PL2019193
ADDITION TO LEES SUMMIT SUBARU
Commercial Final Development Plan
Commercial Final Development Plan
Approved
06/03/2019
MCBOB LLC
Locations
Contacts
MCBOB LLC, Address:3200 NW OUTER RD S  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 07/16/2019 07/16/2019
Gene Williams, P.E.
DE Contact Field Eng. Inspector
Corrective Action Required
07/09/2019

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), right of way fee, and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $4,992.46
DE Contact ROW Inspector
Corrective Action Required
07/09/2019

Contact Field Engineering Inspections at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Future Repair Work
Corrective Action Required
07/09/2019

Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
Building Codes Review No Comments 07/16/2019 07/15/2019
Joe Frogge
Traffic Review No Comments 07/16/2019 07/11/2019
Michael Park
Planning Review No Comments 07/16/2019 07/09/2019
Hector Soto Jr.
Fire Review Approved with Conditions 07/16/2019 07/09/2019
Jim Eden
Code Statement
Informational
07/09/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
FDC
Informational
07/09/2019

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Maintain access to FDC.
Engineering Review Approved with Conditions 07/01/2019 07/01/2019
Gene Williams, P.E.
Corrective Action Required
07/01/2019

The number of copies is not sufficient for final distribution. Engineering appears to have only received one (1) incomplete set (perhaps these were insertion sheets?). Please contact the City concerning the number of plan sets that are required prior to final approval.
DE Engineers Estimate
Corrective Action Required
07/01/2019

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), right of way fee, and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $4,992.46
DE Contact Field Eng. Inspector
Corrective Action Required
07/01/2019

Contact Field Engineering Inspections at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Contact ROW Inspector
Corrective Action Required
07/01/2019

Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
DE Future Repair Work
Corrective Action Required
07/01/2019

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
DE C&O #12 Cut & Fill
Corrective Action Required
07/01/2019

Any cut and / or fill operations, which cause public infrastructure to exceed the maximum / minimum depths of cover shall be mitigated by relocating the infrastructure vertically and / or horizontally to meet the specifications contained within the City’s Design and Construction Manual.
Building Codes Review Approved with Conditions 07/01/2019 06/28/2019
Joe Frogge
Traffic Review No Comments 07/01/2019 06/27/2019
Michael Park
Planning Review Corrections 07/01/2019 06/26/2019
Victoria Nelson
Corrective Action Required
06/26/2019

Curb Islands - We understand the need for easier flow. However, it is a requirement within our UDO that the end of each parking bay have curbed islands when adjacent to a travel aisle or driveway. One option we can give you that will allow an easy flow to meet your needs, and will meet the requirements of our UDO, is to install islands with a mountable curb. If you still wish to have no curb and only striped areas, then you will need to get Planning Commission and City Council approval through a preliminary development plan public hearing process in order to request a UDO modification. This process typically takes approximately 3 months and has a $2,130 application fee. Additionally, there is no guarantee of City Council approval.
Fire Review Approved with Conditions 07/01/2019 06/24/2019
Jim Eden
Code Statement
Informational
06/24/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
FDC
Informational
06/24/2019

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Maintain access to FDC.
Engineering Review Corrections 06/17/2019 06/17/2019
Gene Williams, P.E.
Corrective Action Required
06/17/2019

Sheet C1.4: Please change note 2 which references the wrong City. This should read "City of Lee's Summit Development Services Department".
Corrective Action Required
06/17/2019

Sheet C1.4: Where will the trench drain be directed? It appears to daylight to the north. This would appear to have an adverse impact on the property to the north.
Corrective Action Required
06/17/2019

Is there any increase in the amount of impervious area? If so, how much is the increase? Are exceptions warranted to detention based on the Design and Construction Manual?
Planning Review Corrections 06/17/2019 06/17/2019
Hector Soto Jr.
Corrective Action Required
06/12/2019

Trash enclosure-Sheet A1.1 says to reference sheet A4.3 for the design of the new trash enclosure, but sheet A4.3 was not submitted. Please submit the missing sheet. Trash enclosure shall meet the design requiremetns of Section 8.180.G of the UDO.
Corrective Action Required
06/12/2019

Lighting plan-will there be new lighting added on to the new construction? If so, please submit the plan along with manufacturing specifications. All lighting must meet the UDO requirements in Article 8.
Corrective Action Required
06/12/2019

Floodplain-Please update and cite the most recent floodplain information.
Corrective Action Required
06/12/2019

ROW-Please label the ROW width along Independence Avenue.
Corrective Action Required
06/12/2019

Sidewalk width-Please label the existing sidewalk width.
Corrective Action Required
06/12/2019

Utility easements-Please label all existing utility easements.
Corrective Action Required
06/12/2019

Parking-Please update all parking count information.
Corrective Action Required
06/12/2019

Oil and gas-Please add a note stating if there are any gas or oil wells present and use and label the MDR website as the source of information.
Corrective Action Required
06/12/2019

Airport form 7460-Please submit form 7460 to the FAA and send us a copy of the feedback for the building permit.
Corrective Action Required
06/12/2019

Landscaping-currently on the northern limits of the parking, you have the areas at the ends of the parking bays striped. Please modify this so that the two corners have curbed landscape islands, as required under Section 8.810.B.
Traffic Review Approved with Conditions 06/17/2019 06/12/2019
Michael Park
Corrective Action Required
06/12/2019

Do these changes/improvements impact truck (semi-tractor trailer and vehicle delivery) circulation on site? So long as truck circulation can be done on-site and shall not require backing from Independence Ave. and loading/unloading activity from Independence Ave. is not allowed; then traffic has no comments on the FDP.
Fire Review Approved with Conditions 06/17/2019 06/12/2019
Mike Weisenborn
Code Statement
Corrective Action Required
06/12/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
FDC
Corrective Action Required
06/12/2019

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Maintain access to FDC.
Building Codes Review Approved with Conditions 06/12/2019
Joe Frogge
Fire Review Approved with Conditions 06/11/2019
Jim Eden
Code Statement
Corrective Action Required
06/11/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
FDC
Corrective Action Required
06/11/2019

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Maintain access to FDC.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 06/03/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
06/03/2019 Receipt Receipt for transaction: 2019-003172
06/03/2019 Letter Routing Sheet - FDP
06/03/2019 Plans 2019-06-03 LS Subaru FDP
06/17/2019 Letter Applicant Letter - FDP (DFDP)
06/24/2019 Letter Resubmittal Routing Sheet - FDP
07/01/2019 FeeWSFDP
07/02/2019 Letter Applicant Letter - FDP (DFDP)
07/09/2019 Letter Resubmittal Routing Sheet - FDP
07/09/2019 Plans 18087C2-C2.2 Spot Elevation Plan
07/09/2019 Plans 18087C4-C4.1 Details
07/09/2019 Plans 18087C4-C4.2 Details
07/09/2019 Plans 18087C4-C4.3 Details
07/09/2019 Plans Applicant Letter - FDP (DFDP)0 response to comments
07/09/2019 Plans LS Subaru FDP Set Rev4
07/09/2019 Plans 18087 A0.0 fdp
07/09/2019 Plans 18087 A1.1
07/09/2019 Plans 18087 A2.1
07/09/2019 Plans 18087 A3.1
07/09/2019 Plans 18087 A4.3
07/09/2019 Plans 18087 L1.1
07/09/2019 Plans 18087C1-C1.0 Cover
07/09/2019 Plans 18087C1-C1.1 Notes
07/09/2019 Plans 18087C1-C1.2 Site Plan
07/09/2019 Plans 18087C1-C1.3 Demoiltion Plan
07/09/2019 Plans 18087C1-C1.4 Utility Plan
07/09/2019 Plans 18087C2-C2.1 Grading & EC Plan
07/16/2019 Letter Applicant Letter - FDP (DFDP)
07/18/2019 Letter FAA letter_411633543
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home