Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review
|
Approved with Conditions
|
06/07/2024
|
06/06/2024
|
|
Susan Nelson, P.E.
|
|
DE C&O #01 Eng Plans – FDP/PDP
Corrective Action Required
All required engineering plans and studies, including water lines, sanitary sewers, storm drainage, streets and erosion and sediment control shall be submitted along with the final development plan. All public infrastructure must be substantially complete, prior to the issuance of any certificates of occupancy.
|
|
DE C&O #11 Pavement Thickness
Corrective Action Required
Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $22,043.85
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Planning Review
|
Approved with Conditions
|
06/07/2024
|
06/03/2024
|
|
Hector Soto Jr.
|
|
Corrective Action Required
TRASH ENCLOSURES. The trash enclosure shall be constructed with either a solid steel opaque gate painted to be compatible with the color of the masonry or steel walls and building it is to serve or a steel framed semi-opaque gate with a screen mesh material approved by the Director that provides an appropriate visual barrier.
|
|
|
Building Codes Review
|
No Comments
|
06/10/2024
|
06/03/2024
|
|
Mike Weisenborn
|
|
|
Traffic Review
|
No Comments
|
06/10/2024
|
06/03/2024
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
06/10/2024
|
06/03/2024
|
|
Mike Weisenborn
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Miscellaneous Correction
Corrective Action Required
NW Outerview is NOT a public road.
|
|
|
Engineering Review
|
Corrections
|
05/22/2024
|
05/22/2024
|
|
Susan Nelson, P.E.
|
|
Corrective Action Required
Please add a note that identifies the 1 inch domestic water line material as soft type “K” copper prior to the transition to the 2 inch domestic soft type “K” copper water line.
|
|
Corrective Action Required
Include the following note on any profile sheet applicable: “Contractor shall fill and compact to 95% standard density to a point 18 inches minimum above the top of the pipe prior to excavation for the pipe.” Show and label the limits of the compacted fill placement in the profile view using hatching for clarity. Add a note stating that flowable fill is required around all structures.
|
|
Corrective Action Required
The storm sewer profile for Line 1 shows inlets that have substandard drop based on the design requirements of APWA 5604.5 Inverts and Pipes. Verify the design and revise the profile accordingly to show adequate drop through all inlets. Add the flowlines in and out for all inlets in Storm Line 2.
|
|
Corrective Action Required
Please verify the sidewalk geometry for the ADA facilities, including all slopes. Add widths and lengths to the ramps and sidewalk for clarity. Please remove any sidewalk details on Sheet C7.1 that show winged ramps, etc. as they conflict with the City standard sidewalk details.
|
|
|
Planning Review
|
Approved with Conditions
|
05/22/2024
|
05/16/2024
|
|
Hector Soto Jr.
|
|
Corrective Action Required
TRASH ENCLOSURES. The trash enclosure shall be constructed with either a solid steel opaque gate painted to be compatible with the color of the masonry or steel walls and building it is to serve or a steel framed semi-opaque gate with a screen mesh material approved by the Director that provides an appropriate visual barrier.
|
|
|
Traffic Review
|
No Comments
|
05/22/2024
|
05/15/2024
|
|
Erin Ralovo
|
|
|
Building Codes Review
|
No Comments
|
05/22/2024
|
05/15/2024
|
|
Mike Weisenborn
|
|
|
Fire Review
|
Approved with Conditions
|
05/22/2024
|
05/15/2024
|
|
Mike Weisenborn
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Miscellaneous Correction
Corrective Action Required
NW Outerview is NOT a public road.
|
|
|
Planning Review
|
Corrections
|
04/26/2024
|
04/26/2024
|
|
Hector Soto Jr.
|
|
Corrective Action Required
LOT INFORMATION. Label all the property line dimensions for the future Lot 10E configuration.
|
|
Corrective Action Required
DRIVEWAY. Dimension the width of the driveway connection to NW Outerview Rd and the drive aisle that leads to said driveway at the northwest corner of the proposed parking lot.
|
|
Corrective Action Required
DRIVE-THROUGH FACILITY. With the proliferation of dual-drive ordering capabilities for drive-throughs, what consideration has been given in the drive-through design for the future possible need to accommodate a second queue lane at this facility in the open landscape area between the building and the proposed drive-through lane? Staff recommends relocating the trash enclosure in order to facilitate this need in the future.
|
|
Corrective Action Required
MECHANICAL SCREENING. Dash in the location of the roof-top units (RTUs) on the exterior building elevations (Sheets A301 and A302) to review for screening compliance. City ordinance requires all RTUs to be fully screened from view on all sides via the use of parapets extended to a height at least equal to the heights of the units being screened. Take into account the additional height from the curbs on which the RTUs will sit when designing the parapet wall heights.
|
|
Corrective Action Required
EXTERIOR BUILDING ELEVATIONS. To satisfy the requirement for four-sided architecture, some additional sort of architectural embellishment/feature shall be added to the north elevation in order to break up the flat and generally blank wall plane in order to provide visual interest.
|
|
Corrective Action Required
LANDSCAPE PLAN. 1) Tree planting areas shall be a minimum 10' in width, with no tree located less than 4' from the back of curb. It does not appear that the landscape island at the west end of the double-row of parking meets the minimum 10' width. 2) Add the following landscaping requirement calculations to the landscape plan to check for compliance: 1 street tree for each 30' of street frontage; 1 street shrub for each 20' of street frontage; 1 additional open yard tree for every 5,000 sq. ft. of lot area (minus the building footprint); and 2 additional open yard shrubs for every 5,000 sq. ft. of lot area (minus the building footprint). 3) Additionally, screening to a height of 2.5 feet must be provided along the edge of the parking lot or loading area closest to and parallel to the street. (See Sec. 8.820 for full requirements with screening material options).
|
|
Corrective Action Required
CROSS ACCESS AND CROSS PARKING. Add a note to the plans regarding the cross access and cross parking rights and obligations established via the plat that affect the subject lot.
|
|
Corrective Action Required
TRASH ENCLOSURES. Provide a detail of the proposed trash enclosure. The plans reference to see the architectural plans, but no detail is included in the architectural plans. Each trash enclosure shall be constructed of masonry walls or steel architecturally designed walls with either a solid steel opaque gate painted to be compatible with the color of the masonry or steel walls and building it is to serve or a steel framed semi-opaque gate with a screen mesh material approved by the Director that provides an appropriate visual barrier.
|
|
Corrective Action Required
PARKING LOT BOUNDARY. Temporary asphalt curbing shall be provided along the eastern boundary of the parking lot where it will be extended in the future to connect to the abutting lot at the time said pad site is developed. Revise the plans accordingly. However, staff will coordinate on the need and timing of actually constructing said temporary asphalt curbing depending on the progress and timing of the development of the abutting pad site.
|
|
Corrective Action Required
SIGNS. Signs are reviewed and approved under separate cover via a sign permit application. FYI, this site is subject to the signage standards for the Summit Orchards West development established by the developer and approved by the City Council that limits tenants under 5,000 sq. ft. to one (1) wall sign per facade (but no more than 3); a maximum 4' letter/logo height and allowable sign area not to exceed 10% of the facade on which the signs are mounted. Monument signs are limited to one (1) per lot, 12' maximum height, 72 sq. ft. sign face and 96 sq. ft. overall structure area (inclusive of sign face). Visible signs located interior to the building (i.e. inside the window) are exempted from the sign ordinance and thus don't count toward any sign number limitations.
|
|
|
Engineering Review
|
Corrections
|
04/26/2024
|
04/26/2024
|
|
Susan Nelson, P.E.
|
|
Corrective Action Required
Submit an Engineer's Estimate of Probable Construction Costs.
|
|
Corrective Action Required
Submit the SWPPP and a copy of the MDNR Land Disturbance Permit.
|
|
Corrective Action Required
Please add pipe profiles for the 8-inch secondary storm lines. Add storm (inlet and pipe) calculations to the plans.
|
|
Corrective Action Required
Provide the sizes of the existing water main and sanitary sewer lines. Label the existing manholes with the City naming convention. The west existing manhole is MH 22-149 and the east existing manhole is MH 22-148.
|
|
Corrective Action Required
Show size and specific location of water main connection and water meter (LS 6901 L. Water Meters). The water meter shall be located in the R/W or easement within 1 foot of the R/W or easement line, whichever is farthest. Note on the plans that the building service line connection to the water main is made by a corporation stop.
|
|
Corrective Action Required
Add all City standard details that apply to this project. To include, but not limited to, sidewalks/ramps, curbs, pavement joints, etc.
|
|
Corrective Action Required
Add contours where the new sidewalk will be constructed along Chipman Rd. Show how the existing storm sewer manhole will be handled. Show how the sidewalk will transition to the roadway. What is that linework around that last ramp? Will the existing curb be removed and replaced? Please explain.
|
|
Corrective Action Required
Please verify and note, if necessary, that only ornamental trees and shrubs may be planted within any easements.
|
|
|
Fire Review
|
Approved with Conditions
|
04/26/2024
|
04/25/2024
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
Miscellaneous Correction
Corrective Action Required
NW Outerview is NOT a public road.
|
|
|
Traffic Review
|
Corrections
|
04/26/2024
|
04/24/2024
|
|
Erin Ralovo
|
|
Corrective Action Required
Previous plans showed a dual drive-thru but this one only has one lane.
|
|
Corrective Action Required
It is unlcear what the concrete area to the west of the store will be. Is this just a seating area? Will there be picnic tables or benches in this area?
|
|
|
Building Codes Review
|
No Comments
|
04/26/2024
|
04/19/2024
|
|
Joe Frogge
|
|
|