Permit Application Status

PRCOM20245945


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20245945
Building Permit - Commercial
Issued
CURRY INVESTMENT COMPANY
CHANGE OF TENANT
DRAGON J - CHANGE OF TENANT FOR NEW RESTAURANT
11/13/2024
03/03/2025
08/09/2025
Locations
Contacts
CURRY INVESTMENT COMPANY, Address:2700 KENDALLWOOD PKWY STE 208  
STEPHEN MASLAN & COMPANY, Address:8011 PASEO, Phone:(816) 444-6260  
Stephen Maslan - Stephen Maslon & Company, Address:8011 Paseo Suite 201, Phone:(816) 547-8243  
ATLAS MECHANICAL SERVICES INC, Address:26015 RA HWY, Phone:(913) 708-4695  
G.J. ELECTRIC, Address:1511 DOC HENRY RD, Phone:(816) 537-3094  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
CORNERSTONE ARCHITECT LLC, Address:8117 ROBERTS RD, Phone:(816) 838-3472  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 03/04/2025 02/28/2025
Joe Frogge
Health Dept Inspection
Corrective Action Required
02/25/2025

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 2/10/2025 - Not addressed.
IBC 1606.2 Design dead load - structural
Resolved
02/28/2025

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new equipment. 2/10/2025 - Not addressed.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
02/25/2025

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) on roof within 25' of new equipment or provide verification of existing. 2/10/2025 - Not addressed. Receptacle provided for one RTU but exhaust fans and condensing unit are not covered. 2/28/2025 - Plans unclear as to equipment and receptacle locations. To be field verified.
Licensed Contractors Approved 03/04/2025 02/28/2025
Joe Frogge
Fire Plan Review Approved 03/04/2025 02/25/2025
Craig Hill
Building Plan Review Rejected 02/11/2025 02/10/2025
Joe Frogge
Health Dept Inspection
Corrective Action Required
02/04/2025

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational. 2/10/2025 - Not addressed.
IBC 1606.2 Design dead load - structural
Corrective Action Required
02/04/2025

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new equipment. 2/10/2025 - Not addressed.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
02/04/2025

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) on roof within 25' of new equipment or provide verification of existing. 2/10/2025 - Not addressed. Receptacle provided for one RTU but exhaust fans and condensing unit are not covered.
Misc
Resolved
02/05/2025

Unable to verify pipe materials. (we need to make sure no plastic in plenum) Action required: Provide pipe material schedule.
IPC 802.1 Indirect/special waste
Resolved
02/05/2025

2018 IPC 1003.3.8 Direct connection. The discharge piping from a grease interceptor shall be directly connected to the sanitary drainage system. Action required: Amend designs to comply. Grease interceptors must be hard piped into drainage system. 3-compartment sinks to be indirectly connected to interceptor per IPC 802.1.
Fire Plan Review Approved 02/11/2025 02/10/2025
Craig Hill
Licensed Contractors Approved 02/11/2025 02/05/2025
Joe Frogge
Licensed Contractors Approved 11/25/2024 12/05/2024
Joe Frogge
LC - General Contractor
Resolved
12/05/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
LC - MEP Subs
Resolved
12/05/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Approved 11/25/2024 11/25/2024
Craig Hill
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
11/25/2024

2018 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Portable fire extinguishers - general
Corrective Action Required
11/25/2024

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
11/25/2024

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel.
Health Department Review Approved 11/25/2024
Joe Frogge
Building Plan Review Rejected 11/25/2024 11/21/2024
Joe Frogge
Health Dept Review
Resolved
11/25/2024

For the Health Department review contact Deb Sees with the Jackson County Public Works Department, Environmental Services Division, at (816) 797-7162. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required: Comment is informational.
Health Dept Inspection
Corrective Action Required
11/21/2024

For the Health Department inspection contact Deb Sees with the Jackson County Public Works Department, Environmental Health Division at (816) 797-7162. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required: Comment is informational.
IBC 1606.2 Design dead load - structural
Corrective Action Required
11/21/2024

2018 IBC 1606.2 Design dead load. For purposes of design, the actual weights of materials of construction and fixed service equipment shall be used. In the absence of definite information, values used shall be subject to the approval of the building official. Action required: Provide engineer’s report to verify that existing roof structure will support additional load imposed by new equipment.
NEC Article 210.63 Heating, air-conditioning and refrigeration outlet
Corrective Action Required
11/21/2024

2017 NEC Article 210.63 Heating, Air-Conditioning, and Refrigeration Equipment Outlet. A 125-volt, single-phase, 15- or 20-ampere-rated receptacle outlet shall be installed at an accessible location for the servicing of heating, air-conditioning, and refrigeration equipment. The receptacle shall be located on the same level and within 25 feet of the heating, air-conditioning, and refrigeration equipment. The receptacle outlet shall not be connected to the load side of the equipment disconnecting means. Action required: Provide receptacle(s) on roof within 25' of new equipment or provide verification of existing.
Misc
Corrective Action Required
11/21/2024

Unable to verify pipe materials. (we need to make sure no plastic in plenum) Action required: Provide pipe material schedule.
IPC 802.1 Indirect/special waste
Corrective Action Required
11/21/2024

2018 IPC 1003.3.8 Direct connection. The discharge piping from a grease interceptor shall be directly connected to the sanitary drainage system. Action required: Amend designs to comply. Grease interceptors must be hard piped into drainage system. 3-compartment sinks to be indirectly connected to interceptor per IPC 802.1.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $480.00 $480.00 Paid 02/28/2025
$6,798.00
7232302-Commercial License Tax Fee $3,399.00 $3,399.00 Paid 11/14/2024
$3,399.00
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Pending
Alternate Protection Systems Inspection Pending
Miscellaneous Inspection Pending 5/9/2025
In-wall Inspection Failed 4/1/2025 4/1/2025 04/01/2025
Misc
Corrective Action Required
04/01/2025
-Complete all in wall MEPs -Complete installation of welded tube steel supports -Provide structural detail referenced on plans -Fur out wall at demising wall not shown on plans and is 25g. (plans state all walls to be w1 (20g) or W2(18g)
Underslab Plumbing Inspection - Commercial Failed 04/04/2025
Misc
Corrective Action Required
04/04/2025
Underslab plumbing does not match plans -Hand sink and cleanout at end of line not installed. Grease interceptor at wok not installed
In-wall Inspection Failed 4/17/2025 4/17/2025 04/17/2025
Misc
Corrective Action Required
04/17/2025
-Complete all in wall MEPs -Complete installation of welded tube steel supports -Provide structural detail referenced on plans -Fur out wall at demising wall not shown on plans and is 25g. (plans state all walls to be w1 (20g) or W2(18g)
Misc
Corrective Action Required
04/17/2025
4/17/25 No access. Provide lockbox code for inspections. No further inspections will be performed until plans have been updated and approved, engineering changes have been submitted and approved or installation matches approved plans
In-wall Inspection Partial 4/22/2025 4/22/2025 04/22/2025
Misc
Corrective Action Required
04/17/2025
-In wall MEPs not complete **OK to cover top of furout wall for hood
Misc
Resolved
04/22/2025
4/17/25 No access. Provide lockbox code for inspections. No further inspections will be performed until plans have been updated and approved, engineering changes have been submitted and approved or installation matches approved plans
Underslab Plumbing Inspection - Commercial Passed 4/22/2025 4/22/2025 04/22/2025
Misc
Resolved
04/22/2025
Underslab plumbing does not match plans -Hand sink and cleanout at end of line not installed. Grease interceptor at wok not installed
In-wall Inspection Failed 4/29/2025 4/29/2025 04/29/2025
Misc
Corrective Action Required
04/22/2025
-In wall MEPs not complete **OK to cover top of furout wall for hood -Complete plumbing for hand sink, protect dwv in bathroom
In-wall Inspection Passed 5/1/2025 5/1/2025 05/01/2025
Misc
Resolved
05/01/2025
-In wall MEPs not complete **OK to cover top of furout wall for hood -Complete plumbing for hand sink, protect dwv in bathroom
Hood/Duct Inspection Partial 5/9/2025 5/9/2025 05/09/2025
Misc
Informational
05/09/2025
-Light test approved
Hood/Duct Inspection Passed 5/12/2025 5/12/2025 05/12/2025
Misc
Resolved
05/12/2025
-Light test approved
Documents & Images
Date Uploaded File Type Document Name
11/13/2024 Application Form APPLICATION
11/13/2024 Engineer Report/Study GREASE INTERCEPTOR SPEC SHEET - DRAGON J
11/13/2024 Engineer Report/Study LARKEN HOOD CUT SHEET - DRAGON J
11/13/2024 Plans HOOD DRAWING SET - DRAGON J
11/14/2024 Letter License Tax Bill
11/21/2024 Plans FULL DRAWING SET - DRAGON J - 112124
11/25/2024 Letter Health Dept approval
11/26/2024 Letter DS P/R Corrections Document
02/04/2025 Plans Change Order - Dragon J @ Lee Summit
02/10/2025 Letter DS P/R Corrections Document
02/25/2025 Plans Change Order 2 - Dragon J @ Lee Summit
02/25/2025 Letter Response to City Comments 021025
02/28/2025 Engineer Report/Study Engineer letter
02/28/2025 Approved Plans Approved construction plans
02/28/2025 Receipt Receipt for transaction:2025-001221
03/03/2025 Letter DS Building Permit
04/04/2025 Letter INSPECTION SUMMARY
04/04/2025 Letter INSPECTION SUMMARY
04/17/2025 Letter INSPECTION SUMMARY
04/18/2025 Engineer Report/Study 204 NW Oldham Parkway - Framing Inspection
04/18/2025 Drawing 24-242_MP300
04/21/2025 Approved Plans Approved MP300 revision
04/22/2025 Letter INSPECTION SUMMARY
04/22/2025 Letter INSPECTION SUMMARY
04/29/2025 Letter INSPECTION SUMMARY
05/01/2025 Letter INSPECTION SUMMARY
05/09/2025 Letter INSPECTION SUMMARY
05/12/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home