Permit Application Status

PRRES20201062


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20201062
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - COVERED DECK - FINISHED BASEMENT
04/28/2020
05/11/2020
10/14/2022
Locations
Contacts
ROBERTSON REMODELING LLC, Address:500 JAMES ROLO DR  
JASONFW1@COMCAST.NET  
1441 HEATING AND COOLING, LLC, Address:3224 S OWENS SCHOOL RD, Phone:(816) 305-5969  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/30/2020 05/07/2020
Dylan Eppert
Easements
Corrective Action Required
04/30/2020

All easements with dimensions must be provided on the plot plan. MISSING 15' U/E PER PLAT
Basement egress
Corrective Action Required
04/30/2020

Basement egress location(s) and elevation of the lowest adjacent grade must be provided on the plot plan.
Residential Plan Review Approved 04/30/2020 04/30/2020
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,100.14 $1,100.14 Paid 05/11/2020
8331507-Sewer Connection Fee $420.00 $420.00 Paid 05/11/2020
8331401-Water Tap Fee $3,477.00 $3,477.00 Paid 05/11/2020
8350015-Water Meter Fee $425.02 $425.02 Paid 05/11/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/11/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 05/11/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/27/2020
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/27/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 5/11/2020 05/11/2020
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/11/2020
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Footing Inspection - Residential Passed 5/11/2020 (1:15) 5/11/2020 05/11/2020
Underslab Plumbing Inspection - Residential Failed 5/20/2020 5/20/2020 05/20/2020
Misc
Corrective Action Required
05/20/2020
- REPAIR CRUSHED INTERIOR DRAIN TILE -
Underslab Plumbing Inspection - Residential Passed 5/21/2020 5/20/2020 05/20/2020
Misc
Resolved
05/20/2020
- REPAIR CRUSHED INTERIOR DRAIN TILE -
Water Service Inspection - R Passed 6/11/2020 (10:45) 6/11/2020 06/11/2020
Sewer Service Inspection - R Passed 6/11/2020 (10:45) 6/11/2020 06/11/2020
Erosion Control Inspection Residential Failed 6/12/2020 6/12/2020 06/12/2020
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/11/2020
-EROSION CONTROL REQUIRED. -REESTABLISH SILT FENCE AT FRONT AND BACK OF LOT -PROVIDE GRAVEL FILTER AT DRIVE -RESOLVE BEFORE ANY FURTHER INSPECTIONS
Gas Service Inspection - Residential Failed 7/17/2020 7/17/2020 07/17/2020
Electrical Service Inspection Not Ready 7/17/2020 7/17/2020 07/17/2020
Miscellaneous Correction
Corrective Action Required
07/17/2020
****NOT READY***** -THIS LIST IS INCOMPLETE- -NO SERVICE PANEL, NO SERVICE CABLE -LAND ALL ELECTRICAL IN SERVICE PANEL -PROTECT ALL NM WIRES WHERE WITHIN 1 1/4’ OF FACE OF STUD -PROVIDE 20 AMP CIRCUIT IN GARAGE PER CODE
All Rough Inspection - Residential Not Ready 7/17/2020 7/17/2020 07/17/2020
Miscellaneous Correction
Corrective Action Required
07/17/2020
****NOT READY***** —THIS LIST IS NOT COMPLETE— -PROVIDE APPROVED, LEGIBLE, STAMPED PLANS FOR INSPECTION -NO SERVICE PANEL, NO SERVICE CABLE -LAND ALL ELECTRICAL IN SERVICE PANEL -PROTECT ALL NM WIRES WHERE WITHIN 1 1/4’ OF FACE OF STUD -PROVIDE 20 AMP CIRCUIT IN GARAGE PER CODE -MISSING NUTS ON SOLE PLATE AT GARAGE DOOR -ANCHOR BOLTS TO BE SPACED MAX 6’ O.C. IN GARAGE -TIGHTEN ALL ANCHOR BOLTS IN GARAGE -PROVIDE ANCHOR BOLTS WITHIN 12” OF PLATE BREAK IN GARAGE -INSULATE AND BLOCK CANTILEVER IN GARAGE TO FLOOR -NAIL RAFTER AND JOIST CONNECTIONS IN PER CODE -NAIL RAFTER AND RIDGE/ HIP CONNECTIONS IN PER CODE -FIRE BLOCK BEAM WEB IN GARAGE -PROVIDE APPROVED STRAP AND CONNECTIONS AT TOP PLATE OF WALL AT DUCT CHASE -INSTALL SLIDING GLASS DOOR IN BASEMENT
Electrical Service Inspection Failed 8/4/2020 8/4/2020 08/04/2020
Miscellaneous Correction
Corrective Action Required
07/17/2020
-COLOR CODE UFER GROUND AND GAS LINE GROUND
Gas Service Inspection - Residential Passed 8/4/2020 8/4/2020 08/04/2020
All Rough Inspection - Residential Failed 8/4/2020 8/4/2020 08/04/2020
Miscellaneous Correction
Corrective Action Required
07/17/2020
***DO NOT INSULATE*** -BOLT JOISTS AND RIM TO COLUMNS AT DECK -PROVIDE HANGER OR ANGLE CLIP AT END JOISTS NOT BEARING ON COLUMNS -ADDRESS BEARING/ CONNECTION AT OFFSET OF DECK/ HOUSE -PROVIDE 20 AMP DEDICATED CIRCUIT IN GARAGE PER CODE -TIGHTEN ANCHOR BOLT AT PFG -BOLT AT PFG NOT SECURED IN CONCRETE -NAIL RAFTER AND JOIST CONNECTIONS IN PER CODE -NAIL RAFTER AND RIDGE/ HIP CONNECTIONS IN PER CODE -NAIL CORNERS AND INTERESTING WALL STUDS PER CODE -NAIL JOIST LAPS PER CODE OVER PATIO AND IN GARAGE -SEAL PENETRATION IN TOP PLATE AT GARAGE ENTRY DOOR -ATTIC ACCESS REQUIRES 30” OF CLEARANCE PER CODE -SEAL PENETRATIONS IN TOP AND BOTTOM PLATE AT FRIDGE -ADDRESS OVER CUT LVL HIPS IN GREAT ROOM AND MASTER CLOSET -SEAL UPWARD GAPS IN WALL BY STAIRS BETWEEN PLYWOOD AND PLATE -PROVIDE LATERAL SUPPORT FOR (2) 2X12, (3 2X12 AND LVL BEAM IN GREAT-ROOM AND OVER ENTRY -SECURE ALL VERTICAL DWV SMALLER THAN 2” AT MIDPOINT -STEEL COLUMN IN BASEMENT BY STAIRS TO BE 3 1/2” (TYPE F PEIR) PER PLANS -PROVIDE SOLID BLOCKING AT JOISTS ABOVE ALL BEAMS -PROVIDE DOUBLE KING STUDS AT DOORS AND WINDOWS IN ALL 2X6 WALLS IN BASEMENT PER PLANS -TIGHTEN ANCHOR BOLTS IN BASEMENT -MISSING ANCHOR BOLT AT END OF PLATE AT REC ROOM/ MECHANICAL ROOM -COLOR CODE UFER GROUND AND GAS GROUND -SUPPORT PVC FOR COMBUSTION AIR PER CODE -FASTEN BOTTOM PLATE IN BASEMENT PER CODE
Electrical Service Inspection Passed 8/11/2020 8/11/2020 08/11/2020
Miscellaneous Correction
Resolved
08/11/2020
-COLOR CODE UFER GROUND AND GAS LINE GROUND
All Rough Inspection - Residential Failed 8/11/2020 8/11/2020 08/11/2020
Miscellaneous Correction
Corrective Action Required
08/04/2020
***DO NOT INSULATE*** -BOLT JOISTS AND RIM TO COLUMNS AT DECK -ADDRESS BEARING/ CONNECTION AT OFFSET OF DECK/ HOUSE -PROVIDE 20 AMP DEDICATED CIRCUIT IN GARAGE PER CODE-THE 3 RECEPTACLES FOR WALL OUTLETS -ATTIC ACCESS REQUIRES 30” OF CLEARANCE PER CODE -ADDRESS OVER CUT LVL HIPS IN GREAT ROOM AND MASTER CLOSET -PROVIDE SOLID BLOCKING AT JOISTS ABOVE ALL BEAMS -PROVIDE DOUBLE KING STUDS AT DOORS AND WINDOWS IN ALL 2X6 WALLS IN BASEMENT PER PLANS -TIGHTEN ANCHOR BOLTS IN BASEMENT-BEHIND FURNACE -SUPPORT PVC FOR COMBUSTION AIR PER CODE
All Rough Inspection - Residential Failed 8/13/2020 8/13/2020 08/13/2020
Miscellaneous Correction
Corrective Action Required
08/11/2020
***OK TO INSULATE*** -PROVIDE 20 AMP DEDICATED CIRCUIT IN GARAGE PER CODE-THE 3 RECEPTACLES FOR WALL OUTLETS-ONE PER CAR BAY.—ADD THE ONE FOR THE SINGLE BAY THIS WAS PRESENT BUT GOT REMOVED WHEN SWITCHED OVER TO 20 AMP -ADDRESS OVER CUT LVL HIPS IN GREAT ROOM AND MASTER CLOSET -SUPPORT PVC FOR COMBUSTION AIR PER CODE
All Rough Inspection - Residential Passed 8/19/2020 8/19/2020 08/19/2020
Miscellaneous Correction
Resolved
08/19/2020
***OK TO INSULATE*** -PROVIDE 20 AMP DEDICATED CIRCUIT IN GARAGE PER CODE-THE 3 RECEPTACLES FOR WALL OUTLETS-ONE PER CAR BAY.—ADD THE ONE FOR THE SINGLE BAY THIS WAS PRESENT BUT GOT REMOVED WHEN SWITCHED OVER TO 20 AMP -SUPPORT PVC FOR COMBUSTION AIR PER CODE
Driveway Inspection Passed 9/3/2020 9/3/2020 09/08/2020
Misc
Informational
09/08/2020
A Drive Approach inspection was performed Thursday 9-02-2020 and passed subgrade and forms inspection
Sidewalk Inspection Passed 10/08/2020
Erosion Control Inspection Residential Passed 10/26/2020
Misc
Resolved
10/26/2020
Maintain erosion control at street frontage
Deck Final Inspection - Residential Failed 10/26/2020
Miscellaneous Correction
Resolved
10/26/2020
-BOLT JOISTS AND RIM TO COLUMNS AT DECK
Misc
Corrective Action Required
10/26/2020
Replace cut joist hangers at double 2x10 rims at connection to structure
Occupancy Inspection - Codes Residential Failed 10/26/2020 10/26/2020 10/26/2020
Miscellaneous Correction
Resolved
10/26/2020
See corrections for deck
Misc
Corrective Action Required
10/26/2020
-Irrigation permit required -Remove trash and construction debris -All outstanding fees must be paid in full -Final grade per approved plot plan and sod -Remove excavation spoils -Downspouts to discharge minimum 36 inches from foundation -Seal all exterior penetrations -Replace damaged joist hangers at double 2x10 deck rims at connection to structure -Secure conduit at exterior HVAC disconnect -Tamper resistant Schrader valves at exterior HVAC equipment -Faulty exterior GFCI receptacle at front door -Attic access lid needs to be flush fitting with trim -GFCI protection required at laundry circuit -GFCI protection required at dishwasher circuit -AFCI protection required at kitchens, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sun- rooms, recreations rooms, closets, hallways, laundry areas and similar rooms or areas -secure outlet & junction boxes under kitchen sink -All sliding glass doors shall be equipped with a secondary locking device consisting of a metal pin or a surface mounted bolt assembly. Metal pins shall be installed at the intersection of the inner and outer panels of the inside door and shall not penetrate the frame's exterior surface. The surface mounted bolt assembly shall be installed at the base of the door. -complete fireplace trim installation and remove packing debris from cabinet interior -ensure all outlet plates are installed -complete shower door glazing installation -Close unused hole in furnace disconnect outlet box -Receptacles in unfinished basement required to be GFCI protected, at furnace -Breaker lock out devices required at all hardwired appliances not within sight of service panel -Label dedicated circuit as non-GFCI protected in unfinished basement area
Occupancy Inspection - Codes Residential Temporary C of O 10/27/2020 10/27/2020 10/27/2020
Misc
Corrective Action Required
10/26/2020
-Irrigation permit required -All outstanding fees must be paid in full -Final grade per approved plot plan and sod -Remove excavation spoils -Downspouts to discharge minimum 36 inches from foundation -Seal all exterior penetrations
Occupancy Inspection - Codes Residential Temporary C of O 3/17/2021 3/17/2021 03/17/2021
Misc
Corrective Action Required
10/27/2020
-Irrigation permit required -Downspouts to discharge minimum 36 inches from foundation TCO EXTENDED 7 DAYS VALID THROUGH 03/24/2021
Piers/Caissons Inspection - Residential Passed 03/17/2021
Plot Plan Inspection Passed 03/17/2021
Erosion Control Inspection Residential Passed 03/17/2021
Misc
Resolved
03/17/2021
-deficient erosion control installation, shall be in compliance within two days. No further inspections until complete -Street cleanup required immediately. No further inspections until complete -Remove trash from site -Remove overgrown weeds and vegetation
Erosion Control Inspection Residential Passed 03/17/2021
DCM3 ESC REQUIRED 2 DAY
Resolved
03/17/2021
-EROSION CONTROL REQUIRED. -REESTABLISH SILT FENCE AT FRONT AND BACK OF LOT -PROVIDE GRAVEL FILTER AT DRIVE -RESOLVE BEFORE ANY FURTHER INSPECTIONS
Gas Piping Inspection - Residential Passed 03/17/2021
Occupancy Inspection - Codes Residential Failed 05/18/2021
Misc
Corrective Action Required
03/17/2021
-Irrigation permit required -Downspouts to discharge minimum 36 inches from foundation TCO EXTENDED 7 DAYS VALID THROUGH 03/24/2021
Misc
Corrective Action Required
05/18/2021
The temporary certificate of occupancy has expired at this address. If remaining correction items are complete please schedule an occupancy inspection. If remaining correction items are not complete a permit extension request must be submitted in writing with the expected date of completion.
Occupancy Inspection - Codes Residential Full C of O 10/14/2022
Misc
Resolved
10/14/2022
-Irrigation permit required -Downspouts to discharge minimum 36 inches from foundation TCO EXTENDED 7 DAYS VALID THROUGH 03/24/2021
Misc
Resolved
10/14/2022
The temporary certificate of occupancy has expired at this address. If remaining correction items are complete please schedule an occupancy inspection. If remaining correction items are not complete a permit extension request must be submitted in writing with the expected date of completion.
Documents & Images
Date Uploaded File Type Document Name
04/28/2020 Lees Summit PDF permit application
04/28/2020 LOT 16 FINAL survey
04/28/2020 WW016 Spec - Sealed Plans (April 10, 2020)
04/30/2020 Letter Codes Residential Plan Review
04/30/2020 Plans APPROVED HOUSE PLANS
05/07/2020 Plot Plan APPROVED PLOT PLAN
05/11/2020 Receipt Receipt for transaction: 2020-002037
05/11/2020 Letter DS Building Permit
05/11/2020 Letter INSPECTION SUMMARY
05/11/2020 Letter INSPECTION SUMMARY
05/20/2020 Letter INSPECTION SUMMARY
05/20/2020 Letter INSPECTION SUMMARY
05/28/2020 Engineer Report/Study Final_2020.05.28_DPier_LSMO_Pat Cochran Concrete
06/11/2020 Letter INSPECTION SUMMARY
06/11/2020 Letter INSPECTION SUMMARY
06/12/2020 Letter INSPECTION SUMMARY
06/19/2020 Engineer Report/Study BSlab - 1804 SW River Run - Lot 16 Whispering Woods
07/17/2020 Letter INSPECTION SUMMARY
07/17/2020 Letter INSPECTION SUMMARY
07/17/2020 Letter INSPECTION SUMMARY
07/17/2020 Letter INSPECTION SUMMARY
08/04/2020 Letter INSPECTION SUMMARY
08/04/2020 Letter INSPECTION SUMMARY
08/04/2020 Letter INSPECTION SUMMARY
08/11/2020 Letter INSPECTION SUMMARY
08/11/2020 Letter INSPECTION SUMMARY
08/13/2020 Letter INSPECTION SUMMARY
08/18/2020 1804 River Run Drive - Structural Letter (August 17, 2020)
08/19/2020 Letter INSPECTION SUMMARY
09/16/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
10/06/2020 Letter INSPECTION SUMMARY
10/26/2020 Letter INSPECTION SUMMARY
10/26/2020 Letter INSPECTION SUMMARY
10/26/2020 Letter INSPECTION SUMMARY
10/26/2020 Letter INSPECTION SUMMARY
10/26/2020 Letter INSPECTION SUMMARY
10/27/2020 Letter Codes Temporary Certificate of Occupancy
10/27/2020 Receipt Receipt for transaction:2020-007215
03/16/2021 Letter Codes 140 Day Letter
03/16/2021 Letter Codes 140 Day Letter
03/17/2021 Letter Codes Temporary Certificate of Occupancy
03/17/2021 Letter INSPECTION SUMMARY
03/17/2021 Letter INSPECTION SUMMARY
03/17/2021 Letter INSPECTION SUMMARY
03/17/2021 Letter INSPECTION SUMMARY
03/17/2021 Letter INSPECTION SUMMARY
05/18/2021 Letter INSPECTION SUMMARY
09/22/2022 Letter Codes 10 Day Letter
10/14/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home