Summary
PRRES20242369
Building Permit - Residential
Temporary Occupancy
DOMAIN TIMBERLAKE MULTISTATE LLC
NEW SINGLE FAMILY
NEW HOUSE. UNFINISHED BASEMENT. COVERED PATIO. ROOF TRUSSES.
05/10/2024
05/20/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
DOMAIN TIMBERLAKE MULTISTATE LLC, Address:590 MADISON AVE FL 13TH  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
TYLER@SUMMITHOMESKC.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331401-Water Tap Fee $3,760.00 $3,760.00 Paid 05/20/2024
8350015-Water Meter Fee $680.46 $680.46 Paid 05/20/2024
8331507-Sanitary Sewer Development Fee $2,159.00 $2,159.00 Paid 05/20/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 05/20/2024
7232302-Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 05/20/2024
9110078-Valuation Fee New Single Family $1,853.94 $1,853.94 Paid 05/20/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 12/12/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 12/12/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 12/12/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 12/16/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 01/16/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/13/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Erosion Control Inspection Residential Pending
Miscellaneous Correction
Informational
09/30/2024
Erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Pending 4/12/2025
Misc
Corrective Action Required
01/15/2025
TCO EXTENSION GRANTED FOR ANOTHER 30days. 01/15/25 -address to be properly illuminated -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -bring water meter pit to grade (ensure 14”-18” from top of meter to well lid ring) -identify sewer tracer wire
Footing Inspection - Residential Passed 5/31/2024 5/31/2024 05/31/2024
Underslab Plumbing Inspection - Residential Passed 6/20/2024 6/20/2024 06/20/2024
Erosion Control Inspection Residential Partial 6/20/2024 06/20/2024
Misc
Informational
06/20/2024
Erosion control in compliance at time of inspection.
Sewer Service Inspection - R Passed 6/27/2024 6/27/2024 06/27/2024
Erosion Control Inspection Residential Failed 6/27/2024 6/27/2024 06/27/2024
Misc
Resolved
06/27/2024
Erosi
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
06/27/2024
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED.
Water Service Inspection - R Passed 6/28/2024 06/28/2024
All Rough Inspection - Residential Not Ready 7/16/2024 7/16/2024 07/16/2024
Misc
Corrective Action Required
07/16/2024
Nailing not done Strapping not done
Erosion Control Inspection Residential Failed 7/16/2024 07/16/2024
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
07/16/2024
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/16/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS SILT FENCE AT FRONT OF LOT
All Rough Inspection - Residential Partial 8/12/2024 8/12/2024 08/12/2024
Misc
Resolved
08/12/2024
Nailing not done Strapping not done
Misc
Informational
08/12/2024
Garage portal frame nailing only.
All Rough Inspection - Residential Not Ready 9/16/2024 9/16/2024 09/16/2024
Misc
Informational
08/12/2024
Garage portal frame nailing only.
Misc
Corrective Action Required
09/16/2024
09/16/24-inspection denied no city stamped plans on site Furr outs not completed
Erosion Control Inspection Residential Partial 9/30/2024 09/30/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
09/30/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS SILT FENCE AT FRONT OF LOT
Miscellaneous Correction
Informational
09/30/2024
Erosion control measures are in place and must be maintained until CofO
Electrical Service Inspection Passed 9/30/2024 09/30/2024
Gas Service Inspection - Residential Passed 9/30/2024 09/30/2024
All Rough Inspection - Residential Failed 9/30/2024 9/30/2024 09/30/2024
Misc
Informational
09/16/2024
Garage portal frame nailing only.
Misc
Resolved
09/30/2024
09/16/24-inspection denied no city stamped plans on site Furr outs not completed
Miscellaneous Correction
Corrective Action Required
09/30/2024
All garage anchor bolts need to be located in the middle 1/3 of the sole plate Nail all interior corners of garage to code Garage Ibeam calls for a steel column on the east side LIB in garage is not fully nailed off Fire block top of HVAC chase in garage (5) 2x4 stud pack is not fully installed in garage south wall No attic access hatch is installed in garage north ceiling Truss hangers are not installed in garage at C3 trusses Vertically support HVAC line in garage fur down along the east wall Nail garage to pantry corner to code Fire block Smurf tube in pantry at top plate Fire block 14/2 electrical in pantry at top plate Install missing nails in joist hangers in entry to great room BOCA plate is needed for mechanical at baseboard in great room Triple LVL at great room and entry is not fully supported be the top plate Fire block gas line at fireplace floor Gas line is not hooked up to anything at the fireplace Fire block top of chases in great room Nail all corners to code throughout Fire block gas line at stove in floor Install nail in joist hanger in foyer Part of LIB is not installed in the foyer Flex room is missing LIB BOCA plate is needed for mechanical in flex room at the sole plate Fire block balloon framing at 2x6 wall in the steak well east wall Bedroom 1 N/E corner consists of only 2 studs Tie in the corner of closet 2 to bedroom 1 Fire block hole at mechanical in stairwell Stair string beams from the main living to the basement do not have 1 1/2 inches of support of double 2x10’s Stair stringer beams from basement platform to the basement does not have 1 1/2 inches of support Support basement platform with vertical stiff legs Basement window header is not supported with jack studs Steel post columns in basement are not secured at the base Last floor joist in the basement at N/W corner is notched out within 2 inches of the bottom for A/C line Floor joist in basement by HVAC unit has need notched out for a 3 inch DWV line Front and back porch truss tie downs were covered without inspection
All Rough Inspection - Residential Not Ready 10/9/2024 10/9/2024 10/09/2024
Misc
Resolved
10/09/2024
Garage portal frame nailing only.
Miscellaneous Correction
Resolved
10/09/2024
All garage anchor bolts need to be located in the middle 1/3 of the sole plate Nail all interior corners of garage to code Garage Ibeam calls for a steel column on the east side LIB in garage is not fully nailed off Fire block top of HVAC chase in garage (5) 2x4 stud pack is not fully installed in garage south wall No attic access hatch is installed in garage north ceiling Truss hangers are not installed in garage at C3 trusses Vertically support HVAC line in garage fur down along the east wall Nail garage to pantry corner to code Fire block Smurf tube in pantry at top plate Fire block 14/2 electrical in pantry at top plate Install missing nails in joist hangers in entry to great room BOCA plate is needed for mechanical at baseboard in great room Triple LVL at great room and entry is not fully supported be the top plate Fire block gas line at fireplace floor Gas line is not hooked up to anything at the fireplace Fire block top of chases in great room Nail all corners to code throughout Fire block gas line at stove in floor Install nail in joist hanger in foyer Part of LIB is not installed in the foyer Flex room is missing LIB BOCA plate is needed for mechanical in flex room at the sole plate Fire block balloon framing at 2x6 wall in the steak well east wall Bedroom 1 N/E corner consists of only 2 studs Tie in the corner of closet 2 to bedroom 1 Fire block hole at mechanical in stairwell Stair string beams from the main living to the basement do not have 1 1/2 inches of support of double 2x10’s Stair stringer beams from basement platform to the basement does not have 1 1/2 inches of support Support basement platform with vertical stiff legs Basement window header is not supported with jack studs Steel post columns in basement are not secured at the base Last floor joist in the basement at N/W corner is notched out within 2 inches of the bottom for A/C line Floor joist in basement by HVAC unit has need notched out for a 3 inch DWV line Front and back porch truss tie downs were covered without inspection
Miscellaneous Correction
Corrective Action Required
10/09/2024
1617 SW Arborway terrace. All rough (2) Nail all interior corners of garage to code (between the 2 overhead garage doors and also attach king stud to headed that was missed too) Garage Ibeam calls for a steel column on the east side (attach newly installed steel column to the Ibeam) Fire block top of HVAC chase in garage (5) 2x4 stud pack is not fully installed in garage south wall (attach LIB to 5 pack) No attic access hatch is installed in garage north ceiling Install missing nails in joist hanger in entry to great room by stairwell BOCA plate is needed for mechanical at baseboard in great room Fire block gas line at fireplace floor Gas line is not hooked up to fireplace Fire block top of chase in great room containing waste line BOCA plate is needed for mechanical in flex room at the sole plate Stair string beams from the main living to the basement do not have 1 1/2 inches of support of double 2x10’s Stair stringer beams from basement platform to the basement does not have 1 1/2 inches of support Support basement platform with vertical stiff legs Basement window header is not supported with jack studs Steel post columns in basement are not secured at the base Last floor joist in the basement at N/W corner is notched out within 2 inches of the bottom for A/C line Floor joist in basement by HVAC unit has need notched out for a 3 inch DWV line Front and back porch truss tie downs were covered without inspection Nail all up stairs corners to code Not all corrections were made. This is not a complete list Re inspection was not ready
All Rough Inspection - Residential Failed 10/11/2024 10/11/2024 10/11/2024
Miscellaneous Correction
Corrective Action Required
10/09/2024
Gas line is not hooked up to fireplace Fire block great room chases right and left or rear Fireblock primary bedroom E wall to ceiling space
All Rough Inspection - Residential Failed 10/15/2024 10/15/2024 10/15/2024
Miscellaneous Correction
Corrective Action Required
10/11/2024
Secure gas line at fireplace Fireblock primary bedroom E wall to ceiling space seal gaps
All Rough Inspection - Residential Passed 10/16/2024 10/16/2024 10/16/2024
Miscellaneous Correction
Resolved
10/16/2024
Secure gas line at fireplace Fireblock primary bedroom E wall to ceiling space seal gaps
Piers/Caissons Inspection - Residential Passed 11/19/2024 11/19/2024 11/19/2024
Driveway Inspection Partial 11/21/2024 11/21/2024 11/21/2024
Misc
Informational
11/21/2024
11-21-24 Dustin A, DW is formed and compacted. Must cover overnight. Approved to pour
Driveway Inspection Partial 12/2/2024 12/2/2024 12/02/2024
Misc
Informational
11/21/2024
11-21-24 Dustin A, DW is formed and compacted. Must cover overnight. Approved to pour 12-2-24 Dustin A, DW poured to city specs. Cannot pass until forms pulled
Occupancy Inspection - Codes Residential Failed 12/12/2024 12/12/2024 12/12/2024
Misc
Corrective Action Required
12/12/2024
-address to be properly illuminated -address pending driveway inspection -final grade and sod -bring water meter pit to grade (ensure 14”-18” from top of meter to well lid ring) -guard rail at front stoop where required -identify sewer tracer wire
Driveway Inspection Passed 12/12/2024 12/12/2024
Misc
Informational
12/02/2024
11-21-24 Dustin A, DW is formed and compacted. Must cover overnight. Approved to pour 12-2-24 Dustin A, DW poured to city specs. Cannot pass until forms pulled 12-12-24 Dustin A, Forms are pulled passed
Occupancy Inspection - Codes Residential Ready for Temp CO 12/16/2024 12/16/2024 12/16/2024
Misc
Corrective Action Required
12/12/2024
-address to be properly illuminated -final grade and sod -bring water meter pit to grade (ensure 14”-18” from top of meter to well lid ring) -identify sewer tracer wire
Occupancy Inspection - Codes Residential Ready for Temp CO 1/15/2025 01/15/2025
Misc
Corrective Action Required
12/16/2024
TCO EXTENSION GRANTED FOR ANOTHER 30days. 01/15/25 -address to be properly illuminated -final grade and sod -splash blocks and sump pump discharge to extend 36” from foundation -bring water meter pit to grade (ensure 14”-18” from top of meter to well lid ring) -identify sewer tracer wire
Documents & Images
Date Uploaded File Type Document Name
05/10/2024 HT #182 - PERMIT APP
05/17/2024 Approved Plans APPROVED PLANS
05/17/2024 Plot Plan APPROVED PLOT PLAN
05/17/2024 Approved Plans APPROVED TRUSS PACKAGE
05/17/2024 Approved Plans APPROVED TRUSS LAYOUT
05/17/2024 Permit Codes Residential Plan Review
05/20/2024 Permit DS Building Permit
05/20/2024 Receipt Receipt for transaction:2024-003660
05/31/2024 1617 SW Arborway Terr LSMO Footing Inspection Report 5-30-24
05/31/2024 Letter INSPECTION SUMMARY
06/20/2024 Letter INSPECTION SUMMARY
06/20/2024 Letter INSPECTION SUMMARY
06/27/2024 Letter INSPECTION SUMMARY
06/27/2024 Letter INSPECTION SUMMARY
06/28/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
08/12/2024 Letter INSPECTION SUMMARY
09/16/2024 Letter INSPECTION SUMMARY
09/30/2024 Letter INSPECTION SUMMARY
09/30/2024 Letter INSPECTION SUMMARY
09/30/2024 Letter INSPECTION SUMMARY
09/30/2024 Letter INSPECTION SUMMARY
10/07/2024 182 Hawthorn Ridge Field Issue- signed
10/09/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/15/2024 Letter INSPECTION SUMMARY
10/16/2024 Letter INSPECTION SUMMARY
11/19/2024 Letter INSPECTION SUMMARY
11/21/2024 Letter INSPECTION SUMMARY
12/02/2024 Letter INSPECTION SUMMARY
12/12/2024 Letter INSPECTION SUMMARY
12/12/2024 Receipt Receipt for transaction:2024-009485
12/12/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/16/2024 Certificate/License Codes Temporary Certificate of Occupancy
12/16/2024 Receipt Receipt for transaction:2024-009523
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Letter Codes 10 Day Letter
01/15/2025 Application Form HT #182 - TCO Extension 1_15_25
01/15/2025 Letter INSPECTION SUMMARY
01/15/2025 Letter Codes 10 Day Letter
01/16/2025 Certificate/License Codes Temporary Certificate of Occupancy
01/16/2025 Receipt Receipt for transaction:2025-000287
03/13/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/13/2025 Receipt Receipt for transaction:2025-001525
06/04/2025 Letter Codes 140 Day Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents