Permit Application Status

PRCOM20234931


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20234931
Building Permit - Commercial
Certificate of Occupancy
DEER BROOK BGOG LLC
CHANGE OF TENANT
REMODEL OF EXISTING SPACE FOR SALON
09/27/2023
12/05/2023
05/07/2024
02/02/2024
Locations
Contacts
DEER BROOK BGOG LLC, Address:199 S HIGH ST STE 100  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
THUY LY, Address:5119 S SHRANK AVE , Phone:(816) 663-5699  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
CORNERSTONE ARCHITECT LLC, Address:8117 ROBERTS RD, Phone:(816) 838-3472  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 12/28/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
12/28/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Stamped paper plans received 12/21/2023.
Installation acceptance testing
Corrective Action Required
12/28/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule testing.
Miscellaneous Correction
Corrective Action Required
12/28/2023

All future plans shall be submitted electronically through the City Portal at devservices.cityofls.net.
Sprinkler Plan Review Released for Construction 12/14/2023 12/12/2023
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/12/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Sprinkler plansreceived November 30, 2023.
Installation acceptance testing
Corrective Action Required
12/12/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. A visual inspection will be made at the occupancy inspection.
Fire Plan Review Approved 11/20/2023 11/20/2023
Jim Eden
Building Plan Review Approved 11/20/2023 11/16/2023
Joe Frogge
IPC 403.1 Minimum number of fixtures
Resolved
11/16/2023

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Additional water closet required for each gender. (based on 85 occupants) 11/1/23 - Only 1 toilet added when 2 are required. i.e. women need 2 and men need 2. Same applies to lavatories.
IBC 1103.1 Where required - accessibility
Resolved
11/16/2023

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Self-serve drinks station must be fully accessible. Amend design to demonstrate compliance. At a minimum specify counter/sink height, turning space and minimum 36" wide entry. 11/1/23 - Maximum height is to be 34". The 36" in my earlier note was for the non-compliant peninsula that has since been removed.
Licensed Contractors Rejected 11/20/2023 11/16/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
11/13/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 11/1/23: - Santi Construction not licensed with us - On site contact info not provided 11/16/23: - Santi Construction not licensed with us - On site contact info not provided
Fire Plan Review Approved 11/08/2023 11/07/2023
Jim Eden
Portable fire extinguishers - general
Resolved
11/07/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two, 2A,10B,C fire extinguishers. Place near the front and rear of the building in a conspicuous location in a normal path of travel. Verified at inspection.
Miscellaneous Correction
Resolved
11/07/2023

The building is sprinklered and does have an alarm system. Provide shop drawings for both and correct the code analysis.
Miscellaneous Correction
Resolved
11/07/2023

[BE] 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are met based on such modified number and the occupant load does not exceed one occupantper 7 square feet (0.65 m2) of occupiable floor space.Where required by the fire code official, an approvedaisle, seating or fixed equipment diagram substantiatingany increase in occupant load shall be submitted. Whererequired by the fire code official, such diagram shall be posted. Verified at inspection.
Address numbers required
Resolved
11/07/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address for the space shall be posted on the front and rear doors. Verified at inspection.
Building Plan Review Rejected 11/08/2023 11/01/2023
Joe Frogge
IBC 602.1 Type of Construction - general
Resolved
11/01/2023

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Actions required: - Amend Code And Occupant Load Data to show correct construction type which is 5B. - Amend Code And Occupant Load Data to show this is a fully sprinklered building.
IBC 1004.5.1 Increase occupant load
Resolved
11/01/2023

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Amend Code And Occupant Load Data to show correct occupant load to reflect actual conditions. Assign 2 persons to each station. Should be approximately 80 occupants. (we do not use business models to ascertain this number)
IPC 403.1 Minimum number of fixtures
Corrective Action Required
11/01/2023

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Additional water closet required for each gender. (based on 85 occupants) 11/1/23 - Only 1 toilet added when 2 are required. i.e. women need 2 and men need 2. Same applies to lavatories.
IPC 403.2 Separate facilities
Resolved
11/01/2023

2018 IPC 403.2 Separate Facilities. (As amended by Lee’s Summit Code of Ordinances Section 7-405) Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer. 4. Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer. Action required: Label restrooms as Male and Female or apply for Codes Modification Request based on meeting newer code adoption year.
ICC A117.1 604.3.1 Water closet width
Resolved
11/01/2023

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clearance behind water closets.
IBC 1209.2 Finish materials
Resolved
11/01/2023

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials at mop sink. If paint is used it must be epoxy based.
IBC 1103.1 Where required - accessibility
Corrective Action Required
11/01/2023

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Self-serve drinks station must be fully accessible. Amend design to demonstrate compliance. At a minimum specify counter/sink height, turning space and minimum 36" wide entry. 11/1/23 - Maximum height is to be 34". The 36" in my earlier note was for the non-compliant peninsula that has since been removed.
IBC 1109.12.9 Point of sale and service counters - accessibility
Resolved
11/01/2023

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Specify compliant counter at reception area. (minimum 36" length of counter to be maximum 36" high)
IMC 502.1 Required exhaust
Resolved
11/01/2023

2018 IMC 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate, determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1. Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be design to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. (see code section for smoking requirements and exception) Table 403.3.1.1 Footnote h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more required source capture systems operate continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon. Action required: Clarification needed. Amend designs to demonstrate how exhaust air is collected directly at point were mani/pedi's are performed.
Licensed Contractors Rejected 11/08/2023 11/01/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
11/01/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent. 11/1/23: - Santi Construction not licensed with us - On site contact info not provided
LC - MEP Subs
Resolved
11/01/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 10/09/2023 10/09/2023
Jim Eden
Portable fire extinguishers - general
Corrective Action Required
10/09/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two, 2A,10B,C fire extinguishers. Place near the front and rear of the building in a conspicuous location in a normal path of travel. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
10/09/2023

The building is sprinklered and does have an alarm system. Provide shop drawings for both and correct the code analysis.
Miscellaneous Correction
Corrective Action Required
10/09/2023

[BE] 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are met based on such modified number and the occupant load does not exceed one occupantper 7 square feet (0.65 m2) of occupiable floor space.Where required by the fire code official, an approvedaisle, seating or fixed equipment diagram substantiatingany increase in occupant load shall be submitted. Whererequired by the fire code official, such diagram shall be posted. Verified at inspection.
Address numbers required
Corrective Action Required
10/09/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). The address for the space shall be posted on the front and rear doors. Verified at inspection.
Building Plan Review Rejected 10/09/2023 10/04/2023
Joe Frogge
IBC 602.1 Type of Construction - general
Corrective Action Required
09/28/2023

2018 IBC 602.1 General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. the building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire resistance rating not less than that specified in Table 602. Where required to have a fire-resistance rating by Table 601, building elements shall comply with the applicable provisions of Section 703.2. The protection for openings, ducts and air transfer openings in building elements shall not be required unless required by other provisions of this code. Actions required: - Amend Code And Occupant Load Data to show correct construction type which is 5B. - Amend Code And Occupant Load Data to show this is a fully sprinklered building.
IBC 1004.5.1 Increase occupant load
Corrective Action Required
09/28/2023

2018 IBC 1004.5.1 Increased occupant load. The occupant load permitted in any building, or portion thereof, is permitted to be increased from that number established for the occupancies in Table 1004.5, provided that all other requirements of the code are also met based on such modified number and the occupant load does not exceed one occupant per 7 square feet of occupiable floor space. Where required by the building official, an approved aisle, seating or fixed equipment diagram substantiating any increase in occupant load shall be submitted. Where required by the building official, such diagram shall be posted. Action required: Amend Code And Occupant Load Data to show correct occupant load to reflect actual conditions. Assign 2 persons to each station. Should be approximately 80 occupants. (we do not use business models to ascertain this number)
IPC 403.1 Minimum number of fixtures
Corrective Action Required
10/04/2023

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Additional water closet required for each gender. (based on 80 occupants)
IPC 403.2 Separate facilities
Corrective Action Required
10/04/2023

2018 IPC 403.2 Separate Facilities. (As amended by Lee’s Summit Code of Ordinances Section 7-405) Where plumbing fixtures are required, separate facilities shall be provided for each sex. Exceptions: 1. Separate facilities shall not be required for dwelling units and sleeping units. 2. Separate facilities shall not be required in structures or tenant spaces with a total occupant load, including both employees and customers, of 15 or fewer. 3. Separate facilities shall not be required in mercantile occupancies in which the maximum occupant load is 100 or fewer. 4. Separate facilities shall not be required in business occupancies in which the maximum occupant load is 25 or fewer. Action required: Label restrooms as Male and Female or apply for Codes Modification Request based on meeting newer code adoption year.
ICC A117.1 604.3.1 Water closet width
Corrective Action Required
10/04/2023

ICC A117.1 Section 604.3.1 Clearance Width. Clearance around a water closet shall be 60 inches minimum in width, measured perpendicular from the sidewall. Action required: Provide minimum 60" clearance behind water closets.
IBC 1209.2 Finish materials
Corrective Action Required
10/04/2023

2018 IBC 1209.2 Finish Materials. Walls, Floors and partitions in toilet and bathrooms shall comply with Sections 209.2.1 through 1209.2.4. 2018 1209.2.1 Floors and wall bases. In other than dwelling units, toilet, bathing and shower room floor finish materials shall have a smooth, hard, nonabsorbent surface. The intersections of such floors with walls shall have a smooth, hard, nonabsorbent vertical base that extends upward onto the walls not less than 4 inches. 2018 1209.2.2 Walls and partitions. Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of not less than 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. (See code section for possible exceptions.) 1209.2.3 Showers. (see code for details) 1209.2.4 Waterproof joints. (see code for details) Action required: Specify compliant wall finish materials at mop sink. If paint is used it must be epoxy based.
IBC 1103.1 Where required - accessibility
Corrective Action Required
10/04/2023

2018 IBC 1103.1 Where required. Sites, buildings, structures, facilities, elements and spaces, temporary or permanent, shall be accessible to persons with physical disabilities. Action required: Self-serve drinks station must be fully accessible. Amend design to demonstrate compliance. At a minimum specify counter/sink height, turning space and minimum 36" wide entry.
IBC 1109.12.9 Point of sale and service counters - accessibility
Corrective Action Required
10/04/2023

2018 IBC 1109.12.3 Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required: Specify compliant counter at reception area. (minimum 36" length of counter to be maximum 36" high)
IMC 502.1 Required exhaust
Corrective Action Required
10/04/2023

2018 IMC 403.3.1.1 Outdoor airflow rate. Ventilation systems shall be designed to have the capacity to supply the minimum outdoor airflow rate, determined in accordance with this section. In each occupiable space, the ventilation system shall be designed to deliver the required rate of outdoor airflow to the breathing zone. The occupant load utilized for design of the ventilation system shall be not less than the number determined from the estimated maximum occupant load rate indicated in Table 403.3.1.1. Ventilation rates for occupancies not represented in Table 403.3.1.1 shall be those for a listed occupancy classification that is most similar in terms of occupant density, activities and building construction; or shall be determined by an approved engineering analysis. The ventilation system shall be design to supply the required rate of ventilation air continuously during the period the building is occupied, except as otherwise stated in other provisions of the code. (see code section for smoking requirements and exception) Table 403.3.1.1 Footnote h. For nail salons, each manicure and pedicure station shall be provided with a source capture system capable of exhausting not less than 50 cfm. Exhaust inlets shall be located in accordance with Section 502.20. Where one or more required source capture systems operate continuously during occupancy, the exhaust rate from such systems shall be permitted to be applied to the exhaust flow rate required by Table 403.3.1.1 for the nail salon. Action required: Clarification needed. Amend designs to demonstrate how exhaust air is collected directly at point were mani/pedi's are performed.
Licensed Contractors Rejected 10/09/2023 10/04/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
10/04/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
10/04/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
7232302-Commercial Excise Tax Fee $2,631.75 $2,631.75 Paid 10/04/2023
$2,631.75
9110078-Valuation Fee for Change of Tenant $314.36 $314.36 Paid 12/01/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 02/01/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Failed 12/8/2023 12/7/2023 12/07/2023
Misc
Corrective Action Required
12/07/2023
Provide full set of plan on site, including all the plans sheets for all trades
Underslab Plumbing Inspection - Commercial Failed 12/8/2023 12/08/2023
Misc
Corrective Action Required
12/08/2023
-Underslab plumbing not per plan. Have architect resubmit new plumbing plan -Pressure test of underslab plumbing is required -Provide continuous support of underslab drain -Vent mop sink -Cannot use the back-to-back fitting to connect floor drain and sink drain in south unisex restroom -The combination-waste-and-vent piping receiving the waste from floor receptors cannot receive waste from the middle restrooms drains
In-wall Inspection Failed 12/8/2023 12/08/2023
Misc
Corrective Action Required
12/07/2023
-Protect DVW where within 1.25” of stud and track surface. Protect plumbing at top wall track with BOCA plates -Support water pex line every 32” -Protect pex water lines at studs with plastic grommets -Drain pipe shall slope min 1/8” per ft (not more than 1/2" per ft) -Vent laundry per code. Cannot vent double traps -Provide blocking for the vertical grab bars at water closet -Vent sink on the south side -Vent sink at the SE corner. Connect vent between sinks -Secure MC within 12” of receptacle boxes -Provide receptacles and EM lighting outlets located per plan -Provide exhaust pipings for nail tables and pedicure per plan **Do not rock the ceiling until all MEPs are completed
Underslab Plumbing Inspection - Commercial Failed 12/14/2023 12/14/2023 12/14/2023
Misc
Corrective Action Required
12/08/2023
**12/14-NOT READY FOR INSPECTION -Underslab plumbing not per plan. Have architect resubmit new plumbing plan -Pressure test of underslab plumbing is required -Provide continuous support of underslab drain -Vent mop sink -Cannot use the back-to-back fitting to connect floor drain and sink drain in south unisex restroom -The combination-waste-and-vent piping receiving the waste from floor receptors cannot receive waste from the middle restrooms drains
In-wall Inspection Failed 12/14/2023 12/14/2023 12/14/2023
Misc
Corrective Action Required
12/08/2023
**12/14-NOT READY FOR INSPECTION -Protect DVW where within 1.25” of stud and track surface. Protect plumbing at top wall track with BOCA plates -Support water pex line every 32” -Protect pex water lines at studs with plastic grommets -Drain pipe shall slope min 1/8” per ft (not more than 1/2" per ft) -Vent laundry per code. Cannot vent double traps -Provide blocking for the vertical grab bars at water closet -Vent sink on the south side -Vent sink at the SE corner. Connect vent between sinks -Secure MC within 12” of receptacle boxes -Provide receptacles and EM lighting outlets located per plan -Provide exhaust pipings for nail tables and pedicure per plan
In-wall Inspection Failed 12/15/2023 12/15/2023 12/15/2023
Misc
Corrective Action Required
12/14/2023
**12/14-NOT READY FOR INSPECTION -Protect DVW where within 1.25” of stud and track surface. Protect plumbing at top wall track with BOCA plates -Support water pex line every 32” -Protect pex water lines at studs from damage -Drain pipe shall slope min 1/8” per ft (not more than 1/2" per ft) -Provide blocking for the vertical grab bars at water closet -Secure MC within 12” of receptacle boxes -Provide receptacles and EM lighting outlets located per plan -Provide exhaust pipings for nail tables and pedicure per plan -Addenum: Engineer must address repair of damaged studs at the south wall
Underslab Plumbing Inspection - Commercial Failed 12/15/2023 12/15/2023
Misc
Corrective Action Required
12/14/2023
-Provide wye fitting at vertical-horizontal connection (below north restroom floor) -Provide continuous gravel support of underslab drain. Make sure drain piping is sloped per code -Vent mop sink or eliminate -Plan shows 8" underground pvc exhaust pipe for pedicure and nail table. See M200
Underslab Plumbing Inspection - Commercial Failed 12/18/2023 12/18/2023 12/18/2023
Misc
Corrective Action Required
12/15/2023
-PVC exhaust pipes for pedicure and nail tables not per current plan. Submit revised mechanical plan to city
In-wall Inspection Partial 12/18/2023 12/18/2023 12/18/2023
Misc
Corrective Action Required
12/15/2023
-Engineer must address repair of damaged studs at the south wall **Do not cover south demising wall until it is inspected per engineer letter
Above Ceiling Inspection Failed 1/8/2024 1/8/2024 01/08/2024
Misc
Corrective Action Required
01/08/2024
-Plumbing vent shall be connect to a vent stack extended to outdoor -Add additional ceiling support. Provide information on how far the ceiling channels can span -Submit new mechanical installation plan **Above ceiling at rear of tenant space** -Close open electrical j-boxes -Terminate all MC cables in j-boxes -Secure all MC within 12” of all boxes -Support all trades per code. Support flexible duct off ceiling grids at max 5 ft interval; PVC at 4 ft or less intervals; all water PEX lines every 32”; all MC cables at 6 ft or less intervals -Complete all trades **Not ready for inspection
In-wall Inspection Partial 1/11/2024 01/11/2024
Misc
Corrective Action Required
12/18/2023
-Engineer fix for damaged studs of demising wall-4 ft studs fasten to damaged studs per engineer drawing-OK. Plywood will be installed to reinforce the bottom 4 ft height of the wall. Call for inspection when ready
Underslab Plumbing Inspection - Commercial Passed 01/11/2024
Misc
Resolved
01/11/2024
-PVC exhaust pipes for pedicure and nail tables not per current plan. Submit revised mechanical plan to city
Above Ceiling Inspection Failed 1/11/2024 1/11/2024 01/11/2024
Misc
Corrective Action Required
01/08/2024
-Provide access to mechanical units per code. Provide opening directly in front of the furnaces where the appliances are capable of being serviced and removed through the required opening. -Cannot use ceiling grid support wire to support MC cables -Support PVC @ 4 ft intervals -Secure water lines -Secure MC every 6 ft
In-wall Inspection Passed 1/12/2024 1/12/2024 01/12/2024
Misc
Resolved
01/12/2024
-Engineer fix for damaged studs of demising wall-4 ft studs fasten to damaged studs per engineer drawing-OK. Plywood installed to reinforce the bottom 4 ft height of the wall-OK
Above Ceiling Inspection Passed 1/18/2024 1/18/2024 01/18/2024
Misc
Resolved
01/18/2024
-Provide access to mechanical units per code. Provide opening directly in front of the furnaces where the appliances are capable of being serviced and removed through the required opening. -Cannot use ceiling grid support wire to support MC cables -Support PVC @ 4 ft intervals -Secure water lines -Secure MC every 6 ft
Occupancy Inspection - Codes Commercial Not Ready 1/26/2024 1/26/2024 01/26/2024
Misc
Corrective Action Required
01/26/2024
-Complete corrections for all LSFD -Provide site address at all doors -Install all missing cover plates -Complete all electrical throughout -Install accessible restroom signage -All grab bars to be code compliant -All toilets to be 16" to 18" to centerline from sidewall -Install all accessible restroom accessories and mirrors -GFCIs not tested at inspection due to being covered -Wall and baseboard finishes at restrooms and within 2' of sinks to be non absorbant finish -Complete manicure stations and exhaust system -Provide hammer arrestors at all quick closing valves -Expansion tank cannot be be supported with piping system -Provide additional expansion tank for second water heater or documentation for sizing and capacity of single tank -Water heater discharge pipe must discharge through an air gap not less than 2 times the pipe diameter above the floor drain -Label electrical panels -Update plans to show changes to equipment layout and deletion of mop sink -Provide panic hardware at all exterior doors per note 4 on A401 -Threshold height at back doors cannot exceed 1/2" to landing -Provide complete, orderly, stapled, approved plans for inspection -Not ready fee assessed, pay all fees before rescheduling **This job is not ready for final inpsection and this list is incomplete
Alarm Test Passed 1/31/2024 01/31/2024
Occupancy Inspection - Codes Commercial Failed 2/1/2024 2/1/2024 02/01/2024
Misc
Corrective Action Required
01/26/2024
**Not ready fee assessed, pay all fees before rescheduling** -The pedicure fixture waste receptors shall not be concealed and must be provided with ready access -Provide gfci protection for receptacle near west sink -Restroom signage braille must be within 48” -All toilets to be 16" to 18" to centerline from sidewall -Restroom grab bar must extend min 54” from wall for the side 42” grab bar and 42” for the rear 36” grab bar -Toilet lever must be on approach side -Receptacles inside middle two restrooms must be gfci-protected; same for the receptacle near the sink near the rear exit door -Provide backflow preventer for water supply outlet to the towel steamer -Provide hammer arrestors at 2nd washer valves -Secure both water heater expansion tanks in place -Connect all EGCs to the equipment grounding bus bar; take out the green bonding screws from both sub-panel -Provide screen at dryer outlet damper -Provide a disconnect for the rooftop exhaust fan; wire termination shall be inside boxes; install all conductors inside raceway -Provide 2000 cfm rooftop exhaust fan unit -Secure raceways within 12” of the rooftop AC disconnects; reinforce the AC disconnect supports
Occupancy Inspection - Fire Passed 2/2/2024 2/2/2024 02/02/2024
Occupancy Inspection - Codes Commercial Full C of O 2/2/2024 2/2/2024 02/02/2024
Misc
Resolved
02/02/2024
Documents & Images
Date Uploaded File Type Document Name
09/28/2023 Plans Full Drawing Set - Lavish Nails & Lashes @ Lee Summit
09/28/2023 Application Form UPDATED - Commercial Permit Application - Lavish Nails & Lashes
09/28/2023 Letter License Tax Bill
10/10/2023 Letter DS P/R Corrections Document
10/31/2023 Plans Full Drawing Set - City Comments - Lavish Nails & Lashes @ Lee Summit
10/31/2023 Waiver/Modification Document Code Modification Request - Lavish Nails and Lashes
10/31/2023 Letter 10-24-23 Cover Letter - Lavish Nails
11/09/2023 Letter DS P/R Corrections Document
11/13/2023 Plans Full Drawing Set - City Comments 2 - Lavish Nails & Lashes @ Lee Summit
11/13/2023 Letter 11-13-2023 Cover Letter - Lavish Nails
11/21/2023 Approved Plans approved plan set
11/30/2023 Plans sprinkler plans
12/01/2023 Receipt Receipt for transaction:2023-008820
12/05/2023 Letter DS Building Permit
12/07/2023 Letter INSPECTION SUMMARY
12/07/2023 Approved Plans approved Drawing Set - Lavish Nails & Lashes @ Lee Summit
12/08/2023 Letter INSPECTION SUMMARY
12/08/2023 Letter INSPECTION SUMMARY
12/12/2023 sprinkler plans APPROVED
12/12/2023 Letter Fire (Sprinkler) Plan Review
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/15/2023 Letter INSPECTION SUMMARY
12/15/2023 Letter INSPECTION SUMMARY
12/18/2023 Letter INSPECTION SUMMARY
12/18/2023 Letter INSPECTION SUMMARY
12/28/2023 Letter Fire (Alarm) Plan Review Notice
12/29/2023 23-211_M200
01/08/2024 Letter INSPECTION SUMMARY
01/08/2024 Letter Fire (Alarm) Plan Review Notice
01/11/2024 Engineer Report/Study Stud wall reinf 1155 NE Rice Road
01/11/2024 Letter INSPECTION SUMMARY
01/11/2024 Letter INSPECTION SUMMARY
01/11/2024 Letter INSPECTION SUMMARY
01/12/2024 Letter INSPECTION SUMMARY
01/18/2024 Letter INSPECTION SUMMARY
01/26/2024 Letter INSPECTION SUMMARY
02/01/2024 Letter INSPECTION SUMMARY
02/01/2024 Receipt Receipt for transaction: 2024-000553
02/02/2024 Letter Field Certificate of Occupancy
02/02/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home