Permit Application Status

PRCOM20241130


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20241130
Building Permit - Commercial
Certificate of Occupancy
JADAN DEVELOPMENT COMPANY LLC
CHANGE OF TENANT
THE ARC OF THE OZARKS - REMODEL WITH CHANGE OF TENANT
03/12/2024
04/22/2024
10/07/2024
08/19/2024
Locations
Contacts
JADAN DEVELOPMENT COMPANY LLC, Address:430 NE DICKINSON LN  
Q & Company, LLC, Address:2106 E. Central Ct, Ste 100  
CODYELLIOT@QANDCOMPANYLLC.COM  
SALADINO PLUMBING & HEATING COMPANY, Address:2210 TELEVISION PL, Phone:(816) 833-9900  
BCI Electrical, Inc, Address:PO Box 546  
PLUMBING BY FISHER INC, Address:9875 KILL CREEK RD, Phone:(913) 583-1971  
Buxton Kubik Dodd Design Collective, Address:3100 S National Ave, Suite 300, Phone:(417) 890-5543  
Clay Steinkuhler, Address:2106 E. Central Ct, Ste 100, Phone:(660) 221-9949  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 06/04/2024 06/03/2024
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/03/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Stamped plans receieved 5/21/2024.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/03/2024

2018 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have a current annual inspection.
Installation acceptance testing
Corrective Action Required
06/03/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be completed at the alarm test.
Fire Plan Review Approved with Conditions 04/18/2024 04/19/2024
Jim Eden
Miscellaneous Correction
Resolved
04/19/2024

The ICC Existing Building Code is not adopted by the City of Lee's Summit.
Construction documents - Fire protection systems
Corrective Action Required
04/19/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Construction documents for fire alarm systems
Resolved
04/19/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Address numbers required
Resolved
04/19/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide suite designations on the exterior doors.
Alarm Plan Review Released for Construction 05/01/2024 04/18/2024
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
04/18/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans received 4/17/2024.
Installation acceptance testing
Corrective Action Required
04/18/2024

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm test.
Building Plan Review Approved 04/18/2024 04/17/2024
Joe Frogge
Misc
Resolved
04/17/2024

Describe physical use of Day Program Room 114 in order to establish occupant load. If 50 or more there will be a conflict in the swing of door 114. Exiting from Corridor 109 requires that doors swing in direction of egress. If occupant load of Room 114 is 50 or more and egress is still directed through this room from corridor either do not route egress out of corridor 109 or reverse swing of 114
IBC 1606.2 Design dead load - structural
Resolved
04/17/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load.
Licensed Contractors Approved 04/18/2024 04/11/2024
Joe Frogge
LC - MEP Subs
Resolved
04/11/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Rejected 04/10/2024 04/10/2024
Joe Frogge
Misc
Corrective Action Required
04/10/2024

Describe physical use of Day Program Room 114 in order to establish occupant load. If 50 or more there will be a conflict in the swing of door 114. Exiting from Corridor 109 requires that doors swing in direction of egress. If occupant load of Room 114 is 50 or more and egress is still directed through this room from corridor either do not route egress out of corridor 109 or reverse swing of 114
IBC 1606.2 Design dead load - structural
Corrective Action Required
04/10/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment or provide engineer’s report to verify that existing roof structure will support additional load.
Licensed Contractors Rejected 04/10/2024 04/09/2024
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/09/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved with Conditions 04/10/2024 04/09/2024
Jim Eden
Miscellaneous Correction
Corrective Action Required
04/09/2024

The ICC Existing Building Code is not adopted by the City of Lee's Summit.
Construction documents for fire alarm systems
Corrective Action Required
04/09/2024

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings for review and approval.
Construction documents - Fire protection systems
Corrective Action Required
04/09/2024

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide shop drawings for review and approval.
Address numbers required
Corrective Action Required
04/09/2024

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide suite designations on the exterior doors.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $5,600.00 $5,600.00 Paid 04/22/2024
$34,056.00
7232302-Commercial License Tax Fee $17,028.00 $17,028.00 Paid 04/18/2024
$17,028.00
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 07/18/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 4/24/2024 04/24/2024
Underslab Plumbing Inspection - Commercial Passed 4/24/2024 04/24/2024
In-wall Inspection Failed 5/3/2024 5/3/2024 05/03/2024
Misc
Corrective Action Required
05/03/2024
-Protect plumbing per code throughout -Support plumbing from lateral movement at mid-wall height -Secure MC within 12” of box in kitchen area
In-wall Inspection Passed 5/6/2024 5/6/2024 05/06/2024
Misc
Resolved
05/06/2024
-Protect plumbing per code throughout -Support plumbing from lateral movement at mid-wall height -Secure MC within 12” of box in kitchen area
Above Ceiling Inspection Partial 6/6/2024 6/6/2024 06/06/2024
Misc
Informational
06/06/2024
Above-ceiling OK to drop tiles: -rm 107/107A, 108/108A, 110 to 114/114A/114B, 115/115A, 116 to 125, 139 to 143
Above Ceiling Inspection Passed 6/17/2024 6/17/2024 06/17/2024
Misc
Informational
06/06/2024
Above-ceiling OK to drop tiles: -rm 107/107A, 108/108A, 110 to 114/114A/114B, 115/115A, 116 to 125, 139 to 143 -Rest of the building above-ceiling-OK
Occupancy Inspection - Codes Commercial Ready for Temp CO 7/18/2024 7/18/2024 07/18/2024
Misc
Corrective Action Required
07/18/2024
-Approval required from Fire -Provide weatherproof cover for north exterior receptacle -Secure rooftop gas piping to support blocks; support gas piping at max 10 ft intervals; complete connection of gas piping to RTUs -Provide knee protection under rm 138 sink -Provide restroom signage -Adjust west exit door opening force to 5 lbs or less -Receptacle within six ft of sink must be gfci-protected (rm 114) -Post occupancy load sign in training room -Loose receptacle in training room 135 -All receptacles in kitchen area must be gfci-protected -Provide backflow preventer for ice maker -Provide receptacle within 25 ft if the rooftop units -Secure RTU whips within 12” of disconnects -Provide RTU breakers sized per unit labels
Alarm Test Failed 07/18/2024
Occupancy Inspection - Fire Temporary C of O 7/19/2024 7/19/2024 07/19/2024
Occupancy Inspection - Codes Commercial Temporary C of O 8/15/2024 8/15/2024 08/15/2024
Misc
Corrective Action Required
07/18/2024
-Approval required from Fire
Alarm Test Passed 8/15/2024 8/15/2024 08/19/2024
Occupancy Inspection - Codes Commercial Full C of O 8/19/2024 08/19/2024
Misc
Resolved
08/19/2024
-Approval required from Fire
Documents & Images
Date Uploaded File Type Document Name
03/12/2024 Application Form APPLICATION
03/27/2024 Letter AOLS Tenant Use Letter
03/27/2024 Specifications AOTO Lees Summit Reno Specifications Pkg 03_25_24
03/27/2024 Plans AOTO Lees Summit Reno CD Permit Pkg 03_25_24
03/28/2024 Letter License Tax Bill
04/10/2024 Letter DS P/R Corrections Document
04/11/2024 Letter AOTOLS Addendum 02 Narrative - 04_11_24
04/11/2024 Plans AOTO Lees Summit Reno CD Permit Pkg 04_11_24 w Add 02
04/11/2024 Letter AOTO LS Plan Review Response Letter - 041124
04/17/2024 Engineer Report/Study ArcoftheOzarks-0000-Lee'sSummit-MO-FA-J01-04162024 Submittal Book
04/17/2024 Plans ArcOfTheOzarks-0000-Lee'sSummit-MO-FA-J01-04122024 signed
04/18/2024 Letter Fire (Alarm) Plan Review Notice
04/18/2024 Drawing ArcOfTheOzarks-0000-Lee'sSummit-MO-FA-J01-04122024 signed APPROVED
04/19/2024 Approved Plans Approved construction plans
04/22/2024 Receipt Receipt for transaction: 2024-002544
04/22/2024 Letter DS Building Permit
04/24/2024 Letter INSPECTION SUMMARY
04/24/2024 Letter INSPECTION SUMMARY
05/03/2024 Letter INSPECTION SUMMARY
05/06/2024 Letter INSPECTION SUMMARY
05/21/2024 5-24-0066-The Arc of the Ozarks-FS Plans_stamped
06/03/2024 5-24-0066-The Arc of the Ozarks-FS Plans_stamped APPROVED
06/03/2024 Letter Fire (Sprinkler) Plan Review
06/06/2024 Letter INSPECTION SUMMARY
06/17/2024 Letter INSPECTION SUMMARY
07/18/2024 Letter INSPECTION SUMMARY
07/18/2024 Certificate/License Codes Temporary Certificate of Occupancy
07/18/2024 Receipt Receipt for transaction:2024-005977
08/07/2024 Approved Plans Approved cover sheet revision
08/15/2024 Certificate/License Codes Temporary Certificate of Occupancy
08/19/2024 Letter Codes Final Certificate of Occupancy
08/19/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home