Permit Application Status

PRCOM20214290


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20214290
Building Permit - Commercial
Certificate of Occupancy
ORTHO KING PROPERTIES LLC
CHANGE OF TENANT
TENANT FINISH FOR ORTHODONTIST CLINIC
08/17/2021
12/13/2021
08/16/2022
11/29/2022
Locations
Contacts
DEV INC, Address:8807 MONROVIA ST, Phone:(913) 322-8882  
jason@dev-inc.com, Address:jason@dev-inc.com  
F & G MECHANICAL SERVICES INC, Address:17219 BEL RAY PLACE, Phone:(816) 322-0810  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
MAGNUM PLUMBING LLC, Address:1100 S WINTERBROOKE DR., Phone:(913) 461-8645  
DEV INC, Address:8807 MONROVIA ST, Phone:(913) 322-8882  
ORTHO KING PROPERTIES LLC, Address:721 NE LAKEWOOD BLVD  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 04/05/2022 04/01/2022
Jim Eden
Hazardous material identification
Corrective Action Required
03/29/2022

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for the x-ray area.
Address numbers required
Corrective Action Required
03/29/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Building Plan Review Approved 04/05/2022 03/29/2022
Joe Frogge
ICC A117.1 404.2.5 Two Doors or gates in series
Resolved
03/29/2022

ICC A117.1 404.2.5 - Two doors or gates in series. Distance between two hinged or pivoted doors or gates in series shall be 48 inches minimum plus the width of any door or gate swinging into the space. The space between the doors and gates shall provide a turning space. Action required: Modify Vestibule 100 to comply.
Licensed Contractors Approved 04/05/2022 03/29/2022
Joe Frogge
Fire Plan Review Approved with Conditions 09/22/2021 02/16/2022
Ben Hicks
Hazardous material identification
Corrective Action Required
02/09/2022

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for the x-ray area.
Address numbers required
Corrective Action Required
02/09/2022

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Building Plan Review Rejected 09/22/2021 02/10/2022
Joe Frogge
ICC A117.1 404.2.5 Two Doors or gates in series
Corrective Action Required
02/10/2022

ICC A117.1 404.2.5 - Two doors or gates in series. Distance between two hinged or pivoted doors or gates in series shall be 48 inches minimum plus the width of any door or gate swinging into the space. The space between the doors and gates shall provide a turning space. Action required: Modify Vestibule 100 to comply.
Licensed Contractors Approved 09/08/2021 11/17/2021
Joe Frogge
LC - MEP Subs
Resolved
11/17/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Magnum not currently licensed.) 9/7/21 - acknowledged in letter
Building Plan Review Approved 09/15/2021 09/08/2021
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Resolved
09/08/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Minimum 18" required at latch side of door #112 between Hall and Waiting. 9/7/21 - Door #112 still not compliant.
Fire Plan Review Approved with Conditions 09/15/2021 09/08/2021
Joe Frogge
Hazardous material identification
Corrective Action Required
09/08/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for the x-ray area.
Address numbers required
Corrective Action Required
09/08/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Building Plan Review Rejected 09/14/2021 09/07/2021
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
09/07/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Minimum 18" required at latch side of door #112 between Hall and Waiting. 9/7/21 - Door #112 still not compliant.
IBC 1606.2 Design dead load - structural
Resolved
09/07/2021

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment being replaced or provide engineer’s report to verify that existing roof structure will support additional load. 9/7/21 - new unit is lighter, per architect.
IPC 608.1 Backflow
Resolved
09/07/2021

2018 IPC 608.17.9 Dental pumping equipment. The water supply connection to each dental pumping equipment system, the water supply system shall be protected against backflow in accordance with Section 608.14.1, 608.14.2, 608.14.5, 608.14.6 or 608.14.8. Action required: Modify designs to demonstrate how water supply is protected from backflow as well as showing how cross contamination is avoided at chairs.
IBC 1013.1 Where required - exit sign
Resolved
09/07/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign at front double doors.
IBC 1008.3 Emergency power for illumination - at exit discharge
Resolved
09/07/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Licensed Contractors Rejected 09/14/2021 09/07/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
09/07/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Magnum not currently licensed.) 9/7/21 - acknowledged in letter
Fire Plan Review Approved with Conditions 09/14/2021 09/07/2021
Michael Weissenbach
Hazardous material identification
Corrective Action Required
09/07/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for the x-ray area.
Address numbers required
Corrective Action Required
09/07/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Duct smoke detectors
Resolved
09/07/2021

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Provide duct detection for all RTU's over 2000 CFM.
Illumination required
Resolved
09/07/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exits.
Building Plan Review Rejected 08/27/2021 08/24/2021
Joe Frogge
ICC A117.1 404.2.3.2 Swinging Doors Maneuvering Clearance
Corrective Action Required
08/24/2021

ICC A117.1 Section 404.2.3.2 Swinging Doors and gates. Swinging doors and gates shall have maneuvering clearances complying with Table 404.2.3.2. Action required: Minimum 18" required at latch side of door #112 between Hall and Waiting.
IBC 1606.2 Design dead load - structural
Corrective Action Required
08/24/2021

"2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide verification that either the weight of new roof top equipment is less than or equal to original equipment being replaced or provide engineer’s report to verify that existing roof structure will support additional load."
IPC 608.1 Backflow
Corrective Action Required
08/24/2021

2018 IPC 608.17.9 Dental pumping equipment. The water supply connection to each dental pumping equipment system, the water supply system shall be protected against backflow in accordance with Section 608.14.1, 608.14.2, 608.14.5, 608.14.6 or 608.14.8. Action required: Modify designs to demonstrate how water supply is protected from backflow as well as showing how cross contamination is avoided at chairs.
IBC 1013.1 Where required - exit sign
Corrective Action Required
08/24/2021

2018 IBC Exit Signs 1013.1 Where Required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. The path of egress travel to exits and within exits shall be marked by readily visible exit signs to clearly indicate the direction of egress travel in cases where the exit of the path of egress travel is not immediately visible to the occupants. Intervening means of egress doors within exits shall be marked by exit signs. Exit sign placement shall be such that no point in an exit access corridor or exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. (see code section for exceptions) Action required: Provide exit sign at front double doors.
IBC 1008.3 Emergency power for illumination - at exit discharge
Corrective Action Required
08/24/2021

2018 IBC 1008.3 Emergency power for illumination. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. 1008.3.1 General. In the event of power supply failure in rooms and spaces that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Aisles. 2. Corridors. 3. Exit access stairways and ramps. 1008.3.2 Buildings. In the event of power supply failure in buildings that require two or more means of egress, an emergency electrical system shall automatically illuminate all of the following areas: 1. Interior exit access stairways and ramps. 2. Interior and exterior exit stairways and ramps. 3. Exit passageways. 4. Vestibules and areas on the level of discharge used for exit discharge in accordance with Section 1028.1. 5. Exterior landings as required by Section 1010.1.6 for exit doorways that lead directly to the exit discharge. 1008.3.3 Rooms and Spaces. In the event of power supply failure an emergency electrical system shall automatically illuminate all of the following areas: 1. Electrical equipment rooms. 2. Fire command centers. 3. Fire pump rooms. 4. Generator rooms. 5. Public restrooms with an area greater than 300 square feet. Action required: Provide emergency lighting at exterior side of exits.
Fire Plan Review Rejected 08/27/2021 08/23/2021
Michael Weissenbach
Hazardous material identification
Corrective Action Required
08/23/2021

2018 IFC 407.3- Identification. Individual containers of hazardous materials, cartons or packages shall be marked or labeled in accordance with applicable federal regulations. Buildings, rooms and spaces containing hazardous materials shall be identified by hazard warning signs in accordance with Section 5003.5. (Verified At Inspection) Provide labeling for the x-ray area.
Address numbers required
Corrective Action Required
08/23/2021

2018 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). (Verified At Inspection)
Duct smoke detectors
Corrective Action Required
08/23/2021

2018 IFC 907.3.1 Duct smoke detectors. Smoke detectors installed in ducts shall be listed for the air velocity, temperature and humidity present in the duct. Duct smoke detectors shall be connected to the building's fire alarm control unit when a fire alarm system is required by Section 907.2. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location and shall perform the intended fire safety function in accordance with this code and the International Mechanical Code. Duct smoke detectors shall not be used as a substitute for required open area detection. (Action Required) Provide duct detection for all RTU's over 2000 CFM.
Illumination required
Corrective Action Required
08/23/2021

2018 IFC 1008.1 Illumination required. The means of egress, shall be illuminated at all times the building space served by the means of egress is occupied. (Action Required) Provide exterior emergency lighting at the exits.
Licensed Contractors Rejected 08/23/2021
Joe Frogge
LC - MEP Subs
Corrective Action Required
08/24/2021

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. (Magnum not currently licensed.)
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $816.00 $816.00 Paid 11/17/2021
$13,252.50
8331507-Sewer Connection Fee $330.00 $330.00 Paid 11/17/2021
Commercial Excise Tax Fee $4,815.00 $4,815.00 Paid 02/10/2022
$4,815.00
8331507-Sewer Connection Fee $210.00 $210.00 Paid 04/04/2022
$540.00
Temporary Occupancy Fee $50.00 $50.00 Paid 08/01/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 4/12/2022 4/12/2022 04/12/2022
Underslab Plumbing Inspection - Commercial Failed 4/12/2022 4/12/2022 04/12/2022
Misc
Corrective Action Required
04/12/2022
plumbing fitting incompelte. fernco fitting not installed completely secure banding and recall for inspection. (south center near door)
Underslab Plumbing Inspection - Commercial Passed 4/15/2022 04/15/2022
Misc
Resolved
04/15/2022
plumbing fitting incompelte. fernco fitting not installed completely secure banding and recall for inspection. (south center near door)
Electrical Service Inspection Passed 4/15/2022 4/15/2022 04/15/2022
In-wall Inspection Passed 5/13/2022 5/13/2022 05/13/2022
Rated Assembly Inspection Partial 6/16/2022 6/16/2022 06/16/2022
Misc
Corrective Action Required
06/16/2022
-COMPLETE ROCK ON UNFINISHED SIDE -REMOVE WOOD BLOCKING THROUGH PENETRATIONS IN SEPARATION WALL -ADDRESS ALL THROUGH PENETRATIONS AND GAPS -REMOVE J BOX FROM ASSEMBLY AND COMPLETE ASSEMBLY IN 105 -PROVIDE UL DETAIL FROM THROUGH PENETRATIONS AT 4" PVC **OK TO TAPE ROCK TO DROP CEILING LINE
Rated Assembly Inspection Partial 6/23/2022 6/23/2022 06/23/2022
Misc
Corrective Action Required
06/16/2022
-COMPLETE ROCK ON UNFINISHED SIDE -FIRE CAULK ALL THROUGH PENETRATIONS AND GAPS -COMPLETE ASSEMBLY IN 105
Above Ceiling Inspection Partial 7/12/2022 7/12/2022 07/12/2022
Miscellaneous Correction
Corrective Action Required
07/12/2022
-COMPLETE RATED ASSEMBLY AT SEPARATION WALL- SEAL THROUGH PENETRATIONS, PROVIDE FIRE COLLARS AT DWV, PROVIDE STENCLING PER CODE
Rated Assembly Inspection Failed 7/20/2022 7/20/2022 07/20/2022
Misc
Corrective Action Required
06/23/2022
-COMPLETE ROCK ON UNFINISHED SIDE -FIRE CAULK ALL THROUGH PENETRATIONS AND GAPS -COMPLETE ASSEMBLY IN 105 -FIRE COLLARS AT DWV PENETRATION **CORRECT THE ABOVE DEFICIENCIES; COMPLETE FIREWALL TO EXTERIOR WALLS; SCREW FIRE GB TO WALL PLATE; HAVE A CITY-APPROVED SET OF PLAN ON SITE
Above Ceiling Inspection Partial 7/22/2022 7/22/2022 07/22/2022
Miscellaneous Correction
Corrective Action Required
07/12/2022
-COMPLETE RATED ASSEMBLY AT SEPARATION WALL- SEAL THROUGH PENETRATIONS, PROVIDE STENCLING PER CODE
Rated Assembly Inspection Partial 7/22/2022 7/22/2022 07/22/2022
Misc
Corrective Action Required
07/20/2022
-COMPLETE ROCK ON UNFINISHED SIDE -FIRE CAULK ALL THROUGH PENETRATIONS AND GAPS -COMPLETE ASSEMBLY IN 105 **CORRECT THE ABOVE DEFICIENCIES; COMPLETE FIREWALL TO EXTERIOR WALLS; SCREW FIRE GB TO WALL PLATE; HAVE A CITY-APPROVED SET OF PLAN ON SITE
Occupancy Inspection - Codes Commercial Failed 7/28/2022 7/28/2022 07/28/2022
Misc
Corrective Action Required
07/28/2022
-Provide address at entry door -Complete rated assembly -Provide hammer arrestors at washer
Occupancy Inspection - Fire Passed 7/28/2022 7/28/2022 07/28/2022
Corrective Action Required
07/28/2022
All life safety was appropriate. Okay to occupy with approval form codes.
Occupancy Inspection - Codes Commercial Failed 7/29/2022 7/29/2022 07/29/2022
Misc
Corrective Action Required
07/28/2022
-Provide address at entry door -Provide hammer arrestors at washer 2 items incomplete. Other items that need to be addressed are the Following: Cut over grown vegetation around building and lot. Remove trash container, porta jon. Seal exterior entry of adjoining space. Install approved handicap parking signage , missing 1 west sign. Address east side of building exterior wall covering, door and penetrations. Remove all trash debris, satellite, trash in drive thru. Verify parking lot lighting is compliant and working. Exterior hose bib is hanging out of wall. Drive thru window has plywood over it. Open hole for dryer vent. West exterior light with open box, between windows and roof. Contact our Planning dept, for screening of RTU and plumbing on roof. Address property maintenance of the parking lot.
Occupancy Inspection - Codes Commercial Ready for Temp CO 8/1/2022 8/1/2022 08/01/2022
Misc
Corrective Action Required
07/29/2022
OK FOR TCO Other items that need to be addressed are the Following: Remove porta jon. Seal exterior penetration at east side Verify parking lot lighting is compliaint and working. Drive thru window has plywood over it. Open hole for vaccum vent. Contact our Planning dept, for screening of RTU and plumbing on roof. Address property maintainence of the parking lot.
Occupancy Inspection - Codes Commercial Temporary C of O 8/1/2022 08/01/2022
Misc
Corrective Action Required
08/01/2022
OK FOR TCO Other items that need to be addressed are the Following: Remove porta jon. Seal exterior penetration at east side Verify parking lot lighting is compliaint and working. Drive thru window has plywood over it. Open hole for vaccum vent. Contact our Planning dept, for screening of RTU and plumbing on roof. Address property maintainence of the parking lot.
Occupancy Inspection - Codes Commercial Full C of O 11/29/2022
Misc
Resolved
11/29/2022
Above Ceiling Inspection Passed 11/29/2022
Miscellaneous Correction
Resolved
11/29/2022
-COMPLETE RATED ASSEMBLY AT SEPARATION WALL- SEAL THROUGH PENETRATIONS, PROVIDE STENCLING PER CODE
Rated Assembly Inspection Passed 11/29/2022
Misc
Resolved
11/29/2022
-COMPLETE ROCK ON UNFINISHED SIDE -FIRE CAULK ALL THROUGH PENETRATIONS AND GAPS -COMPLETE ASSEMBLY IN 105 **CORRECT THE ABOVE DEFICIENCIES; COMPLETE FIREWALL TO EXTERIOR WALLS; SCREW FIRE GB TO WALL PLATE; HAVE A CITY-APPROVED SET OF PLAN ON SITE
Miscellaneous Inspection Passed 11/29/2022 11/29/2022
Documents & Images
Date Uploaded File Type Document Name
08/17/2021 Application Form Permit Application. Lakewood
08/17/2021 Application Form Excise Tax Form
08/17/2021 Email planning approval
08/23/2021 Plans Lakewood-TI Permit-Full Set
08/23/2021 Letter License Tax Bill
08/23/2021 Letter Fire Building Plan Review
08/24/2021 Letter DS P/R Corrections Document
09/07/2021 Letter lw ortho response letter
09/07/2021 Plans lw ortho plan resub
09/07/2021 Letter Fire Building Plan Review
09/07/2021 Letter DS P/R Corrections Document
09/08/2021 Letter Permit Review 02 Response
09/08/2021 Drawing A11-Rev02
09/08/2021 Drawing A20-Rev02
09/08/2021 Plans old - Lakewood-TI Permit-Full Set
11/17/2021 Receipt Receipt for transaction:2021-008813
12/13/2021 Letter DS Building Permit
02/09/2022 Plans Lakewood Combined Rev04
02/16/2022 Letter Fire Building Plan Review
02/17/2022 Letter DS P/R Corrections Document
03/29/2022 Letter Permit Review 03 Response
03/29/2022 Plans Lakewood Combined Rev05
04/04/2022 Receipt Receipt for transaction:2022-001859
04/12/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter INSPECTION SUMMARY
04/15/2022 Letter INSPECTION SUMMARY
04/15/2022 Letter INSPECTION SUMMARY
04/27/2022 Letter Final Plan Review Conditions
04/27/2022 Letter DS Building Permit
05/13/2022 Letter INSPECTION SUMMARY
06/16/2022 Letter INSPECTION SUMMARY
06/23/2022 Letter INSPECTION SUMMARY
07/12/2022 Letter INSPECTION SUMMARY
07/20/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter INSPECTION SUMMARY
07/28/2022 Letter INSPECTION SUMMARY
07/29/2022 Letter INSPECTION SUMMARY
07/29/2022 Letter Fire Loss Reduction Form
08/01/2022 Receipt Receipt for transaction:2022-006285
08/01/2022 Letter Codes Temporary Certificate of Occupancy
11/29/2022 Letter Codes Final Certificate of Occupancy
11/29/2022 Letter Field Certificate of Occupancy
11/29/2022 Letter INSPECTION SUMMARY
11/29/2022 Letter INSPECTION SUMMARY
11/29/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home