Permit Application Status

PRRES20193669


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20193669
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - SUSPENDED STOOP - COVERED DECK
12/23/2019
01/10/2020
05/10/2021
Locations
Contacts
NEW MARK HOMES - KC LLC, Address:5207 NW CROOKED ROAD, Phone:(816) 969-9010  
ASHLEY@NEWMARKHOMESKC.COM  
HARRINGTON BROTHERS HEATING & COOLING, Address:15630 S KEELER ST, Phone:(913) 422-5444  
CLASS ONE ELECTRIC INC, Address:PO BOX 24343, Phone:(913) 915-1767  
R & R PLUMBING INC, Address:2001 GASLIGHT DR, Phone:(816) 772-5431  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 12/30/2019 01/08/2020
Dylan Eppert
05 Provide square footage of living area, garage area, unfinished basement
Corrective Action Required
12/26/2019

Provide square footage of living area, garage area, unfinished basement area, etc (IRC Section R304) NEED SQUARE FOOTAGE FOR UNFINISHED AND FINISHED BASEMENT TO BE ABLE TO CALCULATE A FEE. THESE ALSO NEED TO BE ON THE CONSTRUCTION DRAWINGS. IF THE BASEMENT IS NOT FINISHED THE SQUARE FOOTAGE FOR THAT WILL NOT NEED TO BE ON THE DRAWINGS.
Miscellaneous Correction
Corrective Action Required
12/26/2019

CONSTRUCTION DRAWINGS REFERENCE 2012 AND 2018 IRC. PLEASE REMOVE ALL REFERENCES OF THE 2012 BUILDING CODE.
08 Designate locations of smoke detectors and carbon monoxide detectors
Corrective Action Required
12/26/2019

Designate locations of smoke detectors and carbon monoxide detectors. (IRC Section R314 and R315) DOES "SD" MEAN JUST SMOKE OR DOES IT MEAN SMOKE AND CARBON BEING A COMBO. EVERYTHING ON THE CONSTRUCTION DRAWINGS SHOW AS "SD" AND NO REFERENCE TO CARBON DETECTORS PLEASE CLARIFY.
Miscellaneous Correction
Corrective Action Required
12/26/2019

ELECTRICAL CONTRACTOR DOESN'T HAVE A VALID BUSINESS LICENSE.
Plot Plan Review Approved 12/30/2019 01/02/2020
Dylan Eppert
North arrow and scale
Corrective Action Required
12/26/2019

The plot plan must be submitted on either (1) 81/2” x 11”, (2) 81/2”x 14”, or (3) 11” x 17” paper. All information on the plot plan must be drawn to scale. Scale must be 1” = 10’, 20’, or 30’; smaller scales that are multiples of the preceding scales may be used if necessary to represent large sites. All information on the plot plan must be clearly legible.) PLOT PLAN WAS NOT PRINTED OUT TO SCALE.
As-graded plot plan
Corrective Action Required
12/26/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
City infrustructure
Corrective Action Required
12/26/2019

Show all manholes, water valve boxes, fire hydrants, and stormwater structures. SHOW ELEVATIONS FOR FIELD INLET THROAT AND TOP.
Spot elevations
Corrective Action Required
12/26/2019

Spot elevations and/or drainage flow arrows shall be provided throughout the lot. CANNOT COMPLETE UNTIL SCALE HAS BEEN FIXED.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,435.01 $1,435.01 Paid 01/10/2020
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 01/10/2020
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 01/10/2020
8331401-Water Tap Fee $3,477.00 $3,477.00 Paid 01/10/2020
8350015-Water Meter Fee $425.02 $425.02 Paid 01/10/2020
8331507-Sewer Connection Fee $600.00 $600.00 Paid 01/10/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 1/31/2020 (2:30) 1/31/2020 01/31/2020
Underslab Plumbing Inspection - Residential Passed 4/10/2020 4/13/2020 04/13/2020
Piers/Caissons Inspection - Residential Passed 5/19/2020 (1:00) 5/19/2020 05/19/2020
Misc
Informational
05/19/2020
(2) 18 x 36 covered deck piers
Sewer Service Inspection - R Passed 5/29/2020 (11:00) 5/29/2020 05/29/2020
Erosion Control Inspection Residential Failed 06/02/2020
Miscellaneous Correction
Resolved
06/02/2020
-EROSION CONTROL MISSING/ INCOMPLETE -CLEAN MUD AND DEBRIS FROM STREETS WITHIN 48 HOURS
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/02/2020
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Water Service Inspection - R Passed 6/2/2020 (10:15) 6/2/2020 06/02/2020
Erosion Control Inspection Residential Passed 6/5/2020 6/5/2020 06/05/2020
Miscellaneous Correction
Corrective Action Required
06/02/2020
-EROSION CONTROL MISSING/ INCOMPLETE -CLEAN MUD AND DEBRIS FROM STREETS WITHIN 48 HOURS
All Rough Inspection - Residential Failed 6/23/2020 6/23/2020 06/23/2020
Miscellaneous Correction
Corrective Action Required
06/23/2020
—NO PLANS ON SITE-PROVIDE CITY STAMPED PLANS—
Gas Piping Inspection - Residential Passed 6/23/2020 6/23/2020 06/23/2020
Gas Service Inspection - Residential Failed 6/23/2020 6/23/2020 06/23/2020
Miscellaneous Correction
Corrective Action Required
06/23/2020
-NO PRESSURE GAUGE FOUND AT TIME OF INSPECTION
Electrical Service Inspection Failed 6/23/2020 6/23/2020 06/23/2020
Miscellaneous Correction
Corrective Action Required
06/23/2020
-NO PLANS ON SITE-CITY STAMPED PLANS REQUIRED
Gas Service Inspection - Residential Failed 6/24/2020 6/24/2020 06/24/2020
Miscellaneous Correction
Corrective Action Required
06/23/2020
-NO PRESSURE GAUGE FOUND AT TIME OF RE-INSPECTION
Electrical Service Inspection Passed 6/24/2020 6/24/2020 06/24/2020
Miscellaneous Correction
Resolved
06/24/2020
-NO PLANS ON SITE-CITY STAMPED PLANS REQUIRED
All Rough Inspection - Residential Failed 6/24/2020 6/24/2020 06/24/2020
Miscellaneous Correction
Corrective Action Required
06/23/2020
-MAINTAIN GRAVEL FILTER AND SILT FENCE -TIGHTEN ALL ANCHOR BOLTS IN GARAGE -ANCHOR BOLTS SHALL BE IN MIDDLE THIRD OF PLATE IN GARAGE -FIRE STOP BEAM WEBS IN WALLS -NAIL ALL CORNER AND WALL INTERSECTIONS PER CODE -LAUNDRY ROOM RECEPTACLES TO ONLY SERVE LAUNDRY ROOM PER E3703.1 -FIRE STOP CHIMNEY -NAIL SHEATHING IN WEST BEDROOM -NAIL SHEATHING IN UPSTAIRS BEDROOM -NAIL SHEATHING PER PLANS THROUGHOUT EXTERIOR -PROVIDE MISSING SNOW BLOCKING IN UPSTAIRS BEDROOM FOUR -FIRE STOP DEAD SPACES AND BEAM WEBS AT STAIRS -PROVIDE INSULATION AND BLOCKING ABOVE WALL AT CANTILEVERS -PROVIDE JOIST HANGERS ON JOISTS OVER 4’ IN BASEMENT CANTILEVER -SUPPORT NORTH CORNER OF BOTTOM STAIR LANDING -FIRE STOP DUCT CHASE BY STAIR -PROVIDE HEADER FOR CUT JOIST OVER RANGE -SUPPORT BEAM IN NORTHEAST SIDE AT BEAM POCKET -PROVIDE ATTIC ACCESS FOR SPACE ABOVE BREAKFAST AREA AND OWNERS CLOSET AREA -MISSING DOUBLE 2X6 IN UTILITY ROOM -MISSING 2 DOUBLE DOUBLE 2X4 IN UTILITY ROOM -MISSING 2 TRIPLE 2X6 BY WINDOW IN GATHERING ROOM -MISSING DOUBLE 2X8 IN OWNERS CLOSET -MISSING DOUBLE 2X4 IN OWNERS CLOSET -MISSING DOUBLE 2X8 IN OFFICE -MISSING DOUBLE 2X4 IN BEDROOM 5 -MISSING DOUBLE 2X4 IN CLOSET OFF BEDROOM 5 -NAIL JOIST LAP CONNECTIONS IN LOFT HALLWAY -INSTALL STRINGER CONNECTIONS AND THRUST BLOCKS PER PLANS ON STAIRS -NO PRESSURE GAUGE ON GAS FOR INSPECTION-PLEASE PROVIDE FOR RE-INSPECTION
All Rough Inspection - Residential Failed 7/1/2020 7/1/2020 07/01/2020
Miscellaneous Correction
Corrective Action Required
06/24/2020
*DO NOT SHEET ROCK** -MAINTAIN GRAVEL FILTER AND SILT FENCE -FIRE STOP CHIMNEY -NAIL SHEATHING PER PLANS THROUGHOUT EXTERIOR -PROVIDE BLOCKING ABOVE WALL AT CANTILEVERS -INSTALL STRINGER CONNECTIONS AND THRUST BLOCKS PER PLANS ON STAIRS
Gas Service Inspection - Residential Passed 7/1/2020 7/1/2020 07/01/2020
Miscellaneous Correction
Resolved
07/01/2020
-NO PRESSURE GAUGE FOUND AT TIME OF RE-INSPECTION
All Rough Inspection - Residential Passed 7/6/2020 7/6/2020 07/06/2020
Miscellaneous Correction
Informational
07/06/2020
-MAINTAIN GRAVEL FILTER AND SILT FENCE
Sidewalk Inspection Passed 8/11/2020 (P.M.) 8/11/2020 08/12/2020
Misc
Informational
08/12/2020
On Tuesday, 8-11-2020. I performed a field inspection of the sidewalk to be installed and found the subgrade and forming to meet city standard and passed inspection of walk for concrete to be poured. Note: The existing ADA corner that was being tied into where new sidewalk tied-in was installed crooked to the street and forced the contractor to tie-in to the existing corner. Not the prettiest alignment for (10) feet.
Erosion Control Inspection Residential Passed 09/29/2020
Misc
Resolved
09/29/2020
-deficient erosions control installation, shall be in compliance within two days. No further inspections until complete -Street cleanup required immediately. No further inspection until complete -Remove trash from site -Remove overgrown weeds and vegetation -Provide building address
Occupancy Inspection - Codes Residential Failed 10/15/2020 10/15/2020 10/15/2020
Misc
Corrective Action Required
10/15/2020
-irrigation permit required -Drive approach inspection still pending -As graded plot plan required for review -suspended stoop inspection still pending -seal all exterior penetrations -Identify dedicated circuits in garage and basement as non-GFCI protected
Driveway Inspection Passed 8/11/2020 (P.M.) 8/11/2020 11/02/2020
Misc
Informational
11/02/2020
On 8-12-2020, a driveway inspection was conducted and passed inspection.
Erosion Control Inspection Residential Passed 04/08/2021
Misc
Resolved
04/08/2021
-deficient erosions control installation, shall be in compliance within two days. No further inspections until complete -Street cleanup required immediately. No further inspection until complete -Remove trash from site -Remove overgrown weeds and vegetation -Provide building address
Occupancy Inspection - Codes Residential Temporary C of O 4/8/2021 4/8/2021 04/08/2021
Misc
Corrective Action Required
10/15/2020
-As graded plot plan required for review/approval
Plot Plan Inspection Passed 4/13/2021 04/13/2021
Occupancy Inspection - Codes Residential Full C of O 5/10/2021 5/10/2021 05/10/2021
Misc
Resolved
05/10/2021
-As graded plot plan required for review/approval
Documents & Images
Date Uploaded File Type Document Name
12/26/2019 Letter Codes Residential Plan Review
01/03/2020 Letter Codes Residential Plan Review
01/10/2020 Receipt Receipt for transaction: 2020-000130
01/10/2020 Letter DS Building Permit
01/10/2020 Plot Plan DOC011020
01/31/2020 Letter INSPECTION SUMMARY
04/13/2020 Letter INSPECTION SUMMARY
05/19/2020 Letter INSPECTION SUMMARY
05/29/2020 Letter INSPECTION SUMMARY
06/02/2020 Letter INSPECTION SUMMARY
06/02/2020 Letter INSPECTION SUMMARY
06/05/2020 Letter INSPECTION SUMMARY
06/05/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter INSPECTION SUMMARY
07/01/2020 Letter INSPECTION SUMMARY
07/01/2020 Letter INSPECTION SUMMARY
07/06/2020 Letter INSPECTION SUMMARY
09/16/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
09/29/2020 Letter INSPECTION SUMMARY
10/15/2020 Letter INSPECTION SUMMARY
03/22/2021 Letter INSPECTION SUMMARY
03/22/2021 Letter Codes 140 Day Letter
03/22/2021 Letter Codes 140 Day Letter
03/24/2021 200141-AsBuiltApprovalLetter-Lot 35
04/08/2021 Letter INSPECTION SUMMARY
04/08/2021 Letter Codes Temporary Certificate of Occupancy
04/08/2021 signed as built grading lot 25
04/12/2021 Plot Plan Approved As Graded Plot Plan
04/13/2021 Letter INSPECTION SUMMARY
05/10/2021 Letter Codes Final Certificate of Occupancy
05/10/2021 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home