Summary
PRCOM20230107
Building Permit - Commercial
Certificate of Occupancy
GOLF PARK L P
NEW COMMERCIAL
GOLF RANCH - DRIVING RANGE AMENITY BUILDING CONSTRUCTED WITH STORAGE CONTAINERS
01/10/2023
08/21/2023
11/26/2023
02/06/2024
Locations
Contacts
GOLF PARK L P, Address:12122 MELROSE  
BLUE JEANS GOLF LLC, Address:3333 LEE PKWY, SUITE 460, Phone:(530) 520-0238  
MAPP, LLC, Address:344 Third Street  
Aaron's Heat & AirConditioning, Address:5712 Duval St., Phone:(512) 467-2349  
THREE DIAMOND ELECTRIC LLC, Address:27606 E PINK HILL RD, Phone:(816) 228-5470  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
HARRISON FRENCH AND ASSOCIATES, Address:1705 SOUTH WALSON BLVD STE 3, Phone:(479) 273-7780  
Joe Vogel - MAPP LLC, Address:3625 N Hall St. Suite 1400, Phone:(214) 213-4475  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 06/13/2023 08/08/2023
Joe Frogge
LC - MEP Subs
Resolved
08/08/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/26/23 - Is EC still Three Diamond? (we use company names, not license numbers) Also, we still need an HVAC contractor. 6/12/23 - Comment stands. HVAC contractor required.
Building Plan Review Approved 06/13/2023 07/07/2023
Joe Frogge
Health Dept Inspection
Corrective Action Required
06/06/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 5/26/23 - acknowledged in letter
IBC 1015.4 Opening limitations
Resolved
06/12/2023

2018 IBC 1015.4 Opening limitations. Required guards shall not have openings that allow passage of a sphere 4 inches (102 mm) in diameter from the walking surface to the required guard height. Exceptions: 1. From a height of 36 inches (914 mm) to 42 inches (1067 mm), guards shall not have openings that allow passage of a sphere 4-3/8 inches (111 mm) in diameter. 2. The triangular openings at the open sides of a stair, formed by the riser, tread and bottom rail shall not allow passage of a sphere 6 inches (152 mm) in diameter. 3. At elevated walking surfaces for access to and use of electrical, mechanical or plumbing systems or equipment, guards shall not have openings that allow passage of a sphere 21 inches (533 mm) in diameter. 4. In areas that are not open to the public within occupancies in Group I-3, F, H or S, and for alternating tread devices and ship ladders, guards shall not have openings which allow passage of a sphere 21 inches (533 mm) in diameter. 5. In assembly seating areas, guards required at the end of aisles in accordance with 1029.17.4 shall not have openings that allow passage of a sphere 4 inches in diameter (102 mm) up to a height of 26 inches (660 mm). From a height of 26 inches (660 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, guards shall not have openings that allow passage of a sphere 8 inches (203 mm) in diameter. 6. Within individual dwelling units and sleeping units in Group R-2 and R-3 occupancies, guards on the open sides of stairs shall not have openings which allow passage of a sphere 4-3/8 (111 mm) inches in diameter. Action required: 4" maximum opening applies to stair risers as well. Modify design. (currently 4.71") 5/26/23 - Note mentioned in response letter not found. Detail 4 on sheet A101.2 still shows 6.71" risers with 1" flanges at steps which leaves 4.71"
Misc
Resolved
06/12/2023

Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. Action required: Amend designs to demonstrate compliance with minimum R values. 5/26/23: - Ceiling/roof info not provided. - Clarify use of fire rated partition. (if used, a complete UL detail including nail/screw patterns will be required.
Planning - Screening of rooftop equipment
Resolved
07/07/2023

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings to locate condensing units and provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO sections. 5/26/23 - screening locations shown but construction details not found. Also, coordinate directly with Planning Department for approval of screening. Contact: Hector Soto - Hector.Soto@CityofLS.net - 816.969.1600
Zoning Review Approved 07/12/2023 07/07/2023
Joe Frogge
Fire Plan Review Approved with Conditions 06/13/2023 06/12/2023
Joe Frogge
Misc
Informational
06/06/2023

Comments 1 -8 are for the main building and site. Item 9 is for the driving area. Permit approved per conditions for the driving area only.
Installation acceptance testing
Informational
06/06/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Portable fire extinguishers - general
Corrective Action Required
06/06/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Action Required: Provide ABC type extinguishers. Only class A are shown.
Fire Plan Review Approved with Conditions 05/30/2023 05/29/2023
Jim Eden
Misc
Informational
05/29/2023

Comments 1 -8 are for the main building and site. Item 9 is for the driving area. Permit approved per conditions for the driving area only.
Portable fire extinguishers - general
Corrective Action Required
05/29/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required- Action Required: Provide ABC type extinguishers. Only class A are shown.
Portable fire extinguishers for commercial cooking equipment.
Resolved
05/29/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Provide ABC type extinguishers. Only class A are shown.
Installation acceptance testing
Informational
05/29/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Miscellaneous Correction
Resolved
05/29/2023

Clarify what Existing Hardware is for the doors. All spaces shall have doors openable from the inside.
Miscellaneous Correction
Resolved
05/29/2023

Place the ext signs/ emer. lighting over the man door (101).
Miscellaneous Correction
Resolved
05/29/2023

Provide a man door on the stacked storage unit.
Miscellaneous Correction
Resolved
05/29/2023

Correct the building construction type on the Code Analysis to IIB.
Building Plan Review Rejected 05/30/2023 05/26/2023
Joe Frogge
Health Dept Inspection
Corrective Action Required
05/22/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 5/26/23 - acknowledged in letter
IBC 1015.4 Opening limitations
Corrective Action Required
05/22/2023

2018 IBC 1015.4 Opening limitations. Required guards shall not have openings that allow passage of a sphere 4 inches (102 mm) in diameter from the walking surface to the required guard height. Exceptions: 1. From a height of 36 inches (914 mm) to 42 inches (1067 mm), guards shall not have openings that allow passage of a sphere 4-3/8 inches (111 mm) in diameter. 2. The triangular openings at the open sides of a stair, formed by the riser, tread and bottom rail shall not allow passage of a sphere 6 inches (152 mm) in diameter. 3. At elevated walking surfaces for access to and use of electrical, mechanical or plumbing systems or equipment, guards shall not have openings that allow passage of a sphere 21 inches (533 mm) in diameter. 4. In areas that are not open to the public within occupancies in Group I-3, F, H or S, and for alternating tread devices and ship ladders, guards shall not have openings which allow passage of a sphere 21 inches (533 mm) in diameter. 5. In assembly seating areas, guards required at the end of aisles in accordance with 1029.17.4 shall not have openings that allow passage of a sphere 4 inches in diameter (102 mm) up to a height of 26 inches (660 mm). From a height of 26 inches (660 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, guards shall not have openings that allow passage of a sphere 8 inches (203 mm) in diameter. 6. Within individual dwelling units and sleeping units in Group R-2 and R-3 occupancies, guards on the open sides of stairs shall not have openings which allow passage of a sphere 4-3/8 (111 mm) inches in diameter. Action required: 4" maximum opening applies to stair risers as well. Modify design. (currently 4.71") 5/26/23 - Note mentioned in response letter not found. Detail 4 on sheet A101.2 still shows 6.71" risers with 1" flanges at steps which leaves 4.71"
IMC 506.5.3 Grease fan mounting hinge
Resolved
05/26/2023

2018 IMC 506.5.3 Exhaust fan mounting. Up-blast fans serving Type I hoods and installed in a vertical or horizontal position shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning and shall be equipped with a means of restraint to limit the swing of the fan on its hinge. The ductwork shall extend not less than 18 inches above the roof surface. Action required: Provided hinges at grease duct fans for cleaning.
IMC 506.3.13.3 Grease fan termination location
Resolved
05/26/2023

2018 IMC 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet horizontally from or not less than 3 feet above air intake openings into any buildings. (see code for exception) Action required: Relocate grease fans to comply. They appear to be installed next to screening wall.
Misc
Corrective Action Required
05/22/2023

Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. Action required: Amend designs to demonstrate compliance with minimum R values. 5/26/23: - Ceiling/roof info not provided. - Clarify use of fire rated partition. (if used, a complete UL detail including nail/screw patterns will be required.
Planning - Screening of rooftop equipment
Corrective Action Required
05/22/2023

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings to locate condensing units and provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO sections. 5/26/23 - screening locations shown but construction details not found. Also, coordinate directly with Planning Department for approval of screening. Contact: Hector Soto - Hector.Soto@CityofLS.net - 816.969.1600
Licensed Contractors Rejected 05/30/2023 05/26/2023
Joe Frogge
LC - MEP Subs
Corrective Action Required
05/22/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 5/26/23 - Is EC still Three Diamond? (we use company names, not license numbers) Also, we still need an HVAC contractor.
Fire Plan Review Rejected 04/18/2023 04/17/2023
Jim Eden
Misc
Corrective Action Required
04/11/2023

Comments 1 -8 are for the main building and site. Item 9 is for the driving area. Permit approved per conditions for the driving arae only.
Type I hood - Where required
Resolved
04/17/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Provide hood and fire suppression specifications.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/11/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Show class K extinguisher in kitchen. Provide ABC type extinguishers. Only class A are shown.
Installation acceptance testing
Corrective Action Required
04/11/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Illumination required
Resolved
04/17/2023

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show exterior illumination.
Misc
Resolved
04/17/2023

Per IFC definitions, this is not a U occupancy group. The main structure shall be classified as a B occupancy.
Miscellaneous Correction
Corrective Action Required
04/11/2023

Clarify what Existing Hardware is for the doors. All spaces shall have doors openable from the inside.
Locks on gates or barriers
Resolved
04/17/2023

2018 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- A Knox padlock shall be provided on the gate to the facility.
Portable fire extinguishers - general
Corrective Action Required
04/11/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required for the driving area- Provide ABC Type fire extinguishers along the driving area where travel distance would not exceed 75'.
Address numbers required
Resolved
04/17/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Verified at inspection
Miscellaneous Correction
Corrective Action Required
04/17/2023

Place the ext signs/ emer. lighting over the man door (101).
Miscellaneous Correction
Corrective Action Required
04/17/2023

Provide a man door on the stacked storage unit.
Miscellaneous Correction
Corrective Action Required
04/17/2023

Correct the building construction type on the Code Analysis to IIB.
Final Development Plan Review Approved 03/08/2023 04/17/2023
Joe Frogge
Building Plan Review Rejected 04/18/2023 04/13/2023
Joe Frogge
Final Development Plan
Resolved
04/17/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 4/5/23 - acknoledged in letter
Health Dept Inspection
Corrective Action Required
04/13/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 1015.4 Opening limitations
Corrective Action Required
04/13/2023

2018 IBC 1015.4 Opening limitations. Required guards shall not have openings that allow passage of a sphere 4 inches (102 mm) in diameter from the walking surface to the required guard height. Exceptions: 1. From a height of 36 inches (914 mm) to 42 inches (1067 mm), guards shall not have openings that allow passage of a sphere 4-3/8 inches (111 mm) in diameter. 2. The triangular openings at the open sides of a stair, formed by the riser, tread and bottom rail shall not allow passage of a sphere 6 inches (152 mm) in diameter. 3. At elevated walking surfaces for access to and use of electrical, mechanical or plumbing systems or equipment, guards shall not have openings that allow passage of a sphere 21 inches (533 mm) in diameter. 4. In areas that are not open to the public within occupancies in Group I-3, F, H or S, and for alternating tread devices and ship ladders, guards shall not have openings which allow passage of a sphere 21 inches (533 mm) in diameter. 5. In assembly seating areas, guards required at the end of aisles in accordance with 1029.17.4 shall not have openings that allow passage of a sphere 4 inches in diameter (102 mm) up to a height of 26 inches (660 mm). From a height of 26 inches (660 mm) to 42 inches (1067 mm) above the adjacent walking surfaces, guards shall not have openings that allow passage of a sphere 8 inches (203 mm) in diameter. 6. Within individual dwelling units and sleeping units in Group R-2 and R-3 occupancies, guards on the open sides of stairs shall not have openings which allow passage of a sphere 4-3/8 (111 mm) inches in diameter. Action required: 4" maximum opening applies to stair risers as well. Modify design. (currently 4.71")
IMC 506.5.3 Grease fan mounting hinge
Corrective Action Required
04/13/2023

2018 IMC 506.5.3 Exhaust fan mounting. Up-blast fans serving Type I hoods and installed in a vertical or horizontal position shall be hinged and supplied with a flexible weatherproof electrical cable to permit inspection and cleaning and shall be equipped with a means of restraint to limit the swing of the fan on its hinge. The ductwork shall extend not less than 18 inches above the roof surface. Action required: Provided hinges at grease duct fans for cleaning.
IMC 506.3.13.3 Grease fan termination location
Corrective Action Required
04/13/2023

2018 IMC 506.3.13.3 Termination location. Exhaust outlets shall be located not less than 10 feet horizontally from parts of the same or contiguous buildings, adjacent buildings and adjacent property lines and shall be located not less than 10 feet above the adjoining grade level. Exhaust outlets shall be located not less than 10 feet horizontally from or not less than 3 feet above air intake openings into any buildings. (see code for exception) Action required: Relocate grease fans to comply. They appear to be installed next to screening wall.
Misc
Corrective Action Required
04/13/2023

Sec. 7-803. - Non-residential occupancies. The minimum required R-value for each element of the building thermal envelope shall be in accordance with the following: Exception: The Building Official may approve a decreased R-Value for building exterior walls provided the space is normally not occupied by employees and is associated with storage/warehouse or manufacturing. A. Wall assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 11. This requirement does not apply to doors, windows or other openings or approved penetrations nor does it apply to unfinished basement concrete walls. B. Floor assemblies forming portions of a building envelope shall meet or exceed an R factor rating of 19. Exception: Concrete floors in contact with the earth need not be insulated. C. Roof assemblies forming portions of a building envelope shall meet or exceed an R factor 19. Action required: Amend designs to demonstrate compliance with minimum R values.
Planning - Screening of rooftop equipment
Corrective Action Required
04/13/2023

Unified Development Ordinance Article 8, Section 8.180.E Roof mounted equipment – All roof-mounted equipment shall be screened entirely from view by using parapet walls at the same height as the mechanical units. For additions to existing buildings that do not meet this standard, individual screens will be permitted, with the design subject to approval by the Director. Unified Development Ordinance Article 8, Section 8.180.F Ground mounted equipment – Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required: Make needed corrections to drawings to locate condensing units and provide details as to how mechanical equipment will be screened from all 4 sides per referenced UDO sections.
Licensed Contractors Rejected 04/18/2023 04/13/2023
Joe Frogge
LC - MEP Subs
Corrective Action Required
04/11/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Licensed Contractors Rejected 04/05/2023 04/07/2023
Joe Frogge
LC - General Contractor
Resolved
04/07/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
03/29/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Building Plan Review Approved with Conditions 04/05/2023 04/07/2023
Joe Frogge
Final Development Plan
Corrective Action Required
03/29/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational. 4/5/23 - acknoledged in letter
Project cost
Resolved
03/30/2023

The project cost, which is used to establish the permit fee, has not been provided. Action required: Project cost breakdown between amenity building, and driving bay structure. You can remove site costs as they will be covered under the FDP and site permit.
Misc
Resolved
04/05/2023

Show panel locations on plans so we can verify main source of disconnect and grouping requirements.
Gen - Plan submittal documents
Resolved
04/05/2023

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Architectural drawings 1 thru 9 need to be updated with correct city in address and must be sealed/signed by MO state architect or engineer.
Fire Plan Review Approved with Conditions 04/05/2023 04/02/2023
Jim Eden
Misc
Corrective Action Required
03/29/2023

Comments 1 -8 are for the main building and site. Item 9 is for the driving area. Permit approved per conditions for the driving arae only.
Type I hood - Where required
Corrective Action Required
03/29/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Hood required in kitchen if producing grease laden vapors. Provide kitchen plans.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
03/29/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Show class K extinguisher in kitchen. Provide ABC type extinguishers. Only class A are shown.
Installation acceptance testing
Corrective Action Required
03/29/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Illumination required
Corrective Action Required
03/29/2023

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show exterior illumination.
Misc
Corrective Action Required
03/29/2023

Per IFC definitions, this is not a U occupancy group. The main structure shall be classified as a B occupancy.
Miscellaneous Correction
Corrective Action Required
03/29/2023

Clarify what Existing Hardware is for the doors. All spaces shall have doors openable from the inside.
Locks on gates or barriers
Corrective Action Required
03/29/2023

2018 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- A Knox padlock shall be provided on the gate to the facility.
Portable fire extinguishers - general
Corrective Action Required
03/29/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required for the driving area- Provide ABC Type fire extinguishers along the driving area where travel distance would not exceed 75'.
Address numbers required
Corrective Action Required
03/29/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Verified at inspection
Fire Plan Review Approved with Conditions 03/14/2023 03/15/2023
Jim Eden
Misc
Corrective Action Required
02/09/2023

Comments 1 -8 are for the main building and site. Item 9 is for the driving area. Permit approved per conditions for the driving arae only.
Address numbers required
Corrective Action Required
02/09/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Verified at inspection
Type I hood - Where required
Corrective Action Required
02/09/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Hood required in kitchen if producing grease laden vapors. Provide kitchen plans.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
02/09/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Show class K extinguisher in kitchen. Provide ABC type extinguishers. Only class A are shown.
Installation acceptance testing
Corrective Action Required
02/09/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Illumination required
Corrective Action Required
02/09/2023

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show exterior illumination.
Misc
Corrective Action Required
02/09/2023

Per IFC definitions, this is not a U occupancy group. The main structure shall be classified as a B occupancy.
Miscellaneous Correction
Corrective Action Required
02/09/2023

Clarify what Existing Hardware is for the doors. All spaces shall have doors openable from the inside.
Locks on gates or barriers
Corrective Action Required
02/09/2023

2018 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- A Knox padlock shall be provided on the gate to the facility.
Portable fire extinguishers - general
Corrective Action Required
03/15/2023

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required for the driving area- Provide ABC Type fire extinguishers along the driving area where travel distance would not exceed 75'.
Building Plan Review Rejected 03/14/2023 03/09/2023
Joe Frogge
Final Development Plan
Corrective Action Required
02/09/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Project cost
Corrective Action Required
03/09/2023

The project cost, which is used to establish the permit fee, has not been provided. Action required: Project cost breakdown between amenity building, and driving bay structure. You can remove site costs as they will be covered under the FDP and site permit.
Misc
Corrective Action Required
03/09/2023

Show panel locations on plans so we can verify main source of disconnect and grouping requirements.
Gen - Plan submittal documents
Corrective Action Required
03/09/2023

Lee's Summit Code Of Ordinances 7-137. - Submittal Documents. Construction documents, special inspection and structural observation programs, and other data shall be submitted in two (2) or more sets with each application for a permit. A registered design professional licensed by the State of Missouri shall prepare the construction documents. Where special conditions exist, the Building Official is authorized to require additional construction documents to be prepared by a registered design professional licensed by the State of Missouri. Action required: Architectural drawings 1 thru 9 need to be updated with correct city in address and must be sealed/signed by MO state architect or engineer.
Licensed Contractors Rejected 01/25/2023 03/09/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
03/09/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
03/09/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Health Department Review Approved 03/02/2023
Joe Frogge
Building Plan Review Rejected 01/25/2023 02/21/2023
Joe Frogge
Final Development Plan
Corrective Action Required
01/19/2023

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
Project cost
Corrective Action Required
01/19/2023

The project cost, which is used to establish the permit fee, has not been provided. Action required: Project cost breakdown between amenity building, and driving bay structure. You can remove site costs as they will be covered under the FDP and site permit.
Misc
Corrective Action Required
01/19/2023

Demolition permit will be required for pool and pool house. Action required: Comment is informational. Pool must be removed in its entirety. The only foreign material that can be buried is concrete rubble.
Health Dept Review
Resolved
03/09/2023

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 847-7070. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
01/19/2023

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 847-7070. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 1010.1.6 Landings at doors
Corrective Action Required
01/19/2023

2018 IBC 1010.1.6 Landings at doors. Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the fully open position shall not reduce a required dimension by more than 7 inches. Where a landing serves an occupant load of 50 or more, doors in any position shall not reduce the landing to less than one-half its required width. Landings shall have a length measured in the direction of travel of not less than 44 inches. Exception: Landing length in the direction of travel in Groups R-3 and U and within individual units of Group R-2 need not exceed 36 inches. Action required: Provide landings at exterior side of doors.
IPC 403.1 Minimum number of fixtures
Corrective Action Required
01/19/2023

2018 IPC 403.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number shown in Table 403.1, based on the actual use of the building or space. Uses not shown in Table 403.1 shall be considered individually by the code official. The number of occupants shall be determined by the International Building Code. Action required: Provide service/mop sink, drinking fountains and additional female water closets (9 req.) and lavatories (3 req.) per schedule.
Miscellaneous Correction
Corrective Action Required
01/19/2023

Inadequate information to complete review. Provide the following: - Foundation/structural plans for amenity center and driving bay covers - Wall/ceiling construction details (alternate construction types still need review) - Method and R values of insulation - Complete kitchen designs - Complete MEP designs - Roof drainage plan. - Canopy plans. (is space between structures covered?) - Site lighting plan that includes light pole base detail
IBC 1011.11 Handrails - handrails at stairways
Corrective Action Required
01/19/2023

2018 IBC 1011.11 Handrails. Flights of stairways shall have handrails on each side and shall comply with Section 1014. Where glass is used to provide the handrail, the handrail shall also comply with Section 2407. (see code for exceptions) Action required: Handrails required on both sides of stair
NEC Article 250.50 Grounding electrode system
Corrective Action Required
01/19/2023

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide ground to concrete-encased electrode in foundations.
Fire Plan Review Rejected 01/25/2023 01/25/2023
Ben Hicks
Address numbers required
Corrective Action Required
01/25/2023

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action Required: Verified at inspection
Type I hood - Where required
Corrective Action Required
01/25/2023

2018 IFC 609.2- Where required. A Type I hood shall be installed at or above all commercial cooking appliances and domestic cooking appliances used for commercial purposes that produce grease vapors. Action Required: Hood required in kitchen if producing grease laden vapors. Provide kitchen plans.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
01/25/2023

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action Required: Show class K extinguisher in kitchen. Provide ABC type extinguishers. Only class A are shown.
Installation acceptance testing
Corrective Action Required
01/25/2023

2018 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action Required: Call 816-969-1300 to schedule kitchen hood testing
Illumination required
Corrective Action Required
01/25/2023

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. Action Required: Show exterior illumination.
Misc
Corrective Action Required
01/27/2023

Per IFC definitions, this is not a U occupancy group. The main structure shall be classified as a B occupancy.
Miscellaneous Correction
Corrective Action Required
01/27/2023

Clarify what Existing Hardware is for the doors. All spaces shall have doors openable from the inside.
Locks on gates or barriers
Corrective Action Required
01/27/2023

2018 IFC 506.1.1-Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required- A Knox padlock shall be provided on the gate to the facility.
Licensed Contractors Rejected 01/25/2023 01/19/2023
Joe Frogge
LC - General Contractor
Corrective Action Required
01/19/2023

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and an email address & phone number for the on-site contact which is where inspection reports will be sent.
LC - MEP Subs
Corrective Action Required
01/19/2023

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Commercial $1,440.00 $1,440.00 Paid 08/08/2023
$0.00
Commercial Excise Tax Fee $41,250.00 $41,250.00 Paid 04/17/2023
$41,250.00
Temporary Occupancy Fee $50.00 $50.00 Paid 01/11/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Failed 8/31/2023 8/31/2023 08/31/2023
Misc
Corrective Action Required
08/31/2023
Provide approved plan on site and access to underfloor space
Underslab Plumbing Inspection - Commercial Failed 9/1/2023 9/1/2023 09/01/2023
Misc
Corrective Action Required
08/31/2023
-Min 12” cover of underground DVW pipes is required -Support pipe at maximum four ft interval -Provide 4” building drain as shown on plan. Submit revised as-built drawing of plumbing -Inspection of the sewer pipe to the grease trap is required
Electrical Service Inspection Passed 9/19/2023 9/19/2023 09/19/2023
Misc
Informational
09/19/2023
600 amp service approved for release
Underslab Plumbing Inspection - Commercial Failed 12/6/2023 12/6/2023 12/06/2023
Misc
Corrective Action Required
09/01/2023
-Min 12” cover of underground DVW pipes is required -Support pipe at maximum four ft interval -Provide 4” building drain as shown on plan. Submit revised as-built drawing of plumbing -Inspection of the sewer pipe to the grease trap is required **12/6/23-The crawspace walkway is now narrowed , making impossible for the inspector to inspect the plumbing. Verification of the plumbing compliance shall be provided.
Alternate Protection Systems Inspection Passed 12/7/2023 12/07/2023
Occupancy Inspection - Engineering Temporary C of O 12/14/2023 12/14/2023 12/14/2023
Misc
Informational
12/14/2023
12-14-23 RH. Punchlist Structure is in place and sidewalk is poured. Vegetation is all that is needed and contractor has sod on site.
Occupancy Inspection - Planning Failed 12/14/2023 12/14/2023 12/14/2023
Corrective Action Required
12/14/2023
Landscaping (sod) was on site but remains to be installed. All ground cover must be installed or the area must be seeded before a CO or TCO can be issued.
Corrective Action Required
12/14/2023
The ADA parking stall signs were not installed. ADA sings must be installed at the head of each ADA parking stall.
Corrective Action Required
12/14/2023
The accessible ADA path from the parking lot was blocked by an ADA parking stall. There were 7 ADA stalls at the time of my inspection, as the parking lot contains 135 stalls only 6 ADA stalls are required. I spoke with the GC and he stated he will stripe off the stall blocking the path to keep it clear.
Occupancy Inspection - Codes Commercial Failed 12/14/2023 12/14/2023 12/14/2023
Misc
Corrective Action Required
12/14/2023
-Approval required from: Fire, Planning, Field Engineer, Water, and Jackson County Health -Verification of plumbing -Engineer approval of foundation and tie down of structures -Check location of sewer clean outs -Underground electrical raceway to signage shall be min 18” below grade -Label all breaker slot with numbers corresponding to the breaker schedule -Max stair riser height shall be no more than 3/8” (bottom stair riser height) -Openings between stair treads shall be no more than 4” -Provide landing at bottom of stair -Provide 42” guardrail at stair and handrail on both sides of stair -Secure rooftop AC disconnect and j-boxes -NM cables not allowed in outdoor raceway -Provide max 15 amp breakers for all AC units -Paint and protect all exposed steel -Secure all LFNC wiring within 12” of enclosures; secure ENT within 3 ft of all enclosures -Anchor all buildings into foundation -Working clearance in front of electrical equipment shall be min 4 ft per table 110.34(A), condition 2 -Close all panel open slots -Provide lighting inside electrical equipment room -Secure all LFNC raceways within 12” of service enclosure -All receptacle outlets in kitchen must be gfci per 210.8(B). 3-phase receptacles rated 100 amps or less -Complete electrical under remote blue metal structure
Occupancy Inspection - Fire Passed 12/14/2023 12/14/2023 12/15/2023
Water Service Inspection Passed 12/21/2023 12/21/2023
Misc
Informational
12/21/2023
12-21-23 NS Site Visited and the water was already installed from the last building that was on the golf range.
Occupancy Inspection - Engineering Passed 1/9/2024 1/9/2024 01/09/2024
Misc
Informational
12/14/2023
12-14-23 RH. Punchlist Structure is in place and sidewalk is poured. Vegetation is all that is needed and contractor has sod on site. 1-9-24 NS Site visited and everything on the punch list has been complete besides the sidewalk and the contractor said he is going to seal the hair line cracks in the sidewalk. Passed
Occupancy Inspection - Planning Passed 1/9/2024 1/9/2024 01/09/2024
Underslab Plumbing Inspection - Commercial Passed 01/09/2024
Misc
Resolved
12/14/2023
-Min 12” cover of underground DVW pipes is required -Support pipe at maximum four ft interval -Provide 4” building drain as shown on plan. Submit revised as-built drawing of plumbing -Inspection of the sewer pipe to the grease trap is required **12/6/23-The crawspace walkway is now narrowed , making impossible for the inspector to inspect the plumbing. Verification of the plumbing compliance shall be provided.
Footing Inspection - Commercial Passed 01/09/2024
Informational
01/09/2024
FOUNDATION APPROVED BY ENGINEER
Occupancy Inspection - Codes Commercial Ready for Temp CO 1/9/2024 1/9/2024 01/09/2024
Misc
Corrective Action Required
12/14/2023
-Underground electrical raceway to signage shall be min 18” below grade **Need to verify burial depth of raceway -Max stair riser height shall be no more than 3/8” (bottom stair riser height) **Raise the bottom stair landing to the same level as the bottom tread to eliminate the 2" difference in elevation between bottom tread and landing. Landing depth to be min the width of the stair -Provide 42” guardrail at stair and handrail on both sides of stair **Return handrails to wall, guard, or landing
Occupancy Inspection - Codes Commercial Failed 1/30/2024 1/30/2024 01/30/2024
Misc
Corrective Action Required
01/09/2024
-Underground electrical raceway to signage shall be min 18” below grade **Need to verify burial depth of raceway
Occupancy Inspection - Codes Commercial Full C of O 2/6/2024 02/06/2024
Misc
Resolved
02/06/2024
-Underground electrical raceway to signage shall be min 18” below grade **Need to verify burial depth of raceway
Documents & Images
Date Uploaded File Type Document Name
01/11/2023 Application Form APPLICATION
01/11/2023 Plans 2022-12-30_DD-Set_FamilyGolfPark-MO
01/27/2023 Letter Fire Building Plan Review
03/02/2023 Letter Jackson Cty approval
03/03/2023 Plans 2023-03-02_Permit-Set_BJG-KC
03/15/2023 Letter DS P/R Corrections Document
03/31/2023 Letter 2023-03-28_FGP-Response-Letter_BJG-Lees-Summit_ARCH_TeeLine
03/31/2023 Plans 2023-03-28_FGPTeeLinePermit
04/07/2023 Approved Plans approved - driving bays
04/11/2023 Plans Shipping Container Drawings - Signed and Sealed - 4_10_2023
04/17/2023 Letter Fire Building Plan Review
04/19/2023 Letter DS P/R Corrections Document
05/21/2023 Plans Container Drawings - Permit Set- 05_19_2023
05/21/2023 Letter City of Lee's Summit, MO - Response Letter - 05_19_23
05/30/2023 Letter DS P/R Corrections Document
06/05/2023 Letter 2023-06-01_BJG-Response-Letter_BJG-Lees-Summit-MO
06/05/2023 Plans 2023-06-01_Permit-Revisions_BJG-Lees-Summit-MO
07/05/2023 Plans 2023-05-12_FGPContainerPermitRevs_ARCH
07/05/2023 Letter 2023-06-01_BJG-Response-Letter_BJG-Lees-Summit-MO
07/05/2023 Drawing A101_2 FLOOR PLAN-24x36
07/05/2023 Drawing A212_1 INTERIOR AND EXTERIOR DETAILS-24x36
07/05/2023 Plans 2023-06-01_Permit-Revisions_BJG-Lees-Summit-MO
07/07/2023 Approved Plans Approved - amenity building plans
08/08/2023 Letter License Tax Bill
08/08/2023 Receipt Receipt for transaction:2023-006141
08/21/2023 Letter DS Building Permit
08/31/2023 Letter INSPECTION SUMMARY
09/01/2023 Letter INSPECTION SUMMARY
09/19/2023 Letter INSPECTION SUMMARY
09/19/2023 Letter Fire Building Plan Review
09/19/2023 Letter DS P/R Corrections Document
09/19/2023 Letter Fire Building Plan Review
09/19/2023 Letter Fire Building Plan Review
09/19/2023 Letter Fire Building Plan Review
09/19/2023 Letter Fire Building Plan Review
12/06/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter Fire Building Plan Review
12/14/2023 Letter Fire Building Plan Review
12/14/2023 Letter INSPECTION SUMMARY
01/09/2024 Letter Fire Building Plan Review
01/09/2024 Letter INSPECTION SUMMARY
01/09/2024 Letter INSPECTION SUMMARY
01/09/2024 Letter INSPECTION SUMMARY
01/09/2024 Engineer Report/Study Blue Jeans Golf (Golf Ranch) Foundation Discrepancy Response Letter 1-3-2024
01/09/2024 Jackson County Environmental Health
01/09/2024 Letter INSPECTION SUMMARY
01/09/2024 Letter INSPECTION SUMMARY
01/11/2024 Certificate/License Codes Temporary Certificate of Occupancy
01/11/2024 Receipt Receipt for transaction:2024-000194
01/30/2024 Letter INSPECTION SUMMARY
02/06/2024 Letter Codes Final Certificate of Occupancy
02/06/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.