Summary
PRRES20213817
Building Permit - Residential
Certificate of Occupancy
NEW DUPLEX
NEW DUPLEX. UNFINISHED BASEMENT. UNCOVERED PATIO.
07/23/2021
07/29/2021
01/24/2022
09/02/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 07/31/2021 07/29/2021
Andrea Sessler
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Duplex $1,970.08 $1,970.08 Paid 07/29/2021
8331507-Sewer Connection Fee $900.00 $900.00 Paid 07/29/2021
8331401-Water Tap Fee $7,310.00 $7,310.00 Paid 07/29/2021
8350015-Water Meter Fee $958.48 $958.48 Paid 07/29/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 07/29/2021
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 07/29/2021
8331504-EFHB Middle Big Creek, Full $1,004.40 $1,004.40 Paid 10/22/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 06/28/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 06/28/2022
9110080-3rd and Subsequent Inspection Fee (Per Hour) $100.00 $100.00 Paid 06/28/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 07/14/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 08/12/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 08/12/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/30/2021 9/30/2021 09/30/2021
Misc
Informational
09/30/2021
APPROVED PER DAVID P AINSWORTH 9/21/21
Underslab Plumbing Inspection - Residential Passed 10/19/2021 10/19/2021 10/19/2021
Misc
Informational
10/19/2021
3744/3746 both good.
Sewer Service Inspection - R Partial 12/6/2021 (10:45) 12/6/2021 12/06/2021
Misc
Informational
12/06/2021
3744 OK
Sewer Service Inspection - R Passed 12/7/2021 (9:45) 12/7/2021 12/07/2021
Misc
Informational
12/06/2021
3744 3746 OK
Water Service Inspection - R Partial 12/9/2021 (11:30) 12/9/2021 12/09/2021
Misc
Informational
12/09/2021
3746 ok
Water Service Inspection - R Passed 12/10/2021 (8:45) 12/10/2021 12/10/2021
Misc
Informational
12/09/2021
3746 3744 ok
Erosion Control Inspection Residential Failed 12/10/2021 12/10/2021 12/10/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/10/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Not Ready 5/3/2022 5/3/2022 05/03/2022
Misc
Corrective Action Required
05/03/2022
INSPECTION DENIED -MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE -NO CITY STAMPED PLANS ON SITE
Electrical Service Inspection Failed 5/3/2022 05/03/2022
Misc
Corrective Action Required
05/03/2022
INSPECTION DENIED -MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE -NO CITY STAMPED PLANS ON SITE
Gas Service Inspection - Residential Failed 5/3/2022 05/03/2022
Misc
Corrective Action Required
05/03/2022
INSPECTION DENIED -MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE -NO CITY STAMPED PLANS ON SITE
Rated Assembly Inspection Failed 5/3/2022 5/3/2022 05/03/2022
Misc
Corrective Action Required
05/03/2022
INSPECTION DENIED -MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE -NO CITY STAMPED PLANS ON SITE
Erosion Control Inspection Residential Failed 5/3/2022 5/3/2022 05/03/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/03/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Misc
Corrective Action Required
05/03/2022
-MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE
Rated Assembly Inspection Failed 5/4/2022 5/4/2022 05/04/2022
Misc
Corrective Action Required
05/03/2022
-No vents or ducts at roof deck within 4’ of firewall -fire rock break away clips per plans -repair damaged sections of fire rock -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement
Gas Service Inspection - Residential Failed 5/4/2022 5/4/2022 05/04/2022
Misc
Corrective Action Required
05/03/2022
COMPLETE GAS LINE INSTALL, PRESSURE TEST REQUIRED
Electrical Service Inspection Failed 5/4/2022 5/4/2022 05/04/2022
Misc
Corrective Action Required
05/03/2022
-label disconnect and meter can with address 3746: -remove panel bonding screw from sub panel -UFER ground required by code 3744: E3607.5 SYSTEM GROUNDING. An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect. -Provide jumper from ground bar to neutral bar or land CEE on neutral bar
All Rough Inspection - Residential Failed 5/4/2022 5/4/2022 05/04/2022
Misc
Corrective Action Required
05/03/2022
-Maintain gravel filter on drive, min 6" lift, address before scheduling reinspection UNIT 3746: -nail sheathing garage PFH per plans -install and tighten all anchor bolts garage -provide tension straps garage PFH per plans -fur out HVAC garage wall for insulation -Lower light boxes to ceiling height furred downs garage -fireblock plumbing, HVAC garage fur down -(2) nails each stud/plate LIB strap per plans -12” oc nailing all abutting and intersecting corners -provide nail protection plates all NM within 1 1/4” end of stud - see great room, foyer -provide header and secure joist to header with joist hanger at HVAC box out kitchen, joist currently supported by non load bearing wall -provide security blocking front door -Fireblock all tub traps -provide vent master bath plumbing -have engineer address floor joist above service panel basement, bores for NM less than 2” apart -complete gas piping, pressure test required -anchor SCH 40 steel column basement floor -provide joist hanger at joist to header connection above furnace -remove panel bonding screw from sub panel -UFER ground required by code -No vents or ducts at roof deck within 4’ of firewall -fire rock break away clips per plans -repair damaged sections of fire rock -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement UNIT 3744: -nail sheathing garage PFH per plans -provide tension straps garage PFH per plans -anchor bolts shall be in middle third of sill plate at garage -fireblock HVAC/plumbing fur out garage wall -ensure UFER remains accessible at finish -fur out HVAC garage wall for insulation -Lower light boxes to ceiling height furred downs garage -(2) nails each stud/plate LIB strap per plans -12” oc nailing all abutting and intersecting corners -install stud shoe DWV garage wall powder room -provide header and secure joist to header with joist hanger at HVAC box out kitchen, joist currently supported by non load bearing wall -provide security blocking at front door -provide vent master bath plumbing -provide protection plate bottom plate pex laundry, master bed side of wall -complete gas lines, pressure test required -anchor SCH 40 steel column to floor at basement -address floor joist overbored for DWV SE corner basement -No vents or ducts at roof deck within 4’ of firewall -fire rock break away clips per plans -repair damaged sections of fire rock -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement E3607.5 SYSTEM GROUNDING. An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect. -Provide jumper from ground bar to neutral bar or land CEE on neutral bar
Erosion Control Inspection Residential Failed 5/4/2022 5/4/2022 05/04/2022
Misc
Corrective Action Required
05/03/2022
-MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE
All Rough Inspection - Residential Not Ready 5/16/2022 5/16/2022 05/16/2022
Misc
Corrective Action Required
05/04/2022
5/16/22 NOT READY UNIT 3746: -nail sheathing garage PFH per plans -fur out HVAC garage wall for insulation (3.5" for R13) -fireblock plumbing, HVAC garage fur down -(2) nails each stud/plate LIB strap per plans -12” oc nailing all abutting and intersecting corners -provide nail protection plates all NM within 1 1/4” end of stud - see great room, foyer -provide header and secure joist to header with joist hanger at HVAC box out kitchen, joist currently supported by non load bearing wall -Fireblock all tub traps -provide vent master bath plumbing -have engineer address floor joist above service panel basement, bores for NM less than 2” apart -complete gas piping, pressure test required -provide joist hanger at joist to header connection above furnace -remove panel bonding screw from sub panel -UFER ground required by code -No vents or ducts at roof deck within 4’ of firewall -fire rock break away clips per plans -repair damaged sections of fire rock -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement UNIT 3744: -fireblock HVAC/plumbing fur out garage wall -ensure UFER remains accessible at finish -fur out HVAC garage wall for insulation -12” oc nailing all abutting and intersecting corners -install stud shoe DWV garage wall powder room -provide header and secure joist to header with joist hanger at HVAC box out kitchen, joist currently supported by non load bearing wall -provide vent master bath plumbing -provide protection plate bottom plate pex laundry, master bed side of wall -complete gas lines, pressure test required -address floor joist overbored for DWV SE corner basement -No vents or ducts at roof deck within 4’ of firewall -fire rock break away clips per plans -repair damaged sections of fire rock -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement E3607.5 SYSTEM GROUNDING. An unspliced main bonding jumper shall be used to connect the equipment grounding conductor(s) and the service-disconnect enclosure to the grounded conductor of the system within the enclosure for each service disconnect. -Provide jumper from ground bar to neutral bar or land CEE on neutral bar
Driveway Inspection Partial 5/18/2022 5/18/2022 05/18/2022
Misc
Informational
05/18/2022
On 5.18.2022 I performed a driveway inspection and pass the subgrade to pour concrete
Sidewalk Inspection Partial 5/18/2022 5/18/2022 05/18/2022
Misc
Informational
05/18/2022
On 5.18.2022 I performed a sidewalk inspection and pass the subgrade to pour concrete
Gas Service Inspection - Residential Passed 5/23/2022 5/23/2022 05/23/2022
Misc
Resolved
05/23/2022
COMPLETE GAS LINE INSTALL, PRESSURE TEST REQUIRED
Electrical Service Inspection Failed 5/23/2022 5/23/2022 05/23/2022
Misc
Corrective Action Required
05/04/2022
-label disconnect and meter can with address
All Rough Inspection - Residential Failed 5/23/2022 5/23/2022 05/23/2022
Misc
Corrective Action Required
05/16/2022
UNIT 3746: -fur out HVAC garage wall for insulation (3.5" for R13), fireblock at HVAC, pan off bottom of furrred down -have engineer address floor joist above service panel basement, bores for NM less than 2” apart, repair per submitted engineer letter -provide joist hanger at joist to header connection above furnace -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -repair damaged sections of fire rock, provide UL listing and cert for yellow and gray caulk used on firewall -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3744: -fur out HVAC garage wall for insulation, fireblock around HVAC, pan off bottom of furred down -address floor joist overbored for DWV SE corner basement, repair per submitted engineer letter -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -repair damaged sections of fire rock, provide UL listing and cert on gray and yellow caulking used on firewall -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Rated Assembly Inspection Failed 5/23/2022 5/23/2022 05/23/2022
Misc
Corrective Action Required
05/04/2022
UNIT 3746: -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -repair damaged sections of fire rock, provide UL listing and cert for yellow and gray caulk used on firewall -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3744: -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -repair damaged sections of fire rock, provide UL listing and cert on gray and yellow caulking used on firewall -fire rock required to be seated in H stud -rock required to seat in C channel at roof deck -see rock at master bed roof deck, rock is short of deck and can see daylight from next door unit, also rock is cut back from framing at front wall can see through to next door unit -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Erosion Control Inspection Residential Partial 5/23/2022 05/23/2022
Misc
Resolved
05/23/2022
-MAINTAIN GRAVEL FILTER ON DRIVE, 6" MIN LIFT CONTINUOUS ON DRIVE
Electrical Service Inspection Failed 5/25/2022 05/25/2022
Misc
Corrective Action Required
05/23/2022
-label disconnect and meter can with address
All Rough Inspection - Residential Failed 5/25/2022 5/25/2022 05/25/2022
Misc
Corrective Action Required
05/23/2022
UNIT 3746: -have engineer address floor joist above service panel basement, bores for NM less than 2” apart, repair per submitted engineer letter -provide joist hanger at joist to header connection above furnace -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -provide UL listing and cert for yellow and gray caulk used on firewall -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3744: -address floor joist overbored for DWV SE corner basement, repair per submitted engineer letter -have engineer with truss manufacturer address gable truss damaged for repairs of fire rock -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -provide UL listing and cert on gray and yellow caulking used on firewall -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Rated Assembly Inspection Failed 5/25/2022 05/25/2022
Misc
Corrective Action Required
05/23/2022
UNIT 3746: -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -provide UL listing and cert for yellow and gray caulk used on firewall -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3744: -No vents or ducts at roof deck within 4’ of firewall, see dryer duct -provide UL listing and cert on gray and yellow caulking used on firewall -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Erosion Control Inspection Residential Partial 5/25/2022 05/25/2022
Electrical Service Inspection Passed 5/31/2022 5/31/2022 05/31/2022
Misc
Resolved
05/31/2022
-label disconnect and meter can with address
All Rough Inspection - Residential Failed 5/31/2022 5/31/2022 05/31/2022
Misc
Corrective Action Required
05/25/2022
UNIT 3746: OK to insulate and rock UNIT 3744: -address floor joist overbored for DWV SE corner basement, repair per submitted engineer letter -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Rated Assembly Inspection Failed 5/31/2022 5/31/2022 05/31/2022
Misc
Corrective Action Required
05/25/2022
UNIT 3744: -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk
Erosion Control Inspection Residential Partial 5/31/2022 05/31/2022
All Rough Inspection - Residential Passed 6/1/2022 6/1/2022 06/01/2022
Misc
Resolved
06/01/2022
Erosion Control Inspection Residential Partial 6/1/2022 06/01/2022
Sidewalk Inspection Partial 6/16/2022 6/16/2022 06/16/2022
Misc
Informational
05/18/2022
On 5.18.2022 I performed a sidewalk inspection and pass the subgrade to pour concrete. On 6.16.2022 I performed a side of the building sidewalk inspection and pass the subgrade to pour concrete.
Driveway Inspection Passed 7/12/2022 7/12/2022 07/12/2022
Misc
Informational
05/18/2022
On 5.18.2022 I performed a driveway inspection and pass the subgrade to pour concrete
Sidewalk Inspection Passed 7/12/2022 7/12/2022 07/12/2022
Misc
Informational
06/16/2022
THIS IS A DUPLEX 3744 AND 3746 SW MARYVILLE PLACE. On 5.18.2022 I performed a sidewalk inspection and pass the subgrade to pour concrete. On 6.16.2022 I performed a side of the building sidewalk inspection and pass the subgrade to pour concrete.
Occupancy Inspection - Codes Residential Failed 7/13/2022 7/13/2022 07/13/2022
Misc
Corrective Action Required
07/13/2022
-final grade and sod -splash blocks -gutters and downspouts -maintain erosion control until sod is placed UNIT 3746: -mud and tape garage ceiling at garage door brackets -cover plates all switches and outlets
Occupancy Inspection - Codes Residential Ready for Temp CO 7/14/2022 7/14/2022 07/14/2022
Misc
Corrective Action Required
07/13/2022
-final grade and sod -splash blocks -gutters and downspouts -maintain erosion control until sod is placed - -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3746: - final grade and sod -splash blocks -gutters and downspouts -maintain erosion control until sod is placed TCO EXPIRATION 8/13/22 3746 Only
Occupancy Inspection - Codes Residential Temporary C of O 7/14/2022 07/14/2022
Misc
Corrective Action Required
07/14/2022
-final grade and sod -splash blocks -gutters and downspouts -maintain erosion control until sod is placed - -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk UNIT 3746: - final grade and sod -splash blocks -gutters and downspouts -maintain erosion control until sod is placed TCO EXPIRATION 8/13/22
Rated Assembly Inspection Passed 8/5/2022 8/5/2022 08/05/2022
Misc
Resolved
08/05/2022
UNIT 3744: -seal firewall penetration SE cable basement, this requires UL approved fire rated intumescent caulk NOY COMPLETE Shawn Hoffman 07/14/2022 9:11 AM
Occupancy Inspection - Codes Residential Failed 8/5/2022 8/5/2022 08/05/2022
Misc
Corrective Action Required
07/14/2022
-final grade and sod -splash blocks -gutters and downspouts UNIT 3746: - final grade and sod -splash blocks -gutters and downspouts TCO EXPIRATION 8/13/22 UNIT 3744: - GARAGE DOOR MUST BE SELF CLOSING - SECURE CEILING LIGHT FIXTURE LAUNDRY - SUPPORT BASEMENT HANDRAIL - CORRECT GRADING AT REAR OF LOT, NEGATIVE SLOPE TOWARDS CENTER OF REAR LOT RESULTING IN POOLING AND STANDING WATER
Occupancy Inspection - Codes Residential Ready for Temp CO 8/11/2022 8/11/2022 08/11/2022
Misc
Corrective Action Required
08/05/2022
Pay TCO fee for 30 days , both units need to be compete before a CofO can be issued until then $50 fee each 30 days with submittal and approval of TCo extension letter. -final grade and sod -splash blocks -gutters and downspout UNIT 3746: - final grade and sod TCO EXPIRATION 8/13/22 UNIT 3744: - GARAGE DOOR MUST BE SELF CLOSING - SECURE CEILING LIGHT FIXTURE LAUNDRY - SUPPORT BASEMENT HANDRAIL - CORRECT GRADING AT REAR OF LOT, NEGATIVE SLOPE TOWARDS CENTER OF REAR LOT RESULTING IN POOLING AND STANDING WATER
Occupancy Inspection - Codes Residential Ready for Temp CO 8/12/2022 08/12/2022
Misc
Corrective Action Required
08/11/2022
Pay TCO fee for 30 days , both units need to be compete before a CofO can be issued until then $50 fee each 30 days with submittal and approval of TCo extension letter. UNIT 3746: TCO EXPIRATION 8/13/22 UNIT 3744: - ready for temp CofO - CORRECT GRADING AT REAR OF LOT, NEGATIVE SLOPE TOWARDS CENTER OF REAR LOT RESULTING IN POOLING AND STANDING WATER
Occupancy Inspection - Codes Residential Temporary C of O 7/14/2022 08/12/2022
Misc
Corrective Action Required
08/12/2022
Pay TCO fee for 30 days , both units need to be compete before a CofO can be issued until then $50 fee each 30 days with submittal and approval of TCo extension letter. UNIT 3746: TCO EXPIRATION 8/13/22 UNIT 3744: - ready for temp CofO - CORRECT GRADING AT REAR OF LOT, NEGATIVE SLOPE TOWARDS CENTER OF REAR LOT RESULTING IN POOLING AND STANDING WATER
Plot Plan Inspection Passed 9/2/2022 09/02/2022
Erosion Control Inspection Residential Passed 9/2/2022 09/02/2022
Occupancy Inspection - Codes Residential Full C of O 9/2/2022 9/2/2022 09/02/2022
Misc
Resolved
09/02/2022
Pay TCO fee for 30 days , both units need to be compete before a CofO can be issued until then $50 fee each 30 days with submittal and approval of TCo extension letter. UNIT 3746: TCO EXPIRATION 8/13/22 UNIT 3744: - ready for temp CofO - CORRECT GRADING AT REAR OF LOT, NEGATIVE SLOPE TOWARDS CENTER OF REAR LOT RESULTING IN POOLING AND STANDING WATER
Documents & Images
Date Uploaded File Type Document Name
07/23/2021 OS #16 - PERMIT APP
07/28/2021 Permit Codes Residential Plan Review
07/28/2021 Approved Plans APPROVED DRAWINGS
07/29/2021 Permit Codes Residential Plan Review
07/29/2021 Permit DS Building Permit
07/29/2021 Receipt Receipt for transaction:2021-006049
08/31/2021 Approved Plans APPROVED TRUSS LAYOUT
08/31/2021 Approved Plans APPROVED TRUSS PACKAGE
09/30/2021 M L Crose 3744 & 3746 SW Maryville Pl LSMO Osage Lot 16 Clayton P 2021-3817 3rd Party Footing Inspection Report 9-21-21
09/30/2021 Letter INSPECTION SUMMARY
10/19/2021 Letter INSPECTION SUMMARY
10/22/2021 Receipt Receipt for transaction: 2021-008192
12/06/2021 Letter INSPECTION SUMMARY
12/07/2021 Letter INSPECTION SUMMARY
12/09/2021 Letter INSPECTION SUMMARY
12/10/2021 Letter INSPECTION SUMMARY
12/10/2021 Letter INSPECTION SUMMARY
01/28/2022 Approved Plans APPROVED DRAWINGS UPDATE
05/03/2022 Letter INSPECTION SUMMARY
05/03/2022 Letter INSPECTION SUMMARY
05/03/2022 Letter INSPECTION SUMMARY
05/03/2022 Letter INSPECTION SUMMARY
05/03/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/10/2022 16 osage letter
05/16/2022 Letter INSPECTION SUMMARY
05/19/2022 16 osage letter #2
05/23/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
05/23/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/26/2022 OS pt_1
05/26/2022 OS pt_2
05/27/2022 OS 16 Truss Repair
05/31/2022 Letter INSPECTION SUMMARY
05/31/2022 Letter INSPECTION SUMMARY
05/31/2022 Letter INSPECTION SUMMARY
05/31/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/01/2022 Letter INSPECTION SUMMARY
06/28/2022 Receipt Receipt for transaction:2022-005214
06/29/2022 Approved Plans APPROVED PLANS
06/29/2022 LOT 16 MINOR PLAT SEAL
07/06/2022 Photograph APPROVED PLOT PLAN
07/12/2022 Letter INSPECTION SUMMARY
07/13/2022 Letter INSPECTION SUMMARY
07/14/2022 Receipt Receipt for transaction:2022-005730
07/14/2022 Letter Codes Temporary Certificate of Occupancy
07/21/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/05/2022 Letter INSPECTION SUMMARY
08/12/2022 Receipt Receipt for transaction:2022-006634
08/12/2022 Receipt Receipt for transaction:2022-006640
08/12/2022 Letter Codes Temporary Certificate of Occupancy
09/02/2022 Letter Codes Final Certificate of Occupancy
09/02/2022 Letter Field Certificate of Occupancy
09/02/2022 Letter INSPECTION SUMMARY
09/02/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home