Summary
PRRES20216100
Building Permit - Residential
Certificate of Occupancy
MCFARLAND CUSTOM BUILDERS INC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. COVERED PATIO. SUSPENDED STOOP. STOP WORK ORDER generated on 04/04/2022 12:00 AM by username 'Khanh Nguyen'. STOP WORK ORDER removed on 06/30/2022 12:00 AM by username 'Khanh Nguyen'. STOP WORK ORDER generated on 04/30/2024 12:00 AM by username 'Khanh Nguyen'. STOP WORK ORDER removed on 05/09/2024 12:00 AM by username 'Khanh Nguyen'.
11/23/2021
03/31/2022
09/11/2022
08/09/2024
Locations
Contacts
MCFARLAND CUSTOM BUILDERS, Address:P O BOX 25285, Phone:(816) 215-1660  
MCFARLAND CUSTOM BUILDERS INC, Address:9601 NE BARRY RD STE 130  
Marisa McFarland, Address:suite 130  
MCFARLAND CUSTOM BUILDERS, Address:P O BOX 25285, Phone:(816) 215-1660  
JOE KILOWATT INC, Address:6506 ROYAL, Phone:(816) 792-4888  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
BRENT@MCFARLANDKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $570.00 $570.00 Paid 03/31/2022
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 03/31/2022
8350015-Water Meter Fee $479.24 $479.24 Paid 03/31/2022
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 03/31/2022
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 03/31/2022
9110078-Valuation Fee New Single Family $1,450.31 $1,450.31 Paid 03/31/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 05/09/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 06/10/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 06/10/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 04/01/2022
Miscellaneous Correction
Corrective Action Required
04/01/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
Erosion Control Inspection Residential Failed 4/4/2022 4/4/2022 04/01/2022
Miscellaneous Correction
Corrective Action Required
04/01/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
Erosion Control Inspection Residential Failed - Stop Work 4/4/2022 4/4/2022 04/04/2022
Miscellaneous Correction
Corrective Action Required
04/01/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
04/04/2022
STREET CLEAN UP REQUIRED IMMEDIATELY. THE BUILDER WAS CALLED LAST WEEK 3/31/22 ABOUT THE EROSION CONTROL FAILURE AND SIGNIFICANT AMOUNT OF SILT FLOWING ONTO THE STREET. TODAY (4/4/22), THE EROSION CONTROL HAS NOT BEEN REPAIRED AND STREET HAS NOT BEEN CLEANED UP. PERMIT IS PUT IN STOP-WORK ORDER UNTIL EROSION CONTROL IS IN COMPLIANCE
Erosion Control Inspection Residential Failed 05/02/2022
Miscellaneous Correction
Corrective Action Required
04/04/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
04/04/2022
STREET CLEAN UP REQUIRED IMMEDIATELY. THE BUILDER WAS CALLED LAST WEEK 3/31/22 ABOUT THE EROSION CONTROL FAILURE AND SIGNIFICANT AMOUNT OF SILT FLOWING ONTO THE STREET. TODAY (4/4/22), THE EROSION CONTROL HAS NOT BEEN REPAIRED AND STREET HAS NOT BEEN CLEANED UP. PERMIT IS PUT IN STOP-WORK ORDER UNTIL EROSION CONTROL IS IN COMPLIANCE
Misc
Corrective Action Required
05/02/2022
**5/2-EROSION CONTROL SIGN POSTED. EROSION CONTROL AND STREET CLEANUP SHALL BE COMPLETED WITHIN TWO BUSINESS DAYS. FAILURE TO COMPLY WITH EROSION CONTROL REQUIREMENT WILL RESULT IN AN ISSUANCE OF STOP-WORK ORDER. CONTACT THE BUILDER BY PHONE. HE SAID HE WILL GET THE EROSION CONTROL ISSUE RESOLVED
Miscellaneous Correction
Corrective Action Required
05/02/2022
5-2-22 AN stilt in roadway and storm inlet needs to be cleaned up.
Erosion Control Inspection Residential Failed 5/5/2022 5/5/2022 05/02/2022
Miscellaneous Correction
Corrective Action Required
05/02/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
05/02/2022
STREET CLEAN UP REQUIRED IMMEDIATELY. THE BUILDER WAS CALLED LAST WEEK 3/31/22 ABOUT THE EROSION CONTROL FAILURE AND SIGNIFICANT AMOUNT OF SILT FLOWING ONTO THE STREET. TODAY (4/4/22), THE EROSION CONTROL HAS NOT BEEN REPAIRED AND STREET HAS NOT BEEN CLEANED UP. PERMIT IS PUT IN STOP-WORK ORDER UNTIL EROSION CONTROL IS IN COMPLIANCE
Miscellaneous Correction
Corrective Action Required
05/02/2022
5-2-22 AN stilt in roadway and storm inlet needs to be cleaned up.
Erosion Control Inspection Residential Partial 6/30/2022 6/30/2022 06/30/2022
Miscellaneous Correction
Resolved
06/30/2022
4-1-22 AN silt fence needs to be repaired and silt in road way needs to be cleaned up immediately. This spot alway seems to be a issue.
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
06/30/2022
STREET CLEAN UP REQUIRED IMMEDIATELY. THE BUILDER WAS CALLED LAST WEEK 3/31/22 ABOUT THE EROSION CONTROL FAILURE AND SIGNIFICANT AMOUNT OF SILT FLOWING ONTO THE STREET. TODAY (4/4/22), THE EROSION CONTROL HAS NOT BEEN REPAIRED AND STREET HAS NOT BEEN CLEANED UP. PERMIT IS PUT IN STOP-WORK ORDER UNTIL EROSION CONTROL IS IN COMPLIANCE
Miscellaneous Correction
Corrective Action Required
05/02/2022
MAINTAIN EROSION CONTROL DURING THE CONSTRUCTION PROCESS
Sewer Service Inspection - R Passed 6/30/2022 06/30/2022
Water Service Inspection - R Partial 6/30/2022 06/30/2022
Underslab Plumbing Inspection - Residential Passed 6/30/2022 6/30/2022 06/30/2022
Miscellaneous Inspection Failed 6/30/2022 06/30/2022
Misc
Corrective Action Required
06/30/2022
FOOTING WAS NOT INSPECTED AND APPROVED BY CITY. 3RD PARTY APPROVAL OF THE FOOTING SHALL BE SUBMITTED TO THE CITY WITHIN TWO DAYS. NO FURTHER INSPECTIONS WILL BE ALLOWED UNTIL THE FOOTING APPROVAL FROM THE 3RD PARTY IS SUBMITTED
Water Service Inspection - R Passed 7/1/2022 (10:45) 7/1/2022 07/01/2022
Erosion Control Inspection Residential Failed 11/29/2022 11/29/2022
Miscellaneous Correction
Corrective Action Required
06/30/2022
RESTORE EROSION CONTROL ALONG THE STREET. A SIGNIFICANT AMOUNT OF MUD WAS DEPOSITED ON THE STREET. THE STREET SHALL BE CLEANED UP IMMEDIATELY. FAILURE TO COMPLY WITH THE ABOVE WILL RESULT IN AN ISSUANCE OF STOP-WORK ORDER **11/29 EROSION CONTROL SIGN POSTED
Erosion Control Inspection Residential Passed 12/2/2022 12/02/2022
Miscellaneous Correction
Informational
12/02/2022
EROSION CONTROL RESTORED ALONG THE STREET. MUD HAS BEEN CLEANED OFF THE STREET. **MAINTAIN EROSION CONTROL DURING THE WHOLE CONSTRUCTION PHASE
Erosion Control Inspection Residential Failed 5/31/2023 05/31/2023
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/31/2023
EROSION CONTROL REQUIRED ALONG THE STREET. STREET CLEANUP SHALL BE PERFORMED IMMEDIATELY. MUD&SILT SHALL BE CLEANED OFF THE STREET CURB AND STORM INLET. PROTECT STORM INLET WITH GUTTER BUDDY IN SUCH WAY TO ALSO ALLOW STORM WATER DRAINAGE. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. FAILURE TO COMPLY WITH THE EROSION CONTROL REQUIREMENT WILL RESULT IN ISSUANCE OF A STOP-WORK ORDER
Gas Service Inspection - Residential Failed 7/10/2023 7/10/2023 07/10/2023
Misc
Corrective Action Required
07/10/2023
-Provide min ten psi pressure for testing
Electrical Service Inspection Failed 7/10/2023 7/10/2023 07/10/2023
Misc
Corrective Action Required
07/10/2023
-Install covers at SE conductor connections to main breaker -Bond enclosure by tightening the main bonding screw all the way in -Install a #4 copper conductor jumper from the grounding bus bar where the ufer GEC is connected to to the middle grounded bus bar; or directly connect the ufer GEC to the middle grounded bus bar
Electrical Service Inspection Failed 07/10/2023
Misc
Corrective Action Required
07/10/2023
-Install covers at SE conductor connections to main breaker -Bond enclosure by tightening the main bonding screw all the way in -Install a #4 copper conductor jumper from the grounding bus bar where the ufer GEC is connected to to the middle grounded bus bar; or directly connect the ufer GEC to the middle grounded bus bar
All Rough Inspection - Residential Failed 7/10/2023 7/10/2023 07/10/2023
Misc
Corrective Action Required
07/10/2023
**CLEAN MUD AND DEBRIS FROM STREET CURB AND STORM INLET. INSTALL GUTTER BUDDY IN FRONT OF THE STORM INLET WITH THE CONCRETE BLOCK BETWEEN THE INLET AND GUTTER BUDDY TO ALLOW WATER TO FLOW INTO THE INLET -Nail the garage PFH walls sheathing per code. Remove all siding and trims for verification -Nail siding per code @ 6” oc along the edge and 12” oc in field -Fb penetrations of wall plates throughput; Fb plumbing wall space at entry closet from joist space; fb plumbing space at rear hearth room wall; fb floor penetration at plumbing traps -Notched joist above foyer exceeds code allowance -Bolt flitch plate beam above front dining per plan -Provide triple joist above front dining per plan or have engineer address/change plan -Pan off return air space at front dining from joist space and adjacent garage space -Seal all holes/gaps and penetrations of return air space throughout -Nail corner studs w/16d @12” oc or equivalent nailing -Nail joists to interior wall top plates per code -Fasten fireplace to framing -Engineer to address rear living room walls not framed per plan. Plan calls for 2x6 walls with two min 1200 lbs straps on both sides and HDU4 straps to tie down walls to foundation wall. See detail on 3/S505 -Strap unlapped top plates of the same curved walls above -Install (8)2x6 support for I beam near rear patio door -Install hanger at connection to I beam above rear patio door -Provide security blockings at patio door per security code ; fill in (with solid wood) void behind hinges and at strike plate side from 12” above to 12” below strike plate -Protect wiring at bottom wall plate near patio door -Provide CSPF walls at rear dining room per plan -Provide roof collar ties @ 4 ft interval above rear patio -Fur out garage wall at return air space for R-13 insulation; do same for R-19 at ceiling -Fully nail stud shoe at half bathroom -Strap exterior wall top plate where bored more than 50% -Anchor garage sill plates within 12” of breaks -Complete garage duct/plumbing spaces and fire block as required -Fur around garage steel column for GB fire protection -Tighten anchor nuts at garage PFH walls -Support duct above garage minimum every 10 ft -Provide (2)2x4 support for double joist at garage/kitchen wall -Strap exterior wall top plates where lapped less than 24” at 2nd fl rear bathroom; strap at master shower wall plates -Reinforce non-continuous studs at bedroom 4 gable wall -Install H2.5 straps for lvl ridge beam above bedroom 4 per plan; provide (2)2x4 support for lvl ridge beam support -Fb 2nd fl duct chase from roof -Pan off return air space from 2nd fl duct chase -Close off hole in laundry floor -Tape seal dryer duct joint -Bathroom fan flexible duct is limited to maximum 14 ft per UL label. Install combination of flexible duct and hard duct to meet code requirement -Provide master bedroom wall receptacle spaced per code -Provide attic access to roof space -Provide studs shoes for master bathroom exterior wall studs bored more than 40% -Complete all trades at front of master bathroom; Support ridge above window -Provide ceiling rafter space for R-30 insulation above master bathroom -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **DO NOT INSULATE
Erosion Control Inspection Residential Failed 9/8/2023 09/08/2023
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/31/2023
**Overgrown grass and weed shall be mowed within two business days
Erosion Control Inspection Residential Passed 9/13/2023 09/13/2023
DCM3 ESC REQUIRED 2 DAY
Resolved
09/13/2023
**Overgrown grass and weed shall be mowed within two business days
Electrical Service Inspection Passed 9/25/2023 9/25/2023 09/25/2023
Misc
Resolved
09/25/2023
-Install covers at SE conductor connections to main breaker -Bond enclosure by tightening the main bonding screw all the way in -Install a #4 copper conductor jumper from the grounding bus bar where the ufer GEC is connected to to the middle grounded bus bar; or directly connect the ufer GEC to the middle grounded bus bar
Gas Service Inspection - Residential Passed 9/25/2023 9/25/2023 09/25/2023
Misc
Resolved
09/25/2023
-Provide min ten psi pressure for testing
All Rough Inspection - Residential Failed 9/25/2023 9/25/2023 09/25/2023
Misc
Corrective Action Required
07/10/2023
-Nail the garage PFH walls sheathing per code. Remove all siding and trims for verification **Nail sheathing to all studs w/8d@3” oc; nail to LVL header with 8d@3” oc grid pattern -Nail siding per code @ 6” oc along the edge and 12” oc in field **Nail siding to sill plates @6” oc -Notched joist above foyer exceeds code allowance **engineer must address the repair of notched joist -Fb plumbing space at rear hearth room wall -Pan off return air space at front dining from joist space and adjacent garage space -Nail corner studs w/16d @12” oc or equivalent nailing -Engineer to address rear living room walls not framed per plan. Plan calls for 2x6 walls with two min 1200 lbs straps on both sides and HDU4 straps to tie down walls to foundation wall. See detail on 3/S505 -Install (8)2x6 support for I beam near rear patio door -Provide security blockings at patio door per security code ; fill in (with solid wood) void behind hinges and at strike plate side from 12” above to 12” below strike plate -Provide CSPF walls at rear dining room per plan **Not framed per code -Fur out garage wall at return air space for R-13 insulation; do same for R-19 at ceiling **Not done -Strap exterior wall top plate where bored more than 50% **At half bathroom -Anchor garage sill plates within 12” of breaks -Protect wiring at front garage corner -Complete garage duct/plumbing spaces and fire block as required **Fire block space from soffit space -Support duct above garage minimum every 10 ft -Reinforce non-continuous studs at bedroom 4 gable wall -Install H2.5 straps for lvl ridge beam above bedroom 4 per plan **See plan -Pan off return air space from 2nd fl duct chase -Bathroom fan flexible duct is limited to maximum 14 ft per UL label. Install combination of flexible duct and hard duct to meet code requirement -Provide attic access to roof space **Staple wiring along the joists and away from attic access opening. Wiring running across the top of joists where within 6 ft if the attic access opening shall be protected with running board -Provide ceiling rafter space for R-30 insulation above master bathroom -Strap top plate where lapped less than 24” at master shower wall plates -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **DO NOT INSULATE
All Rough Inspection - Residential Failed 10/31/2023 10/31/2023 10/31/2023
Misc
Corrective Action Required
09/25/2023
-Fb plumbing space at rear hearth room wall -Nail corner studs w/16d @12” oc or equivalent nailing -Provide CSPF walls at rear dining room per plan **Not framed per code. Please see the plan page 2/S505; min double 2x12 header is required; nail siding per 2/S505 detail; reinstall electrical -Strap exterior wall top plate where bored more than 50% **At half bathroom -Complete garage duct/plumbing spaces and fire block as required **Fire block space from soffit space -Provide attic access to roof space **Staple wiring along the joists and away from attic access opening. Wiring running across the top of joists where within 6 ft if the attic access opening shall be protected with running board -Strap top plate where lapped less than 24” at master shower wall plates -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK TO INSULATE
Erosion Control Inspection Residential Failed 10/31/2023 10/31/2023
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
10/31/2023
DEFICIENT EROSION CONTROL INSTALLATION. REINSTALL EROSION CONTROL ALONG THE STREET AND CLEAN MUD OFF THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
All Rough Inspection - Residential Not Ready 11/21/2023 11/21/2023 11/21/2023
Misc
Corrective Action Required
10/31/2023
-Nail corner studs w/16d @12” oc or equivalent nailing -Provide CSPF walls at rear dining room per plan **Not framed per code. Please see the plan page 2/S505; min double 2x12 header is required; nail siding per 2/S505 detail; reinstall electrical (exterior nailing and electrical not done) -Strap exterior wall top plate where bored more than 50% **At half bathroom -Complete garage duct/plumbing spaces and fire block as required **Fire block space from soffit space -Provide attic access to roof space **Staple wiring along the joists and away from attic access opening. Wiring running across the top of joists where within 6 ft if the attic access opening shall be protected with running board -Strap top plate where lapped less than 24” at master shower wall plates -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK TO INSULATE
All Rough Inspection - Residential Failed 11/29/2023 11/29/2023 11/29/2023
Misc
Corrective Action Required
11/21/2023
-Engineer to address the living room rear wall not strapped per plan. **Page S505/item 3 shows the detail of the number and location of all the straps and nailing requirement per PFH detail. The engineer must address whether the current installed strappings meets all the plan design/code requirement -Cannot supply the outdoor receptacles (front and back) from the dining circuits. -Provide CSPF walls at rear dining room per plan **Not framed per code. Please see the plan page 2/S505; **nail siding per 2/S505 detail; reinstall electrical (exterior nailing and electrical not done) -Provide attic access to roof space **Staple wiring along the joists and away from attic access opening. Wiring running across the top of joists where within 6 ft if the attic access opening shall be protected with running board -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK TO INSULATE
All Rough Inspection - Residential Failed 12/6/2023 12/6/2023 12/06/2023
Misc
Corrective Action Required
11/29/2023
-Provide attic access to roof space **Staple wiring along the joists and away from attic access opening. Wiring running across the top of joists where within 6 ft if the attic access opening shall be protected with running board -Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK TO INSULATE
Driveway Inspection Passed 5/31/2023 5/31/2023 12/07/2023
Misc
Corrective Action Required
05/31/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, Pre pour inspection was not called back in so no pre pour inspection was done. Checked for ADA compliance and slopes are in compliance. Passed. 5-10-24 NS Site visited to check sidewalk and driveway ADA and it appears that they both passed.
Driveway Inspection Passed 12/7/2023 12/07/2023
Misc
Informational
12/07/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass.
Sidewalk Inspection Failed 12/7/2023 12/07/2023
Misc
Corrective Action Required
05/31/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out.
All Rough Inspection - Residential Partial 12/11/2023 12/11/2023 12/11/2023
Misc
Corrective Action Required
12/06/2023
-Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK to rock. Call for nailing pattern inspection of the braced wall GB when ready (7” on center)
Sidewalk Inspection Partial 12/14/2023 12/14/2023 12/14/2023
Misc
Corrective Action Required
12/07/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed
Sidewalk Inspection Partial 12/19/2023 12/19/2023 12/18/2023
Misc
Corrective Action Required
12/14/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed
Sidewalk Inspection Partial 12/27/2023 12/27/2023 12/27/2023
Misc
Corrective Action Required
12/18/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed 12-27-23 Dustin A, Conditions have not changed
Sidewalk Inspection Failed 1/3/2024 1/3/2024 01/03/2024
Misc
Corrective Action Required
12/27/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed 12-27-23 Dustin A, Conditions have not changed 1-3-24 Dustin A, Conditions have not changed 1-25-24 Dustin A, Conditions have not changed.
Sidewalk Inspection Failed 1/30/2024 1/30/2024 01/25/2024
Misc
Corrective Action Required
01/03/2024
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed 12-27-23 Dustin A, Conditions have not changed 1-3-24 Dustin A, Conditions have not changed 1-25-24 Dustin A, Conditions have not changed
All Rough Inspection - Residential Passed 1/29/2024 1/29/2024 01/29/2024
Misc
Resolved
01/29/2024
-Interior braced wall at kitchen /garage wall will be per GB method. Call for inspection of nailing pattern when ready **OK to rock. Call for nailing pattern inspection of the braced wall GB when ready (7” on center)
Sidewalk Inspection Partial 2/5/2024 2/5/2024 02/05/2024
Misc
Corrective Action Required
01/25/2024
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed 12-27-23 Dustin A, Conditions have not changed 1-3-24 Dustin A, Conditions have not changed 1-25-24 Dustin A, Conditions have not changed 2-5-24 NS Site visited and it appears that sidewalk meets city standards for pre pour.
Erosion Control Inspection Residential Failed - Stop Work 4/30/2024 04/30/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
10/31/2023
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. MUD SHALL BE CLEANED OFF THE STREET IMMEDIATELY
Occupancy Inspection - Codes Residential Failed 5/8/2024 05/08/2024
Misc
Corrective Action Required
05/08/2024
Not ready for inspection. Submit engineer letter approval for footing
Footing Inspection - Residential Passed 05/09/2024
Informational
05/09/2024
Footing approved by engineer
Miscellaneous Inspection Passed 05/09/2024
Misc
Resolved
05/09/2024
FOOTING WAS NOT INSPECTED AND APPROVED BY CITY. 3RD PARTY APPROVAL OF THE FOOTING SHALL BE SUBMITTED TO THE CITY WITHIN TWO DAYS. NO FURTHER INSPECTIONS WILL BE ALLOWED UNTIL THE FOOTING APPROVAL FROM THE 3RD PARTY IS SUBMITTED
Occupancy Inspection - Codes Residential Failed 5/9/2024 5/9/2024 05/09/2024
Misc
Corrective Action Required
05/08/2024
-Obtain lawn irrigation permit and submit backflow valve test report to city -Not-ready fee must be paid prior to issuance of any occupancy -Sidewalk not approved on record -As-graded plot plan is required -Complete electrical to all exterior lights and receptacles -Provide guardrail at open edge of stoop more than 40” above grade, as measured 36” out -Final grade, sod, gutters, downspout and sump pump extension -Seal exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc -Provide sewer tracer wire port at grade -All receptacles in the garage shall be gfci-protected -Fire block penetration of garage wall under sink; separate basement from garage with 5/8” GB -Provide 5/8” GB at access panel above garage -Garage handrail shall be graspable. Handrail profile must be per code (just like handrail inside house) -Install bottom garage door track support brackets within 10” of floor -Label dedicated single-plug receptacle in garage -Open ground receptacles in rear dining -No power to some receptacles -Install the security strike plate at the rear exterior door and screw it into the embedded jamb brace; screw the embedded jamb brace into the studs near the security strike plate -Provide spark ring at living room and master bedroom wall receptacle boxes recessed behind combustible wall finish -Make sure to ground all switches and receptacles throughout house -Basement stair handrail shall be 34”-38”, as measured vertically from top of handrail to tread nose-nose plane -Stair risers shall be no more than 7.75”, with maximum riser height difference of no more than 3/8” -Basement mid-stair landing must be min 36” in depth -Provide a smoke alarm in basement -Secure LFNC raceways within 12” of boxes in basement -Provide single-plug receptacle for the sump pump or provide gfci protection -Provide AFCI protection for all outlets required per NEC 210.12. (Clothes washer) -Provide breaker locks for out-of-sight water heater
Erosion Control Inspection Residential Passed 5/9/2024 5/9/2024 05/09/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
05/09/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. MUD SHALL BE CLEANED OFF THE STREET IMMEDIATELY
Sidewalk Inspection Passed 5/31/2023 5/31/2023 05/10/2024
Misc
Corrective Action Required
05/31/2023
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 5-10-24 NS Site visited to check sidewalk and driveway ADA and it appears that they both passed.
Occupancy Inspection - Codes Residential Ready for Temp CO 5/10/2024 5/10/2024 05/10/2024
Misc
Resolved
05/10/2024
Misc
Informational
05/10/2024
-Obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is -Final grade, sod, gutters, downspout and sump pump extension
Sidewalk Inspection Passed 2/19/2024 06/10/2024
Misc
Corrective Action Required
02/05/2024
5-31-23 NS Site visited and the driveway and sidewalk is holding water did not pass. 12-7-23 Dustin A, No pre pour inspection was performed. Forms are still on . Section is unfinished and there is mud on sw. Failed, Will need to call in pre pour inspection in before rest is poured. Failure to do so will result in tear out. 12-14-23 Dustin A. Conditions have not changed 12-18-23 Dustin A, Conditions have not changed 12-27-23 Dustin A, Conditions have not changed 1-3-24 Dustin A, Conditions have not changed 1-25-24 Dustin A, Conditions have not changed 2-5-24 NS Site visited and it appears that sidewalk meets city standards for pre pour.
Occupancy Inspection - Codes Residential Ready for Temp CO 6/10/2024 06/10/2024
Misc
Informational
05/10/2024
-Obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required prior to sodding -Final grade, sod, gutters, downspout and sump pump extension
Plot Plan Inspection Failed 6/11/2024 06/11/2024
Misc
Corrective Action Required
06/11/2024
Provide a swale at the back side of the lot flowing into the storm inlet at SE corner of lot. The storm inlet is currently covered with grading and must be uncovered Do not sod the lot
Erosion Control Inspection Residential Failed 7/1/2024 07/01/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
07/01/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/01/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
07/01/2024
STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED.
Erosion Control Inspection Residential Failed 7/5/2024 07/05/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
07/01/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/01/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
07/01/2024
STREET AND SIDEWALK CLEAN UP REQUIRED IMMEDIATELY. PERMIT STATUS IS IN VIOLATION STATUS.
Erosion Control Inspection Residential Partial 7/9/2024 07/09/2024
DCM2 ESC DEFICIENT INSTALLATION
Informational
07/09/2024
EROSION CONTROL IS IN COMPLIANCE AND SHALL REMAIN SO UNTIL SODDING
DCM3 ESC REQUIRED 2 DAY
Resolved
07/09/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
07/09/2024
STREET AND SIDEWALK CLEAN UP REQUIRED IMMEDIATELY. PERMIT STATUS IS IN VIOLATION STATUS.
Plot Plan Inspection Failed 7/11/2024 07/11/2024
Misc
Corrective Action Required
06/11/2024
Provide a swale at the back side of the lot flowing into the storm inlet at SE corner of lot. The storm inlet is currently covered with grading and must be uncovered Do not sod the lot
Plot Plan Inspection Passed 7/29/2024 07/29/2024
Misc
Resolved
07/29/2024
Provide a swale at the back side of the lot flowing into the storm inlet at SE corner of lot. The storm inlet is currently covered with grading and must be uncovered Do not sod the lot
Erosion Control Inspection Residential Failed 08/09/2024
DCM2 ESC DEFICIENT INSTALLATION
Informational
07/09/2024
EROSION CONTROL IS IN COMPLIANCE AND SHALL REMAIN SO UNTIL SODDING
Miscellaneous Correction
Corrective Action Required
08/09/2024
8-9-24 NS Site visited and it appears that storm inlet has a sock that is full of dirt and has grass growing out of them and needs to be cleaned out before 8-19-24 If not I will put a stop work order on this permit.
Occupancy Inspection - Codes Residential Full C of O 8/9/2024 8/9/2024 08/09/2024
Misc
Resolved
08/09/2024
Documents & Images
Date Uploaded File Type Document Name
01/24/2022 119 application
01/27/2022 Permit Codes Residential Plan Review
03/15/2022 Permit Codes Residential Plan Review
03/30/2022 Approved Plans APPROVED PLANS
03/30/2022 Plot Plan APPROVED PLOT PLAN
03/30/2022 Permit Codes Residential Plan Review
03/31/2022 Permit DS Building Permit
03/31/2022 Receipt Receipt for transaction:2022-001770
04/01/2022 Letter INSPECTION SUMMARY
04/01/2022 Letter INSPECTION SUMMARY
04/04/2022 Letter Stop Work Order
05/02/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter INSPECTION SUMMARY
06/30/2022 Letter INSPECTION SUMMARY
07/01/2022 Letter INSPECTION SUMMARY
11/29/2022 Letter INSPECTION SUMMARY
12/02/2022 Letter INSPECTION SUMMARY
04/21/2023 Letter Codes 140 Day Letter
05/31/2023 Letter INSPECTION SUMMARY
05/31/2023 Letter INSPECTION SUMMARY
05/31/2023 Letter INSPECTION SUMMARY
05/31/2023 Letter INSPECTION SUMMARY
07/10/2023 Letter INSPECTION SUMMARY
07/10/2023 Letter INSPECTION SUMMARY
07/10/2023 Letter INSPECTION SUMMARY
07/10/2023 Letter INSPECTION SUMMARY
07/10/2023 Letter INSPECTION SUMMARY
09/08/2023 Letter INSPECTION SUMMARY
09/13/2023 Letter INSPECTION SUMMARY
09/25/2023 Letter INSPECTION SUMMARY
09/25/2023 Letter INSPECTION SUMMARY
09/25/2023 Letter INSPECTION SUMMARY
10/20/2023 4813 Jamestowne Dr - framing & strapping & floor joist
10/31/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
11/21/2023 Letter INSPECTION SUMMARY
11/29/2023 Letter INSPECTION SUMMARY
12/01/2023 4813 Jamestowne Dr - revised framing & strapping & floor joist
12/06/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/11/2023 Letter INSPECTION SUMMARY
12/14/2023 Letter INSPECTION SUMMARY
12/18/2023 Letter INSPECTION SUMMARY
12/27/2023 Letter INSPECTION SUMMARY
01/03/2024 Letter INSPECTION SUMMARY
01/25/2024 Letter INSPECTION SUMMARY
01/25/2024 Letter INSPECTION SUMMARY
01/25/2024 Letter INSPECTION SUMMARY
01/25/2024 Letter INSPECTION SUMMARY
01/29/2024 Letter INSPECTION SUMMARY
02/05/2024 Letter INSPECTION SUMMARY
02/05/2024 Letter INSPECTION SUMMARY
04/30/2024 Letter Stop Work Order
05/08/2024 Letter Stop Work Order
05/08/2024 Letter INSPECTION SUMMARY
05/08/2024 3RD Party Insp Report THIRD PARTY FOOTING INSPECTION
05/09/2024 Letter INSPECTION SUMMARY
05/09/2024 Letter INSPECTION SUMMARY
05/09/2024 Letter INSPECTION SUMMARY
05/09/2024 Letter INSPECTION SUMMARY
05/09/2024 Receipt Receipt for transaction:2024-003201
05/10/2024 Letter INSPECTION SUMMARY
05/10/2024 Letter INSPECTION SUMMARY
05/10/2024 Letter INSPECTION SUMMARY
06/05/2024 scan0350
06/10/2024 Certificate/License Codes Temporary Certificate of Occupancy
06/10/2024 Certificate/License Codes Temporary Certificate of Occupancy
06/10/2024 Receipt Receipt for transaction:2024-004546
06/10/2024 Monticello Lot 119 Asbuilt 24_0607
06/10/2024 Plot Plan approved as graded plot plan
06/11/2024 Letter INSPECTION SUMMARY
06/11/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/05/2024 Letter Codes 10 Day Letter
07/05/2024 Letter INSPECTION SUMMARY
07/05/2024 Letter INSPECTION SUMMARY
07/09/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/29/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter Field Certificate of Occupancy
08/09/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home