Permit Application Status

PRCOM20224767


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20224767
Building Permit - Commercial
Certificate of Occupancy
NEW TENANT FINISH
TENANT FINISH FOR OFFICE/WAREHOUSE SPACE FOR ANIMAL CARE PRODUCTS
09/23/2022
11/22/2022
06/02/2024
11/20/2023
Locations
Contacts
KADEAN CONSTRUCTION, Address:3668 S GEYER RD STE 100, Phone:(636) 305-0099  
Curran Architecture, Address:5719 Lawton Loop E. Dr. @212, Phone:(317) 288-0681  
METRO AIR CONDITIONING , Address:8151 MCCOY ST, Phone:(913) 888-3991  
HERITAGE ELECTRIC, Address:841 N MARTWAY DR, Phone:(913) 747-0528  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
Troy Brown, Address:1120 NW Main Street  
jgonzalez@conveyorsolutions.com  
Electrical Systems group, Address:1450 N. McLean Blvd  
Conveyor Solutions Inc., Address:1450 N. McLean Blvd  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 09/07/2023 09/01/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/31/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide stamped shop drawings for the alarm system including contractor information. 8/3/2023 Stamped plans received with contractor information. 8/31/2023- Revised plans received.
Installation acceptance testing
Corrective Action Required
09/01/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Coordinate testing with sprinkler contractor. Call (816) 969-1300 to schedule testing to coordinate testing.
Miscellaneous Correction
Corrective Action Required
09/01/2023

The corridor between the exterior wall and cooler has no appliances present and will be evaluated at testing. Additional coverage may be required.
Misc
Corrective Action Required
09/01/2023

Does FM Global review alarm plans?
Alarm Plan Review Rejected 08/17/2023 08/15/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/03/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide stamped shop drawings for the alarm system including contractor information. 8/3/2023 Stamped plans received with contractor information.
Miscellaneous Correction
Corrective Action Required
08/15/2023

Where is the FACP located? Is this a continuation of another system? Seperate systems shall communicate with the building alarm system.
Miscellaneous Correction
Corrective Action Required
08/15/2023

Smoke detection is not provided above NAC 1,2,and 3.
Miscellaneous Correction
Corrective Action Required
08/15/2023

Audible notification appliances not present in the break room or training room. The coolers are not shown or provided with notification appliances. Make corrections and resubmit plans.
Miscellaneous Correction
Corrective Action Required
08/15/2023

The alarm contractor does not have a City of Lee's Summit Business License. Obtain a license.
Brandon Kalwei 08/03/2023 2:02 PM
Alarm Plan Review Rejected 06/01/2023 06/25/2023
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
06/25/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide stamped shop drawings for the alarm system including contractor information.
Sprinkler Plan Review Released for Construction 05/26/2023 05/24/2023
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
05/24/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. FM Global approved plans for Zoetis space received 5/12/2023.
Installation acceptance testing
Corrective Action Required
05/24/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule hydrostatic and flow testing.
Licensed Contractors Rejected 11/01/2022 04/12/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
04/12/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
04/12/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 03/29/2023 03/29/2023
Jim Eden
Miscellaneous Correction
Corrective Action Required
03/29/2023

Provide plans for exit and emergency lighting in the rack storage araes.
Miscellaneous Correction
Corrective Action Required
03/29/2023

3201.3 Construction documents. At the time of building permit application for new structures designed to accommodate high-piled storage or for requesting a change of occupancy/ use, and at the time of application for a storage permit, plans and specifications shall be submitted for review and approval. In addition to the information required by the International Building Code, the storage permit submittal shall include the information specified in this section. The construction documents shall include all of the following: 1. Floor plan of the building showing locations and dimensions of high-piled storage areas. 2. Usable storage height for each storage area. 3. Number of tiers within each rack, if applicable. 4. Commodity clearance between top of storage and the sprinkler deflector for each storage arrangement. 5. Aisle dimensions between each storage array. 6. Maximum pile volume for each storage array. 7. Location and classification of commodities in accordance with Section 3203. 8. Location of commodities that are banded or encapsulated. 9. Location of required fire department access doors. 10. Type of fire suppression and fire detection systems. 11. Location of valves controlling the water supply of ceiling and in-rack sprinklers. 12. Type, location and specifications of smoke removal and curtain board systems. 13. Dimension and location of transverse and longitudinal flue spaces. 14. Additional information regarding required design features, commodities, storage arrangement and fire protection features within the high-piled storage area shall be provided at the time. Action required- Provide a PE stamped summary for the information listed above. The storage plan shall also be reviewed by the tenants insurance company.
Construction documents for fire alarm systems
Corrective Action Required
03/29/2023

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required- Provide shop drawings for modifications to the buildingg alarm system to provide notification in the rack storage area. Submit plans to the portal at devservices,cityofls.net.
Construction documents - Fire protection systems
Corrective Action Required
03/29/2023

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required- Provide shop drawings for modifications to the building to protect the rack storage area. Submit plans to the portal at devservices,cityofls.net.
Building Plan Review Approved 03/29/2023 03/24/2023
Joe Frogge
IBC 1606.2 Design dead load - structural
Corrective Action Required
03/22/2023

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load from equipment on or supported by roof. Or provide design to strengthen roof accordingly. 10/25/22 - letter provided lists loads but does not speak to the roof capacity to support new loads. Mike Weisenborn 11/22/2022 11:49 AM - Provide a stamped and sealed copy of plan set "LSCC B1 - Zoetis TI - Joist and Deck Field Use 10-10-2022".
Building Plan Review Approved with Conditions 11/01/2022 11/22/2022
Mike Weisenborn
IBC 706.1 Fire and Smoke Protection - General
Resolved
10/25/2022

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Provide complete UL details for rated assemblies that include screw/nail patterns and penetrations.
IBC 1209.2 Urinal partitions - privacy
Resolved
10/25/2022

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide urinal partitions in driver's lounge restrooms. 128 & 130.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
10/25/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door out of Tlt 110.
IBC 1606.2 Design dead load - structural
Corrective Action Required
10/25/2022

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load from equipment on or supported by roof. Or provide design to strengthen roof accordingly. 10/25/22 - letter provided lists loads but does not speak to the roof capacity to support new loads. Mike Weisenborn 11/22/2022 11:49 AM - Provide a stamped and sealed copy of plan set "LSCC B1 - Zoetis TI - Joist and Deck Field Use 10-10-2022".
IBC 1013.1 Where required - exit sign
Resolved
10/25/2022

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign at door 116A leading out of break room. (2 exits required out of this space - do not direct egress through warehouse)
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
10/25/2022

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of door leading out of Break Room to exterior. (and any other doors not installed at shell)
Fire Plan Review Approved with Conditions 11/01/2022 10/31/2022
Ben Hicks
Knox box required
Resolved
10/31/2022

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action Required: Show Knox box next to FDC
Installation acceptance testing
Corrective Action Required
10/25/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call Lee's Summit Fire Department at 816-969-1300 to schedule alarm test/ Hydro/ FDC flow tests
Alarm testing.
Corrective Action Required
10/25/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Action required: Call 816-969-1300 to schedule alarm testing
Portable fire extinguishers - conspicuous locations
Resolved
10/31/2022

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Show extinguisher locations
Miscellaneous Correction
Resolved
10/31/2022

(HMIS). Where required by the fire code official, an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall include the following information: 1. Product name. 2. Component. 3. Chemical Abstract Service (CAS) number. 4. Location where stored or used. 5. Container size. 6. Hazard classification. 7. Amount in storage. 8. Amount in use-closed systems. 9. Amount in use-open systems. Action Required: Show listing for substances kept on premises
Miscellaneous Correction
Corrective Action Required
10/25/2022

IFC 2018 510.1 Emergency responder radio coverage in new buildings. New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication system utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. Action Required: Complete radio study
Emergency power for illumination
Resolved
10/31/2022

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required- Show two exits from break room with emergency exit signage, exterior Egress lighting needed at all exits from building.
Illumination required
Resolved
10/31/2022

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Egress lighting needed at all exterior sides of exits.
Construction documents for fire alarm systems
Corrective Action Required
10/25/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Submit deferred submittal alarm plans to Lee's Summit Fire Department
Construction documents - Fire protection systems
Corrective Action Required
10/25/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Submit deferred plans to Lee's Summit Fire Dept.
Fire Plan Review Rejected 10/05/2022 10/05/2022
Ben Hicks
Knox box required
Corrective Action Required
10/05/2022

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. Action Required: Show Knox box next to FDC
Installation acceptance testing
Corrective Action Required
10/05/2022

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call Lee's Summit Fire Department at 816-969-1300 to schedule alarm test/ Hydro/ FDC flow tests
Alarm testing.
Corrective Action Required
10/05/2022

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Action required: Call 816-969-1300 to schedule alarm testing
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/05/2022

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Show extinguisher locations
Miscellaneous Correction
Corrective Action Required
10/05/2022

(HMIS). Where required by the fire code official, an application for a permit shall include an HMIS, such as Superfund Amendments and Reauthorization Act of 1986 (SARA) Title III, Tier II Report or other approved statement. The HMIS shall include the following information: 1. Product name. 2. Component. 3. Chemical Abstract Service (CAS) number. 4. Location where stored or used. 5. Container size. 6. Hazard classification. 7. Amount in storage. 8. Amount in use-closed systems. 9. Amount in use-open systems. Action Required: Show listing for substances kept on premises
Miscellaneous Correction
Corrective Action Required
10/05/2022

IFC 2018 510.1 Emergency responder radio coverage in new buildings. New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication system utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. Action Required: Complete radio study
Emergency power for illumination
Corrective Action Required
10/05/2022

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Action required- Show two exits from break room with emergency exit signage, exterior Egress lighting needed at all exits from building.
Illumination required
Corrective Action Required
10/05/2022

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action required: Egress lighting needed at all exterior sides of exits.
Construction documents for fire alarm systems
Corrective Action Required
10/05/2022

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Submit deferred submittal alarm plans to Lee's Summit Fire Department
Construction documents - Fire protection systems
Corrective Action Required
10/05/2022

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Submit deferred plans to Lee's Summit Fire Dept.
Building Plan Review Rejected 10/05/2022 09/28/2022
Joe Frogge
IBC 706.1 Fire and Smoke Protection - General
Corrective Action Required
09/28/2022

2018 IBC 706.1 General. Fire walls shall be constructed in accordance with Sections 706.2 through 706.11. The extent and location of such fire walls shall provide a complete separation. Where a fire wall also separates occupancies that are required to be separated by a fire barrier wall, the most restrictive requirements of each separation shall apply. Action required: Provide complete UL details for rated assemblies that include screw/nail patterns and penetrations.
IBC 1209.2 Urinal partitions - privacy
Corrective Action Required
09/28/2022

2018 IBC 1209.3.2 Urinal partitions. Each urinal utilized by the public or employees shall occupy a separate area with walls or partitions to provide privacy. The walls or partitions shall begin at a height not more than 12 inches from and extend not less than 60 inches above the finished floor surface. The walls or partitions shall extend from the wall surface at each side of the urinal not less than 18 inches or to a point not less than 6 inches beyond the outermost front lip of the urinal measures from the finished back wall surface, whichever is greater. Exceptions: 1. Urinal partitions shall not be required in a single-occupant or family or assisted-use toilet room with a lockable door. 2. Toilet rooms located in child day care facilities containing two or more urinals shall be permitted to have one urinal without partitions. Action required: Provide urinal partitions in driver's lounge restrooms. 128 & 130.
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
09/28/2022

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" at latch side of door out of Tlt 110.
IBC 1606.2 Design dead load - structural
Corrective Action Required
09/28/2022

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load from equipment on or supported by roof. Or provide design to strengthen roof accordingly.
IBC 1013.1 Where required - exit sign
Corrective Action Required
09/28/2022

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign at door 116A leading out of break room. (2 exits required out of this space - do not direct egress through warehouse)
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
09/28/2022

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of door leading out of Break Room to exterior. (and any other doors not installed at shell)
Licensed Contractors Approved 10/05/2022 09/23/2022
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $32,243.46 $32,243.46 Paid 11/22/2022
7232302-Industrial/Warehouse Excise Tax Fee $45,078.00 $45,078.00 Paid 09/26/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 08/03/2023
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 3/1/2023 03/01/2023
Misc
Corrective Action Required
03/01/2023
3/1/23 Nothing ready for inspection
Underslab Plumbing Inspection - Commercial Partial 3/2/2023 3/2/2023 03/02/2023
Misc
Corrective Action Required
03/01/2023
AREA D DWV FOR TENANT FINISH NORTHEAST CORNER -COMPLETE EXCEPT LAV AND SANITARY IN LAST 10' OF WEST SECTION
Underslab Electrical Inspection - Commercial Passed 4/11/2023 4/11/2023 04/11/2023
Gas Service Inspection - Commercial Passed 5/22/2023 5/22/2023 05/22/2023
In-wall Inspection Partial 5/26/2023 5/26/2023 05/26/2023
Misc
Corrective Action Required
05/26/2023
-Framing at Pump room near CL 5 and demising wall ok
Rated Assembly Inspection Partial 05/26/2023
Misc
Corrective Action Required
05/26/2023
-Provide UL number and screw pattern detail
Rated Assembly Inspection Partial 6/2/2023 6/2/2023 06/02/2023
Misc
Corrective Action Required
05/26/2023
Demising wall screw pattern: -West side of wall from pass through opening south ok
In-wall Inspection Partial 06/02/2023
Misc
Corrective Action Required
05/26/2023
Pump room near CL 5 -Provide protection plates at top and bottom track for vent line
In-wall Inspection Partial 6/8/2023 6/8/2023 06/08/2023
Misc
Corrective Action Required
06/02/2023
Pump room near CL 5 -Provide protection plates at top and bottom track for vent line Locker rooms 117, 120 -Protect dwv at top and bottom track Office 11A -Secure mc Storage 125 -Complete electrical Penthouse -Incomplete
Misc
Informational
06/08/2023
Areas approved to rock: Unit D TI except 117,120,11a, 127,128, 129,130, 126
In-wall Inspection Partial 06/13/2023
Misc
Corrective Action Required
06/08/2023
Pump room near CL 5 -Provide protection plates at top and bottom track for vent line Locker rooms 117, 120 -Protect dwv at top and bottom track Office 11A -Secure mc Penthouse -Incomplete
Misc
Informational
06/08/2023
Areas approved to rock: Unit D TI except 117,120,11a, 127,128, 129,130, 125, 126
Rated Assembly Inspection Partial 6/13/2023 6/13/2023 06/13/2023
Misc
Corrective Action Required
06/02/2023
Demising wall screw pattern: -West side of wall from pass through opening south ok -West side of wall from pass through opening north ok
In-wall Inspection Partial 6/16/2023 6/16/2023 06/16/2023
Misc
Corrective Action Required
06/13/2023
Pump room near CL 5 -Provide protection plates at top and bottom track for vent line Penthouse -Incomplete
Misc
Informational
06/13/2023
Areas approved to rock: Unit D TI except 117,120,11a, 127,128, 129,130, 125, 126,117,120
Electrical Service Inspection Failed 6/23/2023 06/23/2023
E250.50 Grounding Electrode System
Corrective Action Required
06/23/2023
-Connect metallic water piping to grounding electrode system per NEC 250.50 and 250.52
Electrical Service Inspection Passed 6/26/2023 6/26/2023 06/26/2023
E250.50 Grounding Electrode System
Resolved
06/26/2023
-Connect metallic water piping to grounding electrode system per NEC 250.50 and 250.52
In-wall Inspection Partial 6/29/2023 6/29/2023 06/29/2023
Misc
Corrective Action Required
06/16/2023
Penthouse -Incomplete
Misc
Informational
06/16/2023
-complete except as noted
Rated Assembly Inspection Partial 7/25/2023 7/25/2023 07/25/2023
Misc
Corrective Action Required
06/13/2023
Demising wall screw pattern: -West side complete except at pass through -East side from column line 7-10 ok **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Rated Assembly Inspection Failed 8/2/2023 8/2/2023 08/02/2023
Misc
Corrective Action Required
07/25/2023
Demising wall screw pattern: -West side complete except at pass through -East side from column line 7-10 ok **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Misc
Corrective Action Required
08/02/2023
8/2/23 -Repair holes at pass through- replace rock from stud to stud and maintain screw pattern
In-wall Inspection Failed 8/2/2023 8/2/2023 08/02/2023
Misc
Corrective Action Required
06/29/2023
-Remove rock from penthouse for inspection per previous conversations
Misc
Informational
06/29/2023
-complete except as noted
Rated Assembly Inspection Not Ready 8/3/2023 8/3/2023 08/03/2023
Misc
Corrective Action Required
08/02/2023
Demising wall screw pattern: -West side complete except at pass through -East side from column line 7-10 ok **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Misc
Corrective Action Required
08/02/2023
8/2/23 -Repair holes at pass through- replace rock from stud to stud and maintain screw pattern 8/3/23 Not ready fee assessed
In-wall Inspection Passed 8/3/2023 8/3/2023 08/03/2023
Misc
Resolved
08/03/2023
-Remove rock from penthouse for inspection per previous conversations
Misc
Resolved
08/03/2023
-complete except as noted
Rated Assembly Inspection Partial 8/9/2023 8/9/2023 08/09/2023
Misc
Corrective Action Required
08/03/2023
Demising wall screw pattern: -West side complete -East side from column line 7-10 ok **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Misc
Resolved
08/09/2023
Above Ceiling Inspection Partial 8/16/2023 08/16/2023
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/16/2023
Rooms 116-122
Rated Assembly Inspection Partial 8/16/2023 8/16/2023 08/16/2023
Misc
Corrective Action Required
08/09/2023
Demising wall screw pattern: -West side complete -East side from column line 3-10 ok **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Above Ceiling Inspection Partial 8/17/2023 8/17/2023 08/17/2023
THE FOLLOWING AREAS ARE APPROVED
Corrective Action Required
08/16/2023
Rooms 101-122
Rated Assembly Inspection Partial 8/22/2023 8/22/2023 08/22/2023
Misc
Corrective Action Required
08/16/2023
Demising wall screw pattern: -West side complete -East side complete **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Above Ceiling Inspection Passed 8/23/2023 8/23/2023 08/23/2023
THE FOLLOWING AREAS ARE APPROVED
Resolved
08/23/2023
Rooms 101-122
Miscellaneous Inspection Failed 9/1/2023 9/1/2023 09/01/2023
Misc
Corrective Action Required
09/01/2023
9-1-23 inspection for pre final walkthrough ***INSPECTION DENIED. REMOVE ALL FURNITURE FROM SPACE. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL ALL UNAPPROVED FURNITURE IS REMOVED FROM THE SITE
Rough Electrical Inspection - Commercial Failed 09/06/2023
Misc
Corrective Action Required
09/06/2023
9/6/23 Remove bonding screw from all sub panels
Rated Assembly Inspection Failed 9/15/2023 9/15/2023 09/15/2023
Misc
Corrective Action Required
08/22/2023
Demising wall screw pattern: -West side complete -East side complete **Seal perimeter and all penetrations Riser room screw pattern complete **Seal perimeter and all penetrations
Rated Assembly Inspection Partial 9/21/2023 9/21/2023 09/21/2023
Misc
Corrective Action Required
09/15/2023
Demising wall screw pattern: -West side complete -East side complete **Seal perimeter and all penetrations -West side only: Seal between beams and conduit openings at 4 north columns and north end Riser room screw pattern complete **Seal perimeter and all penetrations
Rated Assembly Inspection Partial 9/28/2023 9/28/2023 09/28/2023
Misc
Corrective Action Required
09/21/2023
Demising wall screw pattern: -West side complete -East side complete **Seal perimeter and all penetrations -West side only: Complete Riser room screw pattern complete **Seal perimeter and all penetrations
Occupancy Inspection - Codes Commercial Failed 9/28/2023 9/28/2023 09/28/2023
Misc
Corrective Action Required
09/28/2023
-Complete corrections for all other departments -Install restroom grab bars per code -Secure all mc within 12" of boxes or equipment -Install all cover plates -Support sprinkler pipes vertically per code at tenant spaces -Complete installation of sinks in restrooms -Correct gap at receptacles at women's restroom and break room -Mirrors to be max 40' aff to reflective surface -Remove plastic above ceilng in IT room -Protect receptacles at charging stations within 6' of water -Complete rated assembly inspections -Complete egress paths at west exit **OK TO STOCK AND TRAIN ONLY
Rated Assembly Inspection Partial 10/3/2023 10/03/2023
Misc
Corrective Action Required
09/28/2023
Demising wall screw pattern: -West side complete -East side complete -Riser room complete **Seal perimeter and all penetrations -West side only: Complete -East side: Seal in between bar joists at north (2) column lines -Riser room complete **INSTALL FIRE RATED JOINT SYSTEM PER IBC 715 THROUGHOUT
Rated Assembly Inspection Passed 10/11/2023 10/11/2023 10/11/2023
Misc
Resolved
10/11/2023
Demising wall screw pattern: -West side complete -East side complete -Riser room complete **Seal perimeter and all penetrations -West side only: Complete -East side: Seal in between bar joists at north (2) column lines -Riser room complete **INSTALL FIRE RATED JOINT SYSTEM PER IBC 715 THROUGHOUT
Miscellaneous Inspection Failed 10/24/2023 10/24/2023 10/24/2023
Misc
Corrective Action Required
10/24/2023
-Submit the racking & conveyor plan to the city for approval under separate permit PRCOM20233787 -Rack near conveyor-tighten all column base anchors
Miscellaneous Inspection Passed 9/20/2023 9/20/2023 11/03/2023
Misc
Resolved
11/03/2023
9-1-23 inspection for pre final walkthrough ***INSPECTION DENIED. REMOVE ALL FURNITURE FROM SPACE. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL ALL UNAPPROVED FURNITURE IS REMOVED FROM THE SITE
Underslab Plumbing Inspection - Commercial Passed 11/03/2023
Misc
Resolved
11/03/2023
AREA D DWV FOR TENANT FINISH NORTHEAST CORNER -COMPLETE EXCEPT LAV AND SANITARY IN LAST 10' OF WEST SECTION
Rough Electrical Inspection - Commercial Passed 11/03/2023
Misc
Resolved
11/03/2023
9/6/23 Remove bonding screw from all sub panels
Occupancy Inspection - Codes Commercial Failed 11/10/2023 11/10/2023 11/10/2023
Misc
Corrective Action Required
09/28/2023
-Complete corrections for all other departments -Complete generator **OK TO STOCK AND TRAIN ONLY
Occupancy Inspection - Codes Commercial Full C of O 11/20/2023 11/20/2023 11/20/2023
Misc
Resolved
11/20/2023
-Complete corrections for all other departments -Complete generator **OK TO STOCK AND TRAIN ONLY
Documents & Images
Date Uploaded File Type Document Name
09/23/2022 Application Form Zoetis TI Permit Application
09/23/2022 Plans LSCC B1 - Zoetis TI - Permit Set 9-20-22 R
09/23/2022 Engineer Report/Study LSCC B1 - Zoetis TI - Fire Protection Hydraulics Calcs 09_07_22
09/23/2022 Plans LSCC B1 - Zoetis TI - Tilt Up Set Revision 09-01-22
10/05/2022 Letter Fire Building Plan Review
10/05/2022 Letter DS P/R Corrections Document
10/25/2022 Letter Permit review response 10-24-22
10/25/2022 Drawing A111 revised 10-24-22
10/25/2022 Drawing A305 revised 10-24-22
10/25/2022 Drawing A109 revised 10-24-22
10/25/2022 Drawing A108 revised 10-24-22
10/25/2022 Letter Project Birkdale Warehouse Building 1 MEP Summary
10/25/2022 Plans LSCC B1 - Zoetis TI - Electrical Permit Set - City Comments 10_20_22
10/31/2022 Letter Fire Building Plan Review
11/07/2022 Plans LSCC B1 - Zoetis TI - Joist and Deck Field Use 10-10-2022
11/07/2022 Plans LSCC B1 - Zoetis TI - Compiled for Permit Set 11-2-22
11/07/2022 Approved Plans approved - LSCC B1 - Zoetis TI - Compiled for Permit Set 11-2-22
11/22/2022 Receipt Receipt for transaction: 2022-009082
11/22/2022 Letter DS Building Permit
12/05/2022 Plans LSCC B1 - Zoetis TI - Structural Permit Set 07-11-22
12/05/2022 Approved Plans approved - LSCC B1 - Zoetis TI - Structural Permit Set 07-11-22
12/20/2022 Plans Complete TI Set to be Stamped 1 of 2 12-20-22
12/20/2022 Plans Complete TI Set to be Stamped 2 of 2 12-20-22
12/20/2022 Approved Plans approved vol 1
12/20/2022 Approved Plans approved vol 2
03/01/2023 Letter INSPECTION SUMMARY
03/02/2023 Letter INSPECTION SUMMARY
03/22/2023 Plans 23-0260 (Zoetis), Dtls (Digitally Signed 02-01-23 SR)
03/22/2023 Plans P221318-Zoetis-Composite_P3 - Stamped
03/22/2023 Engineer Report/Study 23-0260(Zoetis),Calcs (Digitally Signed 02-01-23 SR)
03/22/2023 Engineer Report/Study Calculation Packet - Conveyor Solutions - Zoetis - Lee's Summit, MO - Stamped
03/29/2023 Letter Fire Building Plan Review
04/11/2023 Letter INSPECTION SUMMARY
04/12/2023 Letter DS P/R Corrections Document
05/12/2023 Plans LSCC B1 - Fire Protection Revision 02-22-23 (2)
05/18/2023 LSCC B1 - Zoetis TI - Fire Alarm Submittal Package
05/22/2023 Letter INSPECTION SUMMARY
05/24/2023 Letter Fire (Sprinkler) Plan Review
05/26/2023 Letter INSPECTION SUMMARY
05/26/2023 Letter INSPECTION SUMMARY
06/02/2023 Letter INSPECTION SUMMARY
06/02/2023 Letter INSPECTION SUMMARY
06/08/2023 Letter INSPECTION SUMMARY
06/13/2023 Letter INSPECTION SUMMARY
06/13/2023 Letter INSPECTION SUMMARY
06/16/2023 Letter INSPECTION SUMMARY
06/23/2023 Letter INSPECTION SUMMARY
06/25/2023 Letter Fire (Alarm) Plan Review Notice
06/26/2023 Letter INSPECTION SUMMARY
06/26/2023 Letter INSPECTION SUMMARY
06/29/2023 Letter INSPECTION SUMMARY
07/25/2023 Letter INSPECTION SUMMARY
08/02/2023 Letter INSPECTION SUMMARY
08/02/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/03/2023 Receipt Receipt for transaction:2023-006007
08/03/2023 LSCC B1 - Zoetis TI - Fire Alarm Shop Drawings
08/03/2023 LSCC B1 - Zoetis TI - Fire Alarm Submittal Package
08/09/2023 Letter License Tax Bill
08/15/2023 Letter Fire (Alarm) Plan Review Notice
08/09/2023 Letter License Tax Bill
08/16/2023 Letter INSPECTION SUMMARY
08/16/2023 Letter INSPECTION SUMMARY
08/17/2023 Letter INSPECTION SUMMARY
08/17/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/22/2023 Letter INSPECTION SUMMARY
08/23/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
08/31/2023 LSCC B1 - Zoetis TI - Fire Alarm Drawings Rev 08-29-23
08/31/2023 FE Moran - Fire Pump - Commissioning Report
08/09/2023 Letter License Tax Bill
09/01/2023 Approved Plans LSCC B1 - Zoetis TI - Fire Alarm Drawings Rev 08-29-23 approved
09/01/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter License Tax Bill
08/09/2023 Letter License Tax Bill
09/06/2023 Letter INSPECTION SUMMARY
09/15/2023 Letter INSPECTION SUMMARY
09/21/2023 Letter INSPECTION SUMMARY
09/26/2023 Receipt Receipt for transaction: 2023-007334
09/28/2023 Letter INSPECTION SUMMARY
09/28/2023 Letter INSPECTION SUMMARY
10/03/2023 Letter INSPECTION SUMMARY
10/11/2023 Letter INSPECTION SUMMARY
10/24/2023 Letter INSPECTION SUMMARY
11/03/2023 Letter INSPECTION SUMMARY
11/03/2023 Letter INSPECTION SUMMARY
11/03/2023 Letter INSPECTION SUMMARY
11/10/2023 Letter INSPECTION SUMMARY
11/20/2023 Letter Codes Final Certificate of Occupancy
11/20/2023 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home