Summary
PRRES20212477
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - FINISHED AND UNFINISHED BASEMENT - COVERED DECK STOP WORK ORDER generated on 08/02/2021 12:00 AM by username 'Patrick Schonfeldt'. STOP WORK ORDER removed on 08/03/2021 12:00 AM by username 'Patrick Schonfeldt'.
05/14/2021
05/18/2021
11/10/2021
05/04/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
PERMITTING@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $360.00 $360.00 Paid 05/18/2021
Right of Way Permit Fee $80.00 $80.00 Paid 05/18/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 05/18/2021
Water Tap Fee $3,581.00 $3,581.00 Paid 05/18/2021
Water Meter Fee $455.54 $455.54 Paid 05/18/2021
Valuation Fee New Single Family $902.85 $902.85 Paid 05/18/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed - Stop Work 8/2/2021 8/2/2021 08/02/2021
Misc
Corrective Action Required
08/02/2021
FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE SUBMITTED WITHIN 48 HOURS OF INSPECTION, STOP WORK ISSUED
Underslab Plumbing Inspection - Residential Failed 8/2/2021 8/2/2021 08/02/2021
Misc
Corrective Action Required
08/02/2021
INSPECTION DENIED, FOOTING POURED WITHOUT INSPECTION
Footing Inspection - Residential Passed 8/3/2021 08/03/2021
Misc
Informational
08/03/2021
APPROVED PER BRADLEY HUXOL 6/10/21
Underslab Plumbing Inspection - Residential Passed 8/4/2021 8/4/2021 08/04/2021
Misc
Resolved
08/04/2021
Sewer Service Inspection - R Passed 8/31/2021 (9:00) 8/31/2021 08/31/2021
Water Service Inspection - R Passed 9/1/2021 09/01/2021
Erosion Control Inspection Residential Failed 9/1/2021 9/1/2021 09/01/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
09/01/2021
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
All Rough Inspection - Residential Partial 10/18/2021 10/18/2021 10/18/2021
Misc
Informational
10/18/2021
- GARAGE PORTAL EXTERIOR OK TO COVER
Electrical Service Inspection Passed 12/21/2021 12/21/2021 12/21/2021
Gas Service Inspection - Residential Passed 12/21/2021 12/21/2021 12/21/2021
All Rough Inspection - Residential Failed 12/21/2021 12/21/2021 12/21/2021
Misc
Informational
10/18/2021
- GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
12/21/2021
-No approved truss plans on site, approved truss details and layout should be on site for reinspection, correction list subject to change -unable to inspect covered deck trusses due to lid cover -Address top plates not tied together SE garage exterior wall, SW exterior wall and front entry exterior wall -protect NM within 6’ of attic access -fireblock HVAC/ b vent chase laundry -seal unused top plate bores master bath vanity -connect bath exhaust fan duct master bath -Install windows -seal unused bottom plate bores great room, kitchen -seal top plate penetrations pantry -secure vertical DWV at mid point, 1st floor front bed closet, basement bath -complete furred downs finished basement -fireblock vertical every 10’ between foundation/framing at finished basement -anchor all SCH 40 columns to floor at basement -(2) 2x10 header at basement den window per plans -solid block between joists at cantilevers -address studs overnotched for anchor bolts, basement den daylight exterior wall
All Rough Inspection - Residential Failed 12/29/2021 12/29/2021 12/29/2021
Misc
Informational
12/21/2021
- GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
12/21/2021
-Provide lateral bracing for trusses per plans -fireblock above SW den window -fireblock at steel beam furr down exterior daylight wall in basement den -fireblock vertical every 10’ between foundation/framing at finished basement -(2) 2x10 header at basement den window per plans -solid block between joists at cantilevers
All Rough Inspection - Residential Failed 12/30/2021 12/30/2021 12/30/2021
Misc
Informational
12/29/2021
- GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Corrective Action Required
12/29/2021
-fireblock above SW den window -fireblock above den windows at basement **OK TO INSULATE**
All Rough Inspection - Residential Passed 1/4/2022 1/4/2022 01/04/2022
Misc
Informational
12/30/2021
- GARAGE PORTAL EXTERIOR OK TO COVER
Misc
Resolved
01/04/2022
-fireblock above SW den window -fireblock above den windows at basement **OK TO INSULATE**
Driveway Inspection Passed 4/1/2022 04/01/2022
Driveway Inspection Passed 4/1/2022 4/1/2022 04/01/2022
Misc
Informational
04/01/2022
On Friday 4-01-2022 I performed and passed a driveway inspection.
Sidewalk Inspection Passed 4/1/2022 4/1/2022 04/01/2022
Misc
Informational
04/01/2022
On Friday 4-01-2022, I performed and passed a sidewalk inspection for placement of concrete.
Piers/Caissons Inspection - Residential Passed 4/6/2022 04/06/2022
Misc
Informational
04/06/2022
Addressed in third party footing inspection report.
Occupancy Inspection - Codes Residential Failed 4/6/2022 4/6/2022 04/06/2022
Misc
Corrective Action Required
04/06/2022
-final grade and sod -complete pending sidewalk inspection -address to be properly illuminated -splash blocks and sump pump discharge to extend 36” from foundation -Seal top of meter can, A/c disconnect and all other exterior penetrations. -guard rail where required at front stoop -spark rings required at kitchen backsplash outlets -label all non GFCI outlets in unfinished spaces -(2) 1/2” though bolts at eacH deck post to beam connection
Occupancy Inspection - Codes Residential Failed 4/13/2022 4/13/2022 04/13/2022
Misc
Corrective Action Required
04/06/2022
-sod (manhole lid to remain uncover at time of sod) -complete pending sidewalk inspection -address to be properly illuminated -splash blocks and sump pump discharge to extend 36” from foundation
Plot Plan Inspection Passed 4/13/2022 04/13/2022
Occupancy Inspection - Codes Residential Temporary C of O 4/14/2022 4/14/2022 04/14/2022
Misc
Corrective Action Required
04/13/2022
TCO UNTIL 4/28/22 -sod (manhole lid to remain uncover at time of sod) -complete pending sidewalk inspection -splash blocks and sump pump discharge to extend 36” from foundation
Occupancy Inspection - Codes Residential Failed 4/29/2022 4/29/2022 04/29/2022
Misc
Corrective Action Required
04/14/2022
TCO UNTIL 4/28/22 -uncover man hole lid -complete pending sidewalk inspection
Sidewalk Inspection Passed 5/2/2022 5/2/2022 05/02/2022
Misc
Informational
05/02/2022
All sidewalk at this location was passed on 4-01-2022.
Erosion Control Inspection Residential Passed 5/4/2022 05/04/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
05/04/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Full C of O 5/4/2022 5/4/2022 05/04/2022
Misc
Resolved
05/04/2022
TCO UNTIL 4/28/22 -uncover man hole lid -complete pending sidewalk inspection
Documents & Images
Date Uploaded File Type Document Name
05/14/2021 86 HAWTHORNE RIDGE ROOF LAYOUT
05/14/2021 2731404 RF SEAL 04072021
05/14/2021 H3 #86 - Westport - Craftsman - Sheets- signed
05/14/2021 H3 #86 - PERMIT APP
05/14/2021 LOT 86 FINAL
05/14/2021 Permit Codes Residential Plan Review
05/14/2021 Approved Plans APPROVED PLANS
05/14/2021 Approved Plans APPROVED TRUSS DRAWINGS
05/14/2021 Approved Plans APPROVED TRUSS LAYOUT
05/18/2021 LOT 86 CITY
05/18/2021 Plot Plan APPROVED PLOT PLAN
05/18/2021 Permit Codes Residential Plan Review
05/18/2021 Permit DS Building Permit
05/18/2021 Receipt Receipt for transaction:2021-003153
08/02/2021 Letter Stop Work Order
08/02/2021 Letter INSPECTION SUMMARY
08/03/2021 Lot 86 Hawthorne Ridge Footing Inspection
08/03/2021 Letter INSPECTION SUMMARY
08/04/2021 Letter INSPECTION SUMMARY
08/31/2021 Letter INSPECTION SUMMARY
09/01/2021 Letter INSPECTION SUMMARY
09/01/2021 Letter INSPECTION SUMMARY
10/18/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/21/2021 Letter INSPECTION SUMMARY
12/29/2021 Letter INSPECTION SUMMARY
12/30/2021 Letter INSPECTION SUMMARY
01/04/2022 Letter INSPECTION SUMMARY
04/01/2022 Letter INSPECTION SUMMARY
04/01/2022 Letter INSPECTION SUMMARY
04/01/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/06/2022 Letter INSPECTION SUMMARY
04/13/2022 Letter INSPECTION SUMMARY
04/13/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter Codes Temporary Certificate of Occupancy
05/02/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter Field Certificate of Occupancy
05/04/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home