Permit Application Status

PRRES20240625


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20240625
Building Permit - Residential
Certificate of Occupancy
NEW 3 OR 4 FAMILY
NEW FOURPLEX. UNFINISHED BASEMENT. ROOF TRUSSES.
02/13/2024
02/22/2024
08/13/2024
10/29/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
CARUTHERS ELECTRICAL LLC, Address:30905 E TRUMAN RD, Phone:(816) 508-9050  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
JASONH@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New 3 or 4 Family $4,453.33 $4,453.33 Paid 02/22/2024
Right of Way Permit Fee $85.00 $85.00 Paid 02/22/2024
Residential Excise Tax Fee $2,480.64 $2,480.64 Paid 02/22/2024
Water Tap Fee $15,040.00 $15,040.00 Paid 02/22/2024
Water Meter Fee $2,721.84 $2,721.84 Paid 02/22/2024
Sanitary Sewer Development Fee $8,636.00 $8,636.00 Paid 02/22/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 06/21/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 09/03/2024
Not Ready Inspection Fee $75.00 $75.00 Paid 09/03/2024
3rd and Subsequent Inspection Fee (Per Hour) $75.00 $75.00 Paid 09/25/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 09/25/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Partial 3/28/2024 03/28/2024
Miscellaneous Correction
Informational
03/28/2024
Full erosion control measures are in place and needs to be maintained until CofO
Footing Inspection - Residential Passed 3/28/2024 03/28/2024
Miscellaneous Correction
Informational
03/28/2024
Footing passed by a third party. Piers were not mentioned in the footing inspection Footing appears to be within the approved lot line clearances
Sewer Service Inspection - R Partial 4/10/2024 04/10/2024
Miscellaneous Correction
Informational
04/10/2024
Sewer at 3726 and 3728 both passed. This is a partial pass only. Other units will be scheduled at a later date
Sewer Service Inspection - R Passed 4/11/2024 04/11/2024
Miscellaneous Correction
Informational
04/10/2024
Sewer at 3726 and 3728 both passed. This is a partial pass only. Other units will be scheduled at a later date
Water Service Inspection - R Passed 4/12/2024 04/12/2024
Underslab Plumbing Inspection - Residential Failed 4/17/2024 4/17/2024 04/17/2024
Miscellaneous Correction
Corrective Action Required
04/17/2024
Underslab plumbing Underslab plumbing will not pass until all wood from forms which includes stakes are removed from contact of the ground. R317.1.2 ground contact
Underslab Plumbing Inspection - Residential Passed 4/22/2024 4/22/2024 04/22/2024
Miscellaneous Correction
Resolved
04/22/2024
Underslab plumbing Underslab plumbing will not pass until all wood from forms which includes stakes are removed from contact of the ground. R317.1.2 ground contact
All Rough Inspection - Residential Partial 5/24/2024 5/24/2024 05/24/2024
Miscellaneous Correction
Informational
05/24/2024
Exterior garage portal inspection passed and is ok to cover. Interior of garage was not inspected This is a partial pass only
All Rough Inspection - Residential Failed 6/13/2024 6/13/2024 06/13/2024
Miscellaneous Correction
Resolved
06/13/2024
Exterior garage portal inspection passed and is ok to cover. Interior of garage was not inspected This is a partial pass only
Miscellaneous Correction
Corrective Action Required
06/13/2024
3722, 3726, 3728 and 3730 SW Clayton all rough 3730 Upload engineers letter addressing north side overhang of bottom plate Roof jacks are missing Shoe studs in utility room is missing nails Vent fan of bathroom 3 is not placed correctly 3728 Have engineer address exposed support rebar in concrete located in the garage S/E corner tightened down garage anchor bolt on south wall Have engineer address garage north side sole plate not fully situated on the concrete support wall Roof jacks are missing Support the north side of the 2x10 supporting the stair stringers in the basement closet to the main entry floor Vertically fire block basement rec room south wall every 10 feet on center Basement bathroom 3 vent fan is not connected Tightened down anchor bolts in bedroom 3 3726 Have engineer address sole plate not being fully supported by concrete support wall in garage along south wall LIB in garage chase is not completely nailed off Fire block top plate in garage at low voltage wire north wall Take wooden wedge out of wall cavity in rated assembly in entry for 3/4 inch gap requirement Roof jacks are missing Fire block sole plate of great room along the south wall Stud missing between bathroom 1 and bathroom 2 Basement bathroom 3 vent fan is not connected to flex piping Tightened down anchor bolts in bedroom 3 Gas gauge reads 0 at the time of inspection 3722 Have engineer address garage north side sole plate not fully resting to concrete support wall Replace broken ceiling/floor joist blocking in garage S/E corner Fire block 1 1/2 inch waste line in ceiling/floor cavity in garage for bathroom above Roof jacks are not installed Install hurricane clip in truss in great room where the truss tie down screw is in the middle of a crack above triple windows Stud shoe in utility room is missing nails Stud shoe in bathroom 2 and 1 is missing nails Basement bathroom 3 is missing vent fan and complete installation of flex piping Tightened down anchor bolt in bedroom 3
Electrical Service Inspection Passed 6/13/2024 06/13/2024
Gas Service Inspection - Residential Failed 6/13/2024 06/13/2024
Miscellaneous Correction
Corrective Action Required
06/13/2024
Gas gauge in unit 3726 read 0 when starting inspection Units 3722, 3728 and 3730 all passed
Rated Assembly Inspection Failed 6/13/2024 6/13/2024 06/13/2024
Miscellaneous Correction
Corrective Action Required
06/13/2024
3730-3722 SW Clayton Rated assembly 3730 Passed 3728 vertical fire blocking is missing every 10 feet in living room/kitchen area Vertical fire block basement re room south wall every 10 feet on center 3726 vertical fire block living room utility room to bedroom 2 every 10 feet on center 3722 Passed
Erosion Control Inspection Residential Failed 6/21/2024 06/21/2024
Miscellaneous Correction
Informational
03/28/2024
Full erosion control measures are in place and needs to be maintained until CofO
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
06/21/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. Install erosion control at the front of the lot before scheduling any inspections Full erosion control must be maintained until CofO
Gas Service Inspection - Residential Passed 6/21/2024 6/21/2024 06/21/2024
Miscellaneous Correction
Resolved
06/21/2024
Gas gauge in unit 3726 read 0 when starting inspection Units 3722, 3728 and 3730 all passed
Rated Assembly Inspection Not Ready 6/21/2024 6/21/2024 06/21/2024
Miscellaneous Correction
Resolved
06/21/2024
3730-3722 SW Clayton Rated assembly 3730 Passed 3728 vertical fire blocking is missing every 10 feet in living room/kitchen area Vertical fire block basement re room south wall every 10 feet on center 3726 vertical fire block living room utility room to bedroom 2 every 10 feet on center 3722 Passed
Miscellaneous Correction
Corrective Action Required
06/21/2024
3730-3722 SW Clayton Rated assembly 3730 Passed 3728 vertical fire blocking is missing every 10 feet in living room/kitchen area Vertical fire block basement re room south wall every 10 feet on center (Unit 3728 was not ready for reinspection) 3726 vertical fire block living room utility room to bedroom 2 every 10 feet on center 3722 Passed Not a complete list for reinspection
All Rough Inspection - Residential Not Ready 6/21/2024 6/21/2024 06/21/2024
Miscellaneous Correction
Resolved
06/21/2024
3722, 3726, 3728 and 3730 SW Clayton all rough 3730 Upload engineers letter addressing north side overhang of bottom plate Roof jacks are missing Shoe studs in utility room is missing nails Vent fan of bathroom 3 is not placed correctly 3728 Have engineer address exposed support rebar in concrete located in the garage S/E corner tightened down garage anchor bolt on south wall Have engineer address garage north side sole plate not fully situated on the concrete support wall Roof jacks are missing Support the north side of the 2x10 supporting the stair stringers in the basement closet to the main entry floor Vertically fire block basement rec room south wall every 10 feet on center Basement bathroom 3 vent fan is not connected Tightened down anchor bolts in bedroom 3 3726 Have engineer address sole plate not being fully supported by concrete support wall in garage along south wall LIB in garage chase is not completely nailed off Fire block top plate in garage at low voltage wire north wall Take wooden wedge out of wall cavity in rated assembly in entry for 3/4 inch gap requirement Roof jacks are missing Fire block sole plate of great room along the south wall Stud missing between bathroom 1 and bathroom 2 Basement bathroom 3 vent fan is not connected to flex piping Tightened down anchor bolts in bedroom 3 Gas gauge reads 0 at the time of inspection 3722 Have engineer address garage north side sole plate not fully resting to concrete support wall Replace broken ceiling/floor joist blocking in garage S/E corner Fire block 1 1/2 inch waste line in ceiling/floor cavity in garage for bathroom above Roof jacks are not installed Install hurricane clip in truss in great room where the truss tie down screw is in the middle of a crack above triple windows Stud shoe in utility room is missing nails Stud shoe in bathroom 2 and 1 is missing nails Basement bathroom 3 is missing vent fan and complete installation of flex piping Tightened down anchor bolt in bedroom 3
Miscellaneous Correction
Corrective Action Required
06/21/2024
3722, 3726, 3728 and 3730 SW Clayton all rough (2) 3730 Upload engineers letter addressing north side overhang of bottom plate Roof jacks are missing Shoe studs in utility room is missing nails Vent fan of bathroom 3 is not placed correctly 3728 Have engineer address exposed support rebar in concrete located in the garage S/E corner tightened down garage anchor bolt on south wall Have engineer address garage north side sole plate not fully situated on the concrete support wall Roof jacks are missing Support the north side of the 2x10 supporting the stair stringers in the basement closet to the main entry floor Vertically fire block basement rec room south wall every 10 feet on center Basement bathroom 3 vent fan is not connected Tightened down anchor bolts in bedroom 3 3726 Have engineer address sole plate not being fully supported by concrete support wall in garage along south wall LIB in garage chase is not completely nailed off Fire block top plate in garage at low voltage wire north wall Take wooden wedge out of wall cavity in rated assembly in entry for 3/4 inch gap requirement Roof jacks are missing Fire block sole plate of great room along the south wall Stud missing between bathroom 1 and bathroom 2 Basement bathroom 3 vent fan is not connected to flex piping Tightened down anchor bolts in bedroom 3 Gas gauge reads 0 at the time of inspection 3722 Have engineer address garage north side sole plate not fully resting to concrete support wall Replace broken ceiling/floor joist blocking in garage S/E corner Fire block 1 1/2 inch waste line in ceiling/floor cavity in garage for bathroom above Roof jacks are not installed Install hurricane clip in truss in great room where the truss tie down screw is in the middle of a crack above triple windows Stud shoe in utility room is missing nails Stud shoe in bathroom 2 and 1 is missing nails Basement bathroom 3 is missing vent fan and complete installation of flex piping Tightened down anchor bolt in bedroom 3 Have engineers letter address all units separately for bottom sole plate not fully supported by the concrete foundation support wall Unit 3728 exposed rebar in the garage foundation wall was not completed as per the engineers letter. This is not a complete list. Inspection was not completed because of not being ready 06/20/2024. KBEARD
Rated Assembly Inspection Passed 7/1/2024 07/01/2024
Miscellaneous Correction
Resolved
07/01/2024
3730-3722 SW Clayton Rated assembly 3730 Passed 3728 vertical fire blocking is missing every 10 feet in living room/kitchen area Vertical fire block basement re room south wall every 10 feet on center (Unit 3728 was not ready for reinspection) 3726 vertical fire block living room utility room to bedroom 2 every 10 feet on center 3722 Passed Not a complete list for reinspection
All Rough Inspection - Residential Passed 7/1/2024 7/1/2024 07/01/2024
Miscellaneous Correction
Resolved
07/01/2024
3722, 3726, 3728 and 3730 SW Clayton all rough (2) 3730 Upload engineers letter addressing north side overhang of bottom plate Roof jacks are missing Shoe studs in utility room is missing nails Vent fan of bathroom 3 is not placed correctly 3728 Have engineer address exposed support rebar in concrete located in the garage S/E corner tightened down garage anchor bolt on south wall Have engineer address garage north side sole plate not fully situated on the concrete support wall Roof jacks are missing Support the north side of the 2x10 supporting the stair stringers in the basement closet to the main entry floor Vertically fire block basement rec room south wall every 10 feet on center Basement bathroom 3 vent fan is not connected Tightened down anchor bolts in bedroom 3 3726 Have engineer address sole plate not being fully supported by concrete support wall in garage along south wall LIB in garage chase is not completely nailed off Fire block top plate in garage at low voltage wire north wall Take wooden wedge out of wall cavity in rated assembly in entry for 3/4 inch gap requirement Roof jacks are missing Fire block sole plate of great room along the south wall Stud missing between bathroom 1 and bathroom 2 Basement bathroom 3 vent fan is not connected to flex piping Tightened down anchor bolts in bedroom 3 Gas gauge reads 0 at the time of inspection 3722 Have engineer address garage north side sole plate not fully resting to concrete support wall Replace broken ceiling/floor joist blocking in garage S/E corner Fire block 1 1/2 inch waste line in ceiling/floor cavity in garage for bathroom above Roof jacks are not installed Install hurricane clip in truss in great room where the truss tie down screw is in the middle of a crack above triple windows Stud shoe in utility room is missing nails Stud shoe in bathroom 2 and 1 is missing nails Basement bathroom 3 is missing vent fan and complete installation of flex piping Tightened down anchor bolt in bedroom 3 Have engineers letter address all units separately for bottom sole plate not fully supported by the concrete foundation support wall Unit 3728 exposed rebar in the garage foundation wall was not completed as per the engineers letter. This is not a complete list. Inspection was not completed because of not being ready 06/20/2024. KBEARD
Erosion Control Inspection Residential Partial 7/1/2024 07/01/2024
Miscellaneous Correction
Resolved
07/01/2024
Full erosion control measures are in place and needs to be maintained until CofO
DCM2 ESC DEFICIENT INSTALLATION
Resolved
07/01/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. Install erosion control at the front of the lot before scheduling any inspections Full erosion control must be maintained until CofO
Miscellaneous Correction
Informational
07/01/2024
Full erosion control measures are in place and needs to be maintained until CofO
Sidewalk Inspection Partial 7/9/2024 7/9/2024 07/09/2024
Misc
Informational
07/09/2024
7-9-24 PS Sidewalk pre pour, forms in place and aggregate compacted, approved to pour
Driveway Inspection Partial 7/9/2024 7/9/2024 07/09/2024
Misc
Informational
07/09/2024
7-9-24 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour
Rated Assembly Inspection Not Ready 7/10/2024 07/10/2024
Miscellaneous Correction
Corrective Action Required
07/10/2024
No access provided Concrete driveway just got poured this morning Not ready for inspection
Rated Assembly Inspection Passed 7/11/2024 7/11/2024 07/11/2024
Miscellaneous Correction
Resolved
07/11/2024
No access provided Concrete driveway just got poured this morning Not ready for inspection
Driveway Inspection Passed 7/16/2024 7/16/2024 07/16/2024
Misc
Informational
07/09/2024
7-9-24 PS Driveway approach pre pour, forms in place and aggregate compacted, approved to pour 7-16-24 PS Driveway approach meets LS and ADA specs
Piers/Caissons Inspection - Residential Passed 7/31/2024 07/31/2024
Piers/Caissons Inspection - Residential Passed 8/6/2024 08/06/2024
Occupancy Inspection - Codes Residential Failed 9/4/2024 9/4/2024 09/04/2024
Miscellaneous Correction
Corrective Action Required
09/04/2024
3730 SW Clayton Occupancy 3722 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference Handrail going to the basement does not meet code height Fire block gaps in the ceiling in the garage above the overhead garage door and where the garage door rail bracket meets the ceiling 3726 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference 3728 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference Fire block all gaps in ceiling of garage 3730 First stair up from the main living area to upstairs bedrooms has a riser height greater than the code allowance First stair up from the entry to the main living area has a riser height greater than the code allowed 3/8 of an inch difference Seal attic access hatch upstairs Fire block all gaps in ceiling of garage which includes the garage door rail bracket Front door will not shut Sod, splash pads and sump pump extensions are not installed Seal all exterior penetrations Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar
Sidewalk Inspection Partial 7/16/2024 7/16/2024 09/06/2024
Misc
Informational
07/09/2024
7-9-24 PS Sidewalk pre pour, forms in place and aggregate compacted, approved to pour 7-16-24 PS, Part of Sidewalk meets ADA and LS specs. 9-6-24 Dustin A, Still needs a section poured where there is a atnt box in way, Box will need to be moved
Occupancy Inspection - Codes Residential Failed 9/6/2024 9/6/2024 09/06/2024
Miscellaneous Correction
Resolved
09/06/2024
3730 SW Clayton Occupancy 3722 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference Handrail going to the basement does not meet code height Fire block gaps in the ceiling in the garage above the overhead garage door and where the garage door rail bracket meets the ceiling 3726 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference 3728 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference Fire block all gaps in ceiling of garage 3730 First stair up from the main living area to upstairs bedrooms has a riser height greater than the code allowance First stair up from the entry to the main living area has a riser height greater than the code allowed 3/8 of an inch difference Seal attic access hatch upstairs Fire block all gaps in ceiling of garage which includes the garage door rail bracket Front door will not shut Sod, splash pads and sump pump extensions are not installed Seal all exterior penetrations Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar
Miscellaneous Correction
Corrective Action Required
09/06/2024
3730 SW Clayton Occupancy (2) 3722 Handrail going to the basement does not meet code height 3726 Passed 3728 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference (now appears to have a greater than 2%slope) 3730 First stair up from the entry to the main living area has a riser height greater than the code allowed 3/8 of an inch difference (now appears to have greater than 2% slope) Seal attic access hatch upstairs Sod, splash pads and sump pump extensions are not installed Seal all exterior penetrations Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Sidewalk inspection must pass
Sidewalk Inspection Partial 9/17/2024 9/17/2024 09/17/2024
Misc
Informational
09/06/2024
7-9-24 PS Sidewalk pre pour, forms in place and aggregate compacted, approved to pour 7-16-24 PS, Part of Sidewalk meets ADA and LS specs. 9-6-24 Dustin A, Still needs a section poured where there is a atnt box in way, Box will need to be moved 9-17-24 Dustin A, Missing sections have been formed, compacted. Slopes are in compliance. Approved to pour missing sections
Erosion Control Inspection Residential Failed 9/18/2024 09/18/2024
Miscellaneous Correction
Resolved
09/18/2024
Full erosion control measures are in place and needs to be maintained until CofO
Miscellaneous Correction
Corrective Action Required
09/18/2024
Erosion control measures are missing at the front of the lot next to the street on both sides Full erosion control measures must be maintained until CofO
Occupancy Inspection - Codes Residential Failed 9/18/2024 9/18/2024 09/18/2024
Miscellaneous Correction
Resolved
09/18/2024
3730 SW Clayton Occupancy (2) 3722 Handrail going to the basement does not meet code height 3726 Passed 3728 First stair up from main living area to upstairs bedrooms has a riser height greater than the code allowed 3/8 of an inch difference (now appears to have a greater than 2%slope) 3730 First stair up from the entry to the main living area has a riser height greater than the code allowed 3/8 of an inch difference (now appears to have greater than 2% slope) Seal attic access hatch upstairs Sod, splash pads and sump pump extensions are not installed Seal all exterior penetrations Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Sidewalk inspection must pass
Miscellaneous Correction
Corrective Action Required
09/18/2024
3730 SW Clayton Occupancy 3722 Interior passed Nails are missing in deck joist hangers 3726 Interior passed 3728 Interior passed Sump pump extension is barried Exterior of basement window is missing trim and is exposed to the weather Nails are missing in deck joist hangers 3730 Seal attic access hatch upstairs Seal exterior penetrations Corner brackets are missing for deck rim board to house ledger Sod and splash pads are not installed Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Pay $75 fee associated with this permit Full erosion control measures must be in place before scheduling any more inspections Sidewalk inspection must pass KBEARD 2:10pm
Occupancy Inspection - Codes Residential Failed 9/24/2024 9/24/2024 09/24/2024
Miscellaneous Correction
Resolved
09/24/2024
3730 SW Clayton Occupancy 3722 Interior passed Nails are missing in deck joist hangers 3726 Interior passed 3728 Interior passed Sump pump extension is barried Exterior of basement window is missing trim and is exposed to the weather Nails are missing in deck joist hangers 3730 Seal attic access hatch upstairs Seal exterior penetrations Corner brackets are missing for deck rim board to house ledger Sod and splash pads are not installed Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Pay $75 fee associated with this permit Full erosion control measures must be in place before scheduling any more inspections Sidewalk inspection must pass
Miscellaneous Correction
Corrective Action Required
09/24/2024
3730 SW Clayton Occupancy 3722 Interior passed Nails are missing in deck joist hangers 3726 Interior passed 3728 Interior passed Sump pump extension is barried Exterior of basement window is missing trim and is exposed to the weather Nails are missing in deck joist hangers 3730 Seal attic access hatch upstairs Seal exterior penetrations Corner brackets are missing for deck rim board to house ledger Sod and splash pads are not installed Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Pay $75 fee associated with this permit Full erosion control measures must be in place before scheduling any more inspections Sidewalk inspection still needs to pass Last inspection stated that erosion control measures must be in place before scheduling any more inspections. Erosion control is still not installed at the front of the lot. Clean mud off side walk Walk your property before scheduling your inspections Inspection is denied KBEARD 09/24/24. Time 9:02 am
Sidewalk Inspection Passed 9/24/2024 9/24/2024 09/24/2024
Misc
Informational
09/17/2024
7-9-24 PS Sidewalk pre pour, forms in place and aggregate compacted, approved to pour 7-16-24 PS, Part of Sidewalk meets ADA and LS specs. 9-6-24 Dustin A, Still needs a section poured where there is a atnt box in way, Box will need to be moved 9-17-24 Dustin A, Missing sections have been formed, compacted. Slopes are in compliance. Approved to pour missing sections 9-24-24 Dustin A, SW is poured to city specs. Passed
Plot Plan Inspection Passed 9/25/2024 09/25/2024
Erosion Control Inspection Residential Partial 9/25/2024 09/25/2024
Miscellaneous Correction
Resolved
09/25/2024
Erosion control measures are missing at the front of the lot next to the street on both sides Full erosion control measures must be maintained until CofO
Miscellaneous Correction
Informational
09/25/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Ready for Temp CO 9/25/2024 9/25/2024 09/25/2024
Miscellaneous Correction
Resolved
09/25/2024
3730 SW Clayton Occupancy 3722 Interior passed Nails are missing in deck joist hangers 3726 Interior passed 3728 Interior passed Sump pump extension is barried Exterior of basement window is missing trim and is exposed to the weather Nails are missing in deck joist hangers 3730 Seal attic access hatch upstairs Seal exterior penetrations Corner brackets are missing for deck rim board to house ledger Sod and splash pads are not installed Final grading is not completed for plot plan inspection Unit 3726 has a broken water meter collar Pay $75 fee associated with this permit Full erosion control measures must be in place before scheduling any more inspections Sidewalk inspection still needs to pass Last inspection stated that erosion control measures must be in place before scheduling any more inspections. Erosion control is still not installed at the front of the lot. Clean mud off side walk Walk your property before scheduling your inspections Inspection is denied KBEARD 09/24/24. Time 9:02 am
Miscellaneous Correction
Corrective Action Required
09/25/2024
3722-3730 SW Clayton Occupancy All units Sod and splash pads are not installed Install sump pump extensions Seal all exterior penetrations Pay $75 fee associated with this permit All units pass for TCO only
Erosion Control Inspection Residential Passed 10/29/2024 10/29/2024
Miscellaneous Correction
Resolved
10/29/2024
Full erosion control measures are in place and must be maintained until CofO
Occupancy Inspection - Codes Residential Full C of O 10/29/2024 10/29/2024
Miscellaneous Correction
Resolved
10/29/2024
3722-3730 SW Clayton Occupancy All units Sod and splash pads are not installed Install sump pump extensions Seal all exterior penetrations Pay $75 fee associated with this permit All units pass for TCO only
Documents & Images
Date Uploaded File Type Document Name
02/13/2024 OS #43 - PERMIT APP
02/15/2024 Permit Codes Residential Plan Review
02/16/2024 Plot Plan APPROVED PLOT PLAN
02/22/2024 Approved Plans APPROVED TRUSS PACKAGE
02/22/2024 Approved Plans APPROVED PLANS
02/22/2024 Approved Plans APPROVED TRUSS LAYOUT
02/22/2024 Permit Codes Residential Plan Review
02/22/2024 Permit DS Building Permit
02/22/2024 Receipt Receipt for transaction:2024-001017
03/28/2024 M L Crose 3722, 3726, 3728, 3730 SW Clayton Pl LSMO Osage Lot 46 Clayton P 2024-0625 3rd Party Footing Inspection Report 3-27-24
03/28/2024 Letter INSPECTION SUMMARY
03/28/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
04/11/2024 Letter INSPECTION SUMMARY
04/12/2024 Letter INSPECTION SUMMARY
04/17/2024 Letter INSPECTION SUMMARY
04/22/2024 Letter INSPECTION SUMMARY
05/24/2024 Letter INSPECTION SUMMARY
06/13/2024 Letter INSPECTION SUMMARY
06/13/2024 Letter INSPECTION SUMMARY
06/13/2024 Letter INSPECTION SUMMARY
06/13/2024 Letter INSPECTION SUMMARY
06/20/2024 3RD Party Insp Report OS 43 engineering letter
06/21/2024 Letter INSPECTION SUMMARY
06/21/2024 Letter INSPECTION SUMMARY
06/21/2024 Letter INSPECTION SUMMARY
06/21/2024 Receipt Receipt for transaction:2024-005020
06/21/2024 Letter INSPECTION SUMMARY
06/25/2024 Engineer Report/Study ENGINEER LETTER
07/01/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/01/2024 Letter INSPECTION SUMMARY
07/09/2024 Letter INSPECTION SUMMARY
07/09/2024 Letter INSPECTION SUMMARY
07/10/2024 Letter INSPECTION SUMMARY
07/11/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
07/16/2024 Letter INSPECTION SUMMARY
07/31/2024 Letter INSPECTION SUMMARY
08/06/2024 Letter INSPECTION SUMMARY
09/03/2024 Receipt Receipt for transaction:2024-007425
09/04/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/06/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
09/18/2024 Letter INSPECTION SUMMARY
09/18/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/24/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/25/2024 Certificate/License Codes Temporary Certificate of Occupancy
09/25/2024 Receipt Receipt for transaction:2024-007908
10/29/2024 Letter INSPECTION SUMMARY
10/29/2024 Letter Field Certificate of Occupancy
10/29/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home