Permit Application Status

PRCOM20245463


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20245463
Building Permit - Commercial
Issued - Partial
AURION LC
NEW COMMERCIAL
ASSOCIATED PLASTIC SURGEONS - NEW MEDICAL BUILDING Permit released for site-related work and foundations only. Currently under review for shell only - Infill plans to be submitted at future date
10/16/2024
09/23/2025
Locations
Contacts
DEV INC, Address:8807 MONROVIA ST, Phone:(913) 322-8882  
Kevin Campbell - Dev Inc, Address:8807 Monrovia St., Phone:(913) 322-8882  
MAGNUM PLUMBING LLC, Address:1100 S WINTERBROOKE DR., Phone:(913) 461-8645  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
MAGNUM PLUMBING LLC, Address:1100 S WINTERBROOKE DR., Phone:(913) 461-8645  
Kevin Campbell - Dev Inc, Address:8807 Monrovia St., Phone:(913) 322-8882  
ALPHA-OMEGA GEOTECH, Address:1701 STATE AVE, Phone:(913) 371-0000  
AURION LC, Address:11501 GRANADA LN  
K & J EXCAVATING LLC, Address:16405 E ST. RT. 2 HWY , Phone:(816) 884-3452  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 04/23/2025 04/23/2025
Joe Frogge
LC - MEP Subs
Resolved
04/23/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/27/2025 - Acknowledged in letter. 4/21/2025 - Palmer Electric not licensed with us. Permit not allowed to be issued without full list of MEP subs.
Fire Plan Review Approved 04/23/2025 04/23/2025
Craig Hill
Construction documents for fire alarm systems
Informational
04/16/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarn system.
Construction documents - Fire protection systems
Informational
04/16/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Alarms connected to automatic sprinkler system
Informational
04/16/2025

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Informational only.
Misc
Resolved
04/23/2025

Action required: Provide location of emergency lighting other than exits.
Miscellaneous Correction
Resolved
04/23/2025

Action required: Provide location of exit lights other than at the exit doors.
Building Plan Review Approved with Conditions 04/23/2025 04/21/2025
Joe Frogge
License Tax - Payment
Corrective Action Required
04/16/2025

A one-time impact fee in the form of a license/excise tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $31,605.25 3/27/2025 - Acknowledged in letter.
Building Plan Review Approved with Conditions 03/28/2025 03/27/2025
Joe Frogge
Final Development Plan
Resolved
03/27/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
License Tax - Payment
Corrective Action Required
03/24/2025

A one-time impact fee in the form of a license/excise tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $31,605.25 3/27/2025 - Acknowledged in letter.
IPC 708.1 Cleanouts required
Resolved
03/27/2025

2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11. 2018 IPC 708.1.1 Horizontal drains within buildings. Horizontal drainage pipes in buildings shall have cleanouts located at intervals of not more than 100 feet. Building drains shall have cleanouts located at intervals of not more than 100 feet apart except where manholes are used instead of cleanouts, the manholes hall be located at intervals of not more than 400 feet. The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, the end of the horizontal drain or the end of the building drain. (see code for exception) 2018 IPC 708.1.2 Building sewers. Building sewers smaller than 8 inches shall have cleanouts located at intervals of not more than 100 feet. Building sewers 8 inches and larger shall have a manhole located not more than 200 feet from the junction of the building drain and the building sewer and at intervals of not more than 400 feet. The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, a manhole or the end of the building sewer. 2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access. 2018 IPC 708.1.4 Changes of direction. Where a horizontal drainage pipe, a building drain or a building sewer has a change of horizontal direction greater than 45 degrees, a cleanout shall be installed at the change of direction. Where more than one change of horizontal direction greater than 45 degrees occurs within 40 feet of developed length of piping, the cleanout installed for the first change of direction shall serve as the cleanout for all changes in direction within that 40 feet of developed length of piping. Action required: Provide cleanout near where sanitary leaves building.
IMC 606.2.1 Duct detector
Resolved
03/27/2025

2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Update RTU schedule to show smoke detectors at RTU-7.
NEC Article 110.26 (C)(2) Large equipment
Resolved
03/27/2025

2017 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic hardware. Action required: Provide panic hardware at door 03 out of Electrical Room.
NEC Article 250.50 Grounding electrode system
Resolved
03/27/2025

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide grounding electrode to water service entry.
Licensed Contractors Rejected 03/28/2025 03/27/2025
Joe Frogge
LC - MEP Subs
Corrective Action Required
03/24/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors. 3/27/2025 - Acknowledged in letter.
Fire Plan Review Rejected 03/28/2025 03/26/2025
Craig Hill
Construction documents for fire alarm systems
Informational
03/26/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarn system.
Construction documents - Fire protection systems
Informational
03/26/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Alarms connected to automatic sprinkler system
Informational
03/26/2025

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Informational only.
Portable fire extinguishers - general
Resolved
03/26/2025

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide location of extinguishers
Portable fire extinguishers - conspicuous locations
Resolved
03/26/2025

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Provide location of extinguishers.
Misc
Corrective Action Required
03/24/2025

Action required: Provide location of emergency lighting other than exits.
Miscellaneous Correction
Corrective Action Required
03/24/2025

Action required: Provide location of exit lights other than at the exit doors.
Licensed Contractors Rejected 02/18/2025 02/18/2025
Joe Frogge
LC - General Contractor
Resolved
02/18/2025

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
LC - MEP Subs
Corrective Action Required
02/04/2025

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Fire Plan Review Rejected 02/18/2025 02/18/2025
Craig Hill
Construction documents for fire alarm systems
Corrective Action Required
02/18/2025

2018 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide deferred submittal for alarn system.
Construction documents - Fire protection systems
Corrective Action Required
02/18/2025

2018 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide deferred submittal for protection system.
Alarms connected to automatic sprinkler system
Corrective Action Required
02/18/2025

2018 IFC 903.4.2- Alarms. Approved audible and visual devices shall be connected to every automatic sprinkler system. Such sprinkler water-flow alarm devices shall be activated by water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. Listed alarm notification devices shall be provided on the exterior and interior of the building in an approved location. Where a fire alarm system is installed, actuation of the automatic sprinkler system shall actuate the building fire alarm system. Informational only.
Portable fire extinguishers - general
Corrective Action Required
02/18/2025

2018 IFC 906.2- General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide location of extinguishers
Portable fire extinguishers - conspicuous locations
Corrective Action Required
02/18/2025

2018 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action Required: Provide location of extinguishers.
Misc
Corrective Action Required
02/18/2025

Action required: Provide location of emergency lighting other than exits.
Miscellaneous Correction
Corrective Action Required
02/18/2025

Action required: Provide location of exit lights other than at the exit doors.
Building Plan Review Rejected 02/18/2025 02/11/2025
Joe Frogge
Final Development Plan
Corrective Action Required
02/11/2025

The building permit for this project cannot be issued until the Development Services Department has received, approved, and processed the Final Development Plan. Action required: Comment is informational.
License Tax - Payment
Corrective Action Required
02/11/2025

A one-time impact fee in the form of a license/excise tax must be collected before occupancy can be granted. Please be advised that additional application, review, and inspection fees do apply and additional information pertaining to this will be provided during that stage of your approval process. Action required: Comment is for informational purposes. The fee will be $31,605.25
IPC 708.1 Cleanouts required
Corrective Action Required
02/11/2025

2018 IPC 708.1 Cleanouts Required. Cleanouts shall be provided for drainage piping in accordance with Sections 708.1.1 through 708.1.11. 2018 IPC 708.1.1 Horizontal drains within buildings. Horizontal drainage pipes in buildings shall have cleanouts located at intervals of not more than 100 feet. Building drains shall have cleanouts located at intervals of not more than 100 feet apart except where manholes are used instead of cleanouts, the manholes hall be located at intervals of not more than 400 feet. The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, the end of the horizontal drain or the end of the building drain. (see code for exception) 2018 IPC 708.1.2 Building sewers. Building sewers smaller than 8 inches shall have cleanouts located at intervals of not more than 100 feet. Building sewers 8 inches and larger shall have a manhole located not more than 200 feet from the junction of the building drain and the building sewer and at intervals of not more than 400 feet. The interval length shall be measured from the cleanout or manhole opening, along the developed length of the piping to the next drainage fitting providing access for cleaning, a manhole or the end of the building sewer. 2018 IPC 708.1.3 Building drain and building sewer junction. The junction of the building drain and the building sewer shall be served by a cleanout that is located at the junction or within 10 feet of the developed length of piping upstream of the junction. For the requirements of this section, the removal of a water closet shall not be required to provide cleanout access. 2018 IPC 708.1.4 Changes of direction. Where a horizontal drainage pipe, a building drain or a building sewer has a change of horizontal direction greater than 45 degrees, a cleanout shall be installed at the change of direction. Where more than one change of horizontal direction greater than 45 degrees occurs within 40 feet of developed length of piping, the cleanout installed for the first change of direction shall serve as the cleanout for all changes in direction within that 40 feet of developed length of piping. Action required: Provide cleanout near where sanitary leaves building.
IMC 606.2.1 Duct detector
Corrective Action Required
02/11/2025

2018 IMC 606.2.1 Return air systems. Smoke detectors shall be installed in return air systems with a design capacity greater than 2,000 cfm, in the return air duct or plenum upstream of any filters, exhaust air connections, outdoor air connections, or decontamination equipment and appliances. Exception: Smoke detectors are not required in the return air system where all portions of the building served by the air distribution system are protected by area smoke detectors connected to a fire alarm system in accordance with the International Fire Code. The area smoke detection system shall comply with Section 606.4. Action required: Update RTU schedule to show smoke detectors at RTU-7.
NEC Article 110.26 (C)(2) Large equipment
Corrective Action Required
02/11/2025

2017 NEC Article 110.26 (C)(3) Personnel Doors. Where equipment rated 800 A or more that contains overcurrent devices, switching devices, or control devices is installed and there is a personnel door(s) intended for entrance to and egress from the working space less than 25 feet from the nearest edge of the working space, the door(s) shall open in the direction of egress and be equipped with panic hardware. Action required: Provide panic hardware at door 03 out of Electrical Room.
NEC Article 250.50 Grounding electrode system
Corrective Action Required
02/11/2025

2017 NEC Article 250.50 Grounding Electrode System. All Grounding electrodes as described in 250.52(A)(1) through (A)(7) that are present at each building or structure served shall be bonded together to form the grounding electrodes system. Where none of these grounding electrodes exist, one or more of the grounding electrodes specified in 250.52(A)(4) through (A)(8) shall be installed and used. (see code section for exception) Action required: Provide grounding electrode to water service entry.
Building Plan Review Approved with Conditions 02/11/2025
Joe Frogge
Misc
Corrective Action Required
11/15/2024

This review is for foundations only. Architectural designs have not been reviewed during this process. Action required: Comment is informational.
Licensed Contractors Rejected 11/21/2024 11/15/2024
Joe Frogge
LC - General Contractor
Corrective Action Required
11/15/2024

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawful for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required: Either a Class A or Class B license is required. Provide the company name of the licensed general contractor and the name, email address & phone number for the on-site contact.
LC - MEP Subs
Corrective Action Required
11/15/2024

Lee's Summit Code of Ordinance, Section7-130.4 - Business License. (excerpt) No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Action required: MEP subcontractors are required to be listed on permit. Provide company names of licensed MEP contractors.
Final Development Plan Review Approved 11/21/2024 11/14/2024
Scott Ready
Special Inspections Review Approved 10/30/2024 11/14/2024
Joe Frogge
Alarm Plan Review Pending
Craig Hill
Sprinkler Plan Review Pending
Craig Hill
Fees
Paid Fees Amount Paid Owing Date Paid
91100C8-Sanitary Sewer Insp Fees $155.08 $155.08 Paid 10/29/2024
91100C9-Water Insp Fee $1,370.08 $1,370.08 Paid 10/29/2024
9110068-Storm Fee $1,359.29 $1,359.29 Paid 10/29/2024
9110081-Paved Surface Inspection Fee $4,694.61 $4,694.61 Paid 10/29/2024
9110071-Site Grading Fee $755.92 $755.92 Paid 10/29/2024
9110072-Water Test Fee $200.00 $200.00 Paid 10/29/2024
8350015-Water Meter Fee $5,196.16 $5,196.16 Paid 10/29/2024
8331401-Water Tap Fee $23,840.00 $23,840.00 Paid 10/29/2024
8331507-Sanitary Sewer Development Fee $7,609.00 $7,609.00 Paid 10/29/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 10/29/2024
9110078-Valuation Fee for New Commercial $1,519.56 $1,519.56 Paid 11/25/2024
9110078-Valuation Fee for New Shell Building $6,800.44 $6,800.44 Paid 04/29/2025
Outstanding Fees Amount Paid Owing Date Paid
7232302-Commercial License Tax Fee $31,605.75 $0.00 $31,605.75 Not Paid


$31,605.75    Add Fees to My Cart
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Water Line - Construction Inspection Pending
Sanitary Sewer Construction Inspection Pending
Sanitary - Material Verification Pending
Sanitary Sewer - Air Test Pending
Sanitary Sewer - Mandrel Pending
Sanitary Sewer - Vacuum Pending
Pavement-Proof Roll Pending
Pavement-Surface Pending
Pavement-Aggregate Base Pending
Pavement-Curb Construction Pending
Pavement-Stabilized Subgrade Pending
Storm Sewer Construction Inspection Pending
ESC - (Vegetation/Ground Cover) Pending
Misc
Informational
02/24/2025
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and grass has stopped growing since it is winter 1-16-25 NS Site Visited and grass has stopped growing since it is winter 1-24-25 NS Site Visited and grass has stopped growing since it is winter 2-3-25 NS Site Visited and grass has stopped growing since it is winter 2-10-25 NS Site Visited and grass has stopped growing since it is winter 2-17-25 NS Site Visited and grass has stopped growing since it is winter 2-24-25 NS Site Visited and grass has stopped growing since it is winter
Site Visit Pending
Misc
Informational
02/28/2025
Plastic Surgery 12-13-24 NS Site Visited and crews have not started work. 12-31-24 NS Site visited it appears crews are working on sewer stub and could not find it and called water to come out and camera the lines for them. 1-31-25 NS Site visited crews are not working because of rain. 2-28-25 NS Site visited and it appears no work is being done since the last two weeks it has been snowing or to muddy we are waiting on the water department to do a water test shut off and the insurance building is the only building effected.
Footing Inspection - Commercial Pending
Misc
Corrective Action Required
03/26/2025
Exterior grade beam and column footing: -From E/2.7 to E/1 to B/1 to A/11 to C/11; rest of ext. footing with addition of F3 column footing at H/6 All interior footing
Erosion Control Inspection Pending
Misc
Informational
04/24/2025
Plastics Surgeon 12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues 1-31-25 NS Site Visited and still no erosion control issues 2-3-25 NS Site Visited and still no erosion control issues 2-10-25 NS Site Visited and still no erosion control issues 2-17-25 NS Site Visited and still no erosion control issues 2-24-25 NS Site Visited and still no erosion control issues 2-28-25 NS Site visited and it appears that no erosion control issues 3-08-25 NS visited the site and it appears that no erosion control problem 3-19-25 NS Went to the site and it appears that some fence has been nocked down and will be put back up 3-26-25 NS I went by and did not see any problems with the erosion control. 4-2-25 NS Work is going on, but they are keeping the site clean. 4-16-25 NS Went by and still everything is standing and no dirt or rock on road 4-24-25 NS Site visited, and it appears that no erosion control issues.
Water Service Inspection Pending 4/24/2025
Erosion Control Inspection Partial 12/13/2024 12/13/2024
Misc
Informational
12/13/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter.
ESC - (Vegetation/Ground Cover) Partial 12/13/2024 12/13/2024
Misc
Informational
12/13/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter.
Site Visit Partial 12/13/2024 12/13/2024
Misc
Informational
12/13/2024
12-13-24 NS Site Visited and crews have not started work.
Site Visit Partial 12/31/2024 12/31/2024
Misc
Informational
12/13/2024
Plastic Surgery 12-13-24 NS Site Visited and crews have not started work. 12-31-24 NS Site visited it appears crews are working on sewer stub and could not find it and called water to come out and camera the lines for them.
Erosion Control Inspection Partial 12/31/2024 12/31/2024
Misc
Informational
12/13/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter.
ESC - (Vegetation/Ground Cover) Partial 12/31/2024 12/31/2024
Misc
Informational
12/13/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter.
Erosion Control Inspection Partial 1/25/2025 01/25/2025
Misc
Informational
12/31/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues
ESC - (Vegetation/Ground Cover) Partial 1/25/2025 01/25/2025
Misc
Informational
12/31/2024
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and grass has stopped growing since it is winter 1-16-25 NS Site Visited and grass has stopped growing since it is winter 1-24-25 NS Site Visited and grass has stopped growing since it is winter
Erosion Control Inspection Partial 1/31/2025 01/31/2025
Misc
Informational
01/25/2025
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues 1-31-25 NS Site Visited and still no erosion control issues
Site Visit Partial 1/31/2025 01/31/2025
Misc
Informational
12/31/2024
Plastic Surgery 12-13-24 NS Site Visited and crews have not started work. 12-31-24 NS Site visited it appears crews are working on sewer stub and could not find it and called water to come out and camera the lines for them. 1-31-25 NS Site visited crews are not working because of rain.
Erosion Control Inspection Partial 2/24/2025 02/24/2025
Misc
Informational
01/31/2025
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues 1-31-25 NS Site Visited and still no erosion control issues 2-3-25 NS Site Visited and still no erosion control issues 2-10-25 NS Site Visited and still no erosion control issues 2-17-25 NS Site Visited and still no erosion control issues 2-24-25 NS Site Visited and still no erosion control issues
ESC - (Vegetation/Ground Cover) Partial 2/24/2025 02/24/2025
Misc
Informational
01/25/2025
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and grass has stopped growing since it is winter 1-16-25 NS Site Visited and grass has stopped growing since it is winter 1-24-25 NS Site Visited and grass has stopped growing since it is winter 2-3-25 NS Site Visited and grass has stopped growing since it is winter 2-10-25 NS Site Visited and grass has stopped growing since it is winter 2-17-25 NS Site Visited and grass has stopped growing since it is winter 2-24-25 NS Site Visited and grass has stopped growing since it is winter
Erosion Control Inspection Partial 2/28/2025 02/28/2025
Misc
Informational
02/24/2025
12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues 1-31-25 NS Site Visited and still no erosion control issues 2-3-25 NS Site Visited and still no erosion control issues 2-10-25 NS Site Visited and still no erosion control issues 2-17-25 NS Site Visited and still no erosion control issues 2-24-25 NS Site Visited and still no erosion control issues 2-28-25 NS Site visited and it appears that no erosion control issues
Site Visit Partial 2/28/2025 02/28/2025
Misc
Informational
01/31/2025
Plastic Surgery 12-13-24 NS Site Visited and crews have not started work. 12-31-24 NS Site visited it appears crews are working on sewer stub and could not find it and called water to come out and camera the lines for them. 1-31-25 NS Site visited crews are not working because of rain. 2-28-25 NS Site visited and it appears no work is being done since the last two weeks it has been snowing or to muddy we are waiting on the water department to do a water test shut off and the insurance building is the only building effected.
Footing Inspection - Commercial Partial 3/13/2025 3/13/2025 03/13/2025
Misc
Corrective Action Required
03/13/2025
Exterior grade beam and column footing: -From E/2.7 to E/1 to B/1 to A/11 to C/11
Footing Inspection - Commercial Partial 3/18/2025 3/18/2025 03/18/2025
Misc
Corrective Action Required
03/13/2025
Exterior grade beam and column footing: -From E/2.7 to E/1 to B/1 to A/11 to C/11; rest of ext. footing with addition of F3 column footing at H/6
Footing Inspection - Commercial Partial 3/25/2025 3/25/2025 03/25/2025
Misc
Corrective Action Required
03/18/2025
Exterior grade beam and column footing: -From E/2.7 to E/1 to B/1 to A/11 to C/11; rest of ext. footing with addition of F3 column footing at H/6 Interior footing: -All column footing, except the F4.0-E at E/8.
Footing Inspection - Commercial Partial 3/26/2025 03/26/2025
Misc
Corrective Action Required
03/25/2025
Exterior grade beam and column footing: -From E/2.7 to E/1 to B/1 to A/11 to C/11; rest of ext. footing with addition of F3 column footing at H/6 All interior footing
Erosion Control Inspection Partial 4/23/2025 04/24/2025
Misc
Informational
02/28/2025
Plastics Surgeon 12-13-24 NS Site Visited and grass has stopped growing since it is winter. 12-31-24 NS Site Visited and grass has stopped growing since it is winter. 1-10-25 NS Site Visited and still no erosion control issues 1-16-25 NS Site Visited and still no erosion control issues 1-24-25 NS Site Visited and still no erosion control issues 1-31-25 NS Site Visited and still no erosion control issues 2-3-25 NS Site Visited and still no erosion control issues 2-10-25 NS Site Visited and still no erosion control issues 2-17-25 NS Site Visited and still no erosion control issues 2-24-25 NS Site Visited and still no erosion control issues 2-28-25 NS Site visited and it appears that no erosion control issues 3-08-25 NS visited the site and it appears that no erosion control problem 3-19-25 NS Went to the site and it appears that some fence has been nocked down and will be put back up 3-26-25 NS I went by and did not see any problems with the erosion control. 4-2-25 NS Work is going on, but they are keeping the site clean. 4-16-25 NS Went by and still everything is standing and no dirt or rock on road 4-24-25 NS Site visited, and it appears that no erosion control issues.
Documents & Images
Date Uploaded File Type Document Name
10/16/2024 Approved Plans Approved FDP Full Plan Set_PL2024168_10.16.2024_Admin
10/29/2024 Receipt Receipt for transaction: 2024-008655
11/06/2024 Plans APS Foot Foundation-Permit Full Set
11/06/2024 Application Form APS-CITY APPLICATION
11/12/2024 Engineer Report/Study Associated Plastic Surgeons SI Engagement Letter
11/14/2024 Letter License Tax Bill
11/15/2024 Application Form Application-Footing Foundation
11/18/2024 Engineer Report/Study 240117_E_Plastic_Surgery_Lot_6_&_7_Geotechnical_Report
11/18/2024 Approved Plans Approved Foundation-only Plans
11/25/2024 Receipt Receipt for transaction:2024-009146
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/31/2024 Letter INSPECTION SUMMARY
12/31/2024 Letter INSPECTION SUMMARY
12/31/2024 Letter INSPECTION SUMMARY
01/25/2025 Letter INSPECTION SUMMARY
01/25/2025 Letter INSPECTION SUMMARY
01/31/2025 Letter INSPECTION SUMMARY
01/31/2025 Letter INSPECTION SUMMARY
02/04/2025 Plans APS-Permit Building Shell
02/04/2025 Application Form APS-Permit Application
02/04/2025 Engineer Report/Study APS-Structural Calcs
02/04/2025 Engineer Report/Study APS-GeoTech Report
02/18/2025 Letter DS P/R Corrections Document
02/24/2025 Letter INSPECTION SUMMARY
02/24/2025 Letter Codes Residential Plan Review
02/24/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
03/13/2025 Letter INSPECTION SUMMARY
03/18/2025 Letter INSPECTION SUMMARY
03/21/2025 Letter APS-City Response 01
03/21/2025 Plans APS-Rev 01-Affected Sheets
03/25/2025 Letter INSPECTION SUMMARY
03/26/2025 Letter INSPECTION SUMMARY
03/27/2025 Letter DS P/R Corrections Document
04/16/2025 Letter APS-City Response 02
04/16/2025 Drawing APS-Rev 02-Sheet E21S
04/24/2025 Letter INSPECTION SUMMARY
04/28/2025 Plans APS-Rev 02-Full Set
04/29/2025 Approved Plans Approved construction plans
04/29/2025 Receipt Receipt for transaction:2025-002677
Upload Documents
  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:
Browse..





    Portal Home