Planning Application Status

PL2020158




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2020158
Oakview - Lot 2 (Panera)
Commercial Final Development Plan
Commercial Final Development Plan
Approved
05/21/2020
STAR ACQUISITIONS & DEVELOPMENT LLC
Locations
Contacts
STAR ACQUISITIONS & DEVELOPMENT LLC, Address:244 W MILL STE 101  
STAR DEVELOPMENT CORPORATION, Address:244 W MILL STE 101  
AGC Engineers, INc, Address:405 S Leonard, Suite D, Phone:(816) 781-4200  
SCHARHAG ARCHITECTS, Address:6247 BROOKSIDE BLVD STE 204, Phone:(816) 656-5055  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Codes Review No Comments 09/19/2022 09/14/2022
Mike Weisenborn
Engineering Review Approved with Conditions 09/19/2022 09/14/2022
Nikia Chapman-Freiberger
DE C&O #11 Pavement Thickness
Corrective Action Required
09/12/2022

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
09/12/2022

Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
DE Contact ROW Inspector
Corrective Action Required
09/12/2022

Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
DE Engineers Estimate
Corrective Action Required
09/12/2022

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $42,654.55
DE Future Repair Work
Corrective Action Required
09/12/2022

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Traffic Review No Comments 09/19/2022 09/12/2022
Mike Weisenborn
Fire Review Approved with Conditions 09/19/2022 09/12/2022
Mike Weisenborn
Code Statement
Corrective Action Required
09/12/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code and local amendments. Action required- Correct the occupancy classification to A2. A2 Occupancies with a fire area occupant load over 100 shall be provided with an automatic fire sprinkler. 07/29/2022- Sprinkler system is NOT required. Occupant load will be less than 100. Condition subject to tenant finish review.
Planning Review Approved with Conditions 09/19/2022 09/12/2022
Mike Weisenborn
Miscellaneous Correction
Corrective Action Required
09/12/2022

SIGNAGE. The existing Polytainers monument sign shall be removed from the site as part of the proposed development. City ordinance prohibits off-premise signs. At the time the subject property was platted as a lot separate from the Polytainers facility, the existing sign became an off-premise sign and thus is required to be removed. Staff understands that the applicant is continuing to review this previously made comment.
Engineering Review Approved with Conditions 08/15/2022 08/15/2022
Nikia Chapman-Freiberger
DE C&O #11 Pavement Thickness
Corrective Action Required
08/15/2022

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
08/15/2022

Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
DE Contact ROW Inspector
Corrective Action Required
08/15/2022

Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
DE Engineers Estimate
Corrective Action Required
08/15/2022

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $42,654.55
DE Future Repair Work
Corrective Action Required
08/15/2022

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Building Codes Review No Comments 08/15/2022 08/08/2022
Mike Weisenborn
Traffic Review No Comments 08/15/2022 08/08/2022
Mike Weisenborn
Fire Review Approved with Conditions 08/15/2022 08/08/2022
Mike Weisenborn
Code Statement
Corrective Action Required
08/08/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code and local amendments. Action required- Correct the occupancy classification to A2. A2 Occupancies with a fire area occupant load over 100 shall be provided with an automatic fire sprinkler. 07/29/2022- Sprinkler system is NOT required. Occupant load will be less than 100. Condition subject to tenant finish review.
Planning Review Approved with Conditions 08/15/2022 08/08/2022
Mike Weisenborn
Miscellaneous Correction
Corrective Action Required
08/08/2022

SIGNAGE. The existing Polytainers monument sign shall be removed from the site as part of the proposed development. City ordinance prohibits off-premise signs. At the time the subject property was platted as a lot separate from the Polytainers facility, the existing sign became an off-premise sign and thus is required to be removed. Staff understands that the applicant is continuing to review this previously made comment.
Planning Review Approved with Conditions 08/05/2022 08/04/2022
Hector Soto Jr.
Corrective Action Required
08/04/2022

SIGNAGE. The existing Polytainers monument sign shall be removed from the site as part of the proposed development. City ordinance prohibits off-premise signs. At the time the subject property was platted as a lot separate from the Polytainers facility, the existing sign became an off-premise sign and thus is required to be removed. Staff understands that the applicant is continuing to review this previously made comment.
Engineering Review Corrections 08/01/2022 08/01/2022
Nikia Chapman-Freiberger
Corrective Action Required
08/01/2022

Sheet 3 – EXISTING CONDITIONS: The numbers on the scale bar are incorrect. The drawing's scale is 1"=40' but the bar scales out to ¾” increments so the numbers to correctly match the scale bar are 30,30,60 as shown originally.
Corrective Action Required
08/01/2022

Sheet 4 – SITE PLAN: All ADA-accessible ramps and ADA-accessible ways must have a specific detail associated with them. Please show the locations of these features, and provide a call-out on the plan view with a specific reference to the sheet number and detail number.
Corrective Action Required
08/01/2022

Sheet 12 – DETAILS: Remove the non-compliant sidewalk details on page 12. The correct City details have been included on page 13. The Curb and Gutter Detail must match the City’s details.
Corrective Action Required
08/01/2022

Sheet L100 LANDSCAPE PLAN: Please remove non-ornamental trees from public easements.
Corrective Action Required
08/01/2022

Opinion of Cost: A) Correct item 3 to 6” PCC parking. B) Item 4 seems to have the wrong unit and the drawing shows an area closer to 740sf. Please review and revise. C) Please include line item for temporary curb. D) Item 6 quantity should be reviewed. The drawing shows approximately 415 lf of curb E) There is no line item for the roughly 1,400 sf of concrete area next to the building. Please review and revise. F) Items 9 and 10 seem to have the wrong units. Please review and revise. G) Item 15 reads 1” water service, plans show 2” service. Please review and revise. H) Parking striping does not need to be included in the cost estimate. I) ADA ramps should be included separately from sidewalk.
Fire Review Approved with Conditions 08/01/2022 07/29/2022
Jim Eden
Code Statement
Corrective Action Required
07/25/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code and local amendments. Action required- Correct the occupancy classification to A2. A2 Occupancies with a fire area occupant load over 100 shall be provided with an automatic fire sprinkler. 07/29/2022- Sprinkler system is NOT required. Occupant load will be less than 100. Condition subject to tenant finish review.
FDC
Resolved
07/29/2022

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Action required- The building is indicated to have a fire sprinkler system, but a fire protection main or FDC are not shown. Show the location of the FDC and the hydrant within 100 feet.
Hydrants
Resolved
07/29/2022

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Action required- Correcting Item #2 will meet this requirement. Other hydrants for the site were not shown.
Imposed Loads
Resolved
07/29/2022

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. Confirm the use of heavy duty pavement for the drive lanes.
Traffic Review No Comments 08/01/2022 07/25/2022
Mike Weisenborn
Building Codes Review No Comments 08/01/2022 07/25/2022
Mike Weisenborn
Traffic Review No Comments 07/11/2022 07/12/2022
Hector Soto Jr.
Planning Review Corrections 07/11/2022 07/12/2022
Hector Soto Jr.
Corrective Action Required
07/11/2022

BUILDING ELEVATIONS. - Clarify the full extent of the proposed fiberglass panel. Does it constitute the entirety of the material shown in green on the west, south and east building elevations? Fiberglass is not an approved material under the City's development ordinance (UDO Section 8.170.A). As such, it may be considered for approved as a conditional material, but this requires public hearings in front of both the Planning Commission and City Council. The public hearing process typically takes 3-4 months to complete from the time of application. - Metal paneling is proposed to be used on the south elevation. The extent of the metal proposed to be used also requires approval as a conditional material through the public hearing process as described above. - Except for the canopy, it is difficult to discern how much projection/off-set there may be on each of the building's four elevations. Horizontal and vertical breaks are required to be provided on all building sides in order to provide visual interest and to break up the large expanses of flat wall. Provide an axionometric drawing to depict the degree of offsets/projections provided by the proposed building architecture on all four building sides. - To satisfy the requirement for four-sided architecture, architectural elements used on the building shall be extended to the rear elevation in order to avoid or minimze the appearance of a back side. More specifically, some vertical architectural details shall be provided on the rear building elevation.
Corrective Action Required
07/12/2022

PROPERTY LINE INFORMATION. The property line dimensions and bearing information doesn't match the information shown on the plat. Revise accordingly. If newly resurveyed information differs from that on the plat, list both the measured and platted dimensions and bearings and notate the information as (P) for platted and (M) for measured. Staff understands the comment on the response letter that the bearings may differ because they are based on the state plane coordinates. List both the measured and platted bearings and dimensions as noted in the paragraph above.
Corrective Action Required
07/12/2022

PROPERTY LINE INFORMATION. The property line dimensions and bearing information doesn't match the information shown on the plat. Revise accordingly. If newly resurveyed information differs from that on the plat, list both the measured and platted dimensions and bearings and notate the information as (P) for platted and (M) for measured. Staff understands the comment on the response letter that the bearings may differ because they are based on the state plane coordinates. List both the measured and platted bearings and dimensions as noted in the paragraph above.
Corrective Action Required
07/12/2022

MECHANICAL EQUIPMENT. - Show the location of all roof-top units (RTUs) on the building elevations to the extent possible by dashing them in. RTUs shall be totally screened from view on all sides by extending the building parapets to a height at least equal to the height of the RTUs. Screen panels are not allowed on new construction buildings. - Show the location of all ground units on the site plan to the extent possible. Ground units shall be totally screend from view to a height at least equal to the height of the ground units. The ground units shall be screened using either masonry walls or evergreen landscaping. No information was provided on the resubmittal to show that these previously made comments have been addressed.
Corrective Action Required
07/12/2022

SIGNAGE. The existing Polytainers monument sign shall be removed from the site as part of the proposed development. City ordinance prohibits off-premise signs. At the time the subject property was platted as a lot separate from the Polytainers facility, the existing sign became an off-premise sign and thus is required to be removed. Staff understands that the applicant is continuing to review this previously made comment.
Fire Review Corrections 07/11/2022 07/11/2022
Jim Eden
Code Statement
Corrective Action Required
07/01/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code and local amendments. Action required- Correct the occupancy classification to A2. A2 Occupancies with a fire area occupant load over 100 shall be provided with an automatic fire sprinkler.
FDC
Corrective Action Required
07/01/2022

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Action required- The building is indicated to have a fire sprinkler system, but a fire protection main or FDC are not shown. Show the location of the FDC and the hydrant within 100 feet.
Hydrants
Corrective Action Required
07/01/2022

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Action required- Correcting Item #2 will meet this requirement. Other hydrants for the site were not shown.
Imposed Loads
Corrective Action Required
07/01/2022

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. Confirm the use of heavy duty pavement for the drive lanes.
Engineering Review Corrections 07/11/2022 07/11/2022
Loic Nguinguiri, E.I.
Corrective Action Required
07/11/2022

Add FEMA panel number 29095C0417G to the flood note as well, shown on the cover sheet, since two (2) different FEMA panel numbers encroach into the current site.
Corrective Action Required
07/11/2022

Dena Mezger is an out of date contact for Public Works. Though Michael Park is the current director of PW department, please be aware that names aren’t needed for the City’s contact info.
Corrective Action Required
07/11/2022

Revise general project note 15 to “The contractor shall contact the City’s Development Services Engineering Inspection to schedule a pre-construction meeting with a field engineering inspector prior to any land disturbance work at (816) 969-1200”.
Corrective Action Required
07/11/2022

Information shown in the water notes located on sheet 2 need to match the scope of work shown on the utility plan sheet.
Corrective Action Required
07/11/2022

In regard to the site plan sheet, a temporary (asphalt) curb is likely needed where the parking lot connects to the north.
Corrective Action Required
07/11/2022

While revising the location of the curb inlet leader that currently points at the curb, make sure to also add/show leaders M and R in plan view of the site plan sheet.
Corrective Action Required
07/11/2022

Southern silt fence needs to extend all the way up to the sidewalk abutting to NW Douglas Street.
Corrective Action Required
07/11/2022

A 2” tap is needed at the connection point, along the existing 12” public water main.
Corrective Action Required
07/11/2022

It could be possible to use a 1.5” water meter instead of a 2”, as long as the water demand for the current development does not exceed 50 gpm. If that becomes the case, the domestic water service line will still remain a 2” line all the way in order to accommodate the proposed 1.5” water meter.
Corrective Action Required
07/11/2022

The leaders for the several gas, sanitary and storm components are not so well represented on the utility plan view. Please revise the locations for those. Discrepancies and ambiguities can be seen.
Corrective Action Required
07/11/2022

Show the hydraulic grade line in profile view, on sheet 11. Make sure to also revise the overlapping elevations located in the profile view of storm line 1.
Corrective Action Required
07/11/2022

The normal duty concrete detail shows a PCC thickness that is inferior to the 6” minimum allowed as per UDO section 8.620. Please be aware that the minimum thickness allowed for aggregate base below PCC pavement is 4” only as well. Make sure to also revise the thickness(es) of pavement shown in the curb & gutter base detail accordingly.
Corrective Action Required
07/11/2022

The City requires a 12”-thick minimum layer of granular bedding (aggregate fill) above the edge of utility pipe and a 6”-thick minimum layer underneath. Revise the applicable trenching and backfill construction details accordingly.
Corrective Action Required
07/11/2022

Only ornamental tree varieties are allowed within public easements. Review and verify that the landscaping plan meets this requirement.
Corrective Action Required
07/11/2022

Please provide a SWPPP report and a Missouri DNR permit.
Corrective Action Required
07/11/2022

Please update the Engineer’s Opinion of Probable Construction Cost (EOOPCC) sheet accordingly.
Building Codes Review No Comments 07/11/2022 07/07/2022
Joe Frogge
Planning Review Corrections 06/05/2020 06/05/2020
Hector Soto Jr.
Corrective Action Required
06/05/2020

PROPERTY LINE INFORMATION. The property line dimensions and bearing information doesn't match the information shown on the plat. Revise accordingly. If newly resurveyed information differs from that on the plat, list both the measured and platted dimensions and bearings and notate the information as (P) for platted and (M) for measured.
Corrective Action Required
06/05/2020

RIGHT-OF-WAY. Label the right-of-way width information for both NE Douglas St and NE Victoria Dr. Label and identify the ROW centerline.
Corrective Action Required
06/05/2020

DRIVEWAY AND DRIVE AISLE WIDTHS. All driveways and drive aisles serving two-way traffic shall have a minimum 24' of pavement width (excluding curb and gutter). The driveway and drive aisle on the east side of the building have a pavement width of 22'-6", not the required 24'.
Corrective Action Required
06/05/2020

TRASH ENCLOSURE. The reinforced concrete pad in front of the enclosure shall be a minimum 30' long, measured from the enclosure opening. The plans currently show it approximately 9' long.
Corrective Action Required
06/05/2020

ADA PARKING DETAIL. Revise the parking sign detail on Sheet 12 to show the sign's mounting height to be a minimum of 5' above grade, measured to the bottom of the sign.
Corrective Action Required
06/05/2020

MECHANICAL EQUIPMENT. - Show the location of all roof-top units (RTUs) on the building elevations to the extent possible by dashing them in. RTUs shall be totally screened from view on all sides by extending the building parapets to a height at least equal to the height of the RTUs. Screen panels are not allowed on new construction buildings. - Show the location of all ground units on the site plan to the extent possible. Ground units shall be totally screend from view to a height at least equal to the height of the ground units. The ground units shall be screened using either masonry walls or evergreen landscaping.
Corrective Action Required
06/05/2020

LANDSCAPE PLAN. - The minimum height of evergreen trees is 8' at the time of planting. The proposed juniper trees are listed as being 6' in height. Revise. - The required parking lot landscape screening calculation is included on the Landscape Plan. However, the required landscaping is not shown on the plan. Show the required landscaping on the Landscape Plan.
Corrective Action Required
06/05/2020

BUILDING ELEVATIONS. - The proposed building is composed of four (4) flat walls. While the canopies and awnings provide for the creation of some shadow lines, off-sets or projections shall be provided on all sides of the building to break up the flat wall planes and provide some additional architectural relief. Also, the north elevation shall incorporate additional vertical features to break up the large blank portion of the facade. - Label the proposed exterior material color palette.
Corrective Action Required
06/05/2020

SIGNAGE. - The existing Polytainers monument sign shall be removed from the site as part of the proposed development. City ordinance prohibits off-premise signs. At the time the subject property was platted as a lot separate from the Polytainers facility, the existing sign became an off-premise sign and thus is required to be removed. - The proposed Panera monument sign is shown to be located within a utility easement. No structures, including monument signs, are allowed to be located within a utility easement. The sign shall be relocated outside of any easement and shall be located a minimum 15' away from any public water main and any public sanitary sewer main, measured from the closest outside edge of the public mains.
Engineering Review Corrections 06/05/2020 06/05/2020
Loic Nguinguiri, E.I.
Corrective Action Required
06/05/2020

Please make sure to include a note stating that “The contractor shall contact the City’s Development Services Engineering Inspectors 48 hours prior to any land disturbance work at (816) 969-1200”.
Corrective Action Required
06/05/2020

Please include an oil and/or gas and a FEMA National Flood Hazard information note(s), onto the cover sheet.
Corrective Action Required
06/05/2020

Please add inlet protection to the two (2) curb inlets located southwest of the limits of existing underground storm detention, on sheet 5. Make sure to add intermediate silt fence as well to prevent mud from running across the lot during heavy rain events.
Corrective Action Required
06/05/2020

Since the disturbance area is above 1 acre, please provided a SWPPP and a MDNR permit.
Corrective Action Required
06/05/2020

Please provide an EOOPCC sheet (cost estimate).
Corrective Action Required
06/05/2020

On page 11, a 0.5’ drop is required within inlet 12. Please make sure to also show the hydraulic grade line in the two (2) storm profile views.
Corrective Action Required
06/05/2020

On page 7, please label a 12” x 6” cut-in for the fire line connection and edit leader C to show a 2” tap with 2” water meter and pit.
Corrective Action Required
06/05/2020

On page 4, while redirecting arrow H located by the construction entrance, please label the proposed sidewalk. Feel free to add it to the key legend.
Corrective Action Required
06/05/2020

The City requires either geogrid or stabilized subgrade under the MoDOT Type 5 in the asphalt pavement section. Please revise the pavement details according to the City’s UDO section 8.620.
Corrective Action Required
06/05/2020

The concrete pavement length does not meet UDO requirements. Please revise.
Corrective Action Required
06/05/2020

Please revise sanitary general note 11 to mention City of Lee's Summit.
Corrective Action Required
06/05/2020

Please make sure the water meter location does meet the City's requirements. Feel free to make revisions as necessary.
Traffic Review No Comments 06/05/2020 06/02/2020
Michael Park
Fire Review Corrections 06/05/2020 06/01/2020
Jim Eden
Code Statement
Corrective Action Required
06/01/2020

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code and local amendments.
FDC
Corrective Action Required
06/01/2020

IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official. Show the location of the FDC and the hydrant within 100 feet.
Hydrants
Corrective Action Required
06/01/2020

IFC 507.5.1 - Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official. Correcting Item #2 will meet this requirement. Other hydrants for the site were not shown.
Imposed Loads
Corrective Action Required
06/01/2020

IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities. Confirm the use of heavy duty pavement for the drive lanes.
Building Codes Review No Comments 06/05/2020 05/29/2020
Joe Frogge
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $600.00 $600.00 Paid 05/21/2020
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
05/21/2020 Application Form z-FDP application 5-25-20
05/21/2020 Receipt Receipt for transaction:2020-002347
05/22/2020 Plans 5.22.20 FDP Panera Bread
05/22/2020 Plans 5.22.20 OAKVIEW-LOT 2 (Panera) FDP
06/05/2020 Letter Applicant Letter - FDP (DFDP)
06/14/2021 Email Re Panera Bread - PRCOM20201329
07/01/2022 Plans 6-30-22 Arch FDP
07/01/2022 Engineers Estimate 6-30-22 EOOPCC
07/01/2022 Plans 6-30-22 OAKVIEW LOT 2 - PANERA FDP
07/01/2022 Letter 6-30-22 response to 6-5-20 comments
07/12/2022 Letter Applicant Letter - FDP (DFDP)
07/25/2022 Engineer Report/Study 2022-07-22 SWPPP (Oakview Lot 2 and Lot 4)
07/25/2022 Letter 2022-07-25 Response Ltr
07/25/2022 Engineers Estimate 2022-07-25 Opinion of Cost
07/25/2022 Plans 2022-07-25 OAKVIEW LOT 2 (PANERA SITE PLANS)
08/04/2022 Plans A131 - LIGHTING SCHEDULE
08/04/2022 Plans A200 - EXTERIOR ELEVATIONS
08/04/2022 Plans A201 - EXTERIOR ELEVATIONS
08/04/2022 Plans A210 - EXTERIOR PERSPECTIVES
08/04/2022 Letter RE Oakview Lot 2 Panera-city response letter
08/04/2022 Plans 22302_2406-LeeSummitMO_Shell_G131
08/04/2022 Plans A600 - FINISH SCHEDULE
08/05/2022 Letter Applicant Letter - FDP (DFDP)
08/08/2022 Plans 2022-08-08 OAKVIEW LOT 2 (PANERA SITE PLANS)
08/08/2022 Engineers Estimate 2022-08-08 Opinion of Cost
08/08/2022 Letter 2022-08-08 Response Ltr
08/16/2022 Letter Applicant Letter - FDP (DFDP)
09/07/2022 Activity Document CV Fee Worksheet FY23
09/12/2022 Letter 2022-09-06 Delta No 1 narrative
09/12/2022 Plans 2022-09-06 OAKVIEW LOT 2 (PANERA SITE PLANS)
09/14/2022 Letter Applicant Letter - FDP (DFDP)
01/04/2023 Approved Plans Approved Panera Bread Civil Plans 9.14.2022
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home