Permit Application Status

PRRES20216043


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20216043
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - SUSPENDED SLAB - COVERED DECK
11/19/2021
12/02/2021
05/22/2022
11/01/2022
Locations
Contacts
ROBERT A WASHAM CONSTRUCTION INC, Address:2058 NW SOUTH OUTER RD, Phone:(816) 224-5583  
Lindsay Cutler, Address:2058 NW South Outer Rd, Phone:(816) 224-5583  
LINDSAY@ROBWASHAMHOMES.COM  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $630.00 $630.00 Paid 12/02/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/02/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 12/02/2021
9110078-Valuation Fee New Single Family $1,735.14 $1,735.14 Paid 12/02/2021
8331401-Water Tap Fee $3,655.00 $3,655.00 Paid 12/02/2021
8350015-Water Meter Fee $479.24 $479.24 Paid 12/02/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 10/18/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 10/18/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 10/24/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Passed 1/18/2022 1/18/2022 01/18/2022
Sewer Service Inspection - R Passed 1/18/2022 (8:15) 1/18/2022 01/18/2022
Water Service Inspection - R Passed 1/25/2022 (11:15) 1/25/2022 01/25/2022
Erosion Control Inspection Residential Failed 1/25/2022 01/25/2022
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
01/25/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Erosion Control Inspection Residential Failed 2/28/2022 02/28/2022
DCM2 ESC DEFICIENT INSTALLATION
Resolved
02/28/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
02/28/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. ESTABLISH EROSION CONTROL AT REAR OF LOT
Electrical Service Inspection Not Ready 6/21/2022 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
Electrical still being completed at time of inspection
Gas Service Inspection - Residential Failed 6/21/2022 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
provide minimum 10 psi at gas gauge for inspection.
All Rough Inspection - Residential Failed 6/21/2022 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
-complete all electrical -seal gaps and penetrations into furr down in garage -fire block hvac chase into furr down -header to top plate connection per design -complete venting in garage furr down -address over notched stud for dwv above laundry -missing hanger for floor joist above pantry entry to lvl -complete stove hood vent -rear dining room windows framed to cspf per plans -lib bracing though out per plans -seal gaps in fireblocking above fireplace -address notched triple lvl at hanger see great room / foyer -seal return air at master entry hall -address joist to rafter connection above master -address holes border too close to each other above master bath -seal penetrations in joist space above bed 2 entry for RA -address rafters landing on blocks throughout -provide attic access above master -complete bath fan venting in bed 3/4 bath -address roof supports throughout not landing to plans -fire block hvac chase 2nd floor to ceiling space -missing nails in joist hanger above basement stairs -all anchor bolts to be in the middle 1/3 of sill plate in basement
Erosion Control Inspection Residential Failed 7/5/2022 07/05/2022
DCM3 ESC REQUIRED 2 DAY
Resolved
07/05/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. ESTABLISH EROSION CONTROL AT REAR OF LOT
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
07/05/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
07/05/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
All Rough Inspection - Residential Failed 7/5/2022 7/5/2022 07/05/2022
Misc
Corrective Action Required
06/21/2022
EROSION CONTROL TO BE IN COMPLIANCE BEFORE ANY FURTHER INSPECTIONS -header to top plate connection per design at garage portal frame -address over notched stud for dwv above laundry -complete stove hood vent -rear dining room windows framed to cspf per plans and design -lib bracing though out per plans and -address notched triple lvl at hanger see great room / foyer (provide engineering for fix) -seal return air at master entry hall -address joist to rafter connection above master -address over notched ceiling joist above master -address holes border too close to each other above master bath -seal penetrations in joist space above bed 2 entry for RA -address rafters landing on blocks throughout (provide engineer stamped letter) -complete bath fan venting master bath -all anchor bolts to be in the middle 1/3 of sill plate in basement
All Rough Inspection - Residential Failed 7/7/2022 7/7/2022 07/07/2022
Misc
Corrective Action Required
07/05/2022
-header to top plate connection per design at garage portal frame-PROVIDE 2 ROWS 16d SINKERS 3” OC -rear dining room windows framed to cspf per plans and design-CSPF REQUIRES MIN (3) 11 1/4” HEADER AND EXTERIOR NAILING PATTERN- SEE G4 DETAILS -address notched triple lvl at hanger see great room / foyer (provide engineering for fix)-NO ENGINEERED CORRECTION ON FILE -seal return air at master entry hall-SEE BATHROOM STUD CAVITIES -address holes border too close to each other above master bath-NOT DONE -seal penetrations in joist space above bed 2 entry for RA-NOT DONE -complete bath fan venting master bath-NOT DONE
All Rough Inspection - Residential Failed 7/11/2022 7/11/2022 07/11/2022
Misc
Corrective Action Required
07/07/2022
-header to top plate connection per design at garage portal frame-PROVIDE 2 ROWS 16d SINKERS 3” OC -rear dining room windows framed to cspf per plans and design-CSPF REQUIRES MIN (3") 11 1/4” HEADER AND EXTERIOR NAILING PATTERN- SEE G4 DETAILS -address notched triple lvl at hanger see great room / foyer (provide engineering for fix)-NO ENGINEERED CORRECTION ON FILE -address holes border too close to each other above master bath- PROVIDE HANGER AT DOUBLED JOISTS -seal penetrations in joist space above bed 2 entry for RA-NOT DONE
All Rough Inspection - Residential Not Ready 7/14/2022 7/14/2022 07/14/2022
Misc
Corrective Action Required
07/11/2022
-header to top plate connection per design at garage portal frame-PROVIDE 2 ROWS 16d SINKERS 3” OC not done -rear dining room windows framed to cspf per plans and design-CSPF REQUIRES MIN (3") 11 1/4” HEADER AND EXTERIOR NAILING PATTERN- SEE G4 DETAILS not nailed on exterior -address notched triple lvl at hanger see great room / foyer (provide engineering for fix)-NO ENGINEERED CORRECTION ON FILE -address holes border too close to each other above master bath- PROVIDE HANGER AT DOUBLED JOISTS
All Rough Inspection - Residential Passed 7/15/2022 7/15/2022 07/15/2022
Misc
Resolved
07/15/2022
-header to top plate connection per design at garage portal frame-PROVIDE 2 ROWS 16d SINKERS 3” OC not done -rear dining room windows framed to cspf per plans and design-CSPF REQUIRES MIN (3") 11 1/4” HEADER AND EXTERIOR NAILING PATTERN- SEE G4 DETAILS not nailed on exterior -address notched triple lvl at hanger see great room / foyer (provide engineering for fix)-NO ENGINEERED CORRECTION ON FILE -address holes border too close to each other above master bath- PROVIDE HANGER AT DOUBLED JOISTS
Gas Service Inspection - Residential Failed 7/22/2022 7/22/2022 07/22/2022
Misc
Corrective Action Required
06/21/2022
provide minimum 10 psi at gas gauge for inspection. gauge not working correctly. Mitchell Schwarz 07/22/2022 10:29 AM
Electrical Service Inspection Passed 7/22/2022 7/22/2022 07/22/2022
Misc
Resolved
07/22/2022
Electrical still being completed at time of inspection
Gas Service Inspection - Residential Passed 7/25/2022 7/25/2022 07/25/2022
Misc
Resolved
07/25/2022
provide minimum 10 psi at gas gauge for inspection. gauge not working correctly. Mitchell Schwarz 07/22/2022 10:29 AM
Driveway Inspection Passed 9/12/2022 9/12/2022 09/12/2022
Misc
Informational
09/12/2022
On Monday, 9-12-2022 I performed and passed a driveway inspection for concrete placement.
Sidewalk Inspection Passed 9/12/2022 9/12/2022 09/12/2022
Misc
Informational
09/12/2022
On Monday, 9-12-2022, I performed and passed sidewalk inspection for placement of concrete.
Plot Plan Inspection Passed 9/27/2022 09/27/2022
Footing Inspection - Residential Passed 10/17/2022 10/17/2022
Piers/Caissons Inspection - Residential Passed 10/17/2022 10/17/2022
Erosion Control Inspection Residential Failed 10/17/2022 10/17/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
10/17/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
DCM3 ESC REQUIRED 2 DAY
Resolved
10/17/2022
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Misc
Corrective Action Required
10/17/2022
erosion control to remain in compliance until sod is in place
Occupancy Inspection - Codes Residential Failed 10/17/2022 10/17/2022 10/17/2022
Misc
Corrective Action Required
10/17/2022
inspection denied erosion control not in compliance
Occupancy Inspection - Codes Residential Failed 10/18/2022 10/18/2022 10/18/2022
Misc
Resolved
10/18/2022
inspection denied erosion control not in compliance
Misc
Corrective Action Required
10/18/2022
-sod -splash blocks and sump pump discharge to extend 36” from foundation -seal all exterior penetrations -pay all fees -guard rail at front stoop where 30” from ground 36” out -hardware at front door -complete plumbing for dishwasher -laundry electrical not working -complete electrical in floor room at top of stairs floor and ceiling -open junction box in se bedroom closet 2nd floor -hand rail to basement stairs -install water heater -2 1/2” through bolts at each deck post to beam connection -open junction box at basement patio door -security screws at rear patio door
Occupancy Inspection - Codes Residential Ready for Temp CO 10/24/2022 10/24/2022 10/24/2022
Misc
Corrective Action Required
10/18/2022
-sod -splash blocks and sump pump discharge to extend 36” from foundation -Obtain lawn irrigation permit
Occupancy Inspection - Codes Residential Temporary C of O 10/24/2022 10/24/2022
Misc
Corrective Action Required
10/24/2022
-sod -splash blocks and sump pump discharge to extend 36” from foundation -Obtain lawn irrigation permit
Erosion Control Inspection Residential Passed 11/1/2022 11/1/2022 11/01/2022
Misc
Resolved
11/01/2022
erosion control to remain in compliance until sod is in place
Occupancy Inspection - Codes Residential Full C of O 11/1/2022 11/1/2022 11/01/2022
Misc
Resolved
11/01/2022
-sod -splash blocks and sump pump discharge to extend 36” from foundation -Obtain lawn irrigation permit
Documents & Images
Date Uploaded File Type Document Name
11/19/2021 tax aff- signed by rob
11/19/2021 WW037 - PERMIT APPLICATION
11/23/2021 Permit Codes Residential Plan Review
11/23/2021 Approved Plans APPROVED PLANS
12/02/2021 Plot Plan APPROVED PLOT PLAN
12/02/2021 Permit Codes Residential Plan Review
12/02/2021 Permit DS Building Permit
12/02/2021 Receipt Receipt for transaction:2021-009051
12/10/2021 37 Whispering Woods FTNG
01/18/2022 Letter INSPECTION SUMMARY
01/18/2022 Letter INSPECTION SUMMARY
01/25/2022 Letter INSPECTION SUMMARY
01/25/2022 Letter INSPECTION SUMMARY
02/28/2022 Letter INSPECTION SUMMARY
04/07/2022 Final_2022_03_08_SuspGSlab_LSMO_K & E Flatwork
04/29/2022 Final_2022_03_08_SuspGSlab_LSMO_K E Flatwork
04/29/2022 Final_2022_04_27_SuspStoop_LSMO_KE Flatwork
06/21/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
06/21/2022 Letter INSPECTION SUMMARY
07/01/2022 Rough-In Letter
07/05/2022 Letter INSPECTION SUMMARY
07/05/2022 Letter INSPECTION SUMMARY
07/07/2022 Letter INSPECTION SUMMARY
07/11/2022 Letter INSPECTION SUMMARY
07/13/2022 iStruct Single-Member Calc Report
07/14/2022 Letter INSPECTION SUMMARY
07/14/2022 LVL PIC
07/15/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter INSPECTION SUMMARY
07/22/2022 Letter INSPECTION SUMMARY
07/25/2022 Letter INSPECTION SUMMARY
09/12/2022 Letter INSPECTION SUMMARY
09/12/2022 Letter INSPECTION SUMMARY
09/23/2022 Plot Plan approved plot plan
09/27/2022 Letter INSPECTION SUMMARY
10/17/2022 Letter INSPECTION SUMMARY
10/17/2022 Letter INSPECTION SUMMARY
10/17/2022 Letter INSPECTION SUMMARY
10/17/2022 Letter INSPECTION SUMMARY
10/18/2022 Letter INSPECTION SUMMARY
10/18/2022 Receipt Receipt for transaction:2022-008349
10/24/2022 Certificate/License Codes Temporary Certificate of Occupancy
10/24/2022 Receipt Receipt for transaction:2022-008466
10/24/2022 Certificate/License Codes Temporary Certificate of Occupancy
11/01/2022 Letter INSPECTION SUMMARY
11/01/2022 Letter Field Certificate of Occupancy
11/01/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home