Review Type |
Outcome |
Est. Completion Date |
Completed |
Engineering Review - Water
|
No Comments
|
05/20/2024
|
05/10/2024
|
|
Sue Pyles, P.E.
|
|
Miscellaneous Correction
Corrective Action Required
Sheet C300:
• Please revise the tee size in Plan view to match the revised existing pipe size.
• Please note that Pressure Class 235 or DR18 is adequate. Pressure Class 250 is not necessary.
• The horizontal graphic scale on Sheet C300 appears to be wrong. Please verify and revise as needed.
• The north arrow is pointing west, please revise.
• There appears to be a 20’ Utility Easement along the north property line. Please verify. If it is present, then the proposed U/E at that location is not required.
|
|
Miscellaneous Correction
Corrective Action Required
Please add the following items to the estimate:
• Thrust Block
• Tee
• Bends
|
|
Miscellaneous Correction
Corrective Action Required
The existing 16" water main on the south side of SE Thompson Drive is located within the R/W. Please revise the plans to correctly locate the main. The proposed U/E will not be required since the extension will be within the R/W.
|
|
|
Engineering Review - Water
|
Corrections
|
04/16/2024
|
04/16/2024
|
|
Sue Pyles, P.E.
|
|
Miscellaneous Correction
Please submit an Engineer’s Estimate of Probable Construction Costs.
|
|
Miscellaneous Correction
The existing water main on the south side of SE Thompson Drive is 16” line, please revise.
|
|
Miscellaneous Correction
Our records indicate the existing water main on the north side of SE Thompson Drive is a 16” line. Please verify and revise if necessary.
|
|
Miscellaneous Correction
The existing water main running east west at the north connection point is an 8” line. Please revise valves accordingly.
|
|
Miscellaneous Correction
Please show and label all existing utility easements and provide easements for any sections of public main outside of existing easements.
|
|
Miscellaneous Correction
Will the tee and valves for the Flex Space fire line be installed as a part of this plan set? The notes were unclear if the tee and valves were future or just the fire line.
|
|
Miscellaneous Correction
Please remove the trench check detail, it’s not required.
|
|
Miscellaneous Correction
Corrective Action Required
Sheet C300:
• Please revise the tee size in Plan view to match the revised existing pipe size.
• Please note that Pressure Class 235 or DR18 is adequate. Pressure Class 250 is not necessary.
• The horizontal graphic scale on Sheet C300 appears to be wrong. Please verify and revise as needed.
• The north arrow is pointing west, please revise.
• There appears to be a 20’ Utility Easement along the north property line. Please verify. If it is present, then the proposed U/E at that location is not required.
|
|
Miscellaneous Correction
Corrective Action Required
Please add the following items to the estimate:
• Thrust Block
• Tee
• Bends
|
|
Miscellaneous Correction
Corrective Action Required
The existing 16" water main on the south side of SE Thompson Drive is located within the R/W. Please revise the plans to correctly locate the main. The proposed U/E will not be required since the extension will be within the R/W.
|
|
|
Engineering Review - Water
|
Corrections
|
03/14/2024
|
03/14/2024
|
|
Sue Pyles, P.E.
|
|
Miscellaneous Correction
Corrective Action Required
Please submit an Engineer’s Estimate of Probable Construction Costs.
|
|
Miscellaneous Correction
Corrective Action Required
The existing water main on the south side of SE Thompson Drive is 16” line, please revise.
|
|
Miscellaneous Correction
Corrective Action Required
Our records indicate the existing water main on the north side of SE Thompson Drive is a 16” line. Please verify and revise if necessary.
|
|
Miscellaneous Correction
Corrective Action Required
The existing water main running east west at the north connection point is an 8” line. Please revise valves accordingly.
|
|
Miscellaneous Correction
Corrective Action Required
Please show and label all existing utility easements and provide easements for any sections of public main outside of existing easements.
|
|
Miscellaneous Correction
Corrective Action Required
Will the tee and valves for the Flex Space fire line be installed as a part of this plan set? The notes were unclear if the tee and valves were future or just the fire line.
|
|
Miscellaneous Correction
Corrective Action Required
Please remove the trench check detail, it’s not required.
|
|
|