Permit Application Status

PRRES20215493


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20215493
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
10/20/2021
10/25/2021
04/18/2022
04/19/2023
Locations
Contacts
SAB CONSTRUCTION INC, Address:PO BOX 942, Phone:(816) 524-3855  
Curtis Tate, Address:PO box 942   
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
CURTIS@SABHOMES.COM  
Zack Bryant, Address:200 NW Commerce Court  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $600.00 $600.00 Paid 10/25/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 10/25/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 10/25/2021
9110078-Valuation Fee New Single Family $1,680.69 $1,680.69 Paid 10/25/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 10/25/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 10/25/2021
9110078-Valuation Fee New Single Family $51.56 $51.56 Paid 05/04/2022
$1,732.25
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 05/04/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/02/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 11/24/2021 11/24/2021
Misc
Informational
11/24/2021
Ufer right above sump pump as indicated by 3rd party inspection
Sewer Service Inspection - R Passed 11/30/2021 (10:00) 11/30/2021 11/30/2021
Underslab Plumbing Inspection - Residential Failed 12/7/2021 12/7/2021 12/07/2021
Misc
Corrective Action Required
12/07/2021
Provide proper venting for basement bathroom see code section P3108.2.1 Horizontal wet vent
Water Service Inspection - R Passed 12/9/2021 (2:00) 12/9/2021 12/09/2021
Erosion Control Inspection Residential Failed 12/9/2021 12/09/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/09/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underslab Plumbing Inspection - Residential Passed 12/10/2021 12/10/2021 12/10/2021
Misc
Resolved
12/10/2021
Provide proper venting for basement bathroom see code section P3108.2.1 Horizontal wet vent
Piers/Caissons Inspection - Residential Passed 12/17/2021 (1:30) 12/17/2021 12/17/2021
Erosion Control Inspection Residential Failed 2/10/2022 2/10/2022 02/10/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/10/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
02/10/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
All Rough Inspection - Residential Not Ready 4/25/2022 4/25/2022 04/25/2022
Misc
Corrective Action Required
04/25/2022
inspection denied no city stamed plans on site
Gas Service Inspection - Residential Failed 4/25/2022 4/25/2022 04/25/2022
Misc
Corrective Action Required
04/25/2022
inspection denied no city stamed plans on site
Electrical Service Inspection Failed 4/25/2022 4/25/2022 04/25/2022
Misc
Corrective Action Required
04/25/2022
inspection denied no city stamped plans on site
Gas Service Inspection - Residential Failed 4/26/2022 04/26/2022
Misc
Resolved
04/26/2022
inspection denied no city stamed plans on site
Misc
Corrective Action Required
04/26/2022
complete fire place install
Electrical Service Inspection Passed 4/26/2022 04/26/2022
Misc
Resolved
04/26/2022
inspection denied no city stamped plans on site
All Rough Inspection - Residential Failed 4/26/2022 4/26/2022 04/26/2022
Misc
Resolved
04/26/2022
inspection denied no city stamed plans on site
Misc
Corrective Action Required
04/26/2022
-PFH and pfg nailing to plans/code -strapping at single car pfh -snow block sheathing break in single car -nail all intersecting wall corners to plans -seal top of furr out wall in garage -fire block top of hvac chase -seal penetrations in joist space used for RA above mud hall and in panning -seal top plate penetrations at office/entry -fire block above steal beam at entry -seal penetrations in office RA to second floor -missing double lvl that extends from back wall to entry half bath -hangers for joist above breakfast -missing (3) 2x10 above breakfast E wall -lvl above slider incorrect size and not framed to cs-pf -missing double joists above great room -finish gas line install at fire place, secure fireplace, secure and gas line and protect gas line -support dwv in joist space every 48” OC see master bath and master closet -snow blocking at laundry -missing lvl above hallway -missing double 2x10 above hallway to bed 4 -fire block bed 4 closet walls -fire block bed 4 S wall -seal penetrations bed 4 W wall -protect NM within 6’ of attic access bed 3 closet -fire block bed 3 N wall to ceiling space above front entry -seal top plate penetration in bed 3 S wall -did not inspect lower floor, lower floor plans page missing from city stamped plans. Provide at time of re inspection
All Rough Inspection - Residential Failed 5/2/2022 5/2/2022 05/02/2022
Misc
Corrective Action Required
04/26/2022
-PFH nailing to plans/code -seal top of furr out wall in garage -fire block top of hvac chase -seal penetrations in joist space used for RA above mud hall and in panning and remove blocking -seal penetrations in office RA to second floor -cs-pf at rear slider -finish gas line install at fire place, secure fireplace, secure and gas line and protect gas line -fire block bed 4 S wall seal gaps -protect NM within 6’ of attic access bed 3 closet -columns in basement to be of correct size -(3) 2x6 under lvl at stairs to plans -lvl above stairs in basement incorrect size -(2) 2x10 at bottom of stairs in basement to plans -header above basement slider to plans -stud pack at beam in basement great room -vertical to horizontal fireblock if every 10’ in basement -seal top of furr out walls In basement -fire block furr down ends in basement
All Rough Inspection - Residential Failed 5/5/2022 5/5/2022 05/05/2022
Misc
Corrective Action Required
05/02/2022
-PFH nailing to plans/code -fire block top of hvac chase seal wall penetrations -seal penetrations in joist space used for RA above mud hall and in panning and REMOVE BLOCKING -cs-pf at rear slider remove trim to view nailing pattern -fire block bed 4 S wall seal gaps -protect NM within 6’ of attic access bed 3 closet -vertical to horizontal fireblock if every 10’ in basement seal gaps -seal top of furr out walls In basement seal gaps -fire block furr down ends in basement
All Rough Inspection - Residential Not Ready 5/10/2022 5/10/2022 05/10/2022
Misc
Corrective Action Required
05/05/2022
-PFH nailing to plans/code -cs-pf at rear slider remove trim to view nailing pattern -protect NM within 6’ of attic access bed 3 closet -vertical to horizontal fireblock if every 10’ in basement seal gaps and penetrations -seal top of furr out walls In basement seal gaps -fire block furr down ends in basement
Erosion Control Inspection Residential Failed 5/13/2022 05/13/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
05/13/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
05/13/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. -Maintain gravel filter with 6" lift of 3/4/" gravel, maintain silt fence
Gas Service Inspection - Residential Passed 5/13/2022 5/13/2022 05/13/2022
Misc
Resolved
05/13/2022
complete fire place install
All Rough Inspection - Residential Failed 5/13/2022 5/13/2022 05/13/2022
Misc
Corrective Action Required
05/10/2022
**OK to insulate only -cs-pf at rear slider remove trim to view nailing pattern
Erosion Control Inspection Residential Partial 5/23/2022 5/23/2022 05/23/2022
DCM2 ESC DEFICIENT INSTALLATION
Resolved
05/23/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. -Maintain gravel filter with 6" lift of 3/4/" gravel, maintain silt fence
All Rough Inspection - Residential Not Ready 5/24/2022 5/24/2022 05/24/2022
Misc
Corrective Action Required
05/13/2022
**OK to insulate only -cs-pf at rear slider remove trim to view nailing pattern
All Rough Inspection - Residential Passed 5/24/2022 5/24/2022 05/24/2022
Misc
Informational
05/24/2022
**OK to insulate only -cs-pf at rear slider remove trim to view nailing pattern -fixed per engineer letter
Driveway Inspection Partial 9/9/2022 09/09/2022
Misc
Informational
09/09/2022
9-9-22 RH. Driveway is formed up and aggregate is placed compacted.
Sidewalk Inspection Partial 9/9/2022 09/09/2022
Misc
Informational
09/09/2022
9-9-22 RH. Sidewalk is formed up and aggregate is placed and compacted.
Driveway Inspection Passed 9/16/2022 9/16/2022 09/16/2022
Misc
Informational
09/09/2022
9-9-22 RH. Driveway is formed up and aggregate is placed compacted. 9-16-22 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 9/16/2022 09/16/2022
Misc
Informational
09/09/2022
9-9-22 RH. Sidewalk is formed up and aggregate is placed and compacted. 9-16-22 RH. Sidewalk meets LS and ADA specification.
Occupancy Inspection - Codes Residential Failed 12/20/2022 12/20/2022 12/20/2022
Misc
Corrective Action Required
12/20/2022
-properly illuminate address -garage entry door to be self closing and latching -spark ring at outlet above fireplace -open junction box above 2nd floor hall -spark ring at basement bathroom outlet -address siding from grade at rear of home -splash blocks
Plot Plan Inspection Passed 4/13/2023 04/13/2023
Erosion Control Inspection Residential Passed 4/13/2023 04/13/2023
Occupancy Inspection - Codes Residential Failed 4/13/2023 4/13/2023 04/13/2023
Misc
Corrective Action Required
12/20/2022
-properly illuminate address
Occupancy Inspection - Codes Residential Full C of O 4/19/2023 4/19/2023 04/19/2023
Misc
Resolved
04/19/2023
-properly illuminate address
Documents & Images
Date Uploaded File Type Document Name
10/20/2021 HF43 permit app
10/20/2021 HF43 excise tax app
10/20/2021 Permit Codes Residential Plan Review
10/21/2021 Approved Plans approved plans
10/21/2021 Plot Plan APPROVED PLOT PLAN1
10/25/2021 Permit Codes Residential Plan Review
10/25/2021 Permit DS Building Permit
10/25/2021 Receipt Receipt for transaction:2021-008229
11/23/2021 2023 SW Wheatfield Ct LSMO Hook Farms Lot 43 Foundation Footing Inspection Report 11-4-21
11/24/2021 Letter INSPECTION SUMMARY
11/30/2021 Letter INSPECTION SUMMARY
12/07/2021 Letter INSPECTION SUMMARY
12/09/2021 Letter INSPECTION SUMMARY
12/09/2021 Letter INSPECTION SUMMARY
12/10/2021 Letter INSPECTION SUMMARY
12/17/2021 Letter INSPECTION SUMMARY
12/17/2021 Letter INSPECTION SUMMARY
02/10/2022 Letter INSPECTION SUMMARY
03/31/2022 HF43 - Basement Finish App
03/31/2022 Approved Plans Approved Basement Plan
04/25/2022 Letter INSPECTION SUMMARY
04/25/2022 Letter INSPECTION SUMMARY
04/25/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
04/26/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/04/2022 FRAMING REPORT[1]
05/04/2022 Receipt Receipt for transaction:2022-002861
05/05/2022 Letter INSPECTION SUMMARY
05/10/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
05/13/2022 Letter INSPECTION SUMMARY
05/19/2022 DW FRAMING ADDENDUM 2
05/23/2022 Letter INSPECTION SUMMARY
05/24/2022 Letter INSPECTION SUMMARY
05/24/2022 Letter INSPECTION SUMMARY
09/02/2022 Receipt Receipt for transaction:2022-007226
09/09/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/16/2022 Letter INSPECTION SUMMARY
09/16/2022 Letter INSPECTION SUMMARY
12/20/2022 Letter INSPECTION SUMMARY
04/13/2023 Letter INSPECTION SUMMARY
04/13/2023 Letter INSPECTION SUMMARY
04/13/2023 Letter INSPECTION SUMMARY
04/19/2023 Letter Field Certificate of Occupancy
04/19/2023 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home