Planning Application Status

PL2018139




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2018139
INTERNATIONAL BUILDERS AND CONSULTANTS, INC (IBC)
Commercial Final Development Plan
Commercial Final Development Plan
Approved
08/07/2018
L & M INVESTMENTS LLC
Locations
Contacts
L & M INVESTMENTS LLC, Address:301 DUCK RD  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
DAVIDSON ARCHITECTURE & ENGINEERING, Address:4301 INDIAN CREEK PKWY, Phone:(913) 451-9390  
Reviews
Review Type Outcome Est. Completion Date Completed
Planning Review No Comments 10/17/2018 10/15/2018
Hector Soto Jr.
Fire Review Approved with Conditions 10/17/2018 10/15/2018
Jim Eden
Code Statement
Informational
10/10/2018

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code.
Hazmat
Informational
10/10/2018

IFC 105.6.20 - A Hazardous materials permit is required for the using, dispensing, transporting, handling, and/or storing of extremely hazardous substances. “Extremely Hazardous Substances (EHS) Facilities” are defined as facilities subject to the provisions of Superfund Amendments and Reauthorization Act of 1986 (SARA TITLE III), Section 302, for storing, dispensing, using, or handling of listed chemicals in excess of their threshold planning quantities (TPQ). See amended Section 5001.4 of the 2012 International Fire Code. Acknowledged and will be completed during building permit review. Fleet fueling shall be in accordance with IFC Chapter 23.
Fire Lanes - Marking
Resolved
10/15/2018

IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. The fire lane shall be posted. verified at permit plan review and inspection.
Engineering Review Approved with Conditions 10/17/2018 10/15/2018
Sue Pyles, P.E.
DE C&O #06 Land Disturbance
Corrective Action Required
10/16/2018

A Land Disturbance Permit shall be obtained from the City if ground breaking will take place prior to the issuance of an infrastructure permit, building permit, or prior to the approval of the Final Development Plan / Engineering Plans.
DE C&O #11 Pavement Thickness
Corrective Action Required
10/16/2018

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
10/16/2018

Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Engineers Estimate
Corrective Action Required
10/16/2018

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $17,814.47
DE Future Repair Work
Corrective Action Required
10/16/2018

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Building Codes Review Approved with Conditions 10/17/2018 10/11/2018
Joe Frogge
Corrective Action Required
10/11/2018

Water meter oversized. Action required: Provide calculations to justify size of water meter. 9/25/18 - acknowledged in letter. To be changed to 1" and will be part of MEP portion of building permit submittal.
Traffic Review No Comments 10/17/2018 10/11/2018
Michael Park
Engineering Review Corrections 09/28/2018 09/28/2018
Sue Pyles, P.E.
Corrective Action Required
09/28/2018

Revise Water Quality orifice size to 4" diameter or alternate method to meet APWA requirements and revise Drainage Impact Study per discussion.
Corrective Action Required
09/28/2018

Engineer's Estimate of Probable Construction Costs comments to be sent under separate cover.
Planning Review Approved with Conditions 09/28/2018 09/27/2018
Hector Soto Jr.
Corrective Action Required
09/27/2018

EXTERIOR MATERIALS. A comment I failed to included in the last set of revisions is for clarification on the type of finish for the metal panels used on the north, east and west elevations. It appears that the panels are a smooth finished product. To meet ordinance requirements, the panels are required to have a rough-textured finish. Please resubmit 3 revised copies of Sheet A3.1 only in response to this comment.
Traffic Review No Comments 09/28/2018 09/25/2018
Michael Park
Building Codes Review Approved with Conditions 09/28/2018 09/25/2018
Joe Frogge
Corrective Action Required
09/25/2018

Water meter oversized. Action required: Provide calculations to justify size of water meter. 9/25/18 - acknowledged in letter. To be changed to 1" and will be part of MEP portion of building permit submittal.
Fire Review Approved with Conditions 09/28/2018 09/25/2018
Jim Eden
Code Statement
Informational
09/25/2018

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code.
Hazmat
Informational
09/25/2018

IFC 105.6.20 - A Hazardous materials permit is required for the using, dispensing, transporting, handling, and/or storing of extremely hazardous substances. “Extremely Hazardous Substances (EHS) Facilities” are defined as facilities subject to the provisions of Superfund Amendments and Reauthorization Act of 1986 (SARA TITLE III), Section 302, for storing, dispensing, using, or handling of listed chemicals in excess of their threshold planning quantities (TPQ). See amended Section 5001.4 of the 2012 International Fire Code. Acknowledged and will be completed during building permit review. Fleet fueling shall be in accordance with IFC Chapter 23.
Fire Lanes - Marking
Corrective Action Required
09/25/2018

IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility. The fire lane shall be posted. verified at permit plan review and inspection.
Planning Review Corrections 08/21/2018 08/21/2018
Hector Soto Jr.
Corrective Action Required
08/21/2018

PROPERTY LINE INFORMATION. The arc length listed on Sheet C1.0 for the southeast property line along NE Independence Ave reads 200.38'. It should be 123.90' per the plat.
Corrective Action Required
08/21/2018

DRIVEWAY/DRIVE AISLE WIDTHS. Revise the driveway and internal parking lot drive aisles so they have a minimum 24' pavement width (excluding curb and gutter).
Corrective Action Required
08/21/2018

PARKING SPACE WIDTHS. Revise the parking spaces at either end of the two parking rows on the south side of the building so they are a minimum 9' wide when measured to the face of the curb, not to the back of the curb.
Corrective Action Required
08/21/2018

RETAINING WALL. For your information, retaining walls having any portion exceeding a height of 4' are required to be engineered. This will be reviewed through the building permit process.
Corrective Action Required
08/21/2018

PARKING LOT SETBACK. Parking lots shall be set back a minimum 6' from all property lines. The proposed parking lot is set back slightly more than 4' from the rear (north) property line.
Corrective Action Required
08/21/2018

PROJECT INFORMATION TABLE. Revise the listed front setback requirement from 20' to 50'. While 20' is the minimum for the zoning district, this property was actually platted with a minimum 50' front setback.
Corrective Action Required
08/21/2018

GRAVEL STORAGE AREA. Please elaborate on the use of the gravel area. Will the area be used for vehicle parking/storage or for material and product storage? If the latter, outdoor storage areas of material and product shall be properly screened from view on all sides by means of a solid, sight-obscuring fence not less than 6' in height. An alternative screening option is a living screen consisting of a chain link supplemented with a double staggered row of 8' evergreen trees planted 30' on center.
Corrective Action Required
08/21/2018

EXTERIOR BUILDING MATERIALS. Please provide more detail on the wood rainscreen that is proposed on the front elevation. Is this a wood composite or an architectural wood product such as Prodema? Regular wood is not an allowed material without going through a public hearing process to gain City Council approval. However, a wood composite or other engineered/architectural wood product can be administratively approved.
Corrective Action Required
08/21/2018

LIGHT FIXTURES. The proposed wall pack fixture does not meet the requirement that it be of a design with full 90-degree cut-offs from vertical so that the light source is not visible.
Corrective Action Required
08/21/2018

MECHANICAL EQUIPMENT. Show the location of all proposed roof- and ground-mounted mechanical equipment on the builidng elevations and/or site plan as appropriate. RTUs shall be fully screened from view using parapet wall equal in height to the units being screened. Ground-mounted units shall be screened by masonry walls or evergreen landscaping equal in height to the units being screened.
Engineering Review Corrections 08/21/2018 08/20/2018
Sue Pyles, P.E.
Corrective Action Required
08/20/2018

Show and label the detention basin throughout the plan set.
Corrective Action Required
08/20/2018

Label the easements throughout the plan set.
Corrective Action Required
08/20/2018

Include detention basin outlet structure information and construction details in the plan set.
Corrective Action Required
08/20/2018

Add the backflow preventor vault standard detail to the plan set.
Corrective Action Required
08/20/2018

Submit the SWPPP.
Corrective Action Required
08/20/2018

Sheet C1.2: • Show the existing 8” water main on the south side of Pavestone Drive. • The existing water main along NE Independence Avenue is 16”, not 8” as shown. Revise accordingly. • Connection to the existing 16” water main is not allowed. Revise the plans to show connection to the existing 8” main across Pavestone Drive. Boring under the street will be required, add the appropriate notes for this requirement. • Relocate the water meter to within 1’ of the easement line per Design and Construction Manual Section 6901.L.1. • Since the building is more than 50’ from the public water main, the backflow prevention device is required to be located in a vault located outside of, but within, 5’ of the utility easement line per Design and Construction Manual Section 6901.I.3. • Adjust the leader lines for Construction Note #10 to point to the light poles.
Corrective Action Required
08/20/2018

Sheet C2.1: • Show and label the 100-year WSE on this sheet and all other plan sheets as applicable. • The 100-year WSE must be a minimum of 20’ from any building or property line. Please label the distance to each.
Corrective Action Required
08/20/2018

Sheet C3.1: • Revise this sheet to match revisions to the Drainage Impact Study. • How will erosion be prevented at the HDPE outlets to the detention basin? Is it the intent to have end sections at these locations? • Show and label the overflow spillway, along with provided freeboard to top of embankment.
Corrective Action Required
08/20/2018

Sheet C3.2: • Show the 100-year HGL in the Profile view.
Corrective Action Required
08/20/2018

Drainage Impact Study: • The City of Lee’s Summit follows the Comprehensive Control strategy for maximum development release rates, as well as 40-hour extended detention of the 90% mean annual event, as shown in APWA 5600 Section 5608.4.C.1. Please revise the study to include these requirements. • A waiver must be requested and approved if any onsite drainage is allowed to flow offsite undetained. Drainage Areas 2 & 3 will require a waiver as designed.
Building Codes Review Corrections 08/21/2018 08/16/2018
Joe Frogge
Corrective Action Required
08/16/2018

Water meter oversized. Action required: Provide calculations to justify size of water meter.
Traffic Review Corrections 08/21/2018 08/16/2018
Michael Park
Corrective Action Required
08/16/2018

Provide required sidewalk along street frontage.
Fire Review Corrections 08/21/2018 08/07/2018
Jim Eden
Code Statement
Informational
08/07/2018

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code.
Hydrants
Corrective Action Required
08/07/2018

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Action required: Hydrants not shown on site and utlity plan. Existing hydarnts will likely exceed the maximum 300' distance.
Hazmat
Corrective Action Required
08/07/2018

IFC 105.6.20 - A Hazardous materials permit is required for the using, dispensing, transporting, handling, and/or storing of extremely hazardous substances. “Extremely Hazardous Substances (EHS) Facilities” are defined as facilities subject to the provisions of Superfund Amendments and Reauthorization Act of 1986 (SARA TITLE III), Section 302, for storing, dispensing, using, or handling of listed chemicals in excess of their threshold planning quantities (TPQ). See amended Section 5001.4 of the 2012 International Fire Code. Action required: Provide details on use of the double walled fuel tank indicated in construction notes on C1.2. A completed Hazardous Materials Permit application shall be completed for review.
Knox Locks
Corrective Action Required
08/07/2018

IFC 506.1 - Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. Action required: A Knox padlock shall be installed on the gate.
Imposed Loads
Corrective Action Required
08/07/2018

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. Action required: Fire access shall carry the weight of a 75,000- pound apparatus.
Fire Lane Required
Corrective Action Required
08/07/2018

IFC 503.1.1 - Approved fire apparatus access roads shall be provided for every facility, building or portion of a building hereafter constructed or moved into or within the jurisdiction. The fire apparatus access road shall comply with the requirements of this section and shall extend to within 150 feet (45 720 mm) of all portions of the facility and all portions of the exterior walls of the first story of the building as measured by an approved route around the exterior of the building or facility. Exception: The fire code official is authorized to increase the dimension of 150 feet (45 720 mm) where: 1. The building is equipped throughout with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3. 2. Fire apparatus access roads cannot be installed because of location on property, topography, waterways, nonnegotiable grades or other similar conditions, and an approved alternative means of fire protection is provided. Action required: A paved fire access shall be provided to meet this requirement. Fire lanes shall be posted and free of obstructions.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 08/07/2018
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
08/07/2018 Letter Routing Sheet - FDP
08/21/2018 Letter Applicant Letter - FDP (DFDP)
08/07/2018 Plans FDP application signed
08/07/2018 Receipt Receipt for transaction: 2018-005512
09/21/2018 Plans 18091C3-C3.2 Storm P&P
09/21/2018 Plans 18091C4-C4.1
09/21/2018 Plans 18091C4-C4.2
09/21/2018 Plans 18091C4-C4.3
09/21/2018 Plans 18091C1-C1.0 Cover
09/21/2018 Plans 18091C1-C1.1 Notes
09/21/2018 Plans 18091C1-C1.2 Site Plan
09/21/2018 Plans 18091 IBC SWPPP
09/21/2018 Plans Engineers estimate rev 1
09/21/2018 Plans '18,09.18 IBC Final Development Plan Response
09/21/2018 Plans IBC FDP Combined Set - rev1 09.21.2018
09/21/2018 Letter Resubmittal Routing Sheet - FDP
10/10/2018 Plans 18091 A2.2
10/10/2018 Plans 18091 A3.1 rev2
10/10/2018 Plans IBC elevations A3.1 color rev2
10/10/2018 Plans 18091 A1.1
10/10/2018 Plans 18091 A2.1
10/10/2018 Plans 18091 L1.1
10/10/2018 Plans IBC Photometric Plan - Premier Lighting
10/10/2018 Plans 18091 IBC FDP rev2 drawing set
10/10/2018 Plans Drainage Impact Study REV 2
10/10/2018 Letter Resubmittal Routing Sheet - FDP
09/21/2018 Plans Civil Set
09/21/2018 Plans 18091C2-C2.1 Grading Plan
09/21/2018 Plans 18091C2-C2.2 Phase l GEC
09/21/2018 Plans 18091C2-C2.3 Phase Il GEC
09/21/2018 Plans 18091C2-C2.4 Phase IIl GEC
09/21/2018 Plans 18091C2-C2.5 Spot Elevation Plan
09/21/2018 Plans 18091C3-C3.1 Drainage Map
09/28/2018 Letter Applicant Letter - FDP (DFDP)
10/15/2018 Activity Document Fees PL2018139 IBC, Inc FDP
10/16/2018 Letter Applicant Letter - FDP (DFDP)
10/17/2018 Activity Document Revised Fees PL2018139 IBC, Inc FDP
03/11/2019 Plans 18091 Rev 2 Set
08/16/2019 Plans 18091L1-1-L1.1
08/16/2019 Letter '19,08.15 IBC landscape change request to rock mulch
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home