Permit Application Status

PRCOM20246426


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20246426
Building Permit - Commercial
Issued
CHOYCE LLC
NEW COMMERCIAL
K + R WHOLESALE - NEW WAREHOUSE WITH OFFICE
12/17/2024
03/03/2025
07/26/2025
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
kevin higdon, Address:po box 847  
PRAIRIE CENTER PLUMBING HEATING & A/C, Address:242 N MARION, Phone:(913) 829-6263  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Olsson Engineering, Address:1301 Burlington, Suite 100, Phone:(816) 361-1177  
MD2 DESIGNS, Address:2307 NW OUTER BELT RD, Phone:(816) 372-4384  
CHOYCE LLC, Address:PO BOX 847  
Reviews
Review Type Outcome Est. Completion Date Completed
Special Inspections Review Approved 03/03/2025
Joe Frogge
Building Plan Review Approved with Conditions 03/05/2025 03/03/2025
Joe Frogge
Final Development Plan
Resolved
03/03/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 1/22/2025 - Not addressed. 3/3/2025 - Acknowledged in letter.
License Tax - Payment
Corrective Action Required
02/26/2025

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $4,44.00 1/22/2025 - Not addressed. 3/3/2025 - Acknowledged in letter.
IBC 1704.2 Special Inspections
Resolved
03/03/2025

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 1/22/2025 - Not addressed.
Miscellaneous Correction
Resolved
03/03/2025

Inadequate information to complete review. Provide the following: - - - - -
Engineered truss package
Resolved
03/03/2025

Copies of the pre-engineered metal building package (PEMB) were not provided at the time of permit application. Action required: Provide PEMB package or request deferral. 1/22/2025 - Not addressed.
Gen - Plan submittal documents
Resolved
03/03/2025

**Note added on 1/22/2025** Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted digitally with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: All plans must be sealed/signed by architect or engineer.
Licensed Contractors Approved 03/05/2025 03/03/2025
Joe Frogge
Fire Plan Review Approved with Conditions 03/05/2025 03/03/2025
Joe Frogge
Construction documents for fire alarm systems
Corrective Action Required
02/28/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarm system.
Construction documents - Fire protection systems
Corrective Action Required
02/28/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Misc
Resolved
03/03/2025

2018 IFC 1008.3.1 & 3.2 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate all of the following: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or mor means of egress. 2. Corridors, interior exit stairways and ramps and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than their levels of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. Provide exterior emergency lighting at all marked exits.
Alarm Plan Review Released for Construction 02/21/2025 02/21/2025
Craig Hill
Alarms connected to automatic sprinkler system
Corrective Action Required
02/21/2025

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system.
Alarm testing.
Corrective Action Required
02/21/2025

2018 IFC 904.4.2- Alarm testing. Notification appliances, connections to fire alarm systems, and connections to approved supervising stations shall be tested in accordance with this section and Section 907 to verify proper operation. Information Only: Call 816-969-1300 to schedule alarm testing, 24 hours in advance. Coordinate with sprinkler testing.
Fire Plan Review Approved 01/27/2025 01/27/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
01/17/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Corrective Action Required
01/17/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Final Development Plan Review Approved 01/24/2025 01/24/2025
Daniel Fernandez
Building Plan Review Rejected 01/27/2025 01/22/2025
Joe Frogge
Final Development Plan
Corrective Action Required
01/17/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 1/22/2025 - Not addressed.
License Tax - Payment
Corrective Action Required
01/17/2025

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $4,44.00 1/22/2025 - Not addressed.
IBC 1704.2 Special Inspections
Corrective Action Required
01/17/2025

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections. 1/22/2025 - Not addressed.
Code analysis required
Resolved
01/22/2025

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update Code Notes on cover sheet to show that building is fully sprinklered.
Miscellaneous Correction
Corrective Action Required
01/17/2025

Inadequate information to complete review. Provide the following: - Complete construction details for mezzanine. (floor, decking, guard rail, stair geometry, etc.) 1/22/2025 - Incomplete - Details show joists show both wood joists and bar joists, neither of which are sized. How is guard rail attached? - Complete HVAC design. (furnace spec, outside air calcs, duct sizes, combustion air/vent, RR exhaust, etc.) 1/22/2025 - Incomplete - - -
Engineered truss package
Corrective Action Required
01/17/2025

Copies of the pre-engineered metal building package (PEMB) were not provided at the time of permit application. Action required: Provide PEMB package or request deferral. 1/22/2025 - Not addressed.
IBC 1010.1.6 Landings at doors
Resolved
01/22/2025

2018 IBC 1010.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Landings required at all exit doors including door on north side of building.
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
01/22/2025

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior sides of exterior doors. Re: front door.
NEC Article 210.8 (B) Other than dwelling units GFCI
Resolved
01/22/2025

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
IBC 1109.11 Seating at tables, counters and work surfaces - accessibility
Resolved
01/22/2025

2018 IBC 1109.11 Seating at tables, counters and work surfaces. Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible. (see code for exception) Action required: Amend designs to show that breakroom counter top is no taller than 34"
IPC 305.4 Freezing - protection of potable water
Resolved
01/22/2025

Protection of Potable Water System 2018 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Provide method of heating room/space where water enters building.
Gen - Plan submittal documents
Corrective Action Required
01/22/2025

**Note added on 1/22/2025** Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted digitally with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: All plans must be sealed/signed by architect or engineer.
Licensed Contractors Approved 01/27/2025 01/22/2025
Joe Frogge
Fire Plan Review Rejected 01/03/2025 01/03/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
01/02/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Construction documents - Fire protection systems
Corrective Action Required
01/02/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Misc
Corrective Action Required
01/02/2025

1008.1 Means of egress illumination. Illumination shall be provided in the means of egress in accordance with Section 1008.2. Under emergency power, means of egress illumination shall comply with Section 1008.3 Action required: Provide emergency exterior illumination at all doors exiting the building.
Miscellaneous Correction
Corrective Action Required
01/02/2025

Provide occupant load for the mezzanine.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
01/02/2025

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Provide location of fire extinguishers.
Building Plan Review Rejected 01/03/2025 12/30/2024
Joe Frogge
Final Development Plan
Corrective Action Required
12/30/2024

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
License Tax - Payment
Corrective Action Required
12/30/2024

A one-time impact fee in the form of a license tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $4,44.00
IBC 1704.2 Special Inspections
Corrective Action Required
12/30/2024

2018 IBC 1704.2 Special inspections. Where application is made for construction as described in this section, the owner or the registered design professional in responsible charge acting as the owner’s agent shall employ one or more approved agencies to perform inspections during construction on the types of work listed under Section 1705. These inspections are in addition to the inspections identified in Lee’s Summit Code of Ordinances Chapter 7. (see code section for exceptions) Action required: Provide statement of special inspections / letter of responsibility from company contracted to perform special inspections.
Code analysis required
Corrective Action Required
12/30/2024

A code analysis shall be provided which includes but is not limited to occupancy type, occupant load, construction type, actual area, height and floors, allowable area, height and floors, and the codes to which the project is designed. Action required: Update Code Notes on cover sheet to show that building is fully sprinklered.
Miscellaneous Correction
Corrective Action Required
12/30/2024

Inadequate information to complete review. Provide the following: - Complete construction details for mezzanine. (floor, decking, guard rail, stair geometry, etc.) - Complete HVAC design. (furnace spec, outside air calcs, duct sizes, combustion air/vent, etc.) - Coordinate utilities with Civil plans. - Specify water/sewer entry locations. - Racking heights (if greater than 12' additional provisions will apply)
Engineered truss package
Corrective Action Required
12/30/2024

Copies of the pre-engineered metal building package (PEMB) were not provided at the time of permit application. Action required: Provide PEMB package or request deferral.
IBC 1010.1.6 Landings at doors
Corrective Action Required
12/30/2024

2018 IBC 1010.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Landings required at all exit doors including door on north side of building.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
12/30/2024

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior sides of exterior doors. Re: front door.
NEC Article 210.8 (B) Other than dwelling units GFCI
Corrective Action Required
12/30/2024

2017 NEC Article 210.8 (B) Other Than Dwelling Units. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in the locations specified in 210.8(B)(1) through (10) shall have ground-fault circuit-interrupter protection for personnel. (1) Bathrooms (2) Kitchens (3) Rooftops (4) Outdoors (5) Sinks - where receptacles are installed within 6 feet of the outside edge of the sink. (6) Indoor wet locations (7) Locker rooms with associated showering facilities (8) Garages, service bays, and similar areas other than vehicle exhibition halls and showrooms. (9) Crawl spaces – at or below grade level. (10) Unfinished portions or areas of the basement not intended as habitable rooms. (refer to code for exceptions) Action required: Modify drawings to show that all receptacles within 6' of a sink will by GFCI protected.
IBC 1109.11 Seating at tables, counters and work surfaces - accessibility
Corrective Action Required
12/30/2024

2018 IBC 1109.11 Seating at tables, counters and work surfaces. Where seating or standing space at fixed or built-in tables, counters or work surfaces is provided in accessible spaces, at least 5 percent of the seating and standing spaces, but not less than one, shall be accessible. (see code for exception) Action required: Amend designs to show that breakroom counter top is no taller than 34"
IPC 305.4 Freezing - protection of potable water
Corrective Action Required
12/30/2024

Protection of Potable Water System 2018 IPC 305.4 Freezing. Water, soil, and waste pipes shall not be installed outside of a building, in attics or crawl spaces, concealed in outside walls, or in any other place subjected to freezing temperatures unless adequate provision is made to protect such pipes from freezing by insulation or heat or both. Exterior water supply system piping shall be installed not less than 6” below the frost line (42” below grade) and not less than 12 inches below grade. Action required: Provide method of heating room/space where water enters building.
Licensed Contractors Approved 12/17/2024 12/17/2024
Joe Frogge
Sprinkler Plan Review Pending
Craig Hill
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Commercial $3,520.00 $3,520.00 Paid 03/03/2025
7232302-Industrial/Warehouse License Tax Fee $4,444.00 $4,444.00 Paid 03/03/2025
91100C8-Sanitary Sewer Insp Fees $41.72 $41.72 Paid 01/24/2025
91100C9-Water Insp Fee $409.09 $409.09 Paid 01/24/2025
9110068-Storm Fee $1,042.60 $1,042.60 Paid 01/24/2025
9110081-Street Inspections $4,042.61 $4,042.61 Paid 01/24/2025
9110071-Site Grading Fee $860.40 $860.40 Paid 01/24/2025
8331401-Water Tap Fee $10,595.00 $10,595.00 Paid 01/24/2025
8350015-Water Meter Fee $1,066.76 $1,066.76 Paid 01/24/2025
8331507-Sanitary Sewer Development Fee $6,101.00 $6,101.00 Paid 01/24/2025
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 01/24/2025
9110072-Water Test Fee $200.00 $200.00 Paid 01/24/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Piers/Caissons Inspection - Commercial Pending
Footing Inspection - Commercial Pending
Underslab Plumbing Inspection - Commercial Pending
Water Service Inspection Pending
Electrical Service Inspection Pending
Gas Service Inspection - Commercial Pending
In-wall Inspection Pending
Above Ceiling Inspection Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Pending
Erosion Control Inspection Residential Partial 3/11/2025 3/11/2025 03/11/2025
Misc
Informational
03/11/2025
3-11-25 BR Silt fence is up but needs to add gutter buddies to storm boxes.
Documents & Images
Date Uploaded File Type Document Name
12/17/2024 Letter License Tax Bill
12/17/2024 Application Form Application form
12/17/2024 Engineer Report/Study Newberry Landing Geotech Report
12/17/2024 Plans Construction plans
12/17/2024 Plans structural plans
01/03/2025 Letter DS P/R Corrections Document
01/16/2025 Plans 1460 se broadway plans COM-5095 (HIGDON) 1-13-2025
01/24/2025 Receipt Receipt for transaction:2025-000464
01/27/2025 Letter DS P/R Corrections Document
02/07/2025 AFP_FA_1460_SE_BROADWAY_PE_STAMPED
02/07/2025 AFP_FA_EQUIPMENT_1460_SE_BROADWAY
02/21/2025 AFP_FA_1460_SE_BROADWAY_PE_STAMPED_RFC
02/21/2025 Letter Fire (Alarm) Plan Review Notice
01/27/2025 Approved Plans Stamped FDP Approved Plans_PL2024223
02/26/2025 Letter Response letter
02/26/2025 Plans COM-5095 (HIGDON-2) 2-18-2025 - REO CERT
02/26/2025 Engineer Report/Study CONSTRUCTION Calculations Package Rev 0
02/26/2025 Plans PEMB
03/03/2025 Engineer Report/Study SI letter
03/03/2025 Approved Plans Approved construction plans
03/03/2025 Engineer Report/Study 24-025448-01_FOR CONSTRUCTION Calculations Package Rev 0c
03/03/2025 Plans 24-025448-01 ENH Drawings
03/03/2025 Receipt Receipt for transaction:2025-001257
03/03/2025 Approved Plans Approved PEMB drawings
03/03/2025 Letter DS Building Permit
03/11/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home