Summary
PRRES20241945
Building Permit - Residential
Issued
NEW SINGLE FAMILY
NEW HOUSE. WALKOUT BASEMENT. FINISHED/UNFINISHED BASEMENT. COVERED DECK. SUSPENDED SLAB.
04/18/2024
05/01/2024
10/26/2024
Locations
Contacts
Stone Chase Homes,LLC, Address:30906 E stony point school rd , Phone:(816) 266-7395  
Brian shaw, Address:617 Sw Muriel Dr, Phone:(816) 266-7395  
MCDANIEL FURNACE & SHEET METAL, Address:2905 S M 291 FRONTAGE RD, Phone:(816) 373-6370  
THE SOLAR GUYS, Address:6114 MO-9 HWY STE C1, Phone:(913) 424-2112  
RITEWAY PLUMBING LLC, Address:2101 SW OSAGE DR, Phone:(816) 813-9849  
BRIAN@STONECHASEPROPERTIES.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 05/01/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 05/01/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 05/01/2024
9110078-Valuation Fee New Single Family $1,839.78 $1,839.78 Paid 05/01/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Erosion Control Inspection Residential Pending
DCM2 ESC DEFICIENT INSTALLATION
Informational
08/13/2024
EROSION CONTROL IN COMPLIANCE. MAINTAIN EROSION CONTROL DURING CONSTRUCTION UNTIL SODDING
Occupancy Inspection - Codes Residential Pending
Misc
Corrective Action Required
04/08/2025
-As-graded plot plan is required -Remove trashed silt fence along the rear of lot and provide seeding to disturbed area -Install address -Install splash blocks at downspouts and sump pump extension -Secure grinder pump ENT within 3 ft if controller -Gravel at window well -Install flood light at rear -Deck: lag screw both ledger boards to floor rim per code; support joists to ledger with approved device; engineer to address the beam-post connections not per code. Code requires two 1/2” through bolts or approved post caps; engineer address for deck beam not per plan. Plan calls for 3.5”x14” treated Paralam -Seal exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc -Provide sewer tracer wire port at grade -Connect downspout to drain at front entry -Fix lights above master closet -Fix ground fault at right master bathroom receptacle -Screw the exterior door embedded metal jamb brace into studs through the four pre-drilled holes; fully screw the strike plate to the embedded jamb brace (4 offset holes) -Provide receptacles for cabinet wall spaces adjacent to the fireplace. Receptacles inside cabinet do not count as the required receptacles -Install the water hammer arrestor for dishwasher water supply -Loop the dishwasher drain up high and secure in place -Complete kitchen hood installation -Garage and garage-to-pantry doors not self-closing -Secure water service line -Secure EMT raceway within 3 ft of light box (space under garage) -Install smoke and CO outside basement bedrooms -Install box extension for receptacle near basement walkout door -Locate and make accessible the ufer grounding connection
Footing Inspection - Residential Passed 5/30/2024 05/30/2024
Erosion Control Inspection Residential Failed 6/14/2024 6/14/2024 06/14/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
06/14/2024
DEFICIENT EROSION CONTROL INSTALLATION ALONG THE REAR OF LOT. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Underslab Plumbing Inspection - Residential Passed 6/14/2024 6/14/2024 06/14/2024
Suspended Slab Inspection Passed 7/19/2024 07/19/2024
Erosion Control Inspection Residential Failed 7/22/2024 07/22/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
06/14/2024
DEFICIENT EROSION CONTROL INSTALLATION ALONG THE REAR OF LOT. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Sewer Service Inspection - R Failed 7/22/2024 07/22/2024
Misc
Corrective Action Required
07/22/2024
INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY AND NO ADDRESS POSTED
Piers/Caissons Inspection - Residential Failed 7/22/2024 7/22/2024 07/22/2024
Misc
Corrective Action Required
07/22/2024
INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY AND NO ADDRESS POSTED
Sewer Service Inspection - R Passed 7/22/2024 07/22/2024
Misc
Resolved
07/22/2024
Erosion Control Inspection Residential Partial 7/29/2024 07/29/2024
DCM2 ESC DEFICIENT INSTALLATION
Informational
07/29/2024
EROSION CONTROL IN COMPLIANCE. MAINTAIN EROSION CONTROL DURING CONSTRUCTION UNTIL SODDING
Piers/Caissons Inspection - Residential Passed 7/29/2024 07/29/2024
Misc
Resolved
07/29/2024
INSPECTION DENIED DUE TO EROSION CONTROL DEFICIENCY AND NO ADDRESS POSTED
Gas Service Inspection - Residential Passed 8/2/2024 8/2/2024 08/02/2024
Electrical Service Inspection Passed 8/2/2024 8/2/2024 08/02/2024
All Rough Inspection - Residential Failed 8/2/2024 8/2/2024 08/02/2024
Misc
Corrective Action Required
08/02/2024
-Nail garage PFH wall sheathing to bottom sill plate @3” oc -Provide 2”x2”x3/16” washers for garage PFH walls anchors -Anchor sill plates within 12” of breaks and no closer than 3.5” -Fb all wall plates penetrations throughout. Shall use approved foam for fire blocking; fb floor penetration at tub trap -Nail corner studs w/16d@12” oc or equivalent nailing -Bond metal box above bedroom 2 -Install stud shoe at over-bored laundry wall stud -Protect plumbing at laundry wall top plate -Master toilet wall is not a bearing wall. Install roof beam and purlin -Install hanger support at lvl-lvl beam connection above fireplace -Provide security blockings for master bedroom exterior door at strike plate height, 3 stud spaces out; install door frame and fill in gap at strike plate side and hinges per security code -Plan calls for 2 king and 2 trimmer studs at great room exterior wall -Brace ends of roof lvl beams against rotation -Add blockings underneath the 18” I beam point load -Provide wall receptacle spacing near basement wet bar per code -Provide stud shoes for basement non-bearing wall studs bored more than 60% -Fb basement wall vertically at max ten ft intervals. Fb all gaps and penetrations; fb wall from soffits; fb gaps at top of wall space; shall use approved foam for fire blocking -Toe nail all joists to wall top plates and sill plates in basement per code. 4-8d or 3-10d -Provide security blockings for basement walkout door at strike plate height on both sides of door, 3 stud spaces out; install door frame and fill in gap at strike plate side and hinges per security code -Fb basement bathroom wall and dead space from soffit; fb floor penetration at trap above bedroom 3; fb all basement wall from soffits -Anchor rear basement bedroom sill plate within 12” of break -Support PVC above bedroom 3 at max 4 ft -Double joists above home theater room -Anchor column at home theater/bedroom wall -Support basement stair landing joists -Provide engineer report for suspended garage and stoop slab **DO NOT INSULATE
All Rough Inspection - Residential Failed 8/8/2024 8/8/2024 08/08/2024
Misc
Corrective Action Required
08/02/2024
-Provide 2”x2”x3/16” washers for garage PFH walls anchors -Anchor sill plates within 12” of breaks and no closer than 3.5” -Fb all wall plates penetrations throughout. Shall use approved foam for fire blocking; -Provide security blockings for master bedroom exterior door at strike plate height, 3 stud spaces out; install door frame and fill in gap at strike plate side and hinges per security code -Plan calls for 2 king and 2 trimmer studs at great room exterior wall -Fb basement wall vertically at max ten ft intervals. Fb all gaps and penetrations; fb wall from soffits; fb gaps at top of wall space; shall use approved foam for fire blocking -Toe nail all joists to wall top plates and sill plates in basement per code. 4-8d or 3-10d -Provide security blockings for basement walkout door at strike plate height on both sides of door, 3 stud spaces out; install door frame and fill in gap at strike plate side and hinges per security code -Fb basement bathroom wall and dead space from soffit; fb floor penetration at trap above bedroom 3; fb all basement wall from soffits -Provide engineer report for suspended garage and stoop slab **DO NOT INSULATE
Erosion Control Inspection Residential Partial 8/13/2024 08/13/2024
DCM2 ESC DEFICIENT INSTALLATION
Informational
07/29/2024
EROSION CONTROL IN COMPLIANCE. MAINTAIN EROSION CONTROL DURING CONSTRUCTION UNTIL SODDING
All Rough Inspection - Residential Partial 8/13/2024 8/13/2024 08/13/2024
Misc
Corrective Action Required
08/08/2024
-Anchor sill plates within 12” of breaks and no closer than 3.5”; anchor within middle 1/3 of sill plates -Plan calls for 2 king and 2 trimmer studs at great room exterior wall **Wrap straps to wall top plate and nail per engineer -Fb basement wall vertically at max ten ft intervals. Fb all gaps and penetrations; fb gaps at top of wall space -Toe nail all joists to wall top plates and sill plates in basement per code. 4-8d or 3-10d -Support dryer duct **OK TO INSULATE
All Rough Inspection - Residential Passed 8/15/2024 8/15/2024 08/15/2024
Misc
Resolved
08/15/2024
Driveway Inspection Partial 9/16/2024 9/16/2024 09/16/2024
Misc
Informational
09/16/2024
9-16-24 DP. SW was formed, aggregatge compacted. Approved to pour.
Driveway Inspection Passed 9/24/2024 9/24/2024 09/24/2024
Misc
Informational
09/16/2024
9-16-24 DP. SW was formed, aggregatge compacted. Approved to pour. 9-24-24 NS Driveway and Sidewalk pass.
Occupancy Inspection - Codes Residential Failed 4/8/2025 4/8/2025 04/08/2025
Misc
Corrective Action Required
04/08/2025
-As-graded plot plan is required -Remove trashed silt fence along the rear of lot and provide seeding to disturbed area -Install address -Install splash blocks at downspouts and sump pump extension -Secure grinder pump ENT within 3 ft if controller -Gravel at window well -Install flood light at rear -Deck: lag screw both ledger boards to floor rim per code; support joists to ledger with approved device; engineer to address the beam-post connections not per code. Code requires two 1/2” through bolts or approved post caps; engineer address for deck beam not per plan. Plan calls for 3.5”x14” treated Paralam -Seal exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc -Provide sewer tracer wire port at grade -Connect downspout to drain at front entry -Fix lights above master closet -Fix ground fault at right master bathroom receptacle -Screw the exterior door embedded metal jamb brace into studs through the four pre-drilled holes; fully screw the strike plate to the embedded jamb brace (4 offset holes) -Provide receptacles for cabinet wall spaces adjacent to the fireplace. Receptacles inside cabinet do not count as the required receptacles -Install the water hammer arrestor for dishwasher water supply -Loop the dishwasher drain up high and secure in place -Complete kitchen hood installation -Garage and garage-to-pantry doors not self-closing -Secure water service line -Secure EMT raceway within 3 ft of light box (space under garage) -Install smoke and CO outside basement bedrooms -Install box extension for receptacle near basement walkout door -Locate and make accessible the ufer grounding connection
Documents & Images
Date Uploaded File Type Document Name
04/18/2024 LOT 26 FINAL
04/18/2024 WLO026 SPEC - Sealed Plans (Mar 13, 2024)
04/22/2024 LS
04/22/2024 Application Form EXCISE TAX
04/30/2024 Application Form Updated LS app
04/30/2024 LOT 26 CITY
04/30/2024 Grinder Pump Submittal
04/29/2024 Permit Codes Residential Plan Review
05/01/2024 Plot Plan APPROVED PLOT PLAN
05/01/2024 Approved Plans APPROVED PLANS
05/01/2024 Permit Codes Residential Plan Review
05/01/2024 Permit DS Building Permit
05/01/2024 Receipt Receipt for transaction:2024-002805
05/30/2024 Letter INSPECTION SUMMARY
06/14/2024 Letter INSPECTION SUMMARY
06/14/2024 Letter INSPECTION SUMMARY
07/19/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/22/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
08/02/2024 Letter INSPECTION SUMMARY
08/02/2024 Letter INSPECTION SUMMARY
08/02/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/13/2024 Letter INSPECTION SUMMARY
08/15/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
04/08/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.