Permit Application Status

PRRES20212479


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20212479
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - FINISHED AND UNFINISHED BASEMENT - COVERED DECK
05/14/2021
05/14/2021
04/25/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $420.00 $420.00 Paid 05/14/2021
Right of Way Permit Fee $80.00 $80.00 Paid 05/14/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 05/14/2021
Water Tap Fee $3,581.00 $3,581.00 Paid 05/14/2021
Water Meter Fee $455.54 $455.54 Paid 05/14/2021
Valuation Fee New Single Family $1,028.38 $1,028.38 Paid 05/14/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 04/13/2022
Not Ready Inspection Fee $50.00 $50.00 Paid 04/13/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 6/18/2021 6/18/2021 06/18/2021
Underslab Plumbing Inspection - Residential Not Ready 7/19/2021 7/19/2021 07/19/2021
Misc
Corrective Action Required
07/19/2021
INSPECTION DENIED -POST ADDRESS -MAINTAIN EROSION CONTROL, CLEAN MUD/GRAVEL FROM STREET -BACKFILL AT FOUNDATION TO ALLOW INSPECTION
Underslab Plumbing Inspection - Residential Passed 7/22/2021 7/22/2021 07/22/2021
Misc
Resolved
07/22/2021
All Rough Inspection - Residential Partial 8/10/2021 8/10/2021 08/10/2021
Misc
Informational
08/10/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Sewer Service Inspection - R Passed 8/27/2021 8/27/2021 08/27/2021
Water Service Inspection - R Passed 8/31/2021 08/31/2021
Erosion Control Inspection Residential Failed 8/31/2021 8/31/2021 08/31/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
08/31/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Electrical Service Inspection Failed 11/2/2021 11/02/2021
Misc
Corrective Action Required
11/02/2021
- color code GEC at service panel
Gas Service Inspection - Residential Failed 11/2/2021 11/02/2021
Misc
Corrective Action Required
11/02/2021
-Gas pressure must maintain 10 psi for test
All Rough Inspection - Residential Failed 11/2/2021 11/2/2021 11/02/2021
Misc
Informational
08/10/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
11/02/2021
-Maintain sections of damaged silt fence and gravel filter -Anchor bolts within 12” of plate breaks in garage and basement -seal all top plate penetrations - garage -protect NM within 6’ of attic access -instersecting corner studs removed for electrical garage SW corner and electrical at front bedroom SE corner -bocca protection plate DWV top plate garage wall -dryer duct over max length -install bedroom windows -12” oc nailing at all abutting and intersecting wall corners -fireblock between top plates at dbl wall kitchen and foyer -protection plate at bottom plate pex fridge kitchen -clarify exterior wall bracing at dining room windows, no detail shown in plans -(4) 2X stud pack all girder truss bearing ends per plans -Fireblock between top plates at finished basement -Fireblock between studs at bump out top plate garage walls -Fireblock vertical to horizontal at furred down soffit ends -security blocking at basement walkout -land electrical at basement den wall receptacle -complete DWV basement mech room -address cut joist for DWV, NW basement -address cut joist for DWV, SE basement -Protection plates, DWV bottom and top plate basement bath -Floor joist overbored for DWV, basement bedroom SE wall -2x4 laid flat at furred down in basement bedroom, connect to floor joist above to support the ceiling load -(2) 2x10 joists at covered deck cantilever per plans
Gas Service Inspection - Residential Failed 11/9/2021 11/9/2021 11/09/2021
Misc
Corrective Action Required
11/02/2021
-pressure at 0 psi, Gas pressure must maintain 10 psi for test
Electrical Service Inspection Passed 11/9/2021 11/9/2021 11/09/2021
Misc
Resolved
11/09/2021
- color code GEC at service panel
All Rough Inspection - Residential Failed 11/9/2021 11/9/2021 11/09/2021
Misc
Informational
11/02/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
11/02/2021
-seal all top plate penetrations - garage -dryer duct over max length -install bedroom windows -CS-PF bracing per plans at dining room windows -Fireblock between top plates at finished basement -Fireblock between studs at bump out top plate basement -Fireblock vertical to horizontal at furred down soffit ends - remove Kraft paper from insulation used as fireblock
All Rough Inspection - Residential Failed 11/12/2021 11/12/2021 11/11/2021
Misc
Informational
11/09/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
11/09/2021
-install bedroom windows -CS-PF bracing per plans at dining room windows - nailing at exterior sheathing per plans, see IRC 602.10.6.4, min overlap at band rim joist w/ 8D nailing 3" oc at top and bottom of band/rim joist, install tension straps at top plate/header/jack stud per plans/code **OK TO INSULATE**
Gas Service Inspection - Residential Passed 11/16/2021 11/16/2021 11/16/2021
Misc
Resolved
11/16/2021
-pressure at 0 psi, Gas pressure must maintain 10 psi for test
All Rough Inspection - Residential Failed 11/16/2021 11/16/2021 11/16/2021
Misc
Informational
11/11/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
11/11/2021
-install bedroom windows **OK TO INSULATE AND ROCK**
All Rough Inspection - Residential Passed 12/7/2021 12/7/2021 12/07/2021
Misc
Informational
11/16/2021
-GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Resolved
12/07/2021
-install bedroom windows **OK TO INSULATE AND ROCK**
Plot Plan Inspection Passed 1/28/2022 01/28/2022
Erosion Control Inspection Residential Failed 2/1/2022 02/01/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/01/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
02/01/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Failed 2/1/2022 2/1/2022 02/01/2022
Misc
Corrective Action Required
02/01/2022
*inspection denied* -no premises identification -erosion control not in compliance Mitchell Schwarz 02/01/2022 9:12 AM
Piers/Caissons Inspection - Residential Passed 2/2/2022 02/02/2022
Misc
Informational
02/02/2022
addressed in third party footing inspection
Occupancy Inspection - Codes Residential Failed 2/2/2022 2/2/2022 02/02/2022
Misc
Resolved
02/02/2022
*inspection denied* -no premises identification -erosion control not in compliance Mitchell Schwarz 02/01/2022 9:12 AM
Misc
Corrective Action Required
02/02/2022
-sod -check water meter and siding from ground at time of sod -seal top of meter can, A/c disconnect and all other exterior penetrations -splash blocks and sump pump discharge to extend 36” from foundation -obtain lawn irrigation permit -address master bedroom broken window W wall -open junction box in mast bath -remove dust covers for all smoke detectors -address exhaust vent for furnace open Y -back patio light to be of the sealed type -(2) 1/2” through bolts at deck post to beam connections
Occupancy Inspection - Codes Residential Temporary C of O 2/22/2022 2/22/2022 02/22/2022
Misc
Corrective Action Required
02/02/2022
TCO UNTIL 3/22/22 -sod -check water meter and siding from ground at time of sod -splash blocks and sump pump discharge to extend 36” from foundation -obtain lawn irrigation permit
Erosion Control Inspection Residential Failed 2/22/2022 02/22/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/22/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Misc
Corrective Action Required
02/22/2022
MAINTAIN EROSION CONTROL AT FRONT LEFT OF SIDE OF LOT.
Occupancy Inspection - Codes Residential Temporary C of O 3/23/2022 03/23/2022
Misc
Corrective Action Required
02/22/2022
TCO UNTIL 3/22/22 spoke with connor with Summit Homes. Requested a TCO Extension 04/08/22 -sod -check water meter and siding from ground at time of sod -splash blocks and sump pump discharge to extend 36” from foundation -obtain lawn irrigation permit
Erosion Control Inspection Residential Failed 3/30/2022 03/30/2022
Misc
Resolved
03/30/2022
MAINTAIN EROSION CONTROL AT FRONT LEFT OF SIDE OF LOT.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/30/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. address silt fence at back of lot
Occupancy Inspection - Codes Residential Temporary C of O 4/8/2022 04/08/2022
Misc
Corrective Action Required
03/23/2022
TCO UNTIL 3/22/22 spoke with connor with Summit Homes. Requested a TCO Extension 04/08/22 Spoke with ethan with summit homes. requesteed a TCO extension, TCO extened until 4/14/22 -sod -check water meter and siding from ground at time of sod -splash blocks and sump pump discharge to extend 36” from foundation -obtain lawn irrigation permit
Occupancy Inspection - Codes Residential Failed 4/11/2022 4/11/2022 04/11/2022
Misc
Corrective Action Required
04/08/2022
TCO UNTIL 3/22/22 spoke with connor with Summit Homes. Requested a TCO Extension 04/08/22 Spoke with ethan with summit homes. requesteed a TCO extension, TCO extened until 4/14/22 -resolve outstanding inspection fee -final sidewalk and driveway inspection required, contact development services to schedule -lower water meter lid to grade, maintain required 14" - 18" clearance from top of meter to top of lid
Occupancy Inspection - Codes Residential Not Ready 4/12/2022 4/13/2022 04/13/2022
Misc
Corrective Action Required
04/11/2022
4/12/22 - RESCHEDULE INSPECTION WHEN ALL CORRECTIONS COMPLETE Spoke with ethan with summit homes. requesteed a TCO extension, TCO extened until 4/14/22 -resolve outstanding inspection fee -final sidewalk and driveway inspection required, contact development services to schedule -lower water meter lid to grade, maintain required 14" - 18" clearance from top of meter to top of lid ****4/13/22- NO ITEMS FROM THIS LIST HAVE BEEN ADDRESSED, NOT READY FEE ACCESSED
Driveway Inspection Passed 4/13/2022 4/13/2022 04/13/2022
Misc
Informational
04/13/2022
On Wednesday 4-13-2022 I visually viewed and driveway that was already poured. The finish and configuration pass city spec’s.
Sidewalk Inspection Passed 4/13/2022 4/13/2022 04/13/2022
Misc
Informational
04/13/2022
On Wednesday 4-13-2022 I viewed sidewalk already completed and it passes city spec’s for forming and finishing.
Occupancy Inspection - Codes Residential Failed 4/18/2022 4/18/2022 04/18/2022
Misc
Corrective Action Required
04/12/2022
4/12/22 - RESCHEDULE INSPECTION WHEN ALL CORRECTIONS COMPLETE Spoke with ethan with summit homes. requesteed a TCO extension, TCO extened until 4/14/22 -lower water meter lid to grade, maintain required 14" - 18" clearance from top of meter to top of lid
Erosion Control Inspection Residential Passed 4/18/2022 04/18/2022
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
03/30/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. address silt fence at back of lot
Occupancy Inspection - Codes Residential Full C of O 4/25/2022 4/25/2022 04/25/2022
Documents & Images
Date Uploaded File Type Document Name
05/14/2021 157 hawthorne ridge roof layout
05/14/2021 HT #157 - PERMIT APP
05/14/2021 210410
05/14/2021 HT #157 - Newhaven - Farmhouse - Sheets- signed
05/14/2021 LOT 157 FINAL
05/14/2021 Approved Plans APPROVED PLANS
05/14/2021 Approved Plans APPROVED TRUSS DRAWINGS
05/14/2021 Approved Plans APPROVED TRUSS LAYOUT
05/14/2021 Plot Plan APPROVED PLOT PLAN
05/14/2021 Permit Codes Residential Plan Review
05/14/2021 Permit DS Building Permit
05/14/2021 Receipt Receipt for transaction:2021-003031
06/17/2021 Lot 157 Hawthorne Ridge Footing Inspection
06/18/2021 Letter INSPECTION SUMMARY
07/19/2021 Letter INSPECTION SUMMARY
07/22/2021 Letter INSPECTION SUMMARY
08/10/2021 Letter INSPECTION SUMMARY
08/27/2021 Letter INSPECTION SUMMARY
08/31/2021 Letter INSPECTION SUMMARY
08/31/2021 Letter INSPECTION SUMMARY
11/02/2021 Engineer Report/Study TRUSS REPAIR
11/02/2021 Letter INSPECTION SUMMARY
11/02/2021 Letter INSPECTION SUMMARY
11/02/2021 Letter INSPECTION SUMMARY
11/08/2021 157 Hawthorne Ridge Holes in Studs and notched floor joists letter
11/09/2021 Letter INSPECTION SUMMARY
11/09/2021 Letter INSPECTION SUMMARY
11/09/2021 Letter INSPECTION SUMMARY
11/11/2021 Letter INSPECTION SUMMARY
11/16/2021 Letter INSPECTION SUMMARY
11/16/2021 Letter INSPECTION SUMMARY
12/07/2021 Letter INSPECTION SUMMARY
01/26/2022 Plot Plan APPROVED AS GRADED PLOT PLAN
01/31/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
02/01/2022 Letter INSPECTION SUMMARY
02/02/2022 Letter INSPECTION SUMMARY
02/02/2022 Letter INSPECTION SUMMARY
02/22/2022 Letter Codes Temporary Certificate of Occupancy
02/22/2022 Letter INSPECTION SUMMARY
03/23/2022 Letter Codes Temporary Certificate of Occupancy
03/30/2022 Letter INSPECTION SUMMARY
04/08/2022 Letter Codes Temporary Certificate of Occupancy
04/11/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter INSPECTION SUMMARY
04/13/2022 Letter INSPECTION SUMMARY
04/13/2022 Receipt Receipt for transaction:2022-002045
04/13/2022 Letter INSPECTION SUMMARY
04/13/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter INSPECTION SUMMARY
04/18/2022 Letter INSPECTION SUMMARY
04/25/2022 Letter Codes Final Certificate of Occupancy
04/25/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home