Permit Application Status

PRRES20213590


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20213590
Building Permit - Residential
Certificate of Occupancy
NEW 3 OR 4 FAMILY
NEW FOUR PLEX - UNFINISHED BASEMENT - UNCOVERED PATIO
07/12/2021
07/13/2021
10/13/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
JOE@CLOVERANDHIVE.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $3,342.02 $3,342.02 Paid 07/13/2021
8331507-Sewer Connection Fee $1,560.00 $1,560.00 Paid 07/13/2021
8331401-Water Tap Fee $14,620.00 $14,620.00 Paid 07/13/2021
8350015-Water Meter Fee $1,916.96 $1,916.96 Paid 07/13/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 07/13/2021
7232302-Residential Excise Tax Fee $4,308.48 $4,308.48 Paid 07/13/2021
8331504-EFHB Middle Big Creek, Full $1,740.96 $1,740.96 Paid 10/22/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/29/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/29/2022
9110080-3rd and Subsequent Inspection Fee (Per Hour) $150.00 $150.00 Paid 09/29/2022
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 09/29/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 8/24/2021 8/24/2021 08/24/2021
Misc
Informational
08/24/2021
APPROVED PER DAVID AINSWORTH 8/19/21
Sewer Service Inspection - R Passed 9/15/2021 (11:30) 9/15/2021 09/15/2021
Misc
Informational
09/15/2021
3711 and 3715 ok 3713,3715,3717 LOT # 7 (3) SOUTH UNITS APPROVED NO ADDRESS POST ADDRESS CALLED IN 3716 WALSH IS LOT 10 IS WRONG PERMIT #
Sewer Service Inspection - R Partial 9/16/2021 9/16/2021 09/16/2021
Informational
09/15/2021
3717,3715,3713 OK TO COVER
Sewer Service Inspection - R Passed 9/16/2021 09/16/2021
Misc
Informational
09/16/2021
3711 ok
Water Service Inspection - R Passed 9/17/2021 (10:30) 9/17/2021 09/17/2021
Misc
Informational
09/17/2021
3711,3713,3715,3717 OK
Erosion Control Inspection Residential Failed 9/17/2021 9/17/2021 09/17/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/17/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underslab Plumbing Inspection - Residential Failed 9/24/2021 9/24/2021 09/24/2021
Misc
Corrective Action Required
09/24/2021
3715,3717,3713 OK 3711 - SET SUMP PIT AND INTERIOR DRAIN TILE
Underslab Plumbing Inspection - Residential Passed 10/1/2021 10/1/2021 10/01/2021
Misc
Informational
10/01/2021
3715,3717,3713,3711 OK
All Rough Inspection - Residential Not Ready 5/5/2022 5/5/2022 05/05/2022
Misc
Corrective Action Required
05/05/2022
INSPECTION DENIED -MAINTAIN EROSION CONTROL SILT FENCE ON LOT -GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
Electrical Service Inspection Failed 5/5/2022 5/5/2022 05/05/2022
Misc
Corrective Action Required
05/05/2022
INSPECTION DENIED -MAINTAIN EROSION CONTROL SILT FENCE ON LOT -GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
Gas Service Inspection - Residential Failed 5/5/2022 5/5/2022 05/05/2022
Misc
Corrective Action Required
05/05/2022
INSPECTION DENIED -MAINTAIN EROSION CONTROL SILT FENCE ON LOT -GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
Rated Assembly Inspection Failed 5/5/2022 5/5/2022 05/05/2022
Misc
Corrective Action Required
05/05/2022
INSPECTION DENIED -MAINTAIN EROSION CONTROL SILT FENCE ON LOT -GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
Erosion Control Inspection Residential Failed 5/5/2022 5/5/2022 05/05/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/17/2021
INSPECTION DENIED -MAINTAIN EROSION CONTROL SILT FENCE ON LOT -GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
All Rough Inspection - Residential Failed 5/12/2022 5/12/2022 05/12/2022
Misc
Corrective Action Required
05/05/2022
Maintain gravel filter on drive UNIT 3711: -strap top plate garage, less than 24” lap -secure all vertical DWV 2” or less at mid point -maintain access to UFER garage at finish -(2) 20 amp receptacles required for (2) car garage -address top plate corner lap connection required by code at garage wall -provide vertical fireblock every 10’ between studs and fire rock -provide fire rated playwood at roof deck first 4’ from rated wall -provide engineer letter on field fix for overbored joist above front entry -provide nail protection plate at bottom plate SE cable foyer -(2) 2x4 trimmer studs garage entry and owners entry per plans -provide bocca protection plate at DWV bedroom closet 2nd floor -connect bath exhaust duct to fan -sheath wall open to garage mast set bedroom -min (2) nails each stud/plate LIB straps -protect NM within 6’ of attic entry -provide vent for master bath group -provide engineer report for field fix for floor joists bored less than 2” from end of joist for SE cables basement -cap off future vent and radon line above furnace UNIT 3713: -(2) 20 amp receptacles required for (2) car garage -secure all vertical DWV 2” or less at mid point -seal top plate penetrations garage entry -provide engineer letter on field fix for overbored joist above front entry -(2) 2x4 trimmer studs garage entry and owners entry per plans -3” SCH 40 steel columns at W12x26 beam garage per plane -LIB bracing garage per plans -min (2) nails each stud/plate LIB straps -fireblock HVAC/plumbing chase 2nd floor closet -address fire rock not seated in H stud 2nd floor -have engineer with truss manufacturer address dbl girder at master bedroom that the end chord and gusset plate have been sheared down against the fire rock -provide engineer report for field fix for floor joists bored less than 2” from end of joist for SE cables basement -cap off future vent and radon line above furnace -address floor joist bores for NM less than 2” apart above service panel and stair wall -truss hangers per plans NO INSPECTION PERFORMED ON 3715, 3717
Gas Service Inspection - Residential Failed 5/12/2022 5/12/2022 05/12/2022
Misc
Corrective Action Required
05/05/2022
-gas line bond required -Check gauge 3713, no air coming out but needle sticks at 20
Electrical Service Inspection Failed 5/12/2022 5/12/2022 05/12/2022
Misc
Corrective Action Required
05/05/2022
-land SE cable at meter cans -land GEC for UFER at neutral bar -blank off meter can not in use -label disconnects and meter cans with address
Rated Assembly Inspection Failed 5/12/2022 5/12/2022 05/12/2022
Misc
Corrective Action Required
05/05/2022
UNIT 3711: -provide vertical fireblock every 10’ between studs and fire rock -provide fire rated playwood at roof deck first 4’ from rated wall UNIT 3713: -address fire rock not seated in H stud 2nd floor
Erosion Control Inspection Residential Failed 5/12/2022 5/12/2022 05/12/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/05/2022
-GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
Gas Service Inspection - Residential Passed 5/19/2022 5/19/2022 05/19/2022
Misc
Resolved
05/19/2022
-gas line bond required -Check gauge 3713, no air coming out but needle sticks at 20
Electrical Service Inspection Passed 5/19/2022 5/19/2022 05/19/2022
Misc
Resolved
05/19/2022
All Rough Inspection - Residential Failed 5/19/2022 5/19/2022 05/19/2022
Misc
Corrective Action Required
05/12/2022
UNIT 3711: -secure all vertical DWV 2” or less at mid point -cap off future vent and radon line above furnace UNIT 3713: -secure all vertical DWV 2” or less at mid point -fireblock HVAC/plumbing chase 2nd floor closet, fireblock around HVAC and plumbing penetrations -have engineer with truss manufacturer address dbl girder at master bedroom that the end chord and gusset plate have been sheared down against the fire rock, (fix per letter, nail pattern, osb isn’t nailed to bottom chord of truss, move electrical so that this can be done) -cap off future vent and radon line above furnace -address floor joist bores for NM less than 2” apart above service panel and stair wall -truss hangers per plans UNIT 3715: -provide joist hanger dbl lvl garage -secure all vertical DWV2” or less at mid point -non continuous top plate left and right side of garage door -address corner lap connection of top plate to top plate per code at garage -replace stud and provide stud shoe, stud has been overbored for DWV less than 5/8” of stud left at bore for DWV at garage wall and 1st floor powder bath -provide structural straps all top plate bores 50% or more all interior load bearing walls and all exterior walls -address floor joists that have been bored for electrical less than 2” apart, see above garage entry -(4) 9 1/4” lvl at garage per plans -dbl every other 2x10 joist at garage per plans -(5) 2x4 stud pack at garage wall lvl bearing per plans -solid shim trimmer studs cut short of headers throughout -provide all truss hangers per plans -12” oc nailing all abutting intersecting wall corners -seal top plate penetration 2nd floor bathroom -nail all girder trusses together per plans -address dbl girder truss chord and gusset plate at master bedroom sheared down -repair damaged exiting of fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall -Have engineer with truss manufacturer address broken A19 and A21 truss -cap and label future vent at basement UNIT 3717: -address top plates not tied together at garage -secure all vertical DWV 2” or less at mid point -fireblock at dbl wall behind 2nd floor tub -Have engineer with truss manufacturer address lay in truss cut out for roof vent -have engineer address A1 dbl girder truss that has been notched and sheared down along top chord -provide all truss hangers per plans -nail all girder trusses together per plans -cap and label future vent at basement
Rated Assembly Inspection Failed 5/19/2022 5/19/2022 05/19/2022
Misc
Corrective Action Required
05/12/2022
UNIT 3715: -repair damaged fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs
Erosion Control Inspection Residential Partial 5/19/2022 5/19/2022 05/19/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/19/2022
-GRAVEL FILTER REQUIRED ON DRIVE, MIN 6" LIFT
All Rough Inspection - Residential Failed 5/24/2022 5/24/2022 05/24/2022
Misc
Corrective Action Required
05/19/2022
UNIT 3711: COMPLETE, OK TO INSULATE AND ROCK UNIT 3713: -secure all vertical DWV 2” or less at mid point -fireblock HVAC/plumbing chase 2nd floor closet, fireblock around HVAC and plumbing penetrations -have engineer with truss manufacturer address dbl girder at master bedroom that the end chord and gusset plate have been sheared down against the fire rock, (fix per letter, nail pattern, osb isn’t nailed to bottom chord of truss, move electrical so that this can be done) -cap off future vent and radon line above furnace -address floor joist bores for NM less than 2” apart above service panel and stair wall -truss hangers per plans UNIT 3715: -provide joist hanger dbl lvl garage -secure all vertical DWV2” or less at mid point -non continuous top plate left and right side of garage door -address corner lap connection of top plate to top plate per code at garage -replace stud and provide stud shoe, stud has been overbored for DWV less than 5/8” of stud left at bore for DWV at garage wall and 1st floor powder bath -provide structural straps all top plate bores 50% or more all interior load bearing walls and all exterior walls -address floor joists that have been bored for electrical less than 2” apart, see above garage entry -(4) 9 1/4” lvl at garage per plans -dbl every other 2x10 joist at garage per plans -(5) 2x4 stud pack at garage wall lvl bearing per plans -solid shim trimmer studs cut short of headers throughout -provide all truss hangers per plans -12” oc nailing all abutting intersecting wall corners -seal top plate penetration 2nd floor bathroom -nail all girder trusses together per plans -address dbl girder truss chord and gusset plate at master bedroom sheared down -repair damaged exiting of fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall -Have engineer with truss manufacturer address broken A19 and A21 truss -cap and label future vent at basement UNIT 3717: -address top plates not tied together at garage -secure all vertical DWV 2” or less at mid point -fireblock at dbl wall behind 2nd floor tub -Have engineer with truss manufacturer address lay in truss cut out for roof vent -have engineer address A1 dbl girder truss that has been notched and sheared down along top chord -provide all truss hangers per plans -nail all girder trusses together per plans -cap and label future vent at basement
Erosion Control Inspection Residential Partial 05/24/2022
All Rough Inspection - Residential Not Ready 5/25/2022 5/25/2022 05/25/2022
Misc
Corrective Action Required
05/24/2022
**5/25/22 INSPECTION DENIED, NOT READY FOR INSPECTION, ALL CORRECTIONS HAVE NOT BEEN ADDRESSED UNIT 3711: COMPLETE, OK TO INSULATE AND ROCK UNIT 3713: -have engineer with truss manufacturer address dbl girder at master bedroom that the end chord and gusset plate have been sheared down against the fire rock, (fix per letter, nail pattern, osb isn’t nailed to bottom chord of truss, move electrical so that this can be done) **5/25 now the electrical NM will need to be ran as it was cut, why is this not done before scheduling inspection? If another trade is removed or altered during fix of one correction that other trade needs to be corrected before rescheduling inspection** UNIT 3715: -land to boxes and secure all electrical at garage that has been removed for corrections -provide joist hanger dbl lvl garage, nail joist hanger -secure all vertical DWV2” or less at mid point -non continuous top plate left and right side of garage door , **provide engineer letter on field fix** -address corner lap connection of top plate to top plate per code at garage -replace stud and provide stud shoe, stud has been overbored for DWV less than 5/8” of stud left at bore for DWV at garage wall and 1st floor powder bath -provide structural straps all top plate bores 50% or more all interior load bearing walls and all exterior walls -address floor joists that have been bored for electrical less than 2” apart, see above garage entry, **provide engineer letter on field fix** -(4) 9 1/4” lvl at garage per plans -dbl every other 2x10 joist at garage per plans -(5) 2x4 stud pack at garage wall lvl bearing per plans -solid shim trimmer studs cut short of headers throughout -provide all truss hangers per plans -12” oc nailing all abutting intersecting wall corners -seal top plate penetration 2nd floor bathroom -nail all girder trusses together per plans -address dbl girder truss chord and gusset plate at master bedroom sheared down -repair damaged exiting of fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall -Have engineer with truss manufacturer address broken A19 and A21 truss -cap and label future vent at basement UNIT 3717: -address top plates not tied together at garage -secure all vertical DWV 2” or less at mid point -fireblock at dbl wall behind 2nd floor tub -Have engineer with truss manufacturer address lay in truss cut out for roof vent -have engineer address A1 dbl girder truss that has been notched and sheared down along top chord -provide all truss hangers per plans -nail all girder trusses together per plans -cap and label future vent at basement
Rated Assembly Inspection Failed 5/25/2022 05/25/2022
Misc
Corrective Action Required
05/19/2022
UNIT 3715: -repair damaged fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs
All Rough Inspection - Residential Failed 5/27/2022 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/25/2022
**5/25/22 INSPECTION DENIED, NOT READY FOR INSPECTION, ALL CORRECTIONS HAVE NOT BEEN ADDRESSED UNIT 3711: COMPLETE, OK TO INSULATE AND ROCK UNIT 3713: COMPLETE, OK TO INSULATE AND ROCK UNIT 3715: 5/27/22 NOT READY -land to boxes and secure all electrical at garage that has been removed for corrections -provide joist hanger dbl lvl garage, nail joist hanger -secure all vertical DWV2” or less at mid point -non continuous top plate left and right side of garage door , **provide engineer letter on field fix** -address corner lap connection of top plate to top plate per code at garage -replace stud and provide stud shoe, stud has been overbored for DWV less than 5/8” of stud left at bore for DWV at garage wall and 1st floor powder bath -provide structural straps all top plate bores 50% or more all interior load bearing walls and all exterior walls -address floor joists that have been bored for electrical less than 2” apart, see above garage entry, **provide engineer letter on field fix** -(4) 9 1/4” lvl at garage per plans -dbl every other 2x10 joist at garage per plans -(5) 2x4 stud pack at garage wall lvl bearing per plans -solid shim trimmer studs cut short of headers throughout -provide all truss hangers per plans -12” oc nailing all abutting intersecting wall corners -seal top plate penetration 2nd floor bathroom -nail all girder trusses together per plans -address dbl girder truss chord and gusset plate at master bedroom sheared down -repair damaged exiting of fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall -Have engineer with truss manufacturer address broken A19 and A21 truss -cap and label future vent at basement UNIT 3717: -address top plates not tied together at garage -fireblock at dbl wall behind 2nd floor tub OK TO INSULATE
Rated Assembly Inspection Failed 5/27/2022 5/27/2022 05/27/2022
Misc
Corrective Action Required
05/25/2022
UNIT 3715: -repair damaged fire rock -Fire rock must be seated in c channel at roof deck -Fire rock must be seated in H studs
All Rough Inspection - Residential Failed 6/2/2022 6/2/2022 06/02/2022
Misc
Corrective Action Required
05/27/2022
UNIT 3711: COMPLETE, OK TO INSULATE AND ROCK UNIT 3713: COMPLETE, OK TO INSULATE AND ROCK UNIT 3715: -seal all top plate penetrations garage -nail stud shoe at 1st floor powder bath -(5) 2x4 stud pack at garage wall lvl wall bearing per plans -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall (repair per engineer letter) UNIT 3717: COMPLETE, OK TO INSULATE
All Rough Inspection - Residential Failed 6/2/2022 6/2/2022 06/02/2022
Misc
Corrective Action Required
06/02/2022
UNIT 3711: COMPLETE, OK TO INSULATE AND ROCK UNIT 3713: COMPLETE, OK TO INSULATE AND ROCK UNIT 3715: -seal all top plate penetrations garage -nail stud shoe at 1st floor powder bath -(5) 2x4 stud pack at garage wall lvl wall bearing per plans -Have engineer with truss manufacturer address the gable truss top chord has been removed, see above 2nd floor bath at firewall (repair per engineer letter) OK TO INSULATE UNIT 3717: COMPLETE, OK TO INSULATE AND ROCK
Rated Assembly Inspection Passed 6/2/2022 6/2/2022 06/02/2022
Misc
Resolved
06/02/2022
Erosion Control Inspection Residential Partial 06/02/2022
All Rough Inspection - Residential Passed 6/7/2022 6/7/2022 06/07/2022
Misc
Resolved
06/07/2022
Erosion Control Inspection Residential Partial 6/7/2022 06/07/2022
Sidewalk Inspection Partial 6/29/2022 6/29/2022 06/29/2022
Misc
Informational
06/29/2022
On 6.29.2022 Wednesday I performed a sidewalk inspection and passed the subgrade to pour concrete.
Driveway Inspection Passed 6/3/2022 6/3/2022 07/20/2022
Misc
Informational
06/03/2022
On 6.3.2022 Friday I performed 4 driveway inspections (3711, 3713, 3715, 3715) SW Walsh Drive and pass the sub-grades to pour concrete. 7.20.2022 Driveway appears to be in compliance
Sidewalk Inspection Passed 7/20/2022 7/20/2022 07/20/2022
Misc
Informational
06/29/2022
On 6.29.2022 Wednesday I performed a sidewalk inspection and passed the subgrade to pour concrete. 7.20.2022 Sidewalk appears to be in compliance
Driveway Inspection Passed 7/19/2022 7/19/2022 07/28/2022
Misc
Informational
06/03/2022
On 6.3.2022 Friday I performed 4 driveway inspections (3711, 3713, 3715, 3715) SW Walsh Drive and pass the sub-grades to pour concrete. 7.18.2022 Driveways appear to be in compliance
Occupancy Inspection - Codes Residential Failed 9/26/2022 9/26/2022 09/26/2022
Misc
Corrective Action Required
09/26/2022
-maintain erosion control on lot until sod is placed -resolve outstanding inspection fees -final grade and sod -splash blocks -Sump pump discharge min 36” from foundation -uncover water meter lids, provide gravel base water meter wells UNIT 3713: -provide hammer arrestor dishwasher -garage door self closing and latching -mud garage door bracket ceiling penetrations -label breaker #27 at service panel -provide ladder at basement egress window well NO INSPECTION PERFORMED ON UNITS 3711, 3715, 3717
Occupancy Inspection - Codes Residential Ready for Temp CO 9/29/2022 9/29/2022 09/29/2022
Misc
Corrective Action Required
09/26/2022
-maintain erosion control on lot until sod is placed -resolve outstanding inspection fees -final grade and sod -splash blocks -Sump pump discharge min 36” from foundation -uncover water meter lids, provide gravel base water meter wells UNIT 3713: OK FOR TCO NO INSPECTION PERFORMED ON UNITS 3711, 3715, 3717
Occupancy Inspection - Codes Residential Temporary C of O 09/29/2022
Misc
Corrective Action Required
09/29/2022
-maintain erosion control on lot until sod is placed -resolve outstanding inspection fees -final grade and sod -splash blocks -Sump pump discharge min 36” from foundation -uncover water meter lids, provide gravel base water meter wells UNIT 3713: OK FOR TCO NO INSPECTION PERFORMED ON UNITS 3711, 3715, 3717
Erosion Control Inspection Residential Passed 10/6/2022 10/6/2022 10/06/2022
Plot Plan Inspection Passed 10/6/2022 10/6/2022 10/06/2022
Occupancy Inspection - Codes Residential Failed 10/6/2022 10/6/2022 10/06/2022
Misc
Corrective Action Required
09/29/2022
drive electrical ground rod beneath grade at meter can -provide security flood lights at rear UNIT 3711: -tape and mud garage door bracket ceiling penetrations at garage -repair rock at faucet and UFER garage wall -mark dedicated receptacle at basement outlet as not GFCI protected -provide gravel base at water meter well UNIT 3713: OK FOR TCO UNIT 3715: -tape and mud garage door bracket ceiling penetrations at garage -tighten 2nd floor handrail -mark dedicated receptacle at basement outlet as not GFCI protected UNIT 3717: -install outlet and cover plate at kitchen counter outlet -tape and mud garage door bracket ceiling penetrations at garage -mark dedicated receptacle at basement outlet as not GFCI protected -make basement stairs light operable
Occupancy Inspection - Codes Residential Full C of O 10/13/2022 10/13/2022 10/13/2022
Misc
Resolved
10/13/2022
Documents & Images
Date Uploaded File Type Document Name
07/12/2021 OS #7 - PERMIT APP
07/13/2021 Approved Plans Approved Drawings
07/13/2021 Approved Plans Approved Truss Package
07/13/2021 Plot Plan Approved Plot Plan
07/13/2021 Permit Codes Residential Plan Review
07/13/2021 Permit DS Building Permit
07/13/2021 Receipt Receipt for transaction:2021-005587
08/23/2021 M L Crose 3711 3713 3715 3717 SW Walsh Dr LSMO Osage Lot 7 C & H P 2021-3590 3rd Party Footing Inspection Report 8-19-21
08/24/2021 Letter INSPECTION SUMMARY
09/02/2021 Approved Plans Approved Truss Layout
09/15/2021 Letter INSPECTION SUMMARY
09/16/2021 Letter INSPECTION SUMMARY
09/16/2021 Letter INSPECTION SUMMARY
09/17/2021 Letter INSPECTION SUMMARY
09/17/2021 Letter INSPECTION SUMMARY
09/24/2021 Letter INSPECTION SUMMARY
10/01/2021 Letter INSPECTION SUMMARY
10/22/2021 Receipt Receipt for transaction: 2021-008192
01/27/2022 Approved Plans Approved Drawings
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/05/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter INSPECTION SUMMARY
05/12/2022 Letter INSPECTION SUMMARY
05/16/2022 7 osage letter #2
05/16/2022 I51928542_P210272
05/19/2022 Letter INSPECTION SUMMARY
05/19/2022 Letter INSPECTION SUMMARY
05/19/2022 Letter INSPECTION SUMMARY
05/19/2022 Letter INSPECTION SUMMARY
05/19/2022 Letter INSPECTION SUMMARY
05/24/2022 Approved Plans Approved Truss Repair
05/24/2022 Letter INSPECTION SUMMARY
05/24/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/25/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
05/27/2022 Letter INSPECTION SUMMARY
06/02/2022 Letter INSPECTION SUMMARY
06/02/2022 Letter INSPECTION SUMMARY
06/02/2022 Letter INSPECTION SUMMARY
06/02/2022 Letter INSPECTION SUMMARY
06/03/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/07/2022 Letter INSPECTION SUMMARY
06/29/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
07/21/2022 Letter INSPECTION SUMMARY
08/02/2022 Letter INSPECTION SUMMARY
09/26/2022 Letter INSPECTION SUMMARY
09/29/2022 Receipt Receipt for transaction:2022-007914
09/29/2022 Letter Codes Temporary Certificate of Occupancy
10/06/2022 Letter INSPECTION SUMMARY
10/06/2022 Letter INSPECTION SUMMARY
10/06/2022 Letter INSPECTION SUMMARY
10/13/2022 Letter Field Certificate of Occupancy
10/13/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home