Planning Application Status

PL2021432




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2021432
Manor at Bailey Farms 1st Plat - Public Water Main
Engineering Plan Review
Engineering Plan Review
Approved
11/05/2021
CLAYTON PROPERTIES GROUP INC
Locations
Address
1513 SE FALLING STAR DR, LEES SUMMIT, MO 64081

Address
1509 SE FALLING STAR DR, LEES SUMMIT, MO 64081

Address
1405 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1409 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1413 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1416 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1412 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1408 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1404 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1324 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1320 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1316 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1312 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1308 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1304 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1309 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1313 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1317 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1508 SE FALLING STAR DR, LEES SUMMIT, MO 64081

Address
1512 SE FALLING STAR DR, LEES SUMMIT, MO 64081

Address
1517 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1513 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1509 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1505 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1232 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1228 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1224 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1220 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1216 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1212 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1208 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1204 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1142 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1138 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1134 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1130 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1126 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1122 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1105 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1109 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1113 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1117 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1121 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1131 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1141 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Address
1508 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1512 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1516 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1520 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1521 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1517 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1513 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1509 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1505 SE SWEET ROOT DR, LEES SUMMIT, MO 64081

Address
1504 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1508 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1512 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1516 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1513 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1509 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1505 SE RISING SUN DR, LEES SUMMIT, MO 64081

Address
1504 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1508 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1512 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1516 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1451 SE BAILEY FARMS PKWY, LEES SUMMIT, MO 64081

Address
1420 SE RANSON RD, LEES SUMMIT, MO 64081

Property
337011

Property
337012

Property
337013

Property
337019

Property
337020

Property
337021

Property
337022

Property
337023

Property
337024

Property
337025

Property
337026

Property
337027

Property
337028

Property
337029

Property
337030

Property
337031

Property
337032

Property
337033

Property
337034

Property
337035

Property
337036

Property
337037

Property
337038

Property
337039

Property
337040

Property
337041

Property
337042

Property
337043

Property
337044

Property
337045

Property
337046

Property
337047

Property
337048

Property
337049

Property
337050

Property
337051

Property
337052

Property
337053

Property
337054

Property
337055

Property
337056

Property
337057

Property
337058

Property
337059

Property
337060

Property
337061

Property
337062

Property
337063

Property
337064

Property
337065

Property
337066

Property
337067

Property
337069

Property
337070

Property
337071

Property
337072

Property
337073

Property
337074

Property
337075

Property
337076

Property
337077

Property
337078

Property
337079

Property
337080

Property
337081

Property
337082

Property
337083

Property
337084

Address
1100 SE RANCHLAND ST, LEES SUMMIT, MO 64081

Contacts
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
SCHLAGEL & ASSOCIATES, Address:14920 W 107TH ST, Phone:(913) 492-5158  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 05/22/2025 05/23/2025
Gene Williams, P.E.
Engineering Review Approved with Conditions 12/14/2023 12/14/2023
Gene Williams, P.E.
Engineering Review No Comments 11/13/2023 11/13/2023
Gene Williams, P.E.
Engineering Review No Comments 07/15/2022 07/08/2022
Gene Williams, P.E.
Engineering Review No Comments 05/11/2022 05/11/2022
Gene Williams, P.E.
Engineering Review Corrections 02/14/2022 02/15/2022
Gene Williams, P.E.
Corrective Action Required
02/15/2022

Where depth of cover over the top of water mains exceeds 7.0 feet, a waiver is required prior to approval of the plans. The waiver shall be submitted on forms provided by the City under separate cover, and shall provide the citation within the Design and Construction Manual to be waived. The form shall have an attachment which includes a brief summary of the waiver, the location of the excessive depth of cover, the actions that were taken during design to eliminate the depth of cover issues, and the rationale behind the waiver request. Finally, an exhibit showing the plan and profile of the location in question shall be provided. A waiver is required for each location where depth of cover is greater than 7.0 feet, so it appears there will be 8 separate waivers required for this project.
Corrective Action Required
02/15/2022

Please refer to comment 33 in previous applicant letter. Trenching and backfill detail is showing 6 inches over top of pipe for aggregate backfill. The City changed this requirement in July 2020 to 12 inch minimum. Please revise.
Engineering Review Corrections 11/19/2021 11/19/2021
Gene Williams, P.E.
Corrective Action Required
11/19/2021

Tri County Water Authority (TCWA) may have issues with the expanded right of way along Ranson Rd., and may require additional easement for their line and/or relocation of their line. Please coordinate with TCWA (John Overstreet) on this issue, as it may affect lot placement, right of way, off-site traffic improvements on Ranson Rd., or other effects.
Corrective Action Required
11/19/2021

Fire hydrant is too close to the PC at Ranchland St. and Cape Dr. The minimum distance is 20 feet as measured from the PC of the curb return.
Corrective Action Required
11/19/2021

A fire hydrant is required on Sweet Root Dr. Distance requirements cannot include adjacent streets, hence the requirement for a fire hydrant along Sweet Root Dr.
Corrective Action Required
11/19/2021

Sheet 5: It appears the new 8 inch water line beneath Bailey Rd. is being bored. No notes or details are provided, however. Please provide sufficient notes, references to the standard detail for casing carrier pipe (which was missing), casing size, wall thickness, etc. Please refer to the Design and Construction Manual for lateral limits of casing carrier pipe in relation to the roadway. The lateral limits of the casing carrier pipe is dependent upon the depth of the water main.
Corrective Action Required
11/19/2021

Please review the profile view for all segments of water line. Where fill is being provided, provide sufficient notation on the profile view, along with sufficient notes which specify that the fill be brought in and compacted to a plane 18 inches minimum over the top of pipe prior to trenching and installation of pipe.
Corrective Action Required
11/19/2021

Sheet 5: Stub streets serving future phases are shown with fire hydrants within the curb return which is normally not allowed. In this instance, however, it may make sense given the future construction will require these to be relocated. We would recommend an inline placement of the fire hydrants in these instances to facilitate an easier relocation in the future.
Corrective Action Required
11/19/2021

Fire hydrants appear to be missing along Bailey Farms Pkwy. Maximum distance between fire hydrants is 500 feet. Fire hydrants on adjacent cross streets cannot be used to satisfy this requirement.
Corrective Action Required
11/19/2021

Sheet 6: Two (2) of the storm line crossings are too deep. The City allows up to 7 feet maximum depth of cover over a water main.
Corrective Action Required
11/19/2021

Sheet 6: Fire hydrants appear to be missing along Bailey Farms Pkwy. Please see previous comment related to this requirement.
Corrective Action Required
11/19/2021

Sheet 7: Fire hydrant is shown within the curb return on Richland St. The fire hydrant shall be no closer than 20 feet from the PC of the curb return.
Corrective Action Required
11/19/2021

Sheet 7: The water main should be extended a short distance to the west along Cape Dr., and a temporary inline fire hydrant installed.
Corrective Action Required
11/19/2021

Sheet 7: Storm line crossing near sta 4+00 is too deep. Maximum depth of cover is 7 feet as measured from top of pipe.
Corrective Action Required
11/19/2021

Sheet 7: Where are the gate valves at the tees? The City requires two (2) valves for each tee, including the new tee to be installed for the short western extension along Cape Dr. described in the above comment.
Corrective Action Required
11/19/2021

Sheet 8: Fire hydrants are missing along Ranchland St. Maximum distance between fire hydrants is 500 feet. Fire hydrants on adjacent cross-streets cannot be used to satisfy this requirement.
Corrective Action Required
11/19/2021

Sheet 8: Fire hydrants are shown within the curb return which is not allowed. Please see previous comments related to placement of fire hydrants behind the PC of the curb return.
Corrective Action Required
11/19/2021

Sheet 8: Gate valves appear to be missing at tees. Please see previous comments related to this requirement.
Corrective Action Required
11/19/2021

Sheet 9: Valves appear to be missing on this sheet. Please see previous comments related to the placement of two (2) valves in relation to tees. Also, three (3) valves are required at a cross, so please ensure this is considered.
Corrective Action Required
11/19/2021

Sheet 10: Storm crossing shown on the profile view is too deep. Maximum depth of cover is 7 feet.
Corrective Action Required
11/19/2021

Sheet 10: Please see previous comments related to placement of valves in relation to tees and crosses. No valves were shown.
Corrective Action Required
11/19/2021

Sheet 11: Storm line crossings (both) shown in the profile view are too deep. Maximum depth of cover is 7 feet.
Corrective Action Required
11/19/2021

Sheet 11: A fire hydrant is warranted on Sweet Root Dr. Fire hydrants located on adjacent cross streets cannot be used to satisfy the 500 foot maximum distance requirement between fire hydrants.
Corrective Action Required
11/19/2021

Sheet 11: Please refer to previous comments related to the installation of valves in relation to tees and crosses. No such valves were shown on the plans.
Corrective Action Required
11/19/2021

Sheet 12: Both storm line crossings shown on the profile view are too deep. Maximum depth of cover is 7 feet as measured to the top of pipe.
Corrective Action Required
11/19/2021

General Comment Related to All Future Stubs: The City does not allow a plug to be installed at the end of the line as shown in numerous locations. A temporary inline fire hydrant is required. Please go through all sheets related to this requirement and revise.
Corrective Action Required
11/19/2021

Please refer to Sheet 12. As an example of the above comment, please see the notes at the south end of Line 5. The City does not allow a simple cap in this instance, but rather, a temporary inline fire hydrant. Since these are stub streets and the hydrants will be moved in the future, it will be acceptable to place the temporary fire hydrant within the curb return limits rather than 20 feet beyond the PC of the curb return.
Corrective Action Required
11/19/2021

Sheet 12: Please refer to previous comments related to the placement of valves in relation to crosses and tees. No such valves were shown.
Corrective Action Required
11/19/2021

Sheet 13: A blow-off assembly is shown. The City does not allow blow-off assemblies. Please remove and use a temporary fire hydrant.
Corrective Action Required
11/19/2021

Sheet 13: Regarding the temporary fire hydrants along Bailey Pkwy., these fire hydrants shall not count towards the required number of fire hydrants along Bailey Farm Pkwy. The reason is that these are temporary fire hydrants to be relocated along their respective streets in the future, and cannot be used to satisfy the 500 foot rule for maximum distance between fire hydrants along Bailey Farm Pkwy.
Corrective Action Required
11/19/2021

Sheet 14: Profile view for Line 9 and 10 appears incomplete. Please revise.
Corrective Action Required
11/19/2021

Sheet 14: Blow-off assembly is called-out. These are not allowed in the City of Lee's Summit.
Corrective Action Required
11/19/2021

Sheet 14: Please see previous comments related to stub-off streets and temporary fire hydrants. Termination of all water mains shall be at a fire hydrant rather than a plug.
Corrective Action Required
11/19/2021

Sheet 15: Please see previous comments related to the placement of valves in relation to tees and crosses. It appears this was missing from the sheet.
Corrective Action Required
11/19/2021

A trenching and backfill detail was missing. Please ensure the new July 2020 standard of 12 inch aggregate over the top of pipe is shown, rather than the previous 6 inch requirement.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
11/05/2021 Plans 21-130-WAT(REV0)
11/05/2021 Email FW_ Bailey Farms
11/19/2021 Letter DE-Comment Letter (Engineering Plans)
01/31/2022 Letter Response to DE-Comment Letter - Streets - Public Water Main Engineering Plans
01/31/2022 Plans 21-130 WATER(REV1) signed
02/15/2022 Letter DE-Comment Letter (Engineering Plans)
04/26/2022 Waiver/Modification Document NOT REQUIRED Waiver Request Water Depth(REV0) signed
04/26/2022 Plans 21-130 WATER(REV2)sealed
04/26/2022 Letter Response to DE-Comment Letter - Public Water Main
04/26/2022 Engineers Estimate 21-130-EOPC(REV1) Sealed
05/19/2022 Plans 21-130 WATER(REV3) Sealed
05/19/2022 Letter Response to Email Comments dated 5-11-22 - Water Main Approval_doc
05/19/2022 Engineers Estimate 21-130-EOPC(REV2) Sealed
05/31/2022 Email EMAIL COMMENTS WU MAY2022
05/31/2022 Activity Document WATER MODEL ALL MAY 2022
06/30/2022 Plans APPROVABLE WATER(REV4) sealed
06/30/2022 Engineers Estimate 21-130-EOPC(REV3) Sealed MANOR WATER
06/30/2022 Letter Response to PL2021432 Manor at Bailey Farms 1st Plat - Water Line QAQC Water Utilities dated 05-31-2022
07/08/2022 Activity Document EMAIL MDNR CONCURRENCE JUL2022
09/16/2022 Activity Document FeeWorksheetManorAtBaileyFarmsWater
11/18/2022 Activity Document Manor at Bailey Farms MDNR
06/06/2023 Letter APPLICATION EXTENSION REQUEST_Rev 0_PL2021431
10/27/2023 Plans 10272023-21-130-WATER-REV(0) sealed
11/30/2023 Plans 21-130 WATER(REV6)sealed
12/14/2023 Approved Plans WATER - STAMPED CONSTRUCTION PLANS
12/14/2023 Activity Document FeeWorksheetManorBaileyWater
12/14/2023 Email STKY APPROVAL
05/15/2025 Plans 2025_05_14_21-130 WATER As Builts
05/23/2025 Accepted Record Drawings ACCEPTED RECORD DWG WATER
05/27/2025 Accepted Record Drawings 21-130 Manor at Bailey Farms
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home