Corrective Action Required
11/28/2022
11/28/22 - INSPECTION DENIED, NO CITY STAMPED PLANS ON SITE AT TIME OF INSPECTION
Driveway Inspection Partial 12/1/2022 12/1/2022 12/01/2022
Misc
Informational
12/01/2022
12-1-22 RH. Driveway is formed up and aggregate is placed and compacted. Crew is going to use concrete blankets to cover concrete. Approved to pour.
Electrical Service Inspection Failed 12/6/2022 12/6/2022 12/06/2022
Misc
Corrective Action Required
11/28/2022
UNIT 2038: INTERIOR OK UNIT 2036: INTERIOR OK NO INSPECTION ON 2034,2032 OR SERVICE
Gas Service Inspection - Residential Failed 12/6/2022 12/6/2022 12/06/2022
Misc
Corrective Action Required
11/28/2022
UNIT 2038: -complete gas line at furnace -bond gas line -gas line pressure test required UNIT 2036: - gas line bond required (pressure ok) UNITS 2034,2032 NO INSPECTION
Rated Assembly Inspection Failed 12/6/2022 12/6/2022 12/06/2022
Misc
Corrective Action Required
11/28/2022
-Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. NO INSPECTION ON UNITS 2034,2032
All Rough Inspection - Residential Failed 12/6/2022 12/6/2022 12/06/2022
Misc
Resolved
12/06/2022
10/11/22 - NO ALL ROUGH INSPECTION PERFORMED, INSPECTED ALL UNITS GARAGE PORTAL PFH NAIL PATTERN AND ALL UNITS REAR CS-PF NAIL PATTERN ON ZIP BOARD, OK FOR SIDING ON ZIP BOARD
Misc
Corrective Action Required
11/28/2022
Have engineer address condition of trusses used that were stored outside for extended time, sun/water damage, gusset plate condition UNIT 2038: -fireblock mechanical/plumbing chase at garage wall -provide nail protection plate at pex stud penetration for fridge at kitchen wall -great room wall 2x4 continuous stud wall with (5) top plates, structural screws, blocking per detail in plans -have engineer with truss manufacturer address trusses at 2nd floor master bed notched at chords/plates around lay in trusses -complete gas line at furnace -bond gas line -gas line pressure test required -secure HVAC duct and bath exhaust fan at ceiling line of furred down basement bath -Provide bocca protection plate at top plate DWV basement hall closet -tighten all anchor bolts -fireblock vertical to horizontal at furred down soffit ends basement -waste line and HVAC above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. UNIT 2036: -anchor bolts to be within middle third of sill plate -fireblock mechanical/plumbing chase at garage wall -provide nail plate at top plate for HVAC intake/exhaust piping at kitchen/bath wall -nail stud shoes at 2nd floor -(2) nails each stud/plate at lib x bracing strap -great room wall 2x4 continuous stud wall with (5) top plates, structural screws, blocking per detail in plans -land electrical to boxes at basement den -waste line and HVAC above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -seal top plate penetrations at basement bedroom -Provide bocca protection plate at top plate DWV basement hall closet -gas line bond required (Gas pressure ok) UNIT 2034: NOT READY FOR ROUGH INSPECTION UNIT 2032: NOT READY FOR ROUGH INSPECTION
Sidewalk Inspection Passed 12/8/2022 12/8/2022 12/08/2022
Misc
Informational
12/08/2022
11-8-22 RH. Sidewalk meets LS and ADA specification.
Driveway Inspection Passed 12/8/2022 12/8/2022 12/08/2022
Misc
Informational
12/01/2022
12-1-22 RH. Driveway is formed up and aggregate is placed and compacted. Crew is going to use concrete blankets to cover concrete. Approved to pour. 12-8-22 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 12/8/2022 12/08/2022
Misc
Informational
12/08/2022
11-8-22 RH. Sidewalk meets LS and ADA specification.
Electrical Service Inspection Failed 12/12/2022 12/12/2022
Misc
Corrective Action Required
12/06/2022
UNIT 2038: INTERIOR OK UNIT 2036: INTERIOR OK NO INSPECTION ON 2034,2032 OR SERVICE
Rated Assembly Inspection Failed 12/12/2022 12/12/2022
Misc
Corrective Action Required
12/06/2022
-Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. NO INSPECTION ON UNITS 2034,2032
All Rough Inspection - Residential Not Ready 12/12/2022 12/12/2022 12/12/2022
Misc
Corrective Action Required
12/06/2022
-COMPLETE ALL TRUSS REPAIRS PER SUBMITTED ENGINEER LETTERS UNIT 2038: -fireblock mechanical/plumbing chase at garage wall -provide nail protection plate at pex stud penetration for fridge at kitchen wall -great room wall 2x4 continuous stud wall with (5) top plates, structural screws, blocking per detail in plans -have engineer with truss manufacturer address trusses at 2nd floor master bed notched at chords/plates around lay in trusses -complete gas line at furnace -bond gas line -gas line pressure test required -secure HVAC duct and bath exhaust fan at ceiling line of furred down basement bath -Provide bocca protection plate at top plate DWV basement hall closet -tighten all anchor bolts -fireblock vertical to horizontal at furred down soffit ends basement -waste line and HVAC above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. UNIT 2036: -anchor bolts to be within middle third of sill plate -fireblock mechanical/plumbing chase at garage wall -provide nail plate at top plate for HVAC intake/exhaust piping at kitchen/bath wall -nail stud shoes at 2nd floor -(2) nails each stud/plate at lib x bracing strap -great room wall 2x4 continuous stud wall with (5) top plates, structural screws, blocking per detail in plans -land electrical to boxes at basement den -waste line and HVAC above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -seal top plate penetrations at basement bedroom -Provide bocca protection plate at top plate DWV basement hall closet -gas line bond required (Gas pressure ok) UNIT 2034: NOT READY FOR ROUGH INSPECTION, COMPLETE ALL FIREBLOCKING UNIT 2032: NOT READY FOR ROUGH INSPECTION, COMPLETE ALL FIREBLOCKING
Rated Assembly Inspection Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/12/2022
UNITS 2038, 2032 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. UNITS 2036 AND 2034 OK
Gas Service Inspection - Residential Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/06/2022
UNIT 2038: -complete gas line at furnace -bond gas line -gas line pressure test required UNITS 2036, 2034,2032 BOND AND PRESSURE OK
Electrical Service Inspection Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/12/2022
UNIT 2038, 2036, 2034, 2032: INTERIOR OK COMPLETE ALL GROUNDING AT EXTERIOR SERVICE
All Rough Inspection - Residential Failed 12/15/2022 12/15/2022 12/15/2022
Misc
Corrective Action Required
12/12/2022
-COMPLETE ALL TRUSS REPAIRS PER SUBMITTED ENGINEER LETTERS UNIT 2038: -provide nail protection plate at pex stud penetration for fridge at kitchen wall -have engineer with truss manufacturer address trusses at 2nd floor master bed notched at chords/plates around lay in trusses, this hasn’t been addressed by engineer -complete gas line at furnace -bond gas line -gas line pressure test required -Provide bocca protection plate at top plate DWV basement hall closet -fireblock vertical to horizontal at furred down soffit ends basement -radon/furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. UNIT 2036: -anchor bolts to be within middle third of sill plate -nail stud shoes at 2nd floor -radon and furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -seal top plate penetrations at basement bedroom -Provide bocca protection plate at top plate DWV basement hall closet UNIT 2034: -Anchor bolts must be within middle third of sill plate -fireblock at mechanical/plumbing fur out garage wall -secure all NM at garage to code -address bores for pex at floor joist front entry less than 2” apart -provide all blocking at great room 2X4 separation walls per plans -secure NM at great room outlets and fixtures per code -radon and furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -Provide bocca protection plate at top plate DWV basement hall closet -seal top plate penetrations at basement bedroom -fireblock between top plates at basement bedroom UNIT 2032: -Anchor bolts must be within middle third of sill plate -fireblock at mechanical/plumbing fur out garage wall -seal romex bottom plate penetration at foyer closet -provide all blocking at great room 2X4 separation walls per plans -seal all plate penetrations at great room/kitchen -provide hanger at ceiling joist kitchen pantry -protect NM within 6’ of attic entry -have engineer with truss manufacturer address trusses at 2nd floor master bed notched at chords/plates around lay in trusses, this hasn’t been addressed by engineer -provide bocca plate at DWV bottom plate closet den -radon and furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -properly route and secure gas flex line at mechanical -seal all penetrations at top plate den -secure SE cable at furred down -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.
Gas Service Inspection - Residential Passed 12/21/2022 12/21/2022 12/21/2022
Misc
Resolved
12/21/2022
Electrical Service Inspection Failed 12/21/2022 12/21/2022 12/21/2022
Misc
Corrective Action Required
12/15/2022
UNIT 2038, 2036, 2034, 2032: INTERIOR OK COMPLETE ALL GROUNDING AT EXTERIOR SERVICE, LAND CEE TO NEUTRAL BAR AT SERVICE
All Rough Inspection - Residential Failed 12/21/2022 12/21/2022 12/21/2022
Misc
Corrective Action Required
12/15/2022
UNIT 2038: -fireblock vertical to horizontal at furred down soffit ends basement (NOT COMPLETE) -furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 (RADON HAS BEEN RELOCATED PER DISCUSSION BUT NOW ALL UNITS HAVE PARTIAL BUILT CEILING FURRED DOWNS IN MECH ROOMS WITH SOFFIT ENDS BUTTED DIRECTLY ABOVE SERVICE PANELS, WHY?) -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.(NOT COMPLETE) UNIT 2036: -anchor bolts to be within middle third of sill plate (NOT ADDRESSED, SEE GARAGE PORTAL) -furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -fireblock vertical to horizontal at furred down soffit ends basement UNIT 2034: -Anchor bolts must be within middle third of sill plate (NOT ADDRESSED, SEE GARGE PORTAL) -fireblock at mechanical/plumbing fur out garage wall, seal penetrations for plumbing -furred down above service panel at mech room doesn’t allow for clearance per IRC E3405.1 UNIT 2032: -furred down/Gas line above service panel at mech room doesn’t allow for clearance per IRC E3405.1 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0)
Rated Assembly Inspection Failed 12/21/2022 12/21/2022 12/21/2022
Misc
Corrective Action Required
12/15/2022
UNITS 2038 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (NOT COMPLETE) UNITS 2036 AND 2034 OK UNIT 2032 -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PAGE A7.0 IN PLANS)
Electrical Service Inspection Failed 12/28/2022 12/28/2022 12/28/2022
Misc
Corrective Action Required
12/21/2022
UNIT 2038, 2036, 2034, 2032: INTERIOR OK LAND CEE TO NEUTRAL BAR AT SERVICE
All Rough Inspection - Residential Failed 12/28/2022 12/28/2022 12/28/2022
Misc
Corrective Action Required
12/21/2022
UNIT 2038: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.(PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, NAIL PENETRATIONS IN ROCK, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?) UNIT 2036: OK UNIT 2034: -fireblock at mechanical/plumbing fur out garage wall, seal annular space around plumbing at fireblock material UNIT 2032: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, ROCK NOT SEATED IN H STUDS, BOWING OUT, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?)
Rated Assembly Inspection Failed 12/28/2022 12/28/2022
Misc
Corrective Action Required
12/21/2022
UNITS 2036 AND 2034 OK UNIT 2038: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.(PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, NAIL PENETRATIONS IN ROCK, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?) UNIT 2032: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, ROCK NOT SEATED IN H STUDS, BOWING OUT, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?)
Electrical Service Inspection Passed 12/29/2022 12/29/2022 12/29/2022
Misc
Resolved
12/29/2022
UNIT 2038, 2036, 2034, 2032: INTERIOR OK LAND CEE TO NEUTRAL BAR AT SERVICE
All Rough Inspection - Residential Not Ready 12/29/2022 12/29/2022 12/29/2022
Misc
Corrective Action Required
12/28/2022
UNIT 2038: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures.(PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, NAIL PENETRATIONS IN ROCK, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?) UNIT 2036: OK UNIT 2034: OK UNIT 2032: -Fire rated wall to extend to roof deck, R302.2.3 Continuity. The fire-resistance-rated wall or assembly separating townhouses shall be continuous from the foundation to the underside of the roof sheathing, deck or slab. The fire-resistance rating shall extend the full length of the wall or assembly, including wall extensions through and separating attached enclosed accessory structures. (PROVIDE H STUDS AND C CHANNEL AT FIRE ROCK PER ENGINEERED DESIGN, SEE PLANS A7.0, ROCK NOT SEATED IN H STUDS, BOWING OUT, H STUDS MODIFIED LOOKS LIKE FACE SCREWED?)
Rated Assembly Inspection Passed 12/30/2022 12/30/2022
Misc
Resolved
12/30/2022
All Rough Inspection - Residential Passed 12/30/2022 12/30/2022 12/30/2022
Misc
Resolved
12/30/2022
Rated Assembly Inspection Partial 1/4/2023 1/4/2023 01/04/2023
Misc
Corrective Action Required
01/04/2023
1/4/23 - SCREW PATTERN FOR GB BRACING INSPECTED UNITS 2034,2036
Rated Assembly Inspection Passed 1/9/2023 1/9/2023 01/09/2023
Misc
Informational
01/09/2023
1/4/23 -Screw pattern for GB Bracing approved for units 2034 2036 1/9/23 SCREW PATTERN FOR GB BRACING APPROVED FOR UNITS 2032, 2038
Piers/Caissons Inspection - Residential Partial 1/17/2023 01/17/2023
Misc
Informational
01/17/2023
2038 okay
Piers/Caissons Inspection - Residential Partial 1/19/2023 (1:00) 1/19/2023 01/19/2023
Misc
Informational
01/17/2023
2038 okay 2036 OK
Piers/Caissons Inspection - Residential Partial 1/23/2023 01/23/2023
Misc
Informational
01/19/2023
2038 ok 2036 OK 2034 ok
Piers/Caissons Inspection - Residential Failed 1/25/2023 (8:00) 1/25/2023 01/25/2023
Misc
Informational
01/23/2023
2038 ok 2036 OK 2034 ok
Miscellaneous Correction
Corrective Action Required
01/25/2023
- 2032 remove water
Piers/Caissons Inspection - Residential Passed 1/26/2023 1/26/2023 01/26/2023
Misc
Informational
01/25/2023
2038 ok 2036 OK 2034 ok 2032 OK
Miscellaneous Correction
Partial Correction
01/26/2023
- 2032 remove water
Occupancy Inspection - Codes Residential Failed 2/16/2023 2/16/2023 02/16/2023
Misc
Corrective Action Required
02/16/2023
2032 sw holdbrooks On all - Seal top of exterior lights - Seal top of meter can and a/c disconnect - Provide splash pad - Sump discharge to extend 36” away from foundation Deck not inspected, remove temporary bracing 2032 - GFCI front porch - Provide back flow preventer at spigot at water shut off - Attach conduit at water heat at top - Secure properly the gas line to furnace - Outlets in garage, 1 not gfci protected and the other is dead - Garage entry over 30” and required to be a guard - Lights connected to GFCI outlet at living room - Air conditioning compressor not connected - Gfci in upstairs hall tripping bathroom light - Remove temp bracing under deck - 2034 - Could not test GFCI outlet on porch defective - At water main basement break off set screw to into siphon device - No electrical whip to air conditioning compressor - Remove temporary bracing under deck - Gfci in basement tied into lights - Gfci in living room tied to kitchen lights - Gfci on deck tied into living room lights - Outlets in master bedroom dead - Over 3/8” variance on garage stairs - No access to sump pump - 2036 - No access to sump pump - Gfci on deck tied to living room lights - Electrical whip not connected to compressor - Provide back flow preventer at water main in basement - Upstairs gfci tied to lighting 1036 - gfci in living room tied to lights - Air conditioning compressor no electrical - GFCI upstairs hall tied to lighting
Erosion Control Inspection Residential Failed 2/16/2023 02/16/2023
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/16/2023
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Misc
Corrective Action Required
02/16/2023
- Erosion control must be in place until sod is in place. At front of lot - pick up blowing trash and building materials on lot and whole development .
Occupancy Inspection - Codes Residential Failed 2/21/2023 2/21/2023 02/21/2023
Misc
Corrective Action Required
02/16/2023
2032 sw holdbrooks On all - Seal top of exterior lights - Seal top of meter can and a/c disconnect - Provide splash pad - Sump discharge to extend 36” away from foundation 2032 - Provide back flow preventer at spigot at water shut off - - Garage entry over 30” and required to be a guard - 2034 - Could not test GFCI outlet on porch defective - At water main basement break off set screw to into siphon device - 2036 - Provide back flow preventer at water main in 1036
Erosion Control Inspection Residential Failed 2/22/2023 02/22/2023
Misc
Corrective Action Required
02/16/2023
- Erosion control must be in place until sod is in place. At front of lot - pick up blowing trash and building materials on lot and whole development .
Occupancy Inspection - Codes Residential Ready for Temp CO 2/22/2023 2/22/2023 02/22/2023
Misc
Corrective Action Required
02/21/2023
2032 sw holdbrooks On all - Seal top of exterior lights - Seal top of meter can and a/c disconnect - Provide splash pad - Sump discharge to extend 36” away from foundation - Provide final grading and sod. 2032 OK for TCO 2034 -Ok for TCO 2036 - Ok for TCO 1038 Expiration of TCO 3/24/2023
Sidewalk Inspection Passed 03/17/2023
Misc
Informational
12/01/2022
12-1-22 RH. Sidewalk is formed up and aggregate is placed and compacted. Crew is going to use concrete blankets to cover concrete. Approved to pour.
Plot Plan Inspection Passed 3/17/2023 03/17/2023
Erosion Control Inspection Residential Passed 3/17/2023 03/17/2023
Misc
Resolved
03/17/2023
- Erosion control must be in place until sod is in place. At front of lot - pick up blowing trash and building materials on lot and whole development .
Occupancy Inspection - Codes Residential Full C of O 3/17/2023 3/17/2023 03/17/2023
Misc
Resolved
03/17/2023
2032 sw holdbrooks On all - Seal top of exterior lights - Seal top of meter can and a/c disconnect - Provide splash pad - Sump discharge to extend 36” away from foundation - Provide final grading and sod. 2032 OK for TCO 2034 -Ok for TCO 2036 - Ok for TCO 1038 Expiration of TCO 3/24/2023
Documents & Images
Date Uploaded File Type Document Name
09/28/2021 OS #2 - PERMIT APP
09/28/2021 Approved Plans Approved Truss Layout
09/28/2021 Approved Plans Approved Truss Pacakge
09/28/2021 Permit Codes Residential Plan Review
10/05/2021 Daylight Letter
10/08/2021 Plot Plan Approved Plot Plan
10/08/2021 Permit Codes Residential Plan Review
10/11/2021 Permit DS Building Permit
10/11/2021 Receipt Receipt for transaction:2021-007879
01/27/2022 Approved Plans Approved Drawings
03/10/2022 Letter INSPECTION SUMMARY
03/10/2022 Letter Stop Work Order
03/10/2022 M L Crose 2032, 2034, 2036, 2038 SW Holdbrooks Dr LSMO Osage Lot 2 Clayton P 2021-5067 3rd Party Footing Inspection Report 1-15-22
03/11/2022 Letter INSPECTION SUMMARY
03/15/2022 Letter INSPECTION SUMMARY
03/30/2022 Letter INSPECTION SUMMARY
03/30/2022 Letter INSPECTION SUMMARY
05/16/2022 Letter INSPECTION SUMMARY
05/17/2022 Letter INSPECTION SUMMARY
05/18/2022 Letter INSPECTION SUMMARY
05/20/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
05/26/2022 Letter INSPECTION SUMMARY
09/26/2022 Approved Plans Approved Revised Drawings
10/11/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter INSPECTION SUMMARY
11/28/2022 Letter INSPECTION SUMMARY
12/01/2022 Letter INSPECTION SUMMARY
12/01/2022 Letter INSPECTION SUMMARY
12/06/2022 Letter INSPECTION SUMMARY
12/06/2022 Letter INSPECTION SUMMARY
12/06/2022 Letter INSPECTION SUMMARY
12/06/2022 Letter INSPECTION SUMMARY
12/06/2022 Letter INSPECTION SUMMARY
12/07/2022 2 osage truss letter- signed
12/07/2022 OS2 truss pt_1
12/07/2022 OS2 truss pt_2
12/07/2022 OS2 truss pt_ 3
12/07/2022 OS2 truss pt_ 4
12/07/2022 OS2 truss pt_ 5
12/07/2022 OS2 truss pt_ 6
12/07/2022 OS2 truss pt_ 7
12/07/2022 OS2 truss pt_8
12/07/2022 OS2 truss pt_ 9
12/07/2022 OS2 truss pt_ 10
12/08/2022 Letter INSPECTION SUMMARY
12/08/2022 Letter INSPECTION SUMMARY
12/08/2022 Letter INSPECTION SUMMARY
12/08/2022 Letter INSPECTION SUMMARY
12/08/2022 Letter INSPECTION SUMMARY
12/12/2022 Letter INSPECTION SUMMARY
12/12/2022 Letter INSPECTION SUMMARY
12/12/2022 Letter INSPECTION SUMMARY
12/13/2022 OS #2 - Emerald Townhome - Farmhouse - Sheets - REVISION 12-12-22- signed
12/13/2022 Approved Plans APPROVED PAGE A4.0
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/15/2022 Letter INSPECTION SUMMARY
12/20/2022 OS2 letter 1 of 2
12/20/2022 OS2 letter 2 of 2
12/21/2022 OS #2 - HOUSE PLAN SET - 1_31_22 - MU
12/21/2022 OS #2 - Emerald Townhome - Sheets - Signed Unlocked - per Everstead
12/21/2022 Letter INSPECTION SUMMARY
12/21/2022 Letter INSPECTION SUMMARY
12/21/2022 Letter INSPECTION SUMMARY
12/21/2022 Letter INSPECTION SUMMARY
12/28/2022 Letter INSPECTION SUMMARY
12/28/2022 Letter INSPECTION SUMMARY
12/28/2022 Letter INSPECTION SUMMARY
12/29/2022 Letter INSPECTION SUMMARY
12/29/2022 Letter INSPECTION SUMMARY
12/30/2022 Letter INSPECTION SUMMARY
12/30/2022 Letter INSPECTION SUMMARY
01/04/2023 Letter INSPECTION SUMMARY
01/09/2023 Letter INSPECTION SUMMARY
01/17/2023 Letter INSPECTION SUMMARY
01/19/2023 Letter INSPECTION SUMMARY
01/23/2023 Letter INSPECTION SUMMARY
01/25/2023 Letter INSPECTION SUMMARY
01/26/2023 Letter INSPECTION SUMMARY
02/16/2023 Letter INSPECTION SUMMARY
02/16/2023 Letter INSPECTION SUMMARY
02/21/2023 Letter INSPECTION SUMMARY
02/22/2023 Certificate/License Codes Temporary Certificate of Occupancy
02/22/2023 Receipt Receipt for transaction:2023-001037
03/17/2023 Letter Codes Final Certificate of Occupancy
03/17/2023 Letter Field Certificate of Occupancy
03/17/2023 Letter INSPECTION SUMMARY
03/17/2023 Letter INSPECTION SUMMARY
03/17/2023 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home