Summary
PRRES20214283
Building Permit - Residential
Certificate of Occupancy
FIRST CHOICE CUSTOM HOMES LLC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK
08/17/2021
08/25/2021
02/20/2022
09/01/2022
Locations
Contacts
FIRST CHOICE CUSTOM HOMES LLC, Address:PO BOX 860072, Phone:(913) 449-8935  
FIRST CHOICE CUSTOM HOMES LLC, Address:20863 COTTONWOOD CIR  
John Jamison First Choice Custom Homes, Address:P.O. Box 860072  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ADVANCED ELECTRICAL LLC, Address:PO BOX 1573, Phone:(816) 347-8187  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331504-EFHB Middle Big Creek, Full $401.76 $401.76 Paid 08/25/2021
8331507-Sewer Connection Fee $360.00 $360.00 Paid 08/25/2021
Water Tap Fee $3,655.00 $3,655.00 Paid 08/25/2021
Water Meter Fee $479.24 $479.24 Paid 08/25/2021
Right of Way Permit Fee $85.00 $85.00 Paid 08/25/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 08/25/2021
Valuation Fee New Single Family $973.52 $973.52 Paid 08/25/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 04/05/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/2/2021 (11:30) 9/2/2021 09/02/2021
Sewer Service Inspection - R Passed 9/28/2021 09/28/2021
Underslab Plumbing Inspection - Residential Failed 9/29/2021 9/29/2021 09/29/2021
Misc
Corrective Action Required
09/29/2021
POST ADDRESS MAINTAIN SILT FENCE AT FRONT OF LOT
Underslab Plumbing Inspection - Residential Passed 9/30/2021 9/30/2021 09/30/2021
Misc
Resolved
09/30/2021
Water Service Inspection - R Passed 10/1/2021 10/01/2021
Piers/Caissons Inspection - Residential Passed 12/16/2021 (1:00) 12/16/2021 12/16/2021
All Rough Inspection - Residential Failed 12/27/2021 12/27/2021 12/27/2021
Misc
Corrective Action Required
12/27/2021
GARAGE PORTAL EXTERIOR OK TO COVER
Erosion Control Inspection Residential Failed 12/27/2021 12/27/2021 12/27/2021
Misc
Corrective Action Required
12/27/2021
CLEAN MUD AND GRAVEL FROM STREET
All Rough Inspection - Residential Not Ready 3/28/2022 3/28/2022 03/28/2022
Misc
Resolved
03/28/2022
GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
03/28/2022
INSPECTION DENIED - ADDRESS EROSION CONTROL AT FRONT OF LOT, MAINTAIN SILT FENCE - NO FIREBLOCKING HAS BEEN PERFORMED THROUGHOUT, THIS SHOULD BE DONE BEFRORE SCHEDULING ROUGH INSPECTION
Erosion Control Inspection Residential Failed 3/28/2022 03/28/2022
Misc
Corrective Action Required
12/27/2021
ADDRESS EROSION CONTROL AT FRONT OF LOT, MAINTAIN SILT FENCE
Electrical Service Inspection Failed 4/5/2022 4/5/2022 04/05/2022
Misc
Corrective Action Required
04/05/2022
UFER ground required
Gas Service Inspection - Residential Failed 4/5/2022 4/5/2022 04/05/2022
Misc
Corrective Action Required
04/05/2022
-GAS PRESSURE AT 0 PSI ,MUST MAINTAIN 10 PSI FOR TEST -GAS LINE BOND REQUIRED
All Rough Inspection - Residential Failed 4/5/2022 4/5/2022 04/05/2022
Misc
Corrective Action Required
03/28/2022
-Seal all top plate penetrations - see garage wall -provide bocca protection plate at top and bottom plate DWV pantry -provide bocca protection plate DWV kitchen -secure all vertical DWV 2” or less at mid point -seal bottom plate penetration kitchen -provide structural straps at all top plates bored 50% or more all interior load bearing walls and all exterior walls, straps min 1 1/2” wide, 16 gauge, with (4) 10D nails each side of strap and strap must span 6” each side of bore -provide bocca protection plate DWV bottom plate master water closet -provide nail protection plates at stud penetration DWV master water closet and master shower -provide nail protection plate at pex bore at ceiling joist master shower -fireblock floor bore under tub at front bath 1st floor -2x12 purlin at great room per plans -land purlin struts to bearing locations shown on plans -fireblock vertical to horizontal at furred down soffit ends finished basement -fireblock between top plate and foundation wall/framing at finished basement, seal any penetrations through fireblock material, fireblock annular spaces around plumbing etc. -basement wet bar 20 amp circuit required -provide bocca protection plate at top and bottom plate basement bedroom and basement bathroom -have engineer address floor joists that have been hired for low volt/data and electrical less than 2” from end of joist, multiple locations through basement den and both basement bedrooms -secure CSST gas line span along floor joist through den min 3” from end of joist -(3) 1 3/4” x 9 1/4” lvl at basement mechanical per plans -unable to inspect covered deck roof framing with lid installed
Erosion Control Inspection Residential Partial 4/5/2022 4/5/2022 04/05/2022
Misc
Corrective Action Required
03/28/2022
EROSION CONTROL ACCEPTABLE AT TIME OF INSPECTION
Gas Service Inspection - Residential Passed 4/21/2022 4/21/2022 04/21/2022
Misc
Resolved
04/21/2022
Electrical Service Inspection Failed 4/21/2022 4/21/2022 04/21/2022
Misc
Corrective Action Required
04/05/2022
-replace UFER GEC clamp for one rated for rebar with separation of dissimilar metals -identify GEC at termination points
All Rough Inspection - Residential Failed 4/21/2022 4/21/2022 04/21/2022
Misc
Corrective Action Required
04/05/2022
-secure all vertical DWV 2” or less at mid point -fireblock between top plates at finished basement, see above windows north wall bedroom #3 -basement wet bar 20 amp circuit required, countertop receptacles placement per IRC E3901.4.1/NEC 210.52(C)(1) -secure CSST gas line span along floor joist through basement den min 3” from end of joist -replace UFER GEC clamp for one rated for rebar with separation of dissimilar metals -identify GEC at termination points OK TO INSULATE
All Rough Inspection - Residential Passed 4/28/2022 4/28/2022 04/28/2022
Misc
Resolved
04/28/2022
Electrical Service Inspection Passed 4/28/2022 4/28/2022 04/28/2022
Misc
Resolved
04/28/2022
Erosion Control Inspection Residential Partial 4/28/2022 4/28/2022 04/28/2022
Misc
Corrective Action Required
04/05/2022
EROSION CONTROL ACCEPTABLE AT TIME OF INSPECTION
Driveway Inspection Partial 6/13/2022 06/13/2022
Misc
Informational
06/13/2022
On 6.13.2022 I performed a driveway inspection and pass the sub-grade to pour concrete
Sidewalk Inspection Partial 6/13/2022 06/13/2022
Misc
Informational
06/13/2022
On 6.13.2022 Monday I performed a sidewalk inspection and pass the subgrade to pour concrete.
Occupancy Inspection - Codes Residential Failed 8/3/2022 8/3/2022 08/03/2022
Misc
Corrective Action Required
08/03/2022
-maintain erosion control on lot until sod is placed -final driveway and sidewalk inspections required, contact development services to schedule -obtain lawn irrigation system permit -submit as graded plot plan for review and approval -final grade and sod -gutters and downspouts required -splash blocks -provide gravel base at water meter pit -handrail required at garage stairs -provide all cover plates and switch plates -GFCI protection required at dishwasher receptacle -security screws at deck door, (2) 3” screws each hinge and strike plate -provide anti siphon device at main water line spigot basement, clip off head of set screw after tightening -provide AFCI protection at washer circuit
Driveway Inspection Passed 8/5/2022 8/5/2022 08/05/2022
Misc
Informational
06/13/2022
On 6.13.2022 I performed a driveway inspection and pass the sub-grade to pour concrete 8.5.2022 Driveway appears to be compliant
Sidewalk Inspection Passed 8/5/2022 8/5/2022 08/05/2022
Misc
Informational
06/13/2022
On 6.13.2022 Monday I performed a sidewalk inspection and pass the subgrade to pour concrete. 8.5.2022 Sidewalk appears to be compliant
Plot Plan Inspection Passed 8/23/2022 08/23/2022
Erosion Control Inspection Residential Passed 8/29/2022 08/29/2022
Misc
Resolved
08/29/2022
EROSION CONTROL ACCEPTABLE AT TIME OF INSPECTION
Occupancy Inspection - Codes Residential Failed 8/29/2022 8/29/2022 08/29/2022
Misc
Corrective Action Required
08/03/2022
-splash blocks shall discharge 36" from foundation -provide all cover plates and switch plates ( master closet & front bedroom closet)
Occupancy Inspection - Codes Residential Failed 8/31/2022 8/31/2022 08/31/2022
Misc
Corrective Action Required
08/29/2022
Fee’s Irrigation permit # prirg 20223705
Occupancy Inspection - Codes Residential Full C of O 9/1/2022 9/1/2022 09/01/2022
Misc
Resolved
09/01/2022
Documents & Images
Date Uploaded File Type Document Name
08/17/2021 1808 SW Sage Canyon Rd License_Tax_Application
08/17/2021 1808 SW Sage Canyon Rd Residental Permit Application
08/18/2021 Permit Codes Residential Plan Review
08/20/2021 Engineering solutions letter
08/20/2021 Permit Codes Residential Plan Review
08/24/2021 Permit Codes Residential Plan Review
08/24/2021 Permit Codes Residential Plan Review
08/25/2021 Permit DS Building Permit
08/25/2021 Receipt Receipt for transaction:2021-006810
09/02/2021 Letter INSPECTION SUMMARY
09/28/2021 Letter INSPECTION SUMMARY
09/29/2021 Letter INSPECTION SUMMARY
09/30/2021 Letter INSPECTION SUMMARY
10/01/2021 Letter INSPECTION SUMMARY
11/24/2021 Approved Plans APPROVED DRAWINGS
11/24/2021 Plot Plan APPROVED PLOT PLAN
12/16/2021 Letter INSPECTION SUMMARY
12/27/2021 Letter INSPECTION SUMMARY
12/27/2021 Letter INSPECTION SUMMARY
03/28/2022 Letter INSPECTION SUMMARY
03/28/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/05/2022 Receipt Receipt for transaction:2022-001885
04/13/2022 1808 SE Sage Canyon ROW
04/13/2022 1808 SW Sage Canyon APPROVED PLOT PLAN
04/20/2022 DW LETTER McKinley Cottage 1808 SW Sage Canyon Rd
04/21/2022 Letter INSPECTION SUMMARY
04/21/2022 Letter INSPECTION SUMMARY
04/21/2022 Letter INSPECTION SUMMARY
04/28/2022 Letter INSPECTION SUMMARY
04/28/2022 Letter INSPECTION SUMMARY
04/28/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
06/13/2022 Letter INSPECTION SUMMARY
08/03/2022 Letter INSPECTION SUMMARY
08/22/2022 Plot Plan Approved As Graded Plot Plan
08/23/2022 Letter INSPECTION SUMMARY
08/29/2022 Letter INSPECTION SUMMARY
08/29/2022 Letter INSPECTION SUMMARY
08/29/2022 Letter INSPECTION SUMMARY
08/29/2022 Letter INSPECTION SUMMARY
08/31/2022 Letter INSPECTION SUMMARY
09/01/2022 Letter Codes Final Certificate of Occupancy
09/01/2022 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home