Permit Application Status

PRCOM20192495


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20192495
Building Permit - Commercial
Certificate of Occupancy
LBC DEVELOPMENT CORP
NEW COMMERCIAL
NEW DENTAL SURGERY BUSINESS
09/04/2019
10/23/2019
03/15/2020
11/18/2022
Locations
Contacts
LBC DEVELOPMENT CORP, Address:PO BOX 7258  
LITTLE DIXIE CONSTRUCTION LLC, Address:1431 CINNAMON HILL LN STE 209, Phone:(573) 449-7200  
YAEGER ARCHITECTURE, Address:7780 WEST 119TH STREET, Phone:(913) 742-8000  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
REINHOLD ELECTRIC INC, Address:2511 LEMAY FERRY RD, Phone:(314) 631-1158  
SUMMIT MECHANICAL INC, Address:5324 ALGOA RD, Phone:(573) 636-4050  
KENZIE THORP, Address:LITTLE DIXIE CONSTRUCTION, Phone:(573) 864-4533  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 08/10/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
08/10/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Sprinkler Plan Review Released for Construction 01/06/2020
Michael Weissenbach
Installation acceptance testing
Corrective Action Required
01/06/2020

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule a hydrostatic test and a water flow test.
Miscellaneous Correction
Corrective Action Required
01/06/2020

(ACTION REQUIRED) Provide a 4 inch Storz connection for the FDC.
Building Plan Review Approved with Conditions 09/27/2019 10/25/2019
Joe Frogge
Final Development Plan
Resolved
10/25/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 9/17/19 - acknowledged in letter
License Tax Application
Corrective Action Required
09/20/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/17/19 - acknowledged in letter
Engineered truss package
Corrective Action Required
09/20/2019

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/17/19 - deferred
Bldg - Guards - Where required 1013.2
Corrective Action Required
09/20/2019

2012 IBC 1013.2 - Where required. Guards shall be located along open-sided walking surfaces, including mezzanines, equipment platforms, stairs, ramps and landings that are located more than 30 inches measured vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side. Guards shall be adequate in strength and attachment in accordance with Section 1607.8. Guards are required at retaining walls over 30” above grade when walking surfaces are within ten (10) feet of the high side of the retaining wall. (As amended by the City of Lee’s Summit. See code section for possible exceptions.) Action required: Provide guards surrounding equipment platforms per IBC 505.3. 9/17/19 - acknowledged in letter and noted on plans. Field verify
Miscellaneous Correction
Resolved
09/20/2019

Electrical riser is incomplete. Action required: Provide complete electrical riser diagram including all wire and conduit information, grounding electrode systems, etc. Also, there should be no "existing" equipment. 9/17/19 - Unable to verify grouping of shut-offs (max. 6 - where is "meter center?") Also, grounding electrode system not provided. show all required connections - Ufer, rod, etc.
Final Development Plan Review Approved 10/25/2019
Joe Frogge
Licensed Contractors Approved 09/27/2019 10/22/2019
Development Center
LC - MEP Subs
Resolved
10/22/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/17/19 - acknowledged in letter
Fire Plan Review Approved with Conditions 09/27/2019 09/20/2019
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
09/20/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of PE stamped shop drawings for the fire alarm system.
Hazardous material identification
Corrective Action Required
09/20/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection)
Address numbers required
Corrective Action Required
09/20/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Knox box required
Corrective Action Required
09/20/2019

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Verified At Inspection) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Construction documents - Fire protection systems
Corrective Action Required
09/20/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of PE stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
09/20/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/20/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Licensed Contractors Rejected 09/13/2019 09/17/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/13/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 9/17/19 - acknowledged in letter
Building Plan Review Rejected 09/20/2019 09/17/2019
Joe Frogge
Final Development Plan
Corrective Action Required
09/13/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes. 9/17/19 - acknowledged in letter
License Tax Application
Corrective Action Required
09/13/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes. 9/17/19 - acknowledged in letter
Engineered truss package
Corrective Action Required
09/13/2019

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral. 9/17/19 - deferred
Miscellaneous Correction
Resolved
09/17/2019

Fire barrier clarifications required. Action required: Clarify UL# and detail on A-011. 1hr at wall detail but 2hr on UL detail?
Bldg - Accessibility - Toilet and bathing facilities 1109.2
Resolved
09/17/2019

2018 IBC 1109.2 Toilet and bathing facilities. Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. Except as provided for in Sections 1109.2.2 and 1109.2.3, at least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible. (See code section for possible exceptions.) Action required: Restroom 119 to be fully accessible.
Miscellaneous Correction
Resolved
09/17/2019

2018 IBC 427.2.1 One-hour exterior room. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be provided with self-closing smoke- and draft-control assemblies having a fire protections rating of not less than 1 hour. Rooms shall have not less than one exterior wall that is provided with not less than two vents. Each vent shall have a minimum free air opening of not less than 36 square inches for each 1,000 cubic feet at normal temperature and pressure (NTP) of gas stored in the room and shall be not less than 72 square inches in aggregate free opening area. One vent shall be within 6 inches of the floor and one shall be within 6 inches of the ceiling. Rooms shall be provided with not fewer than one automatic fire sprinkler to provide container cooling in case of fire. Actions required: - Provide 1 hour rated door (error in schedule) - Provide exterior wall vents as directed - Provide self-closing smoke- and draft-control assemblies at duct penetrations. (ceiling is not rated)
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Resolved
09/17/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" of clearance at latch side of the following doors: - out of restroom #3/136 - Into Mech/Storage #112 - Out of X-ray/Photo #112
Miscellaneous Correction
Resolved
09/17/2019

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Update all details and references to show correct frost depth which is 36" in this area.
Miscellaneous Correction
Resolved
09/17/2019

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Update structural design of continuous footings with 2,100 psf soil bearing to match report provided.
Miscellaneous Correction
Resolved
09/17/2019

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Bldg - Guards - Where required 1013.2
Corrective Action Required
09/13/2019

2012 IBC 1013.2 - Where required. Guards shall be located along open-sided walking surfaces, including mezzanines, equipment platforms, stairs, ramps and landings that are located more than 30 inches measured vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side. Guards shall be adequate in strength and attachment in accordance with Section 1607.8. Guards are required at retaining walls over 30” above grade when walking surfaces are within ten (10) feet of the high side of the retaining wall. (As amended by the City of Lee’s Summit. See code section for possible exceptions.) Action required: Provide guards surrounding equipment platforms per IBC 505.3. 9/17/19 - acknowledged in letter and noted on plans. Field verify
Misc
Resolved
09/17/2019

Inadequate information to complete review. Action required: Provide battery cut-sheets and quantity information. Room may require automatic ventilation system.
NEC - Equipment outlet 210.63
Resolved
09/17/2019

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience receptacles at equipment platforms.
Miscellaneous Correction
Resolved
09/17/2019

2018 IMC 306.4 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with NFPA 70. Action required: Provide lighting at equipment platforms for maintenance.
Screening - Ground mounted equipment
Resolved
09/17/2019

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment at south side of building will be screened from all 4 sides per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
09/13/2019

Electrical riser is incomplete. Action required: Provide complete electrical riser diagram including all wire and conduit information, grounding electrode systems, etc. Also, there should be no "existing" equipment. 9/17/19 - Unable to verify grouping of shut-offs (max. 6 - where is "meter center?") Also, grounding electrode system not provided. show all required connections - Ufer, rod, etc.
Miscellaneous Correction
Resolved
09/17/2019

Gas piping incomplete. Action required: Specify NG piping to generator.
Mech - Condensate disposal - Evaporators and cooling coils 307.2
Resolved
09/17/2019

2018 IMC 307.2.1 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options) Action required: Modify drawings to show compliance with one of the 4 listed code options as concerns condensate piping.
Fire Plan Review Approved with Conditions 09/20/2019 09/16/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/13/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of PE stamped shop drawings for the fire alarm system.
Hazardous material identification
Corrective Action Required
09/13/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Verified At Inspection)
Address numbers required
Corrective Action Required
09/13/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Knox box required
Corrective Action Required
09/13/2019

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Verified At Inspection) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Stationary storage battery systems - scope
Resolved
09/16/2019

2018 IFC 608.1- Stationary storage battery systems having capacities exceeding the values shown in table 1206.2 shall comply with sections 1206.2.1 through 1206.2.12.6 as applicable. (Action Required) Provide cut sheets and quantities of the batteries for the UPS/electrical room.
Construction documents - Fire protection systems
Corrective Action Required
09/13/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of PE stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
09/13/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/13/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection)
Door operations
Resolved
09/16/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Building Plan Review Rejected 09/18/2019 09/09/2019
Joe Frogge
Final Development Plan
Corrective Action Required
09/09/2019

The building permit for this project can not be issued until the Codes Administration Department has received the approved Final Development Plan from the Planning and Development Department. Action required: Comment is for informational purposes.
License Tax Application
Corrective Action Required
09/09/2019

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit. Action required: Comment is for informational purposes.
Engineered truss package
Corrective Action Required
09/09/2019

Copies of the engineered truss package were not provided at the time of permit application. Action required: Provide roof truss package or request deferral.
Miscellaneous Correction
Corrective Action Required
09/09/2019

Fire barrier clarifications required. Action required: Clarify UL# and detail on A-011. 1hr at wall detail but 2hr on UL detail?
Bldg - Accessibility - Toilet and bathing facilities 1109.2
Corrective Action Required
09/09/2019

2018 IBC 1109.2 Toilet and bathing facilities. Each toilet room and bathing room shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing rooms provided within the facility shall not be located on the inaccessible floor. Except as provided for in Sections 1109.2.2 and 1109.2.3, at least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing room shall be accessible. (See code section for possible exceptions.) Action required: Restroom 119 to be fully accessible.
Miscellaneous Correction
Corrective Action Required
09/09/2019

2018 IBC 427.2.1 One-hour exterior room. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be provided with self-closing smoke- and draft-control assemblies having a fire protections rating of not less than 1 hour. Rooms shall have not less than one exterior wall that is provided with not less than two vents. Each vent shall have a minimum free air opening of not less than 36 square inches for each 1,000 cubic feet at normal temperature and pressure (NTP) of gas stored in the room and shall be not less than 72 square inches in aggregate free opening area. One vent shall be within 6 inches of the floor and one shall be within 6 inches of the ceiling. Rooms shall be provided with not fewer than one automatic fire sprinkler to provide container cooling in case of fire. Actions required: - Provide 1 hour rated door (error in schedule) - Provide exterior wall vents as directed - Provide self-closing smoke- and draft-control assemblies at duct penetrations. (ceiling is not rated)
Accessibility - Swinging doors - maneuvering clearance 404.2.3.2
Corrective Action Required
09/09/2019

ICC A117.1-2017 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Provide minimum 18" of clearance at latch side of the following doors: - out of restroom #3/136 - Into Mech/Storage #112 - Out of X-ray/Photo #112
Miscellaneous Correction
Corrective Action Required
09/09/2019

2018 IBC 1809.5 Frost protection. Except where otherwise protected from frost, foundations and other permanent supports of buildings and structures shall be protected from frost by one or more of the following methods: 1. Extending below the frost line of the locality; 2. Constructing in accordance with ASCE 32; or 3. Erecting on solid rock. (see code section for exceptions) Shallow foundations shall not bear on frozen soil unless such frozen condition is of a permanent character. Action required: Update all details and references to show correct frost depth which is 36" in this area.
Miscellaneous Correction
Corrective Action Required
09/09/2019

2018 IBC 1803.1 General. Geotechnical investigations shall be conducted in accordance with Section 1803.2 and reported in accordance with Section 1803.6. Where required by the building official or where geotechnical investigations involve in-situ testing, laboratory testing or engineering calculations, such investigations shall be conducted by a registered design professional. Action required: Update structural design of continuous footings with 2,100 psf soil bearing to match report provided.
Miscellaneous Correction
Corrective Action Required
09/09/2019

2017 NEC Article 517.13 Grounding of Receptacles and Fixed Electrical Equipment in Patient Care Spaces. Wiring in patient care spaces shall comply with 517.13(A) and (B). (A) Wiring methods. All branch circuits serving patient care spaces shall be provided with an effective ground-fault current path by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. The metal raceway system, metallic cable armor, or sheath assembly shall itself qualify as an equipment grounding conductor in accordance with 250.118. (B) Insulated Equipment Grounding Conductors and Insulated Equipment Bonding Jumpers. (1) General. The following shall be directly connected to an insulated copper equipment grounding conductor that is clearly identified along its entire length by green insulation and installed with the branch circuit conductors in the wiring methods as provided in 517.13(A). 1. The grounding terminals of all receptacles other than isolated ground receptacles. 2. Metal outlet boxes, metal device boxes, or metal enclosures. 3. All non-current-carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over 100 volts. (see code for exceptions) (2) Sizing. Equipment grounding conductors and equipment bonding jumpers shall be sized in accordance with 250.122. Action required: Modify drawings to show that all circuits in patient care areas will have redundant ground system.
Bldg - Guards - Where required 1013.2
Corrective Action Required
09/09/2019

2012 IBC 1013.2 - Where required. Guards shall be located along open-sided walking surfaces, including mezzanines, equipment platforms, stairs, ramps and landings that are located more than 30 inches measured vertically to the floor or grade below at any point within 36 inches horizontally to the edge of the open side. Guards shall be adequate in strength and attachment in accordance with Section 1607.8. Guards are required at retaining walls over 30” above grade when walking surfaces are within ten (10) feet of the high side of the retaining wall. (As amended by the City of Lee’s Summit. See code section for possible exceptions.) Action required: Provide guards surrounding equipment platforms per IBC 505.3.
Misc
Corrective Action Required
09/09/2019

Inadequate information to complete review. Action required: Provide battery cut-sheets and quantity information. Room may require automatic ventilation system.
NEC - Equipment outlet 210.63
Corrective Action Required
09/09/2019

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide convenience receptacles at equipment platforms.
Miscellaneous Correction
Corrective Action Required
09/09/2019

2018 IMC 306.4 Electrical requirements. A luminaire controlled by a switch located at the required passageway opening and a receptacle outlet shall be provided at or near the appliance location in accordance with NFPA 70. Action required: Provide lighting at equipment platforms for maintenance.
Screening - Ground mounted equipment
Corrective Action Required
09/09/2019

Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings that provide details as to how mechanical equipment at south side of building will be screened from all 4 sides per referenced UDO section.
Miscellaneous Correction
Corrective Action Required
09/09/2019

Electrical riser is incomplete. Action required: Provide complete electrical riser diagram including all wire and conduit information, grounding electrode systems, etc. Also, there should be no "existing" equipment.
Miscellaneous Correction
Corrective Action Required
09/09/2019

Gas piping incomplete. Action required: Specify NG piping to generator.
Mech - Condensate disposal - Evaporators and cooling coils 307.2
Corrective Action Required
09/09/2019

2018 IMC 307.2.1 Auxiliary and secondary drain systems. In addition to the requirements of Section 307.2.1, where damage to any building components could occur as a result of overflow from the equipment primary condensate removal system, one of the following auxiliary protection methods shall be provided for each cooling coil or fuel-fired appliance that produces condensate. (see code for 4 options) Action required: Modify drawings to show compliance with one of the 4 listed code options as concerns condensate piping.
Licensed Contractors Rejected 09/18/2019 09/09/2019
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/09/2019

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 09/18/2019 09/09/2019
Michael Weissenbach
Construction documents for fire alarm systems
Corrective Action Required
09/09/2019

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. (Action Required) Provide three sets of PE stamped shop drawings for the fire alarm system.
Hazardous material identification
Corrective Action Required
09/09/2019

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 2703.5. (Informational Purposes)
Address numbers required
Corrective Action Required
09/09/2019

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Knox box required
Corrective Action Required
09/09/2019

2018 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official. (Action Required) Order a Knox Box from knoxbox.com. Placement will be made by the FDC.
Stationary storage battery systems - scope
Corrective Action Required
09/09/2019

2018 IFC 608.1- Stationary storage battery systems having capacities exceeding the values shown in table 1206.2 shall comply with sections 1206.2.1 through 1206.2.12.6 as applicable. (Action Required) Provide cut sheets and quantities of the batteries for the UPS/electrical room.
Construction documents - Fire protection systems
Corrective Action Required
09/09/2019

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. (Action Required) Provide three sets of PE stamped shop drawings for the fire sprinkler system.
Installation acceptance testing
Corrective Action Required
09/09/2019

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. (Informational Purposes) Call (816)969-1300 to schedule testing.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
09/09/2019

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. (Verified At Inspection) Provide 2 2A10BC fire extinguishers
Door operations
Corrective Action Required
09/09/2019

2018 IFC 1010.1.9 Door operations. Except as specifically permitted by this section, egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. (Verified At Inspection)
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $7,908.46 $7,908.46 Paid 10/16/2019
8331506-EFHB Maybrook, Full $980.03 $980.03 Paid 10/16/2019
8331507-Sewer Connection Fee $690.00 $690.00 Paid 10/16/2019
7232302-Commercial License Tax Fee $11,220.00 $11,220.00 Paid 10/16/2019
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 11/06/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Commercial Partial 11/15/2019 (8:00) 11/15/2019 at 9:20 AM 11/15/2019
Misc
Partial Correction
11/15/2019
-EXTERIOR GRADE BEAM AND PADS OK ALL AROUND, EXCEPT THE FRONT PART FROM COLUMN LINE 3 TO 4
Footing Inspection - Commercial Passed 11/18/2019 (1:00) 11/18/2019 at 1:00 PM 11/18/2019
Misc
Informational
11/18/2019
-EXTERIOR GRADE BEAM AND PADS AND INTERIOR FOOTING-OK -4 EXTERIOR PIER PADS
Footing Inspection - Commercial Passed 11/20/2019 11/20/2019 11/20/2019
Underslab Plumbing Inspection - Commercial Passed 11/20/2019 11/20/2019 11/20/2019
Underslab Electrical Inspection - Commercial Passed 11/27/2019 11/26/2019 at 2:40 PM 11/26/2019
Rough Framing Inspection - Commercial Failed 12/23/2019 at 10:10 AM 12/23/2019
Misc
Corrective Action Required
12/23/2019
SHEAR WALLS: -NAIL SHEATHING @ 2" OC -AT SEAMS, BLOCK AND NAIL @ 2" OC
Rough Framing Inspection - Commercial Failed 12/26/2019 12/26/2019 at 11:15 AM 12/26/2019
Misc
Corrective Action Required
12/23/2019
SHEAR WALLS: -NAIL SHEATHING ALONG THE EDGES @ 2"-3" ON CENTER
Rough Framing Inspection - Commercial Partial 1/2/2020 1/2/2020 01/02/2020
Misc
Resolved
01/02/2020
SHEAR WALLS: -NAIL SHEAR WALLS (SW1 ON PLAN) SHEATHING ALONG THE EDGES @ 2"-3" ON CENTER. ALL OTHER EXTERIOR WALL NAILING-OK
Rough Framing Inspection - Commercial Failed 1/10/2020 1/10/2020 01/10/2020
Misc
Corrective Action Required
01/10/2020
Provide city stamped truss package
Rough Framing Inspection - Commercial Failed 2/10/2020 at 1:15 PM 02/10/2020
Misc
Corrective Action Required
01/10/2020
ROOF FRAMING ONLY: -Tie down trusses at front (west) entrance -Nail together all girder trusses per truss details -Install tie down devices against uplift for GT G02&G06 at interior ends; Install tie down devices against uplift for GT G01&G05 at interior ends -Install HJC26 device for corner trusses connection to G06 -Anchor down support studs for G02 -Nail hanger to SW corner truss CJ21 -Brace all trusses per plan
In-wall Inspection Failed 3/31/2020 3/31/2020 at 10:05 AM 03/31/2020
Misc
Corrective Action Required
03/31/2020
-Wall studs at front entry not full height studs -Protect plumbing with BOCA plates at bottom wall plate -Label all in-wall med gas lines -Mechanical floor framing: install double trimmer joists under mechanical unit; install joist hangers where required; install support header for joists; blocking @2 ft oc; frame per plan detail; joists size for mechanical floors per S300 -Install blocking for vertical grab bar at restroom/124 -Screw truss anchor strap at sterilization/127 -Nail truss tie-down devices at laundry/134 -Laundry wall not framed per S7/S410 -Med gas wall must be rated one hour with exposure on both sides -Anchor bearing wall sill plate per detail F6/S210 and F2/S210 -Install hold down anchors for east shear walls -Install tie down devices against uplift for GT G02&G06 at interior ends; Install tie down devices against uplift for GT G01&G05 at interior ends
In-wall Inspection Failed 4/10/2020 4/10/2020 at 2:45 PM 04/10/2020
Misc
Corrective Action Required
03/31/2020
**4/10-GUYS STILL IN THERE SPRAYING FOAM INSULATION. ALSO, ALOT OF THE BELOW DEFICIENCIES HAE NOT BEEN CORRECTED. INSPECTION CANCELED. -Wall studs at front entry not full height studs -Protect plumbing with BOCA plates at bottom wall plate -Mechanical floor framing: install double trimmer joists under mechanical unit; install joist hangers where required; install support header for joists; blocking @2 ft oc; frame per plan detail; joists size for mechanical floors per S300 -Install blocking for vertical grab bar at restroom/124 -Screw truss anchor strap at sterilization/127 -Nail truss tie-down devices at laundry/134 -Laundry wall not framed per S7/S410 -Med gas wall must be rated one hour with exposure on both sides -Anchor bearing wall sill plate per detail F6/S210 and F2/S210 -Install hold down anchors for east shear walls -Install tie down devices against uplift for GT G02&G06 at interior ends; Install tie down devices against uplift for GT G01&G05 at interior ends
In-wall Inspection Failed 4/28/2020 4/28/2020 at 1:20 PM 04/28/2020
Misc
Corrective Action Required
04/10/2020
-Wall studs at front entry not full height studs **Have engineer address fix for this -Protect plumbing with BOCA plates at bottom wall plate **Not done as required per IPC 305.6 -Mechanical floor framing: install 2x lumber the whole bearing area of hangers -Med gas wall must be rated one hour with exposure on both sides **Need architect to submit fix -Install hold down anchors for east shear walls **Have architect address where foundation hold-downs are required for the rear shear wall -Install tie down devices against uplift for GT G02&G06 at interior ends; Install tie down devices against uplift for GT G01&G05 at interior ends **OK TO INSULATE WALLS **OK TO ROCK ONE SIDE OF INTERIOR WALLS ONLY **DO NOT ROCK THE MED RM WALLS
In-wall Inspection Failed 4/30/2020 4/30/2020 at 1:15 PM 04/30/2020
Misc
Corrective Action Required
04/28/2020
-Protect plumbing with BOCA plates at bottom wall plate **Not done as required per IPC 305.6. Code requires protection to extend min 2" above the wall sole plate, where the plumbing is less than 1.25" from wood surface -Med gas wall must be rated one hour with exposure on both sides **Frame the 1-hr wall to roof deck for 5/8" type x rock on both sides. Have architect address what needs to be done with the truss and wall not aligned for 5/8" type x rock -Install hold down anchors for east shear walls **Have architect address where foundation hold-downs are required for the rear shear wall **OK TO INSULATE WALLS **DO NOT ROCK FURTHER
In-wall Inspection Failed 5/1/2020 5/1/2020 at 11:10 AM 05/01/2020
Misc
Corrective Action Required
04/30/2020
-Med gas wall must be rated one hour with exposure on both sides **Frame the 1-hr wall to roof deck for 5/8" type x rock on both sides. Have architect address what needs to be done with the truss and wall not aligned for 5/8" type x rock **OK TO ROCK EXCEPT AT THE MED GAS WALLS
Rated Assembly Inspection Failed 5/11/2020 5/11/2020 05/11/2020
Informational
05/11/2020
NO SCREW INSPECTION NEEDED FOR NON-FIRE-RATED WALLS
In-wall Inspection Passed 5/14/2020 05/14/2020
Misc
Informational
05/14/2020
-Med gas wall must be rated one hour with exposure on both sides **OK TO ROCK MED GAS RM WALLS ON BOTH SIDES. I WILL NEED A LADDER TO VERIFY. THE 2X4 STUD WALL MUST BE ROCKED ON BOTH SIDES WITH 5/8" TYPE X GYP
Rated Assembly Inspection Partial 5/14/2020 5/14/2020 at 12:45 PM 05/14/2020
Misc
Corrective Action Required
05/14/2020
-Med gas wall must be rated one hour with exposure on both sides **OK TO ROCK MED GAS RM WALLS ON BOTH SIDES. I WILL NEED A LADDER TO VERIFY. THE 2X4 STUD WALL OF THE MED RM MUST BE ROCKED ON BOTH SIDES WITH 5/8" TYPE X GYP
Rated Assembly Inspection Failed 5/20/2020 5/20/2020 at 3:15 PM 05/20/2020
Misc
Corrective Action Required
05/14/2020
-Rock open side of the wall. See the opening at end of (2)2x10; Rock around wood at plate line -Screw pattern per UL design -firecaulk all penetrations of the fire-rated wall -the oversized hole at plumbing cleanout inside the med gas rm must be protected with a listed fire-stopping collar -remove all fire-caulking around the fire dampers. Instead, pack in mineral wool around the fire dampers **LEAVE THE LADDER THERE FOR RE-INSPECTION
Underground Electrical Inspection - Commercial Partial 6/12/2020 6/12/2020 06/12/2020
Miscellaneous Correction
Corrective Action Required
06/12/2020
-LINES FROM METER CAN TO SERVICE AT BUILDING
Underground Electrical Inspection - Commercial Partial 6/15/2020 6/15/2020 06/15/2020
Miscellaneous Correction
Corrective Action Required
06/12/2020
-LINES FROM METER CAN BEHIND DUMPSTER TO SERVICE AT BUILDING: FUTURE LINES NORTH TO CORNER OF BUILDING ABOUT 6’ FROM FENCE. 3 LIGHT POLES IN FRONT PARKING FROM MONUMENT SIGHN JUNCTION BOX WITH GROUND RODS 1 LIGHT POLE WITH GROUND ROD BY DUMPSTER PAD
Piers/Caissons Inspection - Commercial Passed 06/15/2020
Miscellaneous Correction
Informational
06/15/2020
(4) 24X48 LIGHT POLE BASES
Rough Framing Inspection - Commercial Passed 7/14/2020 07/14/2020
Misc
Resolved
07/14/2020
ROOF FRAMING ONLY: -Install tie down devices against uplift for GT G02&G06 at interior ends; Install tie down devices against uplift for GT G01&G05 at interior ends
Above Ceiling Inspection Failed 7/14/2020 7/14/2020 at 12:45 PM 07/14/2020
Misc
Corrective Action Required
07/14/2020
NOT READY
Electrical Service Inspection Passed 7/14/2020 7/14/2020 07/14/2020
Rated Assembly Inspection Failed 7/14/2020 7/14/2020 07/14/2020
Misc
Corrective Action Required
05/20/2020
-Rock open side of the wall. See the opening at end of (2)2x10; Rock around wood at plate line -Screw pattern per UL design -firecaulk all penetrations of the fire-rated wall -the oversized hole at plumbing cleanout inside the med gas rm must be protected with a listed fire-stopping collar -remove all fire-caulking around the fire dampers. Instead, pack in mineral wool around the fire dampers **PROVIDE THE INSTALLATION DOCUMENT FOR THE FIRE DAMPER. TAKE A PICTURE OF THE WALL ABOVE THE CEILING
Gas Service Inspection - Commercial Passed 7/23/2020 at 2:05 PM 07/23/2020
Above Ceiling Inspection Not Ready 7/29/2020 7/29/2020 at 1:50 PM 07/29/2020
Misc
Corrective Action Required
07/14/2020
**NOT READY **7/29-NOT READY
Rated Assembly Inspection Failed 7/31/2020 7/31/2020 07/31/2020
Misc
Corrective Action Required
07/14/2020
-Rock open side of the wall. See the opening at end of (2)2x10; Rock around wood at plate line -Screw pattern per UL design -the oversized hole at plumbing cleanout inside the med gas rm must be protected with a listed fire-stopping collar -remove all fire-caulking around the fire dampers. Instead, pack in mineral wool around the fire dampers **HAVE LADDER AVAILABLE SO I CAN AGAIN CLIMB UP INTO THE ATTIC SPACE TO INSPECT **PROVIDE THE INSTALLATION DOCUMENT FOR THE FIRE DAMPER.
Above Ceiling Inspection Failed 7/31/2020 7/31/2020 at 2:25 PM 07/31/2020
Misc
Corrective Action Required
07/31/2020
**NOT READY **7/29-NOT READY
Sprinkler - Hydrostatic Test Passed 6/12/2020 08/03/2020
Alarm Test Not Ready 8/3/2020 08/03/2020
Sprinkler - Flow Test Not Ready 8/3/2020 08/03/2020
Above Ceiling Inspection Failed 8/6/2020 8/6/2020 08/06/2020
Misc
Corrective Action Required
07/31/2020
-Replace surgery light circuits with proper wiring method per NEC 517.13 -Secure Mc within 12” of boxes and close off open box above mezzanine ; complete all electrical -Install auxiliary drain pan underneath all AC coil; install switch-off device for auxiliary drain pans -Label med gas lines...above each rm, on both sides of wall penetrations, at interval no more than 20 ft -Complete return air transfer ducting -Support ceiling grid every 4 ft -Complete all transfer air ducting; Complete all above-ceiling mechanical -Support pvc at maximum 4 ft interval -Insulate wall above ceiling of Major Procedure rm
Above Ceiling Inspection Passed 8/14/2020 8/14/2020 at 1:55 PM 08/14/2020
Misc
Resolved
08/14/2020
Alarm Test Failed 8/17/2020 08/17/2020
Sprinkler - Flow Test Passed 8/17/2020 08/17/2020
Alarm Test Passed 8/20/2020 08/21/2020
Underground Electrical Inspection - Commercial Passed 08/21/2020
Miscellaneous Correction
Resolved
08/21/2020
-LINES FROM METER CAN BEHIND DUMPSTER TO SERVICE AT BUILDING: FUTURE LINES NORTH TO CORNER OF BUILDING ABOUT 6’ FROM FENCE. 3 LIGHT POLES IN FRONT PARKING FROM MONUMENT SIGHN JUNCTION BOX WITH GROUND RODS 1 LIGHT POLE WITH GROUND ROD BY DUMPSTER PAD
Occupancy Inspection - Fire Failed 8/24/2020 08/24/2020
Rated Assembly Inspection Passed 8/31/2020 at 10:00 AM 08/31/2020
Misc
Resolved
08/31/2020
-Rock open side of the wall. See the opening at end of (2)2x10; Rock around wood at plate line -Screw pattern per UL design -the oversized hole at plumbing cleanout inside the med gas rm must be protected with a listed fire-stopping collar -remove all fire-caulking around the fire dampers. **HAVE LADDER AVAILABLE SO I CAN AGAIN CLIMB UP INTO THE ATTIC SPACE TO INSPECT **PROVIDE THE INSTALLATION DOCUMENT FOR THE FIRE DAMPER.
Occupancy Inspection - Fire Temporary C of O 9/4/2020 09/04/2020
Occupancy Inspection - Codes Commercial Temporary C of O 9/4/2020 9/4/2020 09/04/2020
Misc
Corrective Action Required
08/24/2020
-Approval required from: Fire, Planning, Field Service, and Water -Complete installing parking lot lighting -Install tamper-proof caps at AC valves -Make sure breaker size for CU units are per labels. Label all CU units (70; 1-45; 2-40; 3-20; 4-30; 5-15) -Secure LFNC raceways around AC units every 3 ft; secure within 12” of enclosure -Generator not installed at this time -Provide clearance in front of the electrical service equipments per code. Shall move all trees that encroach within the min 36" depth working space in front of the electrical equipment -Secure raceway per code at electrical service -Grounding rod shall be driven down to ground with grounding clamp buried -Label breakers for outdoor panel -Underground electrical to front landscaping lights shall be min 18” below grade -Floor elevation difference not meeting ANSI 117.1 section 303 at front door entrance -Secure MC cables in electrical room within 12” of enclosure -Complete water for lawn irrigation -Receptacles located within six ft of sinks shall be gfci -protected -Install hospital-graded receptacles inside patient care rooms that administer med gas -Provide fire sprinkler protection in server room -Door glazing not installed -Secure all wiring per code up in the mechanical mezzanine; close open electrical box -Provide auxiliary and secondary condensate drainage per IMC 307.2.3 for the mechanical units that are hung above mezzanine floor -Support pvc in attic every 4 ft or less -Complete water heater P&T discharge. Move the copper discharge pipe down closer to pan -Fix the aux drainage pan. Bent the wall straight uo -A truss above the sterilization rm is damaged at the gusset point. Have engineer to address fix for this -Construct a 24" wide walkway to the mechanical equipment above sterilization rm
Occupancy Inspection - Engineering Temporary C of O 9/4/2020 09/04/2020
Misc
Informational
09/04/2020
Approving Temorary Occupancy- Items to be completed. 1. Establish 70% vegetation on the off-site property around the building. 2. Intall 2 sections of temporary curb to the south and the north of the parking lot. Hector Soto was also putting this on his list.
Occupancy Inspection - Planning Temporary C of O 9/4/2020 09/04/2020
Corrective Action Required
09/04/2020
Install trash enclosure doors per the approved plan.
Corrective Action Required
09/04/2020
Install permanent or temporary asphalt curb across the future drive extensions at the southwest corner of the site and the northeast corner of the parking lot in front of the building.
Corrective Action Required
09/04/2020
Install parking lot light poles per the approved plan.
Corrective Action Required
09/04/2020
Complete the sodding in the vicinity of the trash enclosure.
Occupancy Inspection - Fire Passed 9/15/2020 09/15/2020
Occupancy Inspection - Water Utilities Passed 9/4/2020 09/30/2020
Occupancy Inspection - Planning Passed 11/09/2020
Occupancy Inspection - Engineering Failed 11/9/2020 11/09/2020
Misc
Informational
09/04/2020
Approving Temorary Occupancy- Items to be completed. 1. Establish 70% vegetation on the off-site property around the building. 2. Intall 2 sections of temporary curb to the south and the north of the parking lot. Hector Soto was also putting this on his list.
Misc
Corrective Action Required
11/09/2020
Items needed for Final Occupancy 1. Vegetation needs to be established on the adjoining properties where the land was disturbed. 2. 3 year maintenance bond for 50% of the construction cost of the water main extention. 3.Final Affidavit and Agreement. 4. Record drawings for the water main extention.
Occupancy Inspection - Codes Commercial Temporary C of O 11/9/2020 11/9/2020 11/09/2020
Misc
Corrective Action Required
09/04/2020
-Approval required from: Field Service As per Steve Robbins a 30day TCO extension will be issued. Codes Complete.
Occupancy Inspection - Engineering Failed 11/9/2020 11/09/2020
Misc
Informational
11/09/2020
Approving Temorary Occupancy- Items to be completed. 1. Establish 70% vegetation on the off-site property around the building. 2. Intall 2 sections of temporary curb to the south and the north of the parking lot. Hector Soto was also putting this on his list.
Misc
Corrective Action Required
11/09/2020
Items needed for Final Occupancy 1. Vegetation needs to be established on the adjoining properties where the land was disturbed. 2. 3 year maintenance bond for 50% of the construction cost of the water main extention. 3.Final Affidavit and Agreement. 4. Record drawings for the water main extention.
Misc
Corrective Action Required
11/09/2020
Items needed for Final Occupancy 1. Vegetation needs to be established on the adjoining properties where the land was disturbed. 2. 3 year maintenance bond for 50% of the construction cost of the water main extention. 3.Final Affidavit and Agreement. 4. Record drawings for the water main extention. Please give them a 30 day temporary occupancy
Occupancy Inspection - Engineering Passed 11/18/2022 11/18/2022
Misc
Informational
11/09/2020
Approving Temorary Occupancy- Items to be completed. 1. Establish 70% vegetation on the off-site property around the building. 2. Intall 2 sections of temporary curb to the south and the north of the parking lot. Hector Soto was also putting this on his list.
Misc
Corrective Action Required
11/09/2020
Items needed for Final Occupancy 1. Vegetation needs to be established on the adjoining properties where the land was disturbed. 2. 3 year maintenance bond for 50% of the construction cost of the water main extention. 3.Final Affidavit and Agreement. 4. Record drawings for the water main extention.
Misc
Corrective Action Required
11/09/2020
Items needed for Final Occupancy 1. Vegetation needs to be established on the adjoining properties where the land was disturbed. 2. 3 year maintenance bond for 50% of the construction cost of the water main extention. 3.Final Affidavit and Agreement. 4. Record drawings for the water main extention. Please give them a 30 day temporary occupancy
Misc
Corrective Action Required
11/18/2022
All items for us have been turned in and completed.
Occupancy Inspection - Codes Commercial Full C of O 11/18/2022
Misc
Resolved
11/18/2022
-Approval required from: Field Service As per Steve Robbins a 30day TCO extension will be issued. Codes Complete.
Documents & Images
Date Uploaded File Type Document Name
09/06/2019 Letter License Tax Bill
09/09/2019 Letter Fire Building Plan Review
09/09/2019 Letter DS P/R Corrections Document
09/16/2019 Letter Fire Building Plan Review
09/17/2019 Letter DS P/R Corrections Document
10/16/2019 Receipt Receipt for transaction: 2019-006826
10/23/2019 Letter DS Building Permit
11/14/2019 Email KC Surgical Permit Number PRCOM2019-2495
11/15/2019 Letter INSPECTION SUMMARY
11/18/2019 Letter INSPECTION SUMMARY
11/19/2019 Email PRCOM2019-249 KC Surgical - Dumpster Enclosure Footing Change
11/20/2019 Letter INSPECTION SUMMARY
11/20/2019 Letter Codes Plan Review Conditions
11/20/2019 Letter INSPECTION SUMMARY
11/26/2019 Letter INSPECTION SUMMARY
12/23/2019 Letter INSPECTION SUMMARY
12/26/2019 Letter INSPECTION SUMMARY
01/02/2020 Letter INSPECTION SUMMARY
01/06/2020 Letter Fire (Sprinkler) Plan Review
01/10/2020 Letter INSPECTION SUMMARY
02/10/2020 Letter INSPECTION SUMMARY
03/31/2020 Letter INSPECTION SUMMARY
04/10/2020 Letter INSPECTION SUMMARY
04/28/2020 Letter INSPECTION SUMMARY
04/29/2020 Drawing 20200129114608828
04/30/2020 Letter INSPECTION SUMMARY
05/01/2020 Letter INSPECTION SUMMARY
05/11/2020 Letter INSPECTION SUMMARY
05/14/2020 Letter INSPECTION SUMMARY
05/14/2020 Letter INSPECTION SUMMARY
05/20/2020 Letter INSPECTION SUMMARY
06/12/2020 Letter INSPECTION SUMMARY
06/15/2020 Letter INSPECTION SUMMARY
06/15/2020 Letter INSPECTION SUMMARY
07/14/2020 Letter INSPECTION SUMMARY
07/14/2020 Letter INSPECTION SUMMARY
07/14/2020 Letter INSPECTION SUMMARY
07/23/2020 Letter INSPECTION SUMMARY
07/29/2020 Letter INSPECTION SUMMARY
07/31/2020 Letter INSPECTION SUMMARY
07/31/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/06/2020 Letter INSPECTION SUMMARY
08/10/2020 Letter Fire (Alarm) Plan Review Notice
08/14/2020 Letter INSPECTION SUMMARY
08/24/2020 Letter INSPECTION SUMMARY
08/24/2020 Letter INSPECTION SUMMARY
08/31/2020 Letter INSPECTION SUMMARY
09/04/2020 Letter DE-Daily Inspection Summary
11/06/2020 Receipt Receipt for transaction:2020-007444
11/09/2020 Letter DE-Daily Inspection Summary
11/09/2020 Letter Codes Temporary Certificate of Occupancy
11/09/2020 Letter DE-Daily Inspection Summary
11/18/2022 Letter INSPECTION SUMMARY
11/18/2022 Letter Field Certificate of Occupancy
11/18/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home