Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Review
|
Approved with Conditions
|
11/07/2019
|
11/21/2019
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only.
|
|
Fire Lanes - Marking
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Action required: Indicate how and where fire lanes will be marked.
|
|
Water Supply
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required: Provide a water model indicating required fire flows will be met with proposed line sizes. The amended 2018 IFC only allows for a 50% reduction for sprinklered buildings.
09/19/2019- Provide a water model for the project. This is NOT completed by the sprinkler company.
10/09/2019- Per Amended IFC Table B105.2, only a 50% reduction is allowed for sprinklered buildings. Recalculate your avaiable and required fire flow.
11/21/2019- Flow report provided from Kaw Valley Engineering indicates the required fire flow can be provided.
|
|
Misc.
Prior to going vertical with combustible construction all fire hydrants shall be installed and operable along with the base course of asphalt for the fire lanes.
|
|
Misc.
Reference Landscaping Plan- Remove vegetation from in front of the FDC.
|
|
|
Planning Review
|
No Comments
|
11/07/2019
|
11/11/2019
|
|
Dawn Bell
|
|
|
Building Codes Review
|
No Comments
|
11/07/2019
|
11/06/2019
|
|
Joe Frogge
|
|
|
Engineering Review
|
Approved with Conditions
|
11/07/2019
|
11/04/2019
|
|
Sue Pyles, P.E.
|
|
DE C&O #11 Pavement Thickness
Corrective Action Required
Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $145,617.55
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Traffic Review
|
No Comments
|
11/07/2019
|
10/31/2019
|
|
Michael Park
|
|
|
Fire Review
|
Corrections
|
10/23/2019
|
10/25/2019
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only.
|
|
Fire Lanes - Marking
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Action required: Indicate how and where fire lanes will be marked.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required: Provide a water model indicating required fire flows will be met with proposed line sizes. The amended 2018 IFC only allows for a 50% reduction for sprinklered buildings.
09/19/2019- Provide a water model for the project. This is NOT completed by the sprinkler company.
10/09/2019- Per Amended IFC Table B105.2, only a 50% reduction is allowed for sprinklered buildings. Recalculate your avaiable and required fire flow.
|
|
Misc.
Prior to going vertical with combustible construction all fire hydrants shall be installed and operable along with the base course of asphalt for the fire lanes.
|
|
Misc.
Reference Landscaping Plan- Remove vegetation from in front of the FDC.
|
|
|
Planning Review
|
No Comments
|
10/23/2019
|
10/24/2019
|
|
Jennifer Thompson
|
|
|
Building Codes Review
|
No Comments
|
10/23/2019
|
10/23/2019
|
|
Joe Frogge
|
|
|
Engineering Review
|
Approved with Conditions
|
10/23/2019
|
10/21/2019
|
|
Sue Pyles, P.E.
|
|
DE C&O #11 Pavement Thickness
Corrective Action Required
Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $145,617.55
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Traffic Review
|
No Comments
|
10/23/2019
|
10/16/2019
|
|
Michael Park
|
|
|
Engineering Review
|
Approved with Conditions
|
10/11/2019
|
10/11/2019
|
|
Sue Pyles, P.E.
|
|
DE C&O #11 Pavement Thickness
Corrective Action Required
Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $145,617.55
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
|
Planning Review
|
Approved with Conditions
|
10/11/2019
|
10/11/2019
|
|
Jennifer Thompson
|
|
Corrective Action Required
Please provide 3 full size sets of the architectural plans.
|
|
|
Traffic Review
|
No Comments
|
10/11/2019
|
10/10/2019
|
|
Michael Park
|
|
|
Fire Review
|
Corrections
|
10/11/2019
|
10/09/2019
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only.
|
|
Fire Lanes - Marking
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Action required: Indicate how and where fire lanes will be marked.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required: Provide a water model indicating required fire flows will be met with proposed line sizes. The amended 2018 IFC only allows for a 50% reduction for sprinklered buildings.
09/19/2019- Provide a water model for the project. This is NOT completed by the sprinkler company.
10/09/2019- Per Amended IFC Table B105.2, only a 50% reduction is allowed for sprinklered buildings. Recalculate your avaiable and required fire flow.
|
|
Misc.
Prior to going vertical with combustible construction all fire hydrants shall be installed and operable along with the base course of asphalt for the fire lanes.
|
|
Misc.
Reference Landscaping Plan- Remove vegetation from in front of the FDC.
|
|
|
Building Codes Review
|
No Comments
|
10/11/2019
|
10/08/2019
|
|
Joe Frogge
|
|
|
Planning Review
|
Corrections
|
09/19/2019
|
09/23/2019
|
|
Jennifer Thompson
|
|
Corrective Action Required
The calculations for the parking as referenced to the ITE Manual are not reflected accurately within the response memo (only).
|
|
Corrective Action Required
Staff would like to follow-up on the previous comment regarding the functionality of the trash enclosure areas and how they could negatively affect access within the private drives. It seems the truck would be backing in to this areas, crossing traffic, and blocking access for through traffic.
The Concrete pad requirement (reference comment from previous staff comment letter), has not been met.
|
|
Corrective Action Required
Additional Street shrubs are required along the frontages adjacent to private drives. One shrub per 20 feet of street frontage is needed.
|
|
Corrective Action Required
Interior courtyard elevations need additional projections and material changes on the north and south elevations.
The approved preliminary development plan indicated more projections and material changes than what is currently proposed.
|
|
Corrective Action Required
The west elevations do not show the overhead garage door entry into the parking garage, please revise.
|
|
Corrective Action Required
Please label the caliper size for ornamental as 3 inches. Staff could allow 2.5 during the time of planting.
|
|
Corrective Action Required
Please refer to the sidewalk comment provided by Michael Park, please clarify pedestrian connections and revise the necessary sheets.
|
|
|
Engineering Review
|
Corrections
|
09/19/2019
|
09/23/2019
|
|
Sue Pyles, P.E.
|
|
Corrective Action Required
Engineer's Estimate of Probable Construction Costs:
• Include items for Stabilized Subgrade and ADA ramps.
• Revise Item 2 from AB-3 to MoDOT Type 5
• Separate the sanitary sewer overall item into individual items.
• Clarify what the item “Water Service” includes.
• Additional comments may be added based on revisions to plans.
|
|
Corrective Action Required
Review the plan set for overlapping text and revise for clarity.
|
|
Corrective Action Required
Sheet C02:
• This sheet is titled “Existing Condition” but shows existing, proposed, and proposed (by others). Please clarify the intent of this sheet.
• This sheet does not show the proposed (by others) fire hydrant near the SE corner of the building in the easement that is shown. Revise to show this hydrant. If the intent is to relocate this hydrant to be in the proposed island, please coordinate with the developer to have the hydrant installed such that relocation won’t be necessary. Reflect this revision throughout the plan set.
|
|
Corrective Action Required
Sheet C03:
• Please clarify pedestrian connectivity between this lot and adjacent lots. ADA-accessible ramps are required at any connections to the private roads.
• All ADA-accessible ramps and ADA-accessible ways must have a specific detail associated with them. Please show the locations of these features, and provide a call-out on the plan view with a specific reference to the sheet number and detail number.
• The specific details of these features must include, at a minimum, the design details specified in Section 5304.8 of the Design and Construction Manual. Elevation call-outs, although required, are not sufficient. Other design details specified in this section are required, including slope call-outs which comply with the criteria listed in Table LS-5, and section views specified in 5304.8.
• Label all easements, both public and private.
|
|
Corrective Action Required
Sheets C06-C08: There are still several proposed contours that don’t tie back into anything. Please revise.
|
|
Corrective Action Required
Sheet C09: See above comments regarding ADA-accessible design requirements.
|
|
Corrective Action Required
Sheet C11:
• Connection to public sanitary sewer at a MH is not allowed. Show and label the connection as a cut-in wye. The edge of the cut-in wye fitting must be a minimum of 4 feet from the outside edge of the MH.
• The approved Final Development Plans that include construction of the water main this project will connect to does not show any stubs, as shown on this sheet. Please coordinate and revise as required.
|
|
Corrective Action Required
Sheet C12: The approved Final Development Plans that include construction of the water main this project will connect to does not show any stubs, as referred to (but not actually shown) on this sheet. Please coordinate and revise as required. Please revise to show the fire line to the hydrant connecting to the gate valve on the main.
|
|
Corrective Action Required
Sheet C14: The information shown for Structure A6 does not match the approved plans for that structure. Please revise accordingly, and include the other incoming and the outgoing flowlines at that structure in the Profile view.
|
|
Corrective Action Required
Sheet C15: There doesn’t appear to be a sanitary stub, as shown. Please revise as directed in comments above.
|
|
|
Fire Review
|
Corrections
|
09/19/2019
|
09/19/2019
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only.
|
|
Imposed Loads
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Action required: Indicate areas of heavy duty asphalt (capable of supporting 75,000 pounds).
|
|
FDC
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required: IExplain why are there three fire department connections (FDC's)shown on the building for only one riser?
|
|
Fire Lanes - Marking
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Action required: Indicate how and where fire lanes will be marked.
|
|
Fire Lanes
IFC 503.2.1 - Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).
SECTION D105
AERIAL FIRE APPARATUS ACCESS ROADS
D105.1 Where required. Where the vertical distance
between the grade plane and the highest roof surface exceeds 30 feet (9144 mm), approved aerial fire apparatus access roads shall be provided. For purposes of this section, the highest roof surface shall be determined by measurement to the eave of a pitched roof, the intersection of the roof to the
exterior wall, or the top of parapet walls, whichever is greater.
D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm), exclusive of shoulders, in the immediate vicinity of the building or portion thereof.
D105.3 Proximity to building. One or more of the required access routes meeting this condition shall be located not less than 15 feet (4572 mm) and not greater than 30 feet (9144 mm) from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official.
D105.4 Obstructions. Overhead utility and power lines shall not be located over the aerial fire apparatus access road or between the aerial fire apparatus road and the building. Other obstructions shall be permitted to be placed with the approval
of the fire code official.
Action required: How will the intent of this section be met? Provide a turning radius diagram for a 44" aerial apparatus.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required: Provide a water model indicating required fire flows will be met with proposed line sizes. The amended 2018 IFC only allows for a 50% reduction for sprinklered buildings.
09/19/2019- Provide a water model for the project. This is NOT completed by the sprinkler company.
|
|
Misc.
Prior to going vertical with combustible construction all fire hydrants shall be installed and operable along with the base course of asphalt for the fire lanes.
|
|
Misc.
Reference Landscaping Plan- Remove vegetation from in front of the FDC.
|
|
|
Building Codes Review
|
No Comments
|
09/19/2019
|
09/18/2019
|
|
Joe Frogge
|
|
|
Traffic Review
|
Approved with Conditions
|
09/19/2019
|
09/16/2019
|
|
Michael Park
|
|
Corrective Action Required
There should be pedestrian connection(s) between Lot 8 and the adjacent lot to the north and south (e.g. Lot 6) along the west side of Private Road B (or along the east side of the building). There are sidewalks along the building and sidewalks on adjacent lots, these should be connected. There's even a illustrated crosswalk with no sidewalk connection on the north east corner of Lot 8.
|
|
|
Planning Review
|
Corrections
|
08/15/2019
|
08/19/2019
|
|
Jennifer Thompson
|
|
Corrective Action Required
Revise note #11 on the Title Sheet, the correct department to reference is Development Services.
|
|
Corrective Action Required
Provide additional detail in the vicinity map on the Title Sheet.
|
|
Corrective Action Required
Staff has concerns on the functionality of the proposed trash enclosures. It seems there could be a traffic conflict with the way they are proposed. It would seem a development of this size would have a loading dock area that would include a compactor, etc.
The Unified Development Ordinance requires trash enclosure areas shall be improved with a Portland cement concrete pad and a Portland cement concrete approach 30 feet in length, measured from the enclosure opening. The pad and approach shall be improved with a minimum six inches of full depth unreinforced Portland cement concrete constructed on a sub-grade o four inches of granular base course.
Provide a narrative of how trash pick-up is intended to function for this site. Are two trash enclosures adequate?
Also, please provide a detail for the proposed trash enclosures.
|
|
Corrective Action Required
To further evaluate the proposed parking proposal please provide an analysis for proposed parking utilizing/comparing to the Institute of Transportation Engineers, Parking Generation Manual 5th Edition, January 2019.
In addition, on Sheet C03, provide a parking data table summary listing/breaking down the number of units, the type of units, the total square footage of retail, etc. illustrating UDO requirements and the proposed parking proposal.
|
|
Corrective Action Required
On Sheet C03 the heavy duty pavement marking is missing from the drive aisle along the west side of the building.
|
|
Corrective Action Required
On Sheet C03 within the land use table include the proposed FAR and density for the development.
|
|
Corrective Action Required
Provide an accessible sign detail. Please refer to Article 8 for specifications. The City requires the R7-8 sign type. This sign has a white background and green border.
|
|
Corrective Action Required
Label the setbacks for the lot. Please refer to the Ordinance approving the preliminary development plan.
|
|
Corrective Action Required
On Sheet A006 label the parking and drive aisle dimensions. Also label the proposed ADA spaces.
|
|
Corrective Action Required
Clearly indicate the parking lot pole height on Sheet E001, to include and reference the height of the base.
Provide and update Sheet E001 to include any wall pak lighting. Also provide the manufacturer's specifications for the proposed lighting.
|
|
Corrective Action Required
All proposed signs require a separate sign permit submittal and approval prior to the installation of any proposed signage.
|
|
Corrective Action Required
The drive aisle widths have not been met. The minimum drive aisle width is 24' not to include any portion of the curb.
|
|
Corrective Action Required
Revise the landscape plant schedule to reference a 3" caliper for all deciduous trees and 8' height for the evergreen trees.
|
|
Corrective Action Required
The minimum island width with tree plantings shall be 10' in width. Please revise the islands accordingly.
|
|
Corrective Action Required
Any trees located within an easement shall be revised to an ornamental variety.
Show the utility easements on the landscaping plan.
|
|
Corrective Action Required
It appears the number of open yard shrubs is not reflected on the landscape sheet. The total required number of open yard shrubs is 65, however only 54 are shown.
|
|
Corrective Action Required
Additional street trees and shrubs are required along the frontages adjacent to private drives. One tree per 30 feet of street frontage and one shrub per 20 feet of street frontage.
Open yard requirements cannot be counted toward this requirement.
|
|
Corrective Action Required
Please provide color elevations.
|
|
Corrective Action Required
Label the color of the downspouts.
|
|
Corrective Action Required
The courtyard elevations require additional materials to break up the facades. The approved preliminary development plan indicated more material changes within these interior areas.
|
|
|
Engineering Review
|
Corrections
|
08/15/2019
|
08/16/2019
|
|
Sue Pyles, P.E.
|
|
Corrective Action Required
General:
• Submit an Engineer’s Estimate of Probable Construction Costs.
• Submit the SWPPP.
• Nothing has been constructed yet on the site, and the timing of all construction elements is still unknown. Items labeled “Existing” would be better off labeled “Proposed (By Others)” or similar.
• Revise the private road/access drive names to match the Final Development Plan that includes their construction. That FDP names them Private Road A, B and C.
|
|
Corrective Action Required
Sheet C01:
• Revise the Water Utilities address to 1200 SE Hamblen Road in the Utilities contact list.
• Include the author of the oil/gas well source.
• Revise General Note 14 to refer to the 2018 code.
|
|
Corrective Action Required
Sheet C02: Why are some storm sewer called out as “Existing” but not all, and no other utilities are labeled that way? Perhaps adding a legend showing line weights/types or adding “Typ” to labels would be more consistent.
|
|
Corrective Action Required
Sheet C03:
• Label the retaining wall west of the building.
• Revise the weight of the scaled back features, such as hatching and utilities6, to make them readable. Make this revision throughout the plan set, as most lines other than what is proposed with this set of plans is barely readable at best.
|
|
Corrective Action Required
Sheet C06:
• Grading Notes 9 & 10 are not applicable, please remove.
• All proposed contours must tie back into existing contours.
|
|
Corrective Action Required
Sheets C07 & C08:
• Include Top and Bottom Wall elevations.
• All proposed contours must tie back into existing contours.
|
|
Corrective Action Required
Sheet C09:
• There are grading details for Walls A & B, but those walls are not labeled elsewhere in the plans. Please revise.
• Please include a site-specific ADA accessible sidewalk ramp design for the ramp crossing the access drive to the north. See Design and Construction Manual Section 5300 and Table LS-5 for design requirements.
|
|
Corrective Action Required
Sheet C11:
• Please remove references to Public Works from the Site Utility Notes.
• Site Utility Note 11 might have a time requirement typo.
• The fire hydrant installation is adjacent to the fire hydrant installation included in the Private Road Final Development Plan. Please coordinate.
• What are the domestic and fire lines connecting to? Nothing Is shown. Please revise, and include method of connection information.
• Reference and include a 3” meter vault detail.
|
|
Corrective Action Required
Sheet C12: Include connection information for the fire hydrant installation.
|
|
Corrective Action Required
Sheet C13:
• Label drainage areas and include size.
• Label proposed structures and revise structure labels that include “XX” as the label.
|
|
Corrective Action Required
Sheet C14:
• Add pipe crossings to the Profile view.
• The information provided for Structures A6 & N1 does not match the approved plans that will be constructing those storm sewers. Please revise to match.
• Revise the flowlines in the Profile views so that the incoming flowlines are shown on the upstream side of the flowline label and the outgoing flowlines are shown on the downstream side of the flowline label.
• Add the design HGL to the Profile views.
|
|
Corrective Action Required
Sheets C15 & C16:
• The private sanitary service shall not connect directly into manholes. Please revise the connection accordingly.
• Note 3 refers to tees, but Plan & Profile views only show wyes. Please reconcile.
• Add pipe crossings to the Profile view.
• Include material type and lengths of the 4” service lines.
|
|
Corrective Action Required
Sheets C17-C19:
• Revise the Erosion Control Notes to be for this project.
• Include the Disturbed Are acreage, currently “***” is shown.
• Silt fence is not shown on the Plan view, please add.
• Sediment trap is not used, please remove from chart.
|
|
|
Traffic Review
|
Corrections
|
08/15/2019
|
08/16/2019
|
|
Sue Pyles, P.E.
|
|
Corrective Action Required
Add sidewalk extending to the ease-west private drives with ramps for crossing private drives from store fronts. for pedestrian access between lots.
|
|
|
Fire Review
|
Corrections
|
08/15/2019
|
08/15/2019
|
|
Jim Eden
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
For information only.
|
|
Imposed Loads
Corrective Action Required
IFC 503.2.3 - Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
Action required: Indicate areas of heavy duty asphalt (capable of supporting 75,000 pounds).
|
|
FDC
Corrective Action Required
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required: IExplain why are there three fire department connections (FDC's)shown on the building for only one riser?
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
Action required: Indicate how and where fire lanes will be marked.
|
|
Fire Lanes
Corrective Action Required
IFC 503.2.1 - Fire apparatus access roads shall have an unobstructed width of not less than 20 feet (6096 mm), exclusive of shoulders, except for approved security gates in accordance with Section 503.6, and an unobstructed vertical clearance of not less than 13 feet 6 inches (4115 mm).
SECTION D105
AERIAL FIRE APPARATUS ACCESS ROADS
D105.1 Where required. Where the vertical distance
between the grade plane and the highest roof surface exceeds 30 feet (9144 mm), approved aerial fire apparatus access roads shall be provided. For purposes of this section, the highest roof surface shall be determined by measurement to the eave of a pitched roof, the intersection of the roof to the
exterior wall, or the top of parapet walls, whichever is greater.
D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm), exclusive of shoulders, in the immediate vicinity of the building or portion thereof.
D105.3 Proximity to building. One or more of the required access routes meeting this condition shall be located not less than 15 feet (4572 mm) and not greater than 30 feet (9144 mm) from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official.
D105.4 Obstructions. Overhead utility and power lines shall not be located over the aerial fire apparatus access road or between the aerial fire apparatus road and the building. Other obstructions shall be permitted to be placed with the approval
of the fire code official.
Action required: How will the intent of this section be met? Provide a turning radius diagram for a 44" aerial apparatus.
|
|
Water Supply
Corrective Action Required
IFC 507.1 - An approved water supply capable of supplying the required fire flow for fire protection shall be provided to premises upon which facilities, buildings or portions of buildings are hereafter constructed or moved into or within the jurisdiction.
Action required: Provide a water model indicating required fire flows will be met with proposed line sizes. The amended 2018 IFC only allows for a 50% reduction for sprinklered buildings.
|
|
Misc.
Prior to going vertical with combustible construction all fire hydrants shall be installed and operable along with the base course of asphalt for the fire lanes.
|
|
Misc.
Corrective Action Required
Reference Landscaping Plan- Remove vegetation from in front of the FDC.
|
|
|
Building Codes Review
|
Corrections
|
08/15/2019
|
08/15/2019
|
|
Joe Frogge
|
|
Corrective Action Required
Provide sewer cleanouts within 10' of building drain/sewer connections (where piping leaves building) per 2018 IPC 708.1.3 or defer to building MEP.
|
|
Corrective Action Required
Replace water meter pit detail with engineered meter vault detail for 3" water service.
|
|
|