Permit Application Status

PRRES20244827


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20244827
Building Permit - Residential
Issued
NEW DUPLEX
NEW DUPLEX - FINISHED AND UNFINISHED BASEMENT - COVERED PORCH - SUSPENDED SLAB STOP WORK ORDER generated on 10/14/2024 12:00 AM by username 'Mitchell Schwarz'. STOP WORK ORDER removed on 10/16/2024 12:00 AM by username 'Kyle Beard'.
09/11/2024
09/24/2024
03/12/2025
Locations
Contacts
ROCK CREEK HOMES, Address:6126 METCALF LANE, Phone:(913) 522-1945  
Kevin Guinan, Address:6126 Metcalf Lane  
KEVIN@ROCKCREEKHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
PRIDE SERVICES INC, Address:3842 GEORGIA TERR, Phone:(785) 242-9700  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Duplex $2,574.57 $2,574.57 Paid 09/24/2024
8331507-Sanitary Sewer Development Fee $4,570.00 $4,570.00 Paid 09/24/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 09/24/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 09/24/2024
8331401-Water Tap Fee $7,946.00 $7,946.00 Paid 09/24/2024
8350015-Water Meter Fee $1,496.06 $1,496.06 Paid 09/24/2024
Outstanding Fees Amount Paid Owing Date Paid
9110080-Not Ready Inspection Fee $75.00 $0.00 $75.00 Not Paid


$75.00    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Suspended Slab Inspection Pending
Erosion Control Inspection Residential Pending
Misc
Informational
03/19/2025
Erosion control in compliance at time of inspection
Driveway Inspection Pending
Misc
Informational
04/21/2025
4-21-25 BR Driveway is formed up with aggregate placed and compacted. Ready for concrete.
Sidewalk Inspection Pending 5/14/2025 5/14/2025
Misc
Informational
05/07/2025
05-07-25 Jamie S, SW is formed, gravel is compacted, and slopes are in compliance with city standards. Approved to pour.
Footing Inspection - Residential Failed 10/10/2024 10/10/2024 10/10/2024
Miscellaneous Correction
Corrective Action Required
10/10/2024
1413 - 2 splices do not have 24 inches of overlap 1413 and 1415 - Demising wall footing plans call for 3 rebar and 24 inches of footing the entire length from east to west. Demising wall footing is not to plans on site -Demising wall footer steel is sitting on dirt and will not properly be encapsulated in concrete to code
Footing Inspection - Residential Failed - Stop Work 10/14/2024 10/14/2024
Miscellaneous Correction
Resolved
10/14/2024
1413 - 2 splices do not have 24 inches of overlap 1413 and 1415 - Demising wall footing plans call for 3 rebar and 24 inches of footing the entire length from east to west. Demising wall footing is not to plans on site -Demising wall footer steel is sitting on dirt and will not properly be encapsulated in concrete to code
Misc
Corrective Action Required
10/14/2024
Footing poured not to plans. No further inspections until addressed
Footing Inspection - Residential Passed 10/16/2024 10/16/2024
Misc
Resolved
10/16/2024
Footing poured not to plans. No further inspections until addressed
Miscellaneous Correction
Informational
10/16/2024
Field verified garage foundation wall is 12 inches thick and the other interior foundation wall is 8 inches thick
Underslab Electrical Inspection - Residential Passed 10/29/2024 10/29/2024 10/29/2024
Misc
Informational
10/29/2024
1413, 1415
Erosion Control Inspection Residential Partial 10/30/2024 10/30/2024
Misc
Informational
10/30/2024
Erosion control in compliance at time of inspection
Underslab Plumbing Inspection - Residential Passed 10/30/2024 10/30/2024 10/30/2024
Informational
10/30/2024
Underslab electrical OK
Sewer Service Inspection - R Partial 10/30/2024 10/30/2024 10/30/2024
Misc
Informational
10/30/2024
1415 ONLY
Water Service Inspection - R Partial 11/12/2024 11/12/2024 11/12/2024
Misc
Corrective Action Required
11/12/2024
Unit 1415 only-OK
Sewer Service Inspection - R Passed 11/12/2024 11/12/2024 11/12/2024
Misc
Resolved
11/12/2024
1415 ONLY
Water Service Inspection - R Partial 11/14/2024 11/14/2024 11/14/2024
Misc
Informational
11/14/2024
Unit 1413 AND 1415
Water Service Inspection - R Passed 11/14/2024 11/14/2024
Misc
Informational
11/14/2024
Unit 1413 AND 1415
Rated Assembly Inspection Failed 2/10/2025 2/10/2025 02/10/2025
Miscellaneous Correction
Corrective Action Required
02/10/2025
1413 - Vertical fasteners are missing in garage 4 feet from west wall - Fastners are missing along rafters in garage/master bedroom - fasteners are not evenly spaced vertically every 8 inches above master bedroom - Fasteners are not evenly spaced every 8 inches on center in basement at demising wall 1415 - Fasteners are missing along the rafters in the garage/master bedroom - vertical fasteners are missing in areas above garage/master bedroom every 8 inches on center Hole - Fasteners are not evenly spaced every 8 inches on center in basement at demising wall
Electrical Service Inspection Passed 2/10/2025 2/10/2025 02/10/2025
Gas Service Inspection - Residential Passed 2/10/2025 2/10/2025 02/10/2025
All Rough Inspection - Residential Failed 2/10/2025 2/10/2025 02/10/2025
Miscellaneous Correction
Corrective Action Required
02/10/2025
1413 Fasten 2x4 garage king stud to entry king stud at the corner every 12 inches on center Garage NW corner anchor bolts need to be installed in the mi1/3 of the bottom plate Address break in ridge 4 feet from the demising wall Protect electrical within 6 feet of attic access hatch Rafter collar ties are not installed above bedroom 2 Nail bedroom 2 SW corner to code LVL in bathroom 2/entry hall calls for 3 stud pack Bathroom 2 vent fan in not fully vented to the exterior Nail kitchen NE corner to code Nail all corners to code Master bath vent fan is not completed Vertically fire block between bedroom 3 and 4 every 10 feet on center 1415 Garage SE corner anchor bolts are not installed Fasten garage to entry kings studs together every 12 inches on center Jack stud at garage overhead door header does not go all the way down to the bottom plate Address break in ridge 4 feet from the demising wall Rafter collar ties are needed above bedroom 2 LVL in bathroom 2/hallway calls for 3 stud pack LIB in master bathroom is not completely nailed off LVL in kitchen/bathroom 2 calls for a 4 pack to be installed One I beam under the garage does not sit the required 3 inches on concrete Install a BOCA plate in bathroom 4 to bathroom 3 for DWV and water line at the top plate
Erosion Control Inspection Residential Partial 2/10/2025 02/10/2025
Misc
Informational
10/30/2024
Erosion control in compliance at time of inspection
Rated Assembly Inspection Failed 2/19/2025 2/19/2025 02/19/2025
Miscellaneous Correction
Informational
02/19/2025
1413 - Floor joist in basement and above ceiling demize wall approved 1415 - Floor joist in basement and above ceiling demize wall approved
Erosion Control Inspection Residential Partial 2/19/2025 02/19/2025
Misc
Informational
02/10/2025
Erosion control in compliance at time of inspection
All Rough Inspection - Residential Failed 2/19/2025 2/19/2025 02/19/2025
Miscellaneous Correction
Corrective Action Required
02/10/2025
1413 Address break in ridge 4 feet from the demising wall 1415 Address break in ridge 4 feet from the demising wall Waiting on engineers letter with approved repairs
All Rough Inspection - Residential Passed 3/4/2025 3/4/2025 03/04/2025
Miscellaneous Correction
Resolved
03/04/2025
1413 Address break in ridge 4 feet from the demising wall 1415 Address break in ridge 4 feet from the demising wall Waiting on engineers letter with approved repairs
Erosion Control Inspection Residential Partial 3/19/2025 03/19/2025
Misc
Informational
02/19/2025
Erosion control in compliance at time of inspection
Rated Assembly Inspection Partial 3/19/2025 3/19/2025 03/19/2025
Miscellaneous Correction
Informational
02/19/2025
Inside master bathrooms, add more screws at bottom. Fire caulk plumbing penetrations before installing cabinets
Rated Assembly Inspection Passed 3/20/2025 3/20/2025 03/20/2025
Miscellaneous Correction
Resolved
03/20/2025
Inside master bathrooms, add more screws at bottom. Fire caulk plumbing penetrations before installing cabinets
Driveway Inspection Partial 4/21/2025 4/21/2025 04/21/2025
Misc
Informational
04/21/2025
4-21-25 BR Driveway is formed up with aggregate placed and compacted. Ready for concrete.
Sidewalk Inspection Not Ready 5/6/2025 5/6/2025 05/06/2025
Sidewalk Inspection Partial 5/7/2025 5/7/2025 05/07/2025
Misc
Informational
05/07/2025
05-07-25 Jamie S, SW is formed, gravel is compacted, and slopes are in compliance with city standards. Approved to pour.
Documents & Images
Date Uploaded File Type Document Name
09/11/2024 Application - Lot 39
09/11/2024 Tax Form - Lot 39
09/13/2024 Permit Codes Residential Plan Review
09/13/2024 Approved Plans APPROVED PLANS
09/18/2024 Plot Plan APPROVED PLOT PLAN
09/18/2024 Permit Codes Residential Plan Review
09/24/2024 Permit DS Building Permit
09/24/2024 Receipt Receipt for transaction: 2024-007868
10/10/2024 Letter INSPECTION SUMMARY
10/10/2024 1413-15 SW Winthrop Ter_PIER INSP_2024-10-09
10/11/2024 1413-15 SW Winthrop Ter_FTG INSP_2024-10-10
10/14/2024 Letter Stop Work Order
10/16/2024 Approved Plans 10-16-24 APPROVED PLANS
10/16/2024 Letter INSPECTION SUMMARY
10/17/2024 1413-15 SW Winthrop Ter_WALL INSP_2024-10-16
10/29/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
11/12/2024 Letter INSPECTION SUMMARY
11/12/2024 Letter INSPECTION SUMMARY
11/14/2024 Letter INSPECTION SUMMARY
11/19/2024 3RD Party Insp Report THIRD PARTY SUSPENDED SLAB INSPECTION REPORT
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/10/2025 Letter INSPECTION SUMMARY
02/19/2025 Letter INSPECTION SUMMARY
02/19/2025 Letter INSPECTION SUMMARY
02/19/2025 Letter INSPECTION SUMMARY
03/03/2025 Engineer Report/Study ENGINEER FRAMING REPORT
03/04/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
03/20/2025 Letter INSPECTION SUMMARY
04/21/2025 Letter INSPECTION SUMMARY
05/06/2025 Letter INSPECTION SUMMARY
05/07/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents