Permit Application Status

PRRES20242946


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20242946
Building Permit - Residential
Stop Work
NEW DUPLEX
NEW DUPLEX. FINISHED/UNFINISHED BASEMENT. ROOF TRUSSES. UNCOVERED DECK. '. STOP WORK ORDER generated on 07/11/2025 12:00 AM by username 'Jamie Simerly'.
06/07/2024
06/21/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
TAYLOR@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Duplex $2,224.55 $2,224.55 Paid 06/21/2024
Water Tap Fee $7,520.00 $7,520.00 Paid 06/21/2024
Water Meter Fee $1,360.92 $1,360.92 Paid 06/21/2024
Sanitary Sewer Development Fee $4,318.00 $4,318.00 Paid 06/21/2024
Right of Way Permit Fee $85.00 $85.00 Paid 06/21/2024
Residential Excise Tax Fee $1,240.32 $1,240.32 Paid 06/21/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 03/26/2025
3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 03/26/2025
3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 03/26/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 03/26/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 04/28/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Sidewalk Inspection Pending
Miscellaneous Correction
Informational
03/17/2025
03-10-25 Jamie S, SW is compacted, and slopes are in compliance. Allowing one panel transition on west side to existing SW. Approved to pour. 3-17-25 Dustin A, DW is poured to city specs Slopes are in compliance. Cannot pass until ADA ramp is cleaned off so we can check for any cracks. Once cleaned off please call in
Occupancy Inspection - Codes Residential Pending
Misc
Corrective Action Required
05/28/2025
TCO expired a notice of violation sent Wes Bears 05/28/2025 7:27 AM 3710, 3712 sw Knoxville ct BOTH - provide gutters and downspouts - Provide splash pads - Final grading and sod Land - Sidewalk inspection pending - Pay all fees - Land sewer trace wire at grade - Sump discharge to be 36” away from foundation - Seal top of A/C disconnect - Label address at Electrical disconnect - Uncover water meters for inspection Open ***3710 AND 3712 ok for TCO only***
Erosion Control Inspection Residential Pending
Misc
Corrective Action Required
07/11/2025
- Erosion control in place at time of inspection.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/11/2025
07/08/25 Jamie S, Erosion control needs to be reestablished. Street and sidewalk need to be cleaned off. Trash on lot need to be removed. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 07/11/25 Jamie S, Erosion control needs to be reestablished. Street and sidewalk need to be cleaned off. Trash on lot need to be removed.
Erosion Control Inspection Residential Partial 9/5/2024 09/05/2024
Miscellaneous Correction
Informational
09/05/2024
Erosion control measures are in place and must be maintained until CofO
Footing Inspection - Residential Passed 9/5/2024 09/05/2024
Miscellaneous Correction
Informational
09/05/2024
Footing was passed by a third party. Exterior piers were not mentioned in the footing report
Sewer Service Inspection - R Partial 9/12/2024 9/12/2024 09/12/2024
Miscellaneous Correction
Informational
09/12/2024
Sewer at 3712 passed only This is a partial pass only, other unit will be scheduled at a later time.
Sewer Service Inspection - R Passed 9/13/2024 9/13/2024 09/13/2024
Miscellaneous Correction
Resolved
09/13/2024
Sewer at 3712 passed only This is a partial pass only, other unit will be scheduled at a later time.
Water Service Inspection - R Passed 9/13/2024 9/13/2024 09/13/2024
Erosion Control Inspection Residential Failed 9/16/2024 09/16/2024
Miscellaneous Correction
Resolved
09/16/2024
Erosion control measures are in place and must be maintained until CofO
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/16/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Gravel needs to be spread from the foundation to the street curb Repair or replace straw waddle at the front of the property that has been damaged
Underslab Plumbing Inspection - Residential Failed 9/20/2024 9/20/2024 09/20/2024
Miscellaneous Correction
Corrective Action Required
09/20/2024
Remove wood decay stakes from under the slab
Erosion Control Inspection Residential Partial 9/24/2024 09/24/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
09/24/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Gravel needs to be spread from the foundation to the street curb Repair or replace straw waddle at the front of the property that has been damaged
Miscellaneous Correction
Informational
09/24/2024
Erosion control measures are in place and must be maintained until CofO
Underslab Plumbing Inspection - Residential Passed 9/24/2024 9/24/2024 09/24/2024
Miscellaneous Correction
Resolved
09/24/2024
Remove wood decay stakes from under the slab
Erosion Control Inspection Residential Failed 11/1/2024 11/01/2024
Miscellaneous Correction
Resolved
11/01/2024
Erosion control measures are in place and must be maintained until CofO
Miscellaneous Correction
Corrective Action Required
11/01/2024
Straw waddle on the north side of the property is damaged, missing or has been moved Full erosion control measures must be in place and properly maintained until CofO
All Rough Inspection - Residential Failed 12/5/2024 12/5/2024 12/05/2024
Miscellaneous Correction
Informational
12/05/2024
Exterior sheeting and exterior garage PFH passed and is okay to cover This is a partial pass only
Erosion Control Inspection Residential Partial 12/24/2024 12/24/2024
Miscellaneous Correction
Resolved
12/24/2024
Straw waddle on the north side of the property is damaged, missing or has been moved Full erosion control measures must be in place and properly maintained until CofO
Miscellaneous Correction
Informational
12/24/2024
Erosion control is in place and must be properly maintained until CofO
Gas Service Inspection - Residential Passed 12/24/2024 12/24/2024 12/24/2024
Rated Assembly Inspection Passed 12/24/2024 12/24/2024 12/24/2024
Electrical Service Inspection Passed 12/24/2024 12/24/2024 12/24/2024
All Rough Inspection - Residential Not Ready 12/24/2024 12/24/2024 12/24/2024
Miscellaneous Correction
Informational
12/05/2024
Exterior sheeting and exterior garage PFH passed and is okay to cover This is a partial pass only
Miscellaneous Correction
Corrective Action Required
12/24/2024
No plans on site at time of inspection Not ready for inspection
All Rough Inspection - Residential Failed 12/27/2024 12/27/2024 12/27/2024
Miscellaneous Correction
Informational
12/24/2024
Exterior sheeting and exterior garage PFH passed and is okay to cover This is a partial pass only
Miscellaneous Correction
Resolved
12/27/2024
No plans on site at time of inspection Not ready for inspection
Miscellaneous Correction
Corrective Action Required
12/27/2024
3710/3712 SW Knoxville All rough 3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in suds going down to the basement on the south side wall Fire block top plate in basement closet to mechanical room Water shut off needs to be located within 5 feet of entry point 3712 steel column post is not installed in garage along south wall under the Ibeam Water lines holes are drilled closer than 2 inch apart above entry at floor joist Protect mechanical lines in kitchen to bathroom 2 Protect electrical within 6 feet of attic access hatch Mechanical is running through the attic access hatch Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2 Bonding wire is within the ceiling cavity of the rec room at south wall Water shutoff needs to be within 5 feet of entry point Fire block around bonding wire in demising wall Fire block top of electrical service cable at demising wall Fire block missing top plate in basement to mechanical room
Erosion Control Inspection Residential Failed 12/31/2024 12/31/2024
Miscellaneous Correction
Resolved
12/31/2024
Erosion control is in place and must be properly maintained until CofO
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/31/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Install gravel filter Full erosion control measures must be in place and properly maintained until CofO
All Rough Inspection - Residential Failed 12/31/2024 12/31/2024 12/31/2024
Miscellaneous Correction
Informational
12/27/2024
Exterior sheeting and exterior garage PFH passed and is okay to cover This is a partial pass only
Miscellaneous Correction
Resolved
12/31/2024
3710/3712 SW Knoxville All rough 3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in suds going down to the basement on the south side wall Fire block top plate in basement closet to mechanical room Water shut off needs to be located within 5 feet of entry point 3712 steel column post is not installed in garage along south wall under the Ibeam Water lines holes are drilled closer than 2 inch apart above entry at floor joist Protect mechanical lines in kitchen to bathroom 2 Protect electrical within 6 feet of attic access hatch Mechanical is running through the attic access hatch Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2 Bonding wire is within the ceiling cavity of the rec room at south wall Water shutoff needs to be within 5 feet of entry point Fire block around bonding wire in demising wall Fire block top of electrical service cable at demising wall Fire block missing top plate in basement to mechanical room
Miscellaneous Correction
Corrective Action Required
12/31/2024
3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in king studs going down to the basement on the south side wall Fire block top plate in basement closet to mechanical room 3712 steel column post is not installed in garage along south wall under the Ibeam Water lines holes are drilled closer than 2 inch apart above entry at floor joist Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2 Bonding wire is within the ceiling cavity of the rec room at south wall (have engineers report on where electrician cut notched the floor joist within 2 inches from the edge) Fire block top of electrical service cable sleeve at demising wall Fire block missing top plate in basement to mechanical room
All Rough Inspection - Residential Failed 1/17/2025 1/17/2025 01/17/2025
Miscellaneous Correction
Resolved
01/17/2025
Exterior sheeting and exterior garage PFH passed and is okay to cover This is a partial pass only
Miscellaneous Correction
Resolved
01/17/2025
3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in king studs going down to the basement on the south side wall Fire block top plate in basement closet to mechanical room 3712 steel column post is not installed in garage along south wall under the Ibeam Water lines holes are drilled closer than 2 inch apart above entry at floor joist Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2 Bonding wire is within the ceiling cavity of the rec room at south wall (have engineers report on where electrician cut notched the floor joist within 2 inches from the edge) Fire block top of electrical service cable sleeve at demising wall Fire block missing top plate in basement to mechanical room
Miscellaneous Correction
Corrective Action Required
01/17/2025
3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in king studs going down to the basement on the south side wall 3712 Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2
All Rough Inspection - Residential Passed 1/21/2025 1/21/2025 01/21/2025
Miscellaneous Correction
Resolved
01/21/2025
3710 Nail missing in stud shoes in utility room, bathroom 1 and bathroom 2 Install backing for snow blocking at gable above bedroom 2 Install electrical nail guards in king studs going down to the basement on the south side wall 3712 Nail exterior NE corner to code in bedroom 1 Install backing for snow blocking in gable above bedroom 2
Rated Assembly Inspection Passed 1/28/2025 1/28/2025 01/28/2025
Driveway Inspection Partial 3/10/2025 3/10/2025 03/10/2025
Misc
Informational
03/10/2025
03-10-25 Jamie S, DW is compacted. Approved to pour.
Sidewalk Inspection Partial 3/10/2025 03/10/2025
Miscellaneous Correction
Informational
03/10/2025
03-10-25 Jamie S, SW is compacted, and slopes are in compliance. Allowing one panel transition on west side to existing SW. Approved to pour.
Driveway Inspection Passed 3/17/2025 3/17/2025 03/17/2025
Misc
Informational
03/10/2025
03-10-25 Jamie S, DW is compacted. Approved to pour. 3-17-25 Dustin A, Dw is poured and slopes are in compliance Pass
Erosion Control Inspection Residential Failed 3/17/2025 3/17/2025 03/17/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Informational
03/17/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Install gravel filter Full erosion control measures must be in place and properly maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/17/2025
03-17-25 Jamie S, Erosion control is in place. The sidewalks and ADA crossing need to be cleaned up. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Sidewalk Inspection Failed 3/17/2025 3/17/2025 03/20/2025
Miscellaneous Correction
Informational
03/10/2025
03-10-25 Jamie S, SW is compacted, and slopes are in compliance. Allowing one panel transition on west side to existing SW. Approved to pour. 3-17-25 Dustin A, SW is poured to city specs Slopes are in compliance. Cannot pass until ADA ramp is cleaned off so we can check for any cracks. Once cleaned off please call in. 3-20-25 Jamie S, SW Failed due to two panels east of storm box are out of compliance with running slope city compliance standards. ADA ramp to the storm box should be replaced in order to meet running slope of 8.3% or match street grade. Water valve box also needs to be cut down and hat installed.
Erosion Control Inspection Residential Failed - Stop Work 3/20/2025 3/20/2025 03/20/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Informational
03/17/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Install gravel filter Full erosion control measures must be in place and properly maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/17/2025
03-17-25 Jamie S, Erosion control is in place. The sidewalks and ADA crossing need to be cleaned up. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 03-20-25 Jamie S, Sidewalks and ADA crossing are still cover with dirt and debris.
Erosion Control Inspection Residential Partial 3/25/2025 3/25/2025 03/25/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
03/25/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. Install gravel filter Full erosion control measures must be in place and properly maintained until CofO
DCM3 ESC REQUIRED 2 DAY
Resolved
03/25/2025
03-17-25 Jamie S, Erosion control is in place. The sidewalks and ADA crossing need to be cleaned up. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 03-20-25 Jamie S, Sidewalks and ADA crossing are still cover with dirt and debris.
Misc
Corrective Action Required
03/25/2025
- Erosion control in place at time of inspection.
Erosion Control Inspection Residential Partial 3/26/2025 03/26/2025
Misc
Corrective Action Required
03/25/2025
- Erosion control in place at time of inspection.
Occupancy Inspection - Codes Residential Ready for Temp CO 3/26/2025 3/26/2025 03/26/2025
Misc
Corrective Action Required
03/26/2025
3710, 3712 sw Knoxville ct BOTH - provide gutters and downspouts - Provide splash pads - Final grading and sod Land - Sidewalk inspection pending - Pay all fees - Land sewer trace wire at grade - Sump discharge to be 36” away from foundation - Seal top of A/C disconnect - Label address at Electrical disconnect - Uncover water meters for inspection Open 3710 - Fire block around water spigot in garage - Open electrical box in basement bathroom - Floor drain for condensation line not draining basement ***3712 ok for TCO only***
Occupancy Inspection - Codes Residential Ready for Temp CO 3/27/2025 3/27/2025 03/27/2025
Misc
Corrective Action Required
03/26/2025
3710, 3712 sw Knoxville ct BOTH - provide gutters and downspouts - Provide splash pads - Final grading and sod Land - Sidewalk inspection pending - Pay all fees - Land sewer trace wire at grade - Sump discharge to be 36” away from foundation - Seal top of A/C disconnect - Label address at Electrical disconnect - Uncover water meters for inspection Open ***3710 AND 3712 ok for TCO only***
Occupancy Inspection - Codes Residential Failed 4/25/2025 04/25/2025
Misc
Corrective Action Required
03/27/2025
TCO expired a notice of violation sent Wes Bears 04/25/2025 7:27 AM 3710, 3712 sw Knoxville ct BOTH - provide gutters and downspouts - Provide splash pads - Final grading and sod Land - Sidewalk inspection pending - Pay all fees - Land sewer trace wire at grade - Sump discharge to be 36” away from foundation - Seal top of A/C disconnect - Label address at Electrical disconnect - Uncover water meters for inspection Open ***3710 AND 3712 ok for TCO only***
Occupancy Inspection - Codes Residential Failed 5/28/2025 05/28/2025
Misc
Corrective Action Required
04/25/2025
TCO expired a notice of violation sent Wes Bears 05/28/2025 7:27 AM 3710, 3712 sw Knoxville ct BOTH - provide gutters and downspouts - Provide splash pads - Final grading and sod Land - Sidewalk inspection pending - Pay all fees - Land sewer trace wire at grade - Sump discharge to be 36” away from foundation - Seal top of A/C disconnect - Label address at Electrical disconnect - Uncover water meters for inspection Open ***3710 AND 3712 ok for TCO only***
Erosion Control Inspection Residential Failed 7/8/2025 7/8/2025 07/08/2025
Misc
Corrective Action Required
03/26/2025
- Erosion control in place at time of inspection.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/08/2025
07/08/25 Jamie S, Erosion control needs to be reestablished. Street and sidewalk need to be cleaned off. Trash on lot need to be removed. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Failed - Stop Work 7/11/2025 7/11/2025 07/11/2025
Misc
Corrective Action Required
07/08/2025
- Erosion control in place at time of inspection.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/08/2025
07/08/25 Jamie S, Erosion control needs to be reestablished. Street and sidewalk need to be cleaned off. Trash on lot need to be removed. EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. 07/11/25 Jamie S, Erosion control needs to be reestablished. Street and sidewalk need to be cleaned off. Trash on lot need to be removed.
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home